Anda di halaman 1dari 1

1.

GENERAL NOTES
A. GROUND SURFACE OR SUBGRADE SURFACE
(BENEATH CUT SECTION) SUPPORT/PROTECTION SYSTEM: DESIGN AS NECESSARY WITH

SEE CHAP. 8, APP. A, OF THE HIGHWAY DESIGN MANUAL FOR MAXIMUM ALLOWABLE HEIGHT OF COVER. WHERE DESIGN INFORMATION INDICATES UNSUITABLE MATERIAL EXISTS AT OR BELOW THE INVERT ELEVATION, SPECIAL DESIGN FEATURES AND CONSTRUCTION TREATMENTS BASED ON SUBSURFACE EXPLORATIONS ARE NECESSARY.

B. GROUND SURFACE SEE NOTE 1.A.

SUFFICIENT DEPTH TO STABILIZE TRENCH BOTTOM

SEE NOTE 1.A. SUITABLE MATERIAL. SEE NOTE 4.A. C. WHERE UNSUITABLE MATERIAL, NOT ANTICIPATED DURING DESIGN, IS ENCOUNTERED AT OR BELOW INVERT ELEVATION, CONSULT WITH THE REGIONAL GEOTECHNICAL ENGINEER FOR TREATMENT RECOMMENDATIONS. PAYMENT LINES FOR TRENCH AND CULVERT EXCAVATION-OG, OR TRENCH AND CULVERT EXCAVATION 300 SEE NOTES 2.A. AND 2.C. 300
c

D. SUBGRADE AREA MATERIAL SEE NOTE 4.A.


B

THE BEDDING CONTROL LINE (BCL) IS A HORIZONTAL LINE LOCATED BELOW THE INVERT WHICH

REPRESENTS THE BOTTOM ELEVATION FOR BEDDING MATERIAL PLACEMENT AND THE TOP ELEVATION OF UNDERCUT BACKFILL WHERE REQUIRED. THE BCL IS ALSO USED FOR QUANTITY PAYMENT PURPOSES FOR "TRENCH AND CULVERT EXCAVATION" ITEMS, BEDDING MATERIAL PLACEMENT, AND
UNDERCUT MATERIAL PLACEMENT. THE LOCATION OF THE BCL AND THE ACTUAL BEDDING THICKNESS

PAYMENT LINES FOR SELECT GRANULAR FILL


SEE NOTES 4.A. AND 4.C.

VARY WITH PIPE SIZE AND WALL THICKNESS. SEE BEDDING THICKNESS TABLE. PAYMENT LINES FOR SELECT GRANULAR FILL D
INVERT T

OUTER BEDDING AREA SEE NOTE 3.D. 0.6B c BEDDING THICKNESS SEE BEDDING TABLES AND NOTE 3.A.

D INVERT T

SEE NOTES 4.A. AND 4.C.

2. EXCAVATION NOTES
A. WHERE A GENERAL EXCAVATION OF UNSUITABLE OR UNSTABLE MATERIAL IS REQUIRED TO EXTEND BEYOND THE LATERAL AND DEPTH LIMITS INDICATED FOR METHOD A-1 OR A-2, THE EXCAVATION WITHIN THE LIMITS SHOWN WILL BE PAID AS "UNCLASSIFIED EXCAVATION AND DISPOSAL" AND THIS QUANTITY WILL BE DEDUCTED FROM THE RESPECTIVE CONTRACT QUANTITIES FOR "TRENCH AND CULVERT EXCAVATION-OG" OR "TRENCH AND CULVERT EXCAVATION". INSTALL THE CULVERT IN
ACCORDANCE WITH DETAILS FOR METHOD B-1 OR B-2 AS SHOWN ON THE PLANS.

MIDDLE BEDDING SEE NOTE 3.C. B /3 c

BEDDING CONTROL LINE. SEE NOTE 1.D.

B /3 c

MIDDLE BEDDING SEE NOTE 3.C.

B.

WHERE A STABLE WORKING PLATFORM MUST FIRST BE ESTABLISHED OVER A SUBMERGED OR UNSTABLE SURFACE, THE ENGINEER MAY SPECIFY A LOWER EMBANKMENT LEVEL FOR INITIATING THE EXCAVATION FOR THE PIPE. IN THIS CASE, COMPLETE THE REMAINDER OF THE INSTALLATION ABOVE THE "WORKING PLATFORM" USING METHOD B-1.

UNDERCUT BACKFILLED WITH SELECT GRANULAR FILL

SEE NOTE 3.B. MINIMUM WIDTH - SEE BEDDING TABLES

MINIMUM WIDTH - SEE BEDDING TABLES

C.

FOR PIPE INSTALLED IN A ROCK TRENCH, SIDE PAYMENT LINES FOR TRENCH EXCAVATION ARE THE SAME AS SHOWN FOR INSTALLATION METHODS A-1 AND A-2. THE PAYMENT LINE FOR DEPTH OF
EXCAVATION IS THE DEPTH NEEDED TO PLACE THE BEDDING MATERIAL AND THE UNDERCUT BACKFILL

MATERIAL, SELECT GRANULAR FILL.

INSTALLATION METHOD A-1


TRENCH AREA BENEATH ROADWAYS, PAVEMENTS, AND SURFACE LOADS.
NOT TO SCALE

USE AND PAY FOR METHOD A-2 ONLY WHERE SPECIFIED IN THE CONTRACT DOCUMENTS OR APPROVED BY THE ENGINEER.

INSTALLATION METHOD A-2


TRENCH AREAS NOT SUBJECT TO SURFACE LOADS; TRENCH AREAS NOT SENSITIVE TO SETTLEMENT.
NOT TO SCALE

D.

THE MINIMUM TRENCH WIDTH MAY BE ADJUSTED TO (B + 150 mm), IF CONTROLLED LOW STRENGTH c MATERIAL (CLSM) IS TO BE USED AS BACKFILL. SEE MINIMUM BEDDING WIDTH TABLE.

3. BEDDING NOTES
A. USE THE BEDDING THICKNESS TABLE TO DETERMINE THE LOCATION OF THE BEDDING CONTROL LINE (BCL) AND THE MINIMUM BEDDING THICKNESS FOR THE GIVEN PIPE SIZE. COMPUTE THE ACTUAL BEDDING THICKNESS AS THE DISTANCE FROM INVERT TO BCL MINUS THE PIPE WALL THICKNESS.

TOP OF EMBANKMENT SEE NOTE 1.A. B. TO ESTABLISH STABLE BEDDING CONDITIONS, AN UNDERCUT BACKFILLED WITH SELECT GRANULAR FILL MATERIAL MAY BE ORDERED BY THE ENGINEER. THE MINIMUM DEPTH OF UNDERCUT AS MEASURED FROM THE BCL IS 300 mm AND THE MAXIMUM IS 600 mm.
1.5D OR 0.5D + 1500 1.5D OR 0.5D + 1500

VARIES

WHICHEVER IS LESS

OR FLATTER
5H ON 1V

WHICHEVER IS LESS

VARIES

MAXIMUM EMBANKMENT LEVEL BEFORE EXCAVATING FOR PIPE INSTALLATION, SEE NOTE 2.B. 600 mm MIN. SEE NOTE 5.B. C. LOOSELY PLACE SELECT GRANULAR FILL IN MIDDLE BEDDING AREA (B /3). DO NOT COMPACT MIDDLE c BEDDING AREA. D. COMPACT THE OUTER BEDDING AREAS IN CONFORMANCE WITH THE REQUIREMENTS OF y203-3.15 OF
NYSDOT STANDARD SPECIFICATIONS.

600 mm MIN. SEE NOTE 5.B.


300 MAX OR TO
5.A. NOTE SEE REQUIRED. IF RAMPS

300 MAX OR TO Bc

SUBGRADE SURFACE WHICHEVER IS LESS VERTICAL PAYMENT LINE.


SIMULTANEOUSLY PLACE SUITABLE MATERIAL

SUBGRADE SURFACE WHICHEVER IS LESS

4. BACKFILL NOTES
A. COMPACT IN CONFORMANCE WITH THE REQUIREMENTS OF STANDARD SPECIFICATIONS y203-3.15.

SUITABLE MATERIAL - SEE NOTE 4.B.

SUBGRADE AREA MATERIAL - SEE NOTE 4.A. SIDE PAYMENT LINE D T 0.6B c INVERT BEDDING THICKNESS SEE BEDDING TABLES AND NOTE 3.A.
PAYMENT LINES FOR SELECT GRANULAR FILL - SEE NOTE 4.A.

B. COMPACT IN CONFORMANCE WITH THE REQUIREMENTS OF STANDARD SPECIFICATIONS y203-3.12. D T INVERT 0.6B c SEE INSTALLATION METHODS A-1 AND A-2.
C. CONTROLLED LOW STRENGTH MATERIAL (CLSM) PLACED IN CONFORMANCE WITH THE REQUIREMENTS

IN CONTACT WITH SELECT GRANULAR FILL AND SUBGRADE AREA MATERIAL. SHEETING OR OTHER MEANS TO SEPARATE MATERIALS WILL NOT BE ALLOWED. SEE NOTE 5.C.

OF SECTION 204 OF THE STANDARD SPECIFICATIONS AND APPLICABLE CLSM STANDARD SHEET MAY BE USED IN METHODS A-1, A-2 OR B-2.

5. CONSTRUCTION OPERATION NOTES


A.

B /3 c OUTER BEDDING AREA SEE NOTE 3.D.


MINIMUM WIDTH - SEE BEDDING TABLES

BEDDING CONTROL LINE. SEE NOTE 1.D.

AT THE CONTRACTORS RISK, CONSTRUCTION EQUIPMENT MAY BE ALLOWED TO CROSS OVER A PIPE INSTALLATION USING RAMPS CONSTRUCTED AS SHOWN IN METHOD B-1 OR B-2 COMPACTED IN CONFORMANCE WITH THE REQUIREMENTS OF y203.3-12 OF NYSDOT STANDARD SPECIFICATIONS. ALL RAMPS WHICH CANNOT BE USED AS PART OF THE COMPLETED EMBANKMENT ARE INSTALLED AND REMOVED AT THE CONTRACTORS EXPENSE. ANY PIPE OR STRUCTURE DAMAGED OR DISTURBED BY THESE ACTIVITIES MUST BE REPLACED BY THE CONTRACTOR AT NO EXPENSE TO THE STATE.

B /3 c OUTER BEDDING AREA

MIDDLE BEDDING - SEE NOTE 3.C. MINIMUM WIDTH - SEE BEDDING TABLES

SEE NOTE 3.D.

USE AND PAY FOR METHOD B-2 ONLY WHERE SPECIFIED IN THE CONTRACT DOCUMENTS OR APPROVED BY THE ENGINEER. WHERE THE CONTRACTOR

B.

SEE PROOF ROLLING RESTRICTIONS IN y203-3.13E OF NYSDOT STANDARD SPECIFICATIONS.

INSTALLATION METHOD B-1


BEFORE EMBANKMENT
NOT TO SCALE

OTHERWISE ELECTS TO USE METHOD B-2, PAYMENT FOR THE INSTALLATION WILL BE BASED ON METHOD B-1.

INSTALLATION METHOD B-2


AFTER EMBANKMENT
NOT TO SCALE

C.

THE CONTRACTOR, WITH THE APPROVAL OF THE ENGINEER, MAY PLACE A TRAPEZOIDAL SECTION OF SELECT GRANULAR FILL AROUND THE PIPE IN LIEU OF SIMULTANEOUS PLACEMENT WITH SUITABLE MATERIAL. THE MINIMUM DIMENSIONS OF THE TRAPEZOID MUST ENCOMPASS THE PAYMENT LINES FOR THE SELECT GRANULAR FILL AND SUBGRADE AREA MATERIAL AS SHOWN ON INSTALLATION METHOD B-1. NO PAYMENT WILL BE MADE UNDER THIS OPTION FOR SELECT GRANULAR FILL PLACED OUTSIDE THE LIMITS OF INSTALLATION METHOD B-1.

BEDDING THICKNESS TABLE


FOUNDATION TYPE PIPE DIAMETER OR SPAN (mm)

SEE NOTE 1.D. B c 300 < D D < 600 600 < D D < 900 900 < D D < 1200 1200 < D D < 1500 1500 < D D < 1800 1800 < D D < 2100 2100 < D D < 2400 2400 < D D < 2700 2700 < D D < 3300 3300 < D D < 3600 RISE B c FOUNDATION TYPE RISE OUTER RISE SPAN 600 OR LESS SOIL GREATER THAN 600 B + 2*D OR c Bc + 2*SPAN B + 1200 c
PIPE DIAMETER "D"

MINIMUM BEDDING WIDTH TABLE


SEE NOTE 2.D.

NOTE: ALL DIMENSIONS IN MILLIMETERS UNLESS OTHERWISE NOTED

D < 300

STATE OF NEW YORK DEPARTMENT OF TRANSPORTATION


WIDTH METRIC STANDARD SHEET

DISTANCE (mm) SOIL INVERT TO BCL MINIMUM THICKNESS DISTANCE (mm) ROCK INVERT TO BCL MINIMUM THICKNESS

125

150

175

200

225

275

300

325

375

450

500

OR SPAN (mm)

75

75

75

75

75

75

100

125

125

150

175

SPAN

200

225

250

275

300

350

400

450

500

625

675

INSTALLATION DETAILS FOR REINFORCED CONCRETE PIPES


(SHEET 1 OF 1) APPROVED /S/ P.J. CLARK , 2003

150

150

150

150

150

150

200

250

250

325

350 ROCK ALL SIZES B + 600 c

TABLE VALUES ARE BASED ON WALL B THICKNESS FOR CIRCULAR PIPE.

VE PIPE

HE PIPE
B IS OUT-TO-OUT SPAN IN mm. c

ISSUED UNDER EB 03-010 EFFECTIVE: SEPT. 11, 2003

FOR VERTICAL ELLIPTICAL PIPE, AN INCREASE OF ALL TABLE VALUES BY 25 mm IS REQUIRED. FOR HORIZONTAL ELLIPTICAL PIPE: A DEDUCTION OF 25 mm FROM TABLE VALUES IS ALLOWED FOR SPANS GREATER THAN 1200 mm, A DEDUCTION OF 50 mm FROM TABLE VALUES IS ALLOWED FOR SPANS GREATER THAN 2700 mm.

REFERENCE DIMENSIONS FOR ELLIPTICAL PIPE

DEPUTY CHIEF ENGINEER

M203-4R1