STATION Client: Project: Main Earth Matt Calculations for Station Rev B The earthing calculations have been

done on the basis IEEE guide for safety in AC substation grounding (IEEE std 80-2000) The earthing calculations have been done on the basis of following data : 1 2 3 4 5 6 7 8 9 System Voltage System LT fault current System HT fault current Decrement factor(Df) Current division factor(Sf) Maximum grid current for fault at LT system(IG=If*Df*Sf) Maximum grid current for fault at HT system(IG=If*Df*Sf) Fault duration (ts), for fault at LT system Fault duration (ts), for fault at HT system 0.415 KV 50000 A 1000 1 0.5 25000 A 500 1 1 17 1.5 A Sec Sec ohm-m mtr A

10 Soil resistivity(r) 11 Thickness of ballast surface material/dry concrete(hs) 12 Resistivity of ballast surface material/dry concrete(rs) 13 Size of Yard Length(L) Breadth(B)

10000 ohm-m 10 10 100 8 1.5 mtr mtr Sqm Nos mtr

14 Area of Yard for earthing(L*B) 15 No of ground conductor selected 16 Spacing between parallel conductor(D) 17 Lc =Total length of the hrizontal grid in m Lc=L*(B/D+1)+B*(L/D+1) 18 Lp =Peripheral length of grid in m Lp =2*(L+B) 19 Lr =Length of each ground rod 20 LR =Total length of all ground rod LR=Lr*No of grd. Rod

153.33 mtr

40 3

mtr mtr

24

mtr

CML PROJECT -