DETERMINATION OF ANCHOR BOLTS FOR EQIPMENTS STRUCTURAL STATIC ANALYSIS AND CALCULATION LUGGAGE POINT AWTP Rev. 1.2
PART: 27
BOLTS SPECIFICATION
[mm] Universal Columns 260 UC 89.5 RO Base Frame LUGG-S-DS-2200-20 Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS HH Bolt, 304/316SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS M24 M20
[mm] 260 80
[mm] 150 -
Min. distance between anchors and edge of concrete (Require only for anchors) [mm] 155 -
RO Feed Pump
LUGG-S-D2-2200-01 to 18 Super Titan 300x350-695 DWG. A2E50157 Super Titan 350x400-500 DWG. A2E50158 LUGG-S-DS-3600-13 and 14 LUGG-S-DS-2200-24 and 25 LUGG-S-DS-2200-32 and 33 LUGG-S-DS-2200-39
M30
440
320
210
400
M24
370
250
210
350
M12
270
170
150
250
RO Instrument Panel
M12
270
170
150
250
RO Sample Sink
M16
270
170
150
250
RO Floor Pipe Supports (PS-08F and PS-08G) RO Floor Pipe Supports (PS-08A/B/C/D/E)
Prepared by: Marco Arsovic, MSc Mechanical Engineer
M22
260
150
160
250
LUGG-S-DS-2200-39
M20
260
150
160
250
12/19/2007
Page: 235
Doosan Hydro Technology Tampa Florida, 33619 Phone: (813) 805-8368 Fax: (813) 623-6666
DETERMINATION OF ANCHOR BOLTS FOR EQIPMENTS STRUCTURAL STATIC ANALYSIS AND CALCULATION LUGGAGE POINT AWTP Rev. 1.2
PART: 27
BOLTS SPECIFICATION
LENGTH
[mm] RO Floor Pipe Supports (PS-25) CIP Floor Pipe Supports (PS-30, PS31, PS-32A, PS-32B, PS-33, PS-34) CIP Pump & Heater Frame LUGG-S-DS-2200-39 Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS M16
[mm] 260
[mm] 150
Min. distance between anchors and edge of concrete (Require only for anchors) [mm] 160
LUGG-S-DS-3600-10 to 12
M22
260
150
160
250
LUGG-S-DS-3600-01 to 04
Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS HH Bolt, 304/316SS
M16
270
160
150
250
LUGG-S-DS-3600-05 to 08
M16 M12
270 65
160 -
150 -
250 -
12/19/2007
Page: 236
Doosan Hydro Technology Tampa Florida, 33619 Phone: (813) 805-8368 Fax: (813) 623-6666
DETERMINATION OF ANCHOR BOLTS FOR EQIPMENTS STRUCTURAL STATIC ANALYSIS AND CALCULATION LUGGAGE POINT AWTP Rev. 1.2
PART: 27
BOLTS SPECIFICATION
LENGTH
CIP Pump CIP Inline Heater Energy Recovery Turbine CIP Tank
HH Bolt, 304/316SS HH Bolt, 304/316SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS
[mm] 70 70
[mm] -
Min. distance between anchors and edge of concrete (Require only for anchors) [mm] -
M12
270
170
150
250
12/19/2007