PANELCO III SUBSTATION'S EQUIPMENT DATA


A. BINALONAN 10 MVA SUBSTATION
LOCATION: Mcarthur Hi-way, Bued, Binalonan (3 Units identical)

A.1. 69 KV POTENTIAL TRANSFORMER MAKE TYPE SERIAL NO. NSV BIL RATIO PRI. : SEC. RATIO PRI. : TER. FREQUENCY ACCURACY/BURDEN THERMAL RATING TEMP. RISE OIL QUANTITY OIL SPEC TOTAL WIEGHT

ASSOCIATED ENGINEERING COMPANY POF-350 671903/AE1046179715/671899 69 KV 350 KV 350/600:1 350/600:1 60 HZ 0.3W.ZZ 6000 VA 55 C 30 GALS 104-5031-001 700 LBS (3 Units identical)

A.2. 69 KV CURRENT TRANSFORMER MAKE TYPE SERIAL NO. NSV BIL RATIO R.F. @ 30 C FREQUENCY ACCURACY/BURDEN I THERMAL 1 SEC. RMS KA TEMP. RISE I MECH. RMS KA OIL QUANTITY TOTAL WIEGHT

ASSOCIATED ENGINEERING COMPANY IK-350 090145/090152/090146 69 KV 350 KV 50X100:5 1.5 60 HZ 0.3 3X6 55 C 4X8 78 GALS 700 LBS

A.2. 69 KV LIGHTNING ARRESTER MAKE MODEL SERIAL NO. NSV BIL

(3 Units identical) G.E. 9L11MHA060 45052/45039/45018 69 KV 350 KV

A.3. POWER TRANSFORMER MAKE/BRAND SERIAL NUMBER CAPACITY % IMPEDANCE RATED CURRENT XIAN TRANSFORMER A96074-2 10/12.5 MVA 7.5% @ 10 MVA/9.4% @ 12.5 MVA 86.2/107.7 A 437.4/546.7 A 67 KV 13.2 KV 3 60 A OA/FA 65 C 55 C 24,850 KG. 12,000KG. 6,000 KG. 8,670 ltrs 1997 ENERGIZED 09-26-97

H. V. L. V. RATED VOLTAGE H. V. L. V. PHASE FREQUENCY INSULATING CLASS TYPE OF COOLING TEMP. RISE: WINDING OIL APPROX. MASSES CORE & COIL TANK & AUXILLIARY TRANSFORMER OIL DATE MANUFACTURED STATUS DATE ENERGIZED

A.4. OIL CIRCUIT BREAKER A.4.1. FEEDER I OIL CIRCUIT BREKER (OCB 1) MAKE SERIAL NUMBER VOLTAGE RATING AMPERE RATING BIL CYCLE CLOSING VOLTAGE WEIGHT OIL PER TANK DATE MANUFACTURE STATUS DATE ENERGIZED A.4.2. FEEDER II OIL CIRCUIT BREAKER (OCB 2) MAKE SERIAL NUMBER VOLTAGE RATING AMPERE RATING BIL CYCLE CLOSING VOLTAGE WEIGHT OIL PER TANK ALLIS CHALMER 318461 14.4 KV 1200 A 110 KV 60 HZ 190-250 V 2600 LBS 12 GAL ALLIS CHALMER 318464 14.4 KV 1200 A 110 KV 60 HZ 190-250 V 2600 LBS 12 GAL 08/1959 ENERGIZED 1995

DATE MANUFACTURED STATUS DATE ENERGIZED

Aug-59 ENERGIZED 1995

A.5. PROTECTION RELAY A.5.1. FEEDER 25 RELAY SPECIFICATIONS PHASE MAKE TYPE SERIAL # FUNCTION TIME ELEMENT RATING INSTANTENOUS RATING C. T. RATIO A CO-9 1875288A 50/51 4-12A 10-40 A 200/5 B G. E. CO-9 1875288A 50/51 4-12A 10-40 A 200/5 SETTING TAP TIME INST. 4 4 20 4 4 20 4 4 20 1.5 4 CO-9 1875288A 50/51 4-12A 10-40 A 200/5 CO-9 1875283A 51N 0.5-2.5A 200/5 C GROUND

A.5.2. FEEDER II RELAYS SPECIFICATIONS PHASE MAKE TYPE SERIAL # FUNCTION TIME ELEMENT RATING INSTANTENOUS RATING C. T. RATIO A CO-9 1875288A 50/51 4-12A 10-40 A 200/5 B G. E. CO-9 1875288A 50/51 4-12A 10-40 A 200/5 SETTING TAP TIME INST. 4 4 20 4 4 20 4 4 20 1.5 4 CO-9 1875288A 50/51 4-12A 10-40 A 200/5 CO-9 1875283A 51N 0.5-2.5A 200/5 C GROUND

A.4. POWER METER MAKE MODEL OPERATING TEMPERATURE W/ DISPLAY POWER SUPPLY VOLTAGE INPUTS CURRENT INPUTS BAUD RATE FREQUENCY STORAGE TEMP. HUMIDITY DIMENSION WEIGHT

(2 units IDENTICAL) ELECTRO CONTROL 0 C to 50 C 95 to 145 Vac/0.1 amps 120/277/347 VAC Nominal 1 to 5 Amp. AC up to 19200 bps 50/60 Hz (selectable) -30C to 70C 5% to 95%, non condensing 194.6mmx114.3mmx25.4mm 2.2 Kg

B. TAYUG 5 MVA S/S


LOCATION: B.1. POWER TRANSFORMER MAKE SERIAL NUMBER CAPACITY % IMPEDANCE H. V. L. V. PHASE FREQUENCY INSULATING CLASS TYPE OF COOLING TEMP. RISE WINDING OIL NUMBER OF FEEDERS DATE MANUFACTURED STATUS OIL QUANTITY DATE ENERGIZED B.2. AIR CIRCUIT BREAKER (ACB) MAKE RATED VOLTAGE RATED CURRENT IMP. WITHSTAND VOLTAGE RATED INTERRUPTING CURRENT RATED INTERRUPTING CAPACITY MAX. INTERRUPTING CURRENT RATED INTERRUPTING TIME RATED CLOSING VOLTAGE RATED TRIPPING VOLTAGE CONTROL VOLTAGE RANGE MAX. DESIGN VOLTAGE FREQUENCY DATE MFG. OSAKA 5A1502001 5000 KVA 7.1 % 67000 7968/13800 Y 3 60 HZ A OA 65 C 55 C 2 1975 ENERGIZED 7070 ltrs 1975 ACB 1, ACB2, (IDENTICAL) NISSIN ELECTRIC CO, LTD. 13.8 KV 1200A 95 KV 12.6 KA 250 MVA @ 13.8 KV 34 KA 8 CYCLES 100 Vac 48 Vdc DC 35 - DC 50 V 15 KV 60 HZ 1974 TRENCHERA, TAYUG

NET WEIGHT TYPE LOCATION STATUS DATE ENERGIZED A.3. PROTECTION RELAY

690 KG DST2-75 TAYUG S/S ENERGIZED 1975

SPECIFICATIONS PHASE MAKE SERILA NUMBER FUNCTION TIME ELEMENT RATING TIME ELEMENT RATING INSTANTENOUS RATING TYPE C. T. RATIO A 753433 50/51 50/51 4-12A 10-40 A 10R-FIASI 300/5 B NISSIN 753435 50/51 50/51 4-12A 10-40 A 10R-FIASI 300/5 SETTING TAP TIME INST. 5 1 25 5 1 25 5 1 25 1.5 1.25 20 753434 50/51 50/51 4-12A 10-40 A 10R-FIASI 300/5 752842 51N 51N 0.5-2.5A 10R-FIASI 300/5 C GROUND

A.4. POWER METER MAKE MODEL OPERATING TEMPERATURE W/ DISPLAY POWER SUPPLY VOLTAGE INPUTS CURRENT INPUTS BAUD RATE FREQUENCY STORAGE TEMP. HUMIDITY DIMENSION WEIGHT

(2 units IDENTICAL) ELECTRO CONTROL 0 C to 50 C 95 to 145 Vac/0.1 amps 120/277/347 VAC Nominal 1 to 5 Amp. AC up to 19200 bps 50/60 Hz (selectable) -30C to 70C 5% to 95%, non condensing 194.6mmx114.3mmx25.4mm 2.2 Kg

C. UMINGAN SUBSTATION
LOCATION: C.1. 69 KV SURGE ARRESTER MAKE TYPE MCOV BIL FREQUENCY CAURDANETAAN, UMINGAN (3 Units IDENTICAL) EDISON-HUBBARD STATION CLASS METAL OXIDE 48 KV 350 KV 60 HZ

C.2. CURRENT TRANSFORMER MAKE RATED VOLTAGE BIL TYPE FREQUENCY ACCURACY BURDEN RATIO

(3 Units IDENTICAL) EDISON-HUBBARD 69 KV 350 KV COF-350 60 HZ 0.3 ANSI 1.8 50/100:5

C.3. POTENTIAL TRANSFORMER MAKE RATED VOLTAGE BIL RATIO FREQUENCY TYPE ACCURACY BURDEN DESCRIPTION C. 4. 69 KV AIR BREAK SWITCH (ABS) MAKE RATED VOLATGE MAXIMUM VOLTAGE NOMINAL CURRENT BIL MOMENTARY INTERRUPTING CURRENT INSTALLATION NO OF POLES INSULATOR TYPE OF OPERATING MECHANISM

(3 Units IDENTICAL) EDISON HUBBARD 69 KV 350 KV 300:1 60 HZ POF-350 0.3 ANSI ZZ OUTDOOR OIL FILLED

EDISON-HUBBARD CORP. 69 KV 72.5 KV 600 A 350 KV 10 KA VERTICAL BREAK DISCONNECT THREE (3) PORCELAIN MAIN DISCONNECT SWITCH MANUAL TYPE

C.5. SF6 GAS CIRCUIT BREAKER MAKE SERIAL NUMBER RATED MAX VOLTS RATED CONT. CURRENT RATED VOLTAGE RANGE FACTOR RATED SHORT CKT. CURRENT RATED OUT OF PHASE CURRENT FREQUENCY FILL PRESSURE @ 70 F MIN. OPERT'NG PRESSURE @ 70 F RATED OPERT'NG PRESSURE @ 70 F SF6 ALARM PRESSURE @ 70 F SF6 CUT-OUT PRESSURE @ 70 F SIEMENS S. O. 49201-8 SPS-72.5-23-1 72.5 KV 1200A 1.0 (K) 23000A 55000A 60 HZ 80 PSIG 65 PSIG 75 PSIG 70 PSIG 65 PSIG

FULL WAVE IMPULSE WITHSTAND WT. OF BREAKER W/ GAS OVERVOLTAGE FACTOR LINE CHARGING ISOLATED BANK SW. INRUSH PEAK INRUSH FREQ. DATE MANUFACTURE DATE ENERGIZED

350 KV 2840 LBS 2.0 100A 630 A 25000A 3360 HZ 1997 FEBRUARY 27, 1998

PHASE MAKE MODEL FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO TAP TIME INSTANTENOUS C.6. POWER TRANSFORMER MAKE/BRAND SERIAL NUMBER CAPACITY % IMPEDANCE RATED VOLTAGE

A 121FC77B3A 50/51R

SF6 PROTECTION RELAYS B C G. E. 121FC77B3A 121FC77B3A 50/51R 50/51R

GROUND 121FC77B2A 50/51G

2.5 0.75 -

2.5 0.75 -

2.5 0.75 -

0.8 0.75 -

H. V. L. V.

CLASS IMPULSE LEVEL HV WIND. IMPULSE LEVEL LV WIND. OIL QUANTITY TOTAL WEIGHT CURRENT RATING HV CURRENT RATING LV TEMPERATURE RISE NUMBER OF FEEDERS DATE MANUFACTURE STATUS DATE ENERGIZED

XIAN TRANSFORMER 970776-2 5/6.25 MVA 7.18% @ 5MVA/8.98% @ 6.25MVA 67000 V 13200 V OA/FA 350 BIL 110 BIL 7170 ltrs 18250 KG. 43.1/53.9 218.7/273.4 55 C 3 1997 OPERATIONAL FEBRUARY 27, 1998

C.7. 14.4KV OIL CIRCUIT BREAKER (OCB)

OCB 1, 2, 3 (IDENTICAL)

MAKE/BRAND

ALLIS CHALMER

SERIAL NUMBER RATED AMP FREQUENCY VOLTAGE MAX. DESIGN VOLTAGE IMPULSE INS. LEVEL RATED SHT. CKT. CURRENT DATE MANUFACTURED OIL QUANTITY DATE ENERGIZED C.8. OCBs PROTECTION RELAYS C.8.1. FEEDER I RELAYS

37320-1/10441-1/10441-4 600 60HZ 14.4 KV 15.5 KV 110 KV 8900A/8900A/10000A MAR 1971/1965/1965 210 ltrs FEB, 2000

SPECIFICATION PHASE MAKE SERIAL NUMBER MODEL FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO A B G. E. 121AC77B31A 50/51R 4-16A 100/5 121AC77B31A 50/51R 4-16A 100/5 121AC77B31A 50/51R 4-16A 100/5 SETTING TAP TIME INSTANTENOUS 5 1 20 5 1 20 5 1 20 1.5 1 12 121FC77B9A 50/51G 1.5-3A 100/5 C GROUND

C.8.2. FEEDER II RELAYS SPECIFICATION PHASE MAKE SERIAL NUMBER MODEL FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO A B G. E. 121A1C77B31A 121A1C77B31A 50/51R 50/51R 4-16A 4-16A 10-40A 10-40A 50/5 50/5 121A1C77B31A 50/51R 4-16A 10-40A 50/5 121FC77B9A 50/51G 1.5-3A 50/5 C GROUND

SETTING TAP TIME INSTANTENOUS 5 1 10 5 1 10 5 1 10 1.5 1 8

C.8.3. FEEDER III RELAYS SPECIFICATION PHASE MAKE SERIAL NUMBER MODEL FUNCTION TIME ELEMENT A B G. E. 121A1C77B31A 121A1C77B31A 50/51R 50/51R 4-16A 4-16A 121A1C77B31A 50/51R 4-16A 121FC77B9A 50/51G 1.5-3A C GROUND

INSTANTENEOUS RATING C.T. RATIO

10-40A 100/5

10-40A 100/5 SETTING

10-40A 100/5

100/5

TAP TIME INSTANTENOUS

5 1 10

5 1 10

5 1 10

1.5 1 8

D. URDANETA 15 MVA S/S


LOCATION D.1. 60 KV SURGE ARRESTER MAKE TYPE MCOV FREQUENCY BIL MAX. INTERRUPTING CURRENT INSULATOR HIGHEST SYSTEM VOLTAGE RATED NOMINAL VOLTAGE D. 3. 69 KV CURRENT TRANSFORMER MAKE TYPE RATIO RATED VOLTAGE BIL G. E. JKW-150/350 400/800:5 through 1500/3000:5 amp 69 KV 350 KV OHIO BRASS STATION CLASS 57 KV 60 HZ 350 KV 10 KA PORCELAIN 72 KV 60 KV CALLE GARCIA, URDANETA CITY

D. 1. 69 KV AIR BREAK SWITCH (ABS) MAKE TYPE RATED VOLATGE MAXIMUM VOLTAGE NOMINAL CURRENT BIL INSTALLATION NO OF POLES INSULATOR TYPE OF OPERATING MECHANISM SIEMENS TA-OC 69 KV 72 KV 1200 A 350 KV VERTICAL BREAK DISCONNECT THREE (3) GREY PORCELAIN MAIN DISCONNECT SWITCH MANUAL TYPE

D.5. SF6 GAS CIRCUIT BREAKER 69 KV MAKE SERIAL NUMBER RATED MAX VOLTS RATED CONT. CURRENT FREQUENCY FILL PRESSURE @ 70 F RATED OPERATING PRESS. @ 70 F SF6 ALARM RESSURE @ 70 F SIEMENS 48589-1 72.5 KV 1200A 60 HZ 80 PSIG 65 PSIG 70 PSIG

RATED VOLT RANGE FACTOR RATED SHORT CURRENT RATED OUTPHASE CURRENT FULL WAVE IMPULSE VOLT W/STAND WT. OF BREAKER W/ GAS WT. OF SF6 GAS LINE CHARGING OVER VOLTGAE FACTOR ISOLATED BANK SW. INRUSH PEAK INRUSH FREQ DATE MANUFACTURED DATE ENERGIZED

1 (K) 23000A 5500A 350 KV 2840 LBS 15 LBS 100A 2 630A 25000A 3360 HZ JUNE 1995 JULY 1996

D.6. POWER TRANSFORMER LOCATION MAKE/BRAND SERIAL NUMBER CAPACITY % IMPEDANCE H. V. L. V. OIL QUANTITY STATUS IMPULSE INSULATION LEVEL IMPULSE INSULATION LEVEL NUMBER OF FEEDERS DATE MANUFACTURED DATE ENERGIZED CALLE GARCIA, POBLACION, URDANETA G. E. 93307 15,000 KVA 9.95 69000 V 13800 22200 ltrs ENERGIZED 350 KV 550 KV 3 1987 JULY 6, 1996 AVR 1, AVR2, AVR3 (IDENTICAL) SIEMEN 7490-1/7490-2/7490-3 500 KVA 7620 V + 10% in 32-5/8% steps 656A 95KV OA ASTMD-3487 TYPE II MINERAL OIL 3950 LBS. 2194 LBS. 181 GALS URDANETA S/S ENERGIZED 1996

H. V. L. V.

D.7. AUTOMATIC VOLTAGE REGULATOR MAKE/BRAND SERIAL NUMBER CAPACITY VOLTAGE RATING AMPERE RATING BIL CLASS INSULATING FUILD TOTAL WEIGHT UNTANKING WEIGHT OIL LOCATION STATUS DATE ENERGIZED

D.8. 15 KV VACUUM CIRCUIT BREAKER

VCB1,VCB2,VCB3 (IDENTICAL)

MAKE SERIAL NUMBER TYPE RATED MAX VOLTAGE RATED CURRENT BIL RATED SHORT CKT CURRENT VOLTAGE RANGE FACTOR K CLOSE LACTH KA FREQUENCY INTERRUPTING TIME CYCLE MOTOR CLOSE TRIP DATE MANUFACTURED DATE ENERGIZED D.9. VCBs PROTECTION RELAYS D.9.1. FEEDER I RELAYS PHASE MAKE SERIAL NUMBER MODEL FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO TAP TIME INSTANTENOUS D.9.2. FEEDER II RELAYS A SIEMENS H3EZSJB1N1S 4700 PM 50/51R 0.5-20 400/5 3.5 20 20

SIEMENS K-91142A-3/K-91142A-2/K-91142A-1 15-GMI-500-1200-37 15 KV 1200A 95 KV 18 KA 1.3 37 60 HZ 5 CYCLE 104-227 Vac 104-227 Vac 104-227 Vac JUNE 1995 JULY 06, 1996

SPECIFICATION B

GROUND

50/51R 0.5-20 400/5 3.5 20 20

50/51R 0.5-20 400/5 3.5 20 20

50/51G 0.5-5 400/5 1 20 20

SPECIFICATION PHASE MAKE SERIAL NUMBER MODEL FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO A C SIEMENS H3EZSJB1N1S 4700 PM 50/51R 50/51R 0.5-20 0.5-20 400/5 400/5 B GROUND

50/51R 0.5-20 400/5

50/51G 0.5-5 400/5

SETTING TAP TIME INSTANTENOUS 4 10 15.7 4 10 15.7 4 10 15.7 1 20 20

D.9.3. FEEDER III RELAYS SPECIFICATION PHASE A B C GROUND

MAKE SERIAL NUMBER MODEL FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO

50/51R 0.5-20 400/5

SIEMENS H3EZSJB1N1S 4700 PM 50/51R 50/51R 0.5-20 0.5-20 400/5 400/5

50/51G 0.5-5 400/5

SETTING TAP TIME INSTANTENOUS 2.5 20 16.5 2.5 20 16.5 2.5 20 16.5 1 20 20

D.10. POWER METER MAKE MODEL OPERATING TEMPERATURE W/ DISPLAY POWER SUPPLY VOLTAGE INPUTS CURRENT INPUTS BAUD RATE FREQUENCY STORAGE TEMP. HUMIDITY DIMENSION WEIGHT

(3 Units IDENTICAL) SIEMENS 4300 PM 0 C to 50 C 95 to 145 Vac/0.1 amps 120/277/347 VAC Nominal 1 to 5 Amp. AC up to 19200 bps 50/60 Hz (selectable) -30C to 70C 5% to 95%, non condensing 194.6mmx114.3mmx25.4mm 2.2 Kg

E. 5MVA URDANETA S/S


LOCATION E.1. 69 KV SURGE ARRESTER MAKE TYPE SERIAL NO. MCOV FREQUENCY BIL MAX. INTERRUPTING CURRENT CALLE GARCIA, POBLACION, URDANETA (3 Units IDENTICAL) SORESTER ZSE-C12 STATION CLASS M007763/M007762/M007761 46.6 KV 60 HZ 350 KV 10 KA

INSULATOR HIGHEST SYSTEM VOLTAGE RATED NOMINAL VOLTAGE

PORCELAIN 72 KV 60 KV

E.2. POWER TRANSFORMER MAKE SERIAL NUMBER CAPACITY % IMPEDANCE RATED VOLTAGE FREQUENCY CLASS PHASE WINDING TEMP. RISE IMPULSE LEVEL IMPULSE LEVEL IMPULSE LEVEL OIL QUANTITY TOTAL WT. UNTANKING WT. OIL CLASS DATE MANUFACTURED DATE RE-ACTIVATED TAKAOKA 7743912 5000 KVA 6.23 % 67000 V 13800 V 60 HZ OA/FA 3 55 C 350 KV 110 KV 95 KV 5000 ltrs 15300 KGS 7200 KGS 26 KV 1978 7/6/2001

H. V. L. V.

H. V. L. V. N

E.3. OIL CIRCUIT BREAKER (OCB 1) MAKE SERIAL NUMBER RATED AMP FREQUENCY VOLTAGE TYPE CLOSE VOLTS TRIP VOLTS OIL PER TANK IMPULSE INSULATION LEVEL MAXIMUM VOLTAGE RATED SHT. CKT. CURRENT INTERRUPTING TIME WT. OF BREAKER W/ OIL WT. OF TANK W/ OIL DATE RE-ACTIVATED ALLIS CHALMER 41330-1 600 60 HZ 14.4 KV SDO-15-250 125 Vdc 125 Vdc 220 LTRS 110 KV 15.5 KV 8900 A 6 CYCLES 2200 LBS 600 LBS 7/6/2001

E.4. OIL CIRCUIT BREAKER (OCB 2)

MAKE SERIAL NUMBER RATED AMP FREQUENCY VOLTAGE TYPE CLOSE VOLTS TRIP VOLTS OIL PER TANK IMPULSE INSULATION LEVEL MAXIMUM VOLTAGE INT. AMP @ RATED VOLTS WT. OF BREAKER W/ OIL TOTAL WT. OF OIL DATE RE-ACTIVATED E.5.1. FEEDER IV RELAYS

ALLIS CHALMER 15322-2 600 60 HZ 14.4 KV SDO-15-250 230 Vac CAPACITOR TRIP 220 LTRS 110 KV 15.5 KV 14000 A 2200 LBS 405 LBS 7/6/2001

SPECIFICATION PHASE MAKE STYLE NO FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO A 1875286A 50/51R 10-40 300/5 C WESTINGHOUSE 1875286A 1875286A 50/51R 10-40 300/5 50/51R 10-40 300/5 B GROUND 1875286A DQAJAIH 50/51G 0.5-4 300/5

SETTING TAP TIME INSTANTENOUS 5 1.5 40 5 1.5 40 5 1.5 40 1 1.5 40

E.5.2. FEEDER V RELAYS PHASE MAKE STYLE NO MODEL FUNCTION TIME ELEMENT INSTANTENEOUS RATING C.T. RATIO A 1212651B4A 50/51R 10-40 10-40A 300/5 SPECIFICATION B C G. E. 1212651B4A 1212651B4A 50/51R 10-40 10-40A 300/5 50/51R 10-40 10-40A 300/5 GROUND 1212651B4A 50/51G 10-40 300/5

SETTING TAP TIME INSTANTENOUS 5 1.5 40 5 1.5 40 5 1.5 40 5 1.5 40

F. ROSALES S/S LOCATION F.1. 69 KV SURGE ARRESTER MAKE TYPE SERIAL NO. MCOV FREQUENCY BIL MAX. INTERRUPTING CURRENT INSULATOR HIGHEST SYSTEM VOLTAGE RATED NOMINAL VOLTAGE F.2. 69 KV POTENTIAL TRANSFORMER MAKE TYPE SERIAL NO. NSV BIL RATIO PRI : SEC RATIO PRI : TER FREQUENCY ACCURACY THERMAL RATING TEMP RISE OIL QUANTITY TOTAL WEIGHT F.3. 69 KV CURRENT TRANSFORMER MAKE TYPE SERIAL NO. NSV BIL RATIO R.F @ 30 C ACCURACY I THERMAL 1 SEC RMS KA TEMP RISE I MECH RMS KA TOMANA, ROSALES (3 Units IDENTICAL) BOWTHROPE MBA2-60 S855/S854/ 46 KV 60 HZ 350 KV 10 KA PORCELAIN 72 KV 60 KV (3 Units IDENTICAL) ASSOCIATED ENGINEERING COMPANY POF-350 AE1031469614/AE1031469613/AE103146910 69 KV 350 KV 350/600:1 350/600:1 60 HZ 0.3 6000 VA 55 C 300 GALS 700 LBS (3 Units IDENTICAL) ASSOCIATED ENGINEERING COMPANY IK-350 AE1040889712/AE1040889708/AE1040889713 69 KV 350 KV 50X100:5 1.5 60 HZ 0.3 3X6 55 C

OIL QUANTITY TOTAL WEIGHT

4X8 78 GALS 700 LBS

F.4. 69 KV AIR BREAK SWITCH MAKE TYPE SERIAL NO. RATED VOLATGE MAXIMUM VOLTAGE NOMINAL CURRENT BIL MOMENTARY INTERRUPTING CURRENT INSTALLATION NO OF POLES INSULATOR TYPE OF OPERATING MECHANISM CLEAVELAND/PRINCE V2-C 171293A 69 KV 72.5 KV 600 A 350 KV 10 KA VERTICAL BREAK DISCONNECT THREE (3) PORCELAIN MAIN DISCONNECT SWITCH MANUAL TYPE

F.5. SF6 GAS CIRCUIT BREAKER MAKE SERIAL NUMBER RATED MAX VOLTS RATED CONT. CURRENT FREQUENCY FILL PRESSURE @ 20 C RATED OPERATING PRESS. @ 20 C SF6 ALARM RESSURE @ 20 C SF6 CUTOUT PRESSURE @ 20 C SF6 VOLUME @ 20 C SF6 MASS @ 20 C RATED VOLT RANGE FACTOR RATED SHORT CURRENT RATED OUTPHASE CURRENT FULL WAVE IMPULSE VOLT W/STAND WT. OF BREAKER W/ GAS LINE CHARGING OVER VOLTGAE FACTOR ISOLATED BANK SW. INRUSH PEAK INRUSH FREQ DATE MANUFACTURED DATE ENERGIZED F.6. POWER TRANSFORMER MAKE SERIAL NUMBER CAPACITY % IMPEDANCE RATED VOLTAGE SIEMENS 88819 15/20/25 MVA 12% @ 25 MVA 69000 V 13800 V SIEMENS 52112-1 72.5 KV 1200A 60 HZ 4.48 Bar 4.48 Bar 3.93 Bar 3.52 Bar 244.3 Liters 15 Kg 1.0 (K) 31500A 7900A 350 KV 1633 Kg 100A 2 630A 25000A 3360 HZ 2/16/2001 3/6/2002

H. V. L.V.

RATED CURRENTS

H. V. L.V.

VECTOR GROUP FREQUENCY CLASS PHASE WINDING TEMP. RISE OIL TEMP RISE IMPULSE LEVEL H.V. IMPULSE LEVEL L.V. OIL QUANTITY TOTAL WT UNTANKING WT DATE MANUFACTURED DATE ENERGIZED F.7. AUTOMATIC VOLATGE REGULATOR MAKE SERIAL NUMBER PHASE TYPE CAPACITY VOLTAGE RATING AMPERE RATING BIL CLASS INSULATING FUILD TOTAL WEIGHT UNTANKING WEIGHT OIL LOCATION STATUS DATE MANUFACTURE DATE ENERGIZED F.8. VACUUM CIRCUIT BREAKER MAKE TYPE SERIAL NO. IEC RATED VOLTAGE RATED CURRENT RATED LIGHTNING IMPULSE VOLTAGE RATED SHORT CIRCUIT FREQUENCY F.9. VCB's PROTECTION REALAY MAKE TYPE SERIAL NO. RATED CURRENT In RATED FREQUENCY Fn RATED AUX. VOLTAGE SYSTEM INTERFACE

209 A 1046 A Dyn1 60 HZ ONAN/ONAF/OFAF 3 65 C 60 C 325 KV 95 KV 7500 ltrs 31500 KGS 17500 KGS 2001 3/6/2002 (3 Units IDENTICAL) SIEMEN 7063-1/7063-2/7063-3 SINGLE PHASE JFR 500 KVA 7620 V + 10% in 32-5/8% steps 656 A 95 OA ASTMD-3487 TYPE II MINERAL OIL 4705 LBS. 2321 LBS. 208 GALS ROSALES S/S ENERGIZED 3/13/2001 3/6/2002 (5 Units IDENTICAL) SIEMENS MC21 3AH5/0007/305/306/304/308/307 298 17.5 KV 800 A 95 KV 25 KA 50/60 HZ (5 Unist IDENTICAL) SIEMENS 7SJ6025-4EB11-IFAO/FA1 03059718/20/22/21/23 1A or 5A 50 Hz/60Hz (selectable) 125 Vdc RS232; protocol acc. IEC 60870-5-103

F.10 POWER METER MAKE MODEL OPERATING TEMPERATURE W/ DISPLAY POWER SUPPLY VOLTAGE INPUTS CURRENT INPUTS BAUD RATE FREQUENCY STORAGE TEMP. HUMIDITY DIMENSION WEIGHT

(5 Unist IDENTICAL) SIEMENS 9300 PM 0 C to 50 C 85 to 240 Vac/Vdc 120/277/347 VAC Nominal 1 to 5 Amp. AC up to 19200 bps 50/60 Hz (selectable) -30C to 70C 5% to 95%, non condensing 96mmx162.2mmx96mm 2.2 Kg

Prepared by:

Checked by:

LEO P. AQUINO Electrical Equipment Engineer

Engr. SILVINO R. VILLEGAS EECSD Supervisor

Noted by:

Engr. FERDINAND M. CEREZO ESD Manager

F.1. 69KV SURGE ARRESTER MAKE TYPE RATED VOLATGE MCOV MAXIMUM SYSTEM VOLTAGE FREQUENCY BIL NOMINAL DISCHARGE CURRENT LINE DISCHARGE CLASS

ENERGY DISCHARGE CAPABILITY- T LONG DURATION IMPULSE CURREN SHORT CKT CURRENT-0.2s POWER FREQUENCY WITHSTAND V POWER FREQUENCY WITHSTAND V LIGHTNING IMPULSE WITHSTAND VO MINIMUM CREEPAGE DISTANCE

V SURGE ARRESTER SIEMENS 3EP4 060-1PL2 60 KV 48 KV 72 KV 50/60 HZ 325 KV 10 KA 2

5.0 KJ/KV 500A 65.0 KA 250 KV 200 KV 470 KV 2490 MM