By:

Anish Shrivastava

1769-L35E-CompactLogix5335E Controller 1769-SM2Module

AK-U0-RJ45-TB2P (RJ45 RS485 Splitter)

Modbus Slaves
Modbus RTU Network

Modbus Cable

PCS Controller PPI-402

Conzerv EM6400

SIPROTEC 4 7SJ61 Multifunction Protection Relay

Setting the Configuration Mode Switch in 1769 SM2 Module

Before installing the module, make sure its Configuration Mode Switch is correctly set.

SW1 Setting
CONT (Controller) back position PARAM (Parameter) front position

Description
Default settingThe 1769-SM2 module uses the configuration data downloaded from the controller on power-up and when the controller is placed in run mode. The 1769-SM2 module uses its internal parameter settings to configure the module.

SW2 Setting
Single Position (For Single drive per channel) Multi-Drive Position (For Max 5 drives per channel or up 31 RTU slave devices per channel)

Select SW1 in Controller Position and SW2 in Multi-Drive Position.

Configuration and Logic

Module Configuration In Logic

Configuration and Logic

Module Configuration In Logic

1769-SM2 Module Configuration Data

Configuration and Logic

Configuration and Logic

1769-SM2 Module Configuration Data Table

RTU Baud Rate Configuration

e.g.: For baud rate 9600 bits/sec select value 2.

RTU Format Configuration


Where The RTU format consists of three components: data bits (8 data bits only), parity (None, Even or Odd), and stop bits (1 or 2).

e.g.: For None parity and 2 stop bits select value 3.

Logic for reading olding Register data of RTU Devices

Configuration and Logic

Logic for reading olding Register data of RTU Devices

Configuration and Logic

Configuration and Logic


Logic for reading olding Register data of RTU Devices

Path Format: Module Name, 2, Channel No.

Logic for reading olding Register data of RTU Devices

Configuration and Logic

Notes

Slave Device ID, Function Code, Register Address and Length may vary according to the slave devices parameters. Please select the proper data for slave devices otherwise communication fails.

To check slave device parameters use ModScan32 if available.

AK-U0-RJ45-TB2P (RJ45 RS485 Connector) Pin Out:

References
1769 SM 2 Module User Manual
(http://literature.rockwellautomation.com/idc/groups/literature/documents/um/1769-um013_-enp.pdf)

THE END