RCI9H is intended to be used together with the Neles ValvGuard VG9000H safety valve controller. It is needed when a 24 VDC output (DO) is used in the safety system. RCI9H also includes an isolated barrier and can thus also be used for intrinsically safe applications. RCI9H provides HART communication for diagnostics and configuration of the VG9000H. The HART communication is available when a 24 VDC power supply is connected, also during the emergency trip.
FEATURES
24 VDC input from ESD 4/20 mA output to VG9000H Isolated barrier Line fault detection (LFD) Up to SIL3 acc. to IEC 61508
IEC61508 certificate
RCI9H is approved by exida to be used in safety applications up to and including safety integrity level 3 (SIL3).
9 RCI 20 EN 11/2012
METSO
9 RCI 20 EN
Ambient conditions
-20...+60 C
Mechanical specifications
Protection degree Mass Dimensions Mounting IP20 approx. 150 g 20 x 119 x 115 mm on 35 mm DIN mounting rail
Output (VG9000H)
Connection Current Output voltage Load Response time Line fault detection terminals 1+, 3(terminals 1+, 2 for test loop) 1-signal: 20.4 mA 0-signal: 4.2 mA > 13.5 V at 20.4 mA 650 input to output < 40 ms short circuit voltage < 1 V, open circuit voltage > 16 V
HART
Connection terminal 7: source (-) or sink (+) terminal 8: source (+) terminal 9: sink (-) fixed at 11 mA, source or sink mode 9...30 V, sink mode from external supply 600 , source mode, for HART 230
Power supply
Connection Rated voltage Rated current Power consumption: Power Rail or terminals 14+, 1519...30 V DC (nominal 24 VDC) < 35 mA < 0.8 W
Electrical isolation
Input/power supply functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Equipment Voltage Current Power Supply Maximum safe voltage Um 253 V (Attention! The rated voltage can be lower.) Input Maximum safe voltage Um 253 V (Attention! The rated voltage can be lower.) Collective error indication Maximum safe voltage Um 253 V (Attention! The rated voltage can be lower.) ATEX PF 09 CERT 1438 X Ex II 3G Ex nA II T4 Electrical isolation Output/other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V Directive conformity Directive 94/9/EC EN 60079-0, EN 60079-11, EN 60079-15, EN 60079-26, EN 61241-0, EN 61241-11
International approvals
IECEx CES 09.0008 IEC61508 certified by exida up to and including SIL3
Directive conformity
Electromagnetic compatibility Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21: 2006 Protection degree IEC 60529: 2001
9 RCI 20 EN
KFD2-RCI-Ex1
II
Wiring connections
1+
10+
V
HART
2 3117 8+
914+ 15-
24 V DC
ERR 24 V DC
Zone 0, 1, 2
Power Rail
Zone 2
Dimensions (mm)
HART
114.16 109.16 20