Doosan Hydro Technology Tampa Florida, 33619 Phone: (813) 805-8368 Fax: (813) 623-6666

DETERMINATION OF ANCHOR BOLTS FOR EQIPMENTS STRUCTURAL STATIC ANALYSIS AND CALCULATION LUGGAGE POINT AWTP Rev. 1.2

PART: 27

27. BOLTS SPECIFICATION


Note: Thickness of the Grout should not exceed 50mm.

BOLTS SPECIFICATION

DIAMETER LENGTH EQUIPMENT DWG. No. BOLT TYPE

MIN. EMBED. DEPTH

[mm] Universal Columns 260 UC 89.5 RO Base Frame LUGG-S-DS-2200-20 Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS HH Bolt, 304/316SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS M24 M20

[mm] 260 80

[mm] 150 -

Min. distance between anchors and edge of concrete (Require only for anchors) [mm] 155 -

Min. depth of concrete (Require only for anchors) [mm] 400 -

RO Feed Pump

RO Booster Pump CIP Instrument Panel

LUGG-S-D2-2200-01 to 18 Super Titan 300x350-695 DWG. A2E50157 Super Titan 350x400-500 DWG. A2E50158 LUGG-S-DS-3600-13 and 14 LUGG-S-DS-2200-24 and 25 LUGG-S-DS-2200-32 and 33 LUGG-S-DS-2200-39

M30

440

320

210

400

M24

370

250

210

350

M12

270

170

150

250

RO Instrument Panel

M12

270

170

150

250

RO Sample Sink

M16

270

170

150

250

RO Floor Pipe Supports (PS-08F and PS-08G) RO Floor Pipe Supports (PS-08A/B/C/D/E)
Prepared by: Marco Arsovic, MSc Mechanical Engineer

M22

260

150

160

250

LUGG-S-DS-2200-39

M20

260

150

160

250

12/19/2007

Page: 235

Doosan Hydro Technology Tampa Florida, 33619 Phone: (813) 805-8368 Fax: (813) 623-6666

DETERMINATION OF ANCHOR BOLTS FOR EQIPMENTS STRUCTURAL STATIC ANALYSIS AND CALCULATION LUGGAGE POINT AWTP Rev. 1.2

PART: 27

Note: Thickness of the Grout should not exceed 50mm.

BOLTS SPECIFICATION

DIAMETER EQUIPMENT Equipment DWG. No. BOLT TYPE

LENGTH

MIN. EMBED. DEPTH

[mm] RO Floor Pipe Supports (PS-25) CIP Floor Pipe Supports (PS-30, PS31, PS-32A, PS-32B, PS-33, PS-34) CIP Pump & Heater Frame LUGG-S-DS-2200-39 Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS M16

[mm] 260

[mm] 150

Min. distance between anchors and edge of concrete (Require only for anchors) [mm] 160

Min. depth of concrete (Require only for anchors) [mm] 250

LUGG-S-DS-3600-10 to 12

M22

260

150

160

250

LUGG-S-DS-3600-01 to 04

Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS HH Bolt, 304/316SS

M16

270

160

150

250

CIP Cartridge Frame

LUGG-S-DS-3600-05 to 08

M16 M12

270 65

160 -

150 -

250 -

CIP Cartridge Filter

S6GLH36-126-4-12F-IP DWG. R000947

Prepared by: Marco Arsovic, MSc Mechanical Engineer

12/19/2007

Page: 236

Doosan Hydro Technology Tampa Florida, 33619 Phone: (813) 805-8368 Fax: (813) 623-6666

DETERMINATION OF ANCHOR BOLTS FOR EQIPMENTS STRUCTURAL STATIC ANALYSIS AND CALCULATION LUGGAGE POINT AWTP Rev. 1.2

PART: 27

Note: Thickness of the Grout should not exceed 50mm.

BOLTS SPECIFICATION

DIAMETER EQUIPMENT Equipment DWG. No. BOLT TYPE

LENGTH

MIN. EMBED. DEPTH

CIP Pump CIP Inline Heater Energy Recovery Turbine CIP Tank

BM-0052 250NB 200kW Circulation HTR Model: LTP 2000

HH Bolt, 304/316SS HH Bolt, 304/316SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS Hilti HSE 2421 Epoxy Adhesive Anchor-HAS Rod Type, 304/316 SS

[mm] M16 M22

[mm] 70 70

[mm] -

Min. distance between anchors and edge of concrete (Require only for anchors) [mm] -

Min. depth of concrete (Require only for anchors) [mm] -

M12

270

170

150

250

0049-1 M24 390 250 220 400

Prepared by: Marco Arsovic, MSc Mechanical Engineer

12/19/2007