CORRIENTE (AMP)

DESCRIPCION

ACOMETIDA DESDE LINEA DE 14.4 Kv

KVA

Tension (V)

112.50

480

I (100%)

I (110%)

CONDUCTOR POR CORRIENTE


I (125%)

155.54 171.09 194.42

Conductor X Caida de Tension

CondxFase

Conductores

Calibre

Caida %

Distancia (m)

Caida %

Calibre

3X2/0

3.5%

200

4.0%

3X1/0

Calibre final

DUCTO A
EMPLEAR

3X2/0

1 DE 3"

fp
theta
sen (theta)

0.87
0.52
0.49

temp
factor

PARA TENER VALORES REALES DE LA IMPEDANCIA DE


INSERTAR EL FP, IGUALMENTE PARA LA CORRIENTE DE
QUE INSERTAR LA TEMPERATURA AMBIENTE PARA APL

40
0.91

three single conductors In Steel


Capacidad de Capacidad de
corriente
Corriente a 90C
corregida (A)
(A)
Calibre

22.75
27.30
36.40
50.05
68.25
86.45
118.30
136.50
154.70
177.45
204.75
236.60
263.90
291.20
318.50
345.80
391.30
473.20
486.85
559.65
22.75
27.30
36.40
50.05
68.25
86.45
118.30
136.50
154.70
177.45
204.75
236.60
263.90
291.20
318.50
345.80
391.30
22.75
27.30
36.40
50.05

conduit
R

XL

three single conductors In PVC


conduit

XL

25

14

2.90

1.45

6.61

W/1000 ft W/1000 ft W/1000 ft W/1000 ft


0.073
3.1
2.733
0.058

30

12

3.38

1.69

8.97

0.068

1.774

0.054

40

10

4.26

2.13

14.25

0.063

1.2

1.075

0.05

55

5.50

2.75

23.76

0.065

0.78

0.711

0.052

75

6.41

3.21

32.27

0.064

0.49

0.458

0.051

95

8.18

4.09

52.55

0.06

0.31

0.299

0.048

130

9.65

4.83

73.14

0.057

0.2

0.202

0.045

150

11.20

5.60

98.52

0.056

0.15

0.158

0.0445

170

1/0

12.20

6.10

116.90

0.055

0.12

0.132

0.044

195

2/0

13.30

6.65

138.93

0.054

0.1

0.114

0.043

225

3/0

14.60

7.30

167.42

0.052

0.079

0.094

0.042

260

4/0

16.00

8.00

201.06

0.051

0.063

0.080

0.041

290

250

17.80

8.90

248.85

0.052

0.054

0.073

0.041

320

300

19.10

9.55

286.52

0.051

0.045

0.064

0.041

350

350

20.40

10.20

326.85

0.05

0.039

0.059

0.04

380

400

21.50

10.75

363.05

0.049

0.035

0.055

0.04

430

500

23.70

11.85

441.15

0.048

0.029

0.049

0.039

520

600

26.20

13.10

539.13

0.048

0.025

0.045

0.039

535

750

28.80

14.40

651.44

0.048

0.021

0.042

0.038

615

1000

32.60

16.30

834.69

0.046

0.018

0.038

0.037

25

2X14

12.70

6.35

126.68

0.073

3.1

2.733

0.058

30

2X12

14.40

7.20

162.86

0.068

1.774

0.054

40

2X10

15.70

7.85

193.59

0.063

1.2

1.075

0.05

55

2X8

16.70

8.35

219.04

0.065

0.78

0.711

0.052

75

2X6

18.50

9.25

268.80

0.064

0.49

0.458

0.051

95

2X4

22.50

11.25

397.61

0.06

0.31

0.299

0.048

130

2X2

26.90

13.45

568.32

0.057

0.2

0.202

0.045

150

2X1

30.90

15.45

749.91

0.056

0.15

0.158

0.0445

170

2X1/0

32.90

16.45

850.12

0.055

0.12

0.132

0.044

195

2X2/0

35.20

17.60

973.14

0.054

0.1

0.114

0.043

225

2X3/0

37.70

18.85

1116.28

0.052

0.079

0.094

0.042

260

2X4/0

40.50

20.25

1288.25

0.051

0.063

0.080

0.041

290

2X250

44.50

22.25

1555.29

0.052

0.054

0.073

0.041

320

2X300

47.75

23.88

1790.76

0.051

0.045

0.064

0.041

350

2X350

51.00

25.50

2042.83

0.05

0.039

0.059

0.04

380

2X400

53.75

26.88

2269.07

0.049

0.035

0.055

0.04

430

2X500

59.25

29.63

2757.20

0.048

0.029

0.049

0.039

25

3X14

13.30

6.65

138.93

0.073

3.1

2.733

0.058

30

3X12

15.10

7.55

179.08

0.068

1.774

0.054

40

3X10

16.50

8.25

213.83

0.063

1.2

1.075

0.05

55

3X8

17.70

8.85

246.06

0.065

0.78

0.711

0.052

D (mm)

R (mm)

A (mm^2)

68.25
86.45
118.30
136.50
154.70
177.45
204.75
236.60
263.90
291.20
318.50
345.80
391.30
22.75
27.30
36.40
50.05
68.25
86.45
118.30
136.50
154.70
177.45
204.75
236.60
263.90
291.20
318.50
345.80
391.30

75

3X6

19.70

9.85

304.81

0.064

0.49

0.458

0.051

95

3X4

25.30

12.65

502.73

0.06

0.31

0.299

0.048

130

3X2

28.50

14.25

637.94

0.057

0.2

0.202

0.045

150

3X1

32.80

16.40

844.96

0.056

0.15

0.158

0.0445

170

3X1/0

35.00

17.50

962.12

0.055

0.12

0.132

0.044

195

3X2/0

37.40

18.70

1098.59

0.054

0.1

0.114

0.043

225

3X3/0

40.10

20.05

1262.93

0.052

0.079

0.094

0.042

260

3X4/0

43.20

21.60

1465.74

0.051

0.063

0.080

0.041

290

3X250

50.80

25.40

2026.83

0.052

0.054

0.073

0.041

320

3X300

54.70

27.35

2349.99

0.051

0.045

0.064

0.041

350

3X350

58.85

29.43

2720.09

0.05

0.039

0.059

0.04

380

3X400

60.10

30.05

2836.87

0.049

0.035

0.055

0.04

430

3X500

66.30

33.15

3452.37

0.048

0.029

0.049

0.039

25

4X14

14.40

7.20

162.86

0.073

3.1

2.733

0.058

30

4X12

16.30

8.15

208.67

0.068

1.774

0.054

40

4X10

17.90

8.95

251.65

0.063

1.2

1.075

0.05

55

4X8

19.50

9.75

298.65

0.065

0.78

0.711

0.052

75

4X6

22.70

11.35

404.71

0.064

0.49

0.458

0.051

95

4X4

27.60

13.80

598.29

0.06

0.31

0.299

0.048

130

4X2

31.20

15.60

764.54

0.057

0.2

0.202

0.045

150

4X1

36.00

18.00

1017.88

0.056

0.15

0.158

0.0445

170

4X1/0

38.40

19.20

1158.12

0.055

0.12

0.132

0.044

195

4X2/0

41.20

20.60

1333.17

0.054

0.1

0.114

0.043

225

4X3/0

44.20

22.10

1534.39

0.052

0.079

0.094

0.042

260

4X4/0

49.60

24.80

1932.21

0.051

0.063

0.080

0.041

290

4X250

55.18

27.59

2391.41

0.052

0.054

0.073

0.041

320

4X300

59.21

29.61

2753.47

0.051

0.045

0.064

0.041

350

4X350

63.24

31.62

3141.05

0.05

0.039

0.059

0.04

380

4X400

66.65

33.33

3488.92

0.049

0.035

0.055

0.04

430

4X500

73.47

36.74

4239.46

0.048

0.029

0.049

0.039

REALES DE LA IMPEDANCIA DEL CABLE HAY QUE


MENTE PARA LA CORRIENTE DEL CABLE HAY
PERATURA AMBIENTE PARA APLICAR FACTOR DE

three single conductors In PVC


conduit
R

TUBERIA
Z

W/1000 ft W/1000 ft
3.1
2.726

1/2"

12.7

6.4

126.7

1.767

3/4"

19.1

9.5

285.0

1.2

1.069

1"

25.4

12.7

506.7

0.78

0.704

1-1/2"

38.1

19.1

1140.1

0.49

0.451

2"

50.8

25.4

2026.8

0.31

0.293

2-1/2"

63.5

31.8

3166.9

0.19

0.187

3"

76.2

38.1

4560.4

0.16

0.161

3-1/2"

88.9

44.5

6207.2

0.12

0.126

4"

101.6

50.8

8107.3

0.1

0.108

4-1/2"

114.3

57.2

10260.9

0.077

0.088

5"

127.0

63.5

12667.7

0.062

0.074

5-1/2"

139.7

69.9

15327.9

0.052

0.065

6"

152.4

76.2

18241.5

0.044

0.058

0.038

0.053

0.033

0.048

25

1,04

21-25

0.027

0.043

26

26-30

0.023

0.039

30

26-30

0.019

0.035

31

0.96

31-35

0.015

0.031

35

0.96

31-35

3.1

2.726

36

0.91

36-40

1.767

40

0.91

36-40

1.2

1.069

41

0.87

41-45

0.78

0.704

45

0.87

41-45

0.49

0.451

46

0.82

46-50

0.31

0.293

50

0.82

46-50

0.19

0.187

51

0.76

51-55

0.16

0.161

55

0.76

51-55

0.12

0.126

56

0.71

56-60

0.1

0.108

60

0.71

56-60

0.077

0.088

61

0.58

61-70

0.062

0.074

70

0.58

61-70

0.052

0.065

71

0.41

71-80

0.044

0.058

80

0.41

71-80

0.038

0.053

0.033

0.048

0.027

0.043

3.1

2.726

1.767

1.2

1.069

0.78

0.704

TIPO

T Ambiente

D (mm)

Factor a 90

R (mm)

T Ambiente

A (mm^2)

0.49

0.451

0.31

0.293

0.19

0.187

0.16

0.161

0.12

0.126

0.1

0.108

0.077

0.088

0.062

0.074

0.052

0.065

0.044

0.058

0.038

0.053

0.033

0.048

0.027

0.043

3.1

2.726

1.767

1.2

1.069

0.78

0.704

0.49

0.451

0.31

0.293

0.19

0.187

0.16

0.161

0.12

0.126

0.1

0.108

0.077

0.088

0.062

0.074

0.052

0.065

0.044

0.058

0.038

0.053

0.033

0.048

0.027

0.043