Helwan University Faculty of Engineering-Mataria

Civil Engineering Department Theory & Design of Prestressed Concrete Hatem M. Seliem, Ph.D.

ASSIGNMENT NO. 3 Flexure Design of Prestressed Concrete Beams


Q1: The simply supported beam shown below has a span of 23 m and the crosssection shown. The beam is subjected to a uniform gravitational live-load intensity WL = 26.4 kN/m in addition to its self weigh and superimposed dead loads = 30% of LL. The beam is prestressed with 20 normal-relaxation stressrelieved 13 mm diameter 7-wire strand. Determine the following: 1. The required force at transfer 2. The required force at service load stage knowing that the beam is fully
203 mm 760 mm

prestressed.
152 mm 1270 mm 760 mm
Page 1 of 2

Take the following values as given: fcu = 41 MPa, fcui = 31 MPa, fpu = 2000 MPa, , Losses = 15%
203 mm

1270 mm

ec = 483 mm

23 m

Helwan University Faculty of Engineering-Mataria

Civil Engineering Department Theory & Design of Prestressed Concrete Hatem M. Seliem, Ph.D.

Q2: Solve the example given in the lecture using the simplified code method to determine the ultimate moment capacity.

Q3: Calculate the ultimate moment capacity of a pre-tensioned beam with bonded tendons have the cross-section shown below. Use the following values: Aps = 1780 mm2 fcu = 50 MPa, fpu = 1900 MPa,
150 mm 900 mm

fpy = 1710 MPa, fpe = 1020 MPa


200 mm 900 mm 400 mm
Page 2 of 2

150 mm