Basic Formulas

AIR
Sensible (Dry) Heat or Cooling q (btu/hour) = 1.08 x CFM x delta T Where: q = rate of heat transfer in btu/hour CFM = volume or quantity of air flow delta T = temperature difference (F) Latent (Wet) Heat or Cooling ql (btu/hour) = 0.69 x CFM x delta W Where: ql = rate of heat transfer in btu/hour CFM = volume or quantity of air flow delta W = humidity ration difference (grains/lb) Total Heat or Cooling qt (btu/hour) = 4.5 x CFM x delta h

Where: qt = rate of heat transfer in btu/hour CFM = volume or quantity of air flow delta h = enthalpy difference (btu/lb)

WATER
Total Cooling / Sensible Heating q (btu/hour) = 500 x GPM x delta T Where: q = rate of heat transfer in btu/hour GPM = volume or quantity of waterflow Delta T = temperature difference