Short-Circuit Analysis
Types of SC Faults
Three-Phase Ungrounded Fault Three-Phase Grounded Fault Phase to Phase Ungrounded Fault Phase to Phase Grounded Fault Phase to Ground Fault
Fault Current
IL-G can range in utility systems from a few percent to possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all faults).
In industrial systems the situation IL-G > I3-phase is rare. Typically IL-G .87 * I3-phase
In an industrial system, the three-phase fault condition is frequently the only one considered, since this type of fault generally results in Maximum current.
1996-2010 ETAP/Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI Slide 2
Slide 7
Short-Circuit Phenomenon
v(t)
i(t)
)
v(t) Vm Sin( t
Slide 8
v(t)
i(t)
Slide 9
DC Current
Slide 10
Slide 11
Machine Reactance ( = L I )
AC Decay Current
Slide 12
Slide 13
ANSI
2) The ANSI standards handle the dc offset by applying multiplying factors. The ANSI Terms for this current are: Momentary Current Close and Latch Current First Cycle Asymmetrical Current
1996-2010 ETAP/Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI Slide 14
Models
All sources are modeled by an internal voltage behind its impedance. E = Prefault Voltage R = Machine Armature Resistance X = Machine Reactance (Xd, Xd, Xd)
1996-2010 ETAP/Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI Slide 15
Synchronous Generators
Synchronous Generators are modeled in three stages.
Induction Machines
Synchronous Reactance Transient Reactance Subtransient Reactance Treated the same as synchronous motors except they do not contribute to the fault after 2 sec.
Slide 16
Cycle Network
This is the network used to calculate momentary short-circuit current and protective device duties at the cycle after the fault.
1 to 4 Cycle Network
This network is used to calculate the interrupting short-circuit current and protective device duties 1.5-4 cycles after the fault.
30-Cycle Network
This is the network used to calculate the steady-state short-circuit current and settings for over current relays after 30 cycles.
Slide 17
Utility
Xd
Xd
Xd
Turbo Generator
Hydro-Gen with Amortisseur winding Hydro-Gen without Amortisseur winding Condenser Synchronous Motor
Xd
Xd
Xd
Xd
Xd
Xd
0.75*Xd
0.75*Xd
Xd
Xd
Xd
Xd
1.5*Xd
Slide 18
Xd
Xd 1.2*Xd 1.67*Xd
1.5*Xd
1.5*Xd 3.0*Xd
Note: Xd = 1 / LRCpu
Slide 19
HV Circuit Breaker
LV Circuit Breaker
Interrupting Capability
--Fuse
Interrupting Capability
Bus Bracing Instantaneous Settings ---
SWGR / MCC
Relay
---
Slide 20
Fault X/R (Separate R & X Networks) Location of fault (Remote / Local generation)
Comparisons of Momentary capability (1/2 Cycle)
SC Current Duty HV CB Asymmetrical RMS Crest Asymmetrical RMS Crest Symmetrical RMS Asymmetrical RMS Device Rating C&L RMS C&L RMS Asymmetrical RMS
HV Bus
Crest
Symmetrical RMS Asymmetrical RMS
Slide 21
LV Bus
Fault X/R (Separate R & X Networks) Location of Fault (Remote / Local generation) Type and Rating of CB
HV CB
Adj. Symmetrical RMS*** LV CB & Fuse
1996-2010 ETAP/Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI Slide 22
Symmetrical RMS
Slide 23
HV CB Interrupting Duty
Calculate 1 to 4 Cycle Current (Imom, rms, sym) using Cycle Network. Determine Local and Remote contributions (A local contribution is fed predominantly from generators through no more than one transformation or with external reactances in series that is less than 1.5 times generator subtransient reactance. Otherwise the contribution is defined as remote). Calculate no AC Decay ratio (NACD) and multiplying factor MFi NACD = IRemote / ITotal ITotal = ILocal + IRemote (NACD = 0 if all local & NACD = 1 if all remote)
HV CB Interrupting Capability
CB Interrupting kA varies between Max kA and Rated kA as applied kV changes MVAsc capability. ETAPs comparison between CB Duty of Adj. Symmetrical kA and CB capability of Adjusted Int. kA verifies both symmetrical and asymmetrical rating. The Option of C37.010-1999 standard allows user to specify CPT. Generator CB has higher DC rating and is always compared against maximum through SC kA.
1996-2010 ETAP/Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI Slide 25
LV CB Interrupting Duty
LV CB take instantaneous action. Calculate Cycle current Irms, Symm (If) from the cycle network. Calculate X/R ratio and MFi (based on CB type).
Calculate adjusted interrupting current Iadj, rms, symm = MFi * Irms, Symm
Slide 26
Slide 27
L-G Faults
Slide 28
L-G Faults
Symmetrical Components
Slide 29
Sequence Networks
Slide 30
If If
3 Ia 0 3 VPr efault Z1 Z 2 Z0 0
if Zg
Slide 31
Ia 2 If
I a1 3 VPr efault Z1 Z 2
Slide 32
VPr efault Z0 Z 2 Z1 Z0 Z 2 0
if Zg
Slide 33
Slide 34
Slide 35
L-G Faults
L-L-G Faults L-L Faults
One-line diagram displayed results that include: L-G/L-L-G/L-L fault current contributions Sequence voltage and currents
Phase Voltages
1996-2010 ETAP/Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI Slide 36
Slide 37
Slide 38
Slide 39
Slide 40
Transformer Impedance
Reactor Resistance Overload Heater Resistance Adjust Fault Impedance L-G fault Impedance
Slide 41
Tolerance Adjustments
Z 'Transforme r Length 'Cable Z Transforme r * (1 Tolerance ) LengthCable * (1 Tolerance ) LengthTransmissi onLine * (1 Tolerance )
Positive tolerance value is used for IEC Minimum If calculation. Negative tolerance value is used for all other calculations.
Slide 42
Temperature Correction
R 'Copper R ' Alumi (234.5 Tc) ' RBASE * (234.5 Tb) (228.1 Tc) RBASE * (228.1 Tb) Resistance at base tempereatu re
RBASE
R' Resistance at operating temperatur e Tb Conductor base temperatur e in C Tc Conductor temperatur e limit in C
Lump1
Y open grounded
Slide 44
Slide 45
Slide 46
Short-Circuit Alerts
Bus Alert
Protective Device Alert Marginal Device Limit
Slide 47
Bus SC Rating
Type of Device
MV Bus (> 1000 Volts) Momentary Asymmetrical. crest kA Momentary Symmetrical. rms kA LV Bus (<1000Volts) Momentary Asymmetrical. rms kA Bracing Crest Bracing Symmetrical Bracing Asymmetrical
Monitored Parameter
Momentary Asymmetrical. rms kA
Condition Reported
Bracing Asymmetrical
Slide 48
Slide 49
Slide 50