SINAMICS V20 DRIVE

V20-The versatile Inverter for Basic Demands


Power Range 0.12KW to 15KW Voltage Range 1 AC 200V 240V(+/- 10%) 3 AC 380V 480V(+10% /-15%) Control Modes V/f, v^2/f, FCC Supply frequency 50Hz/60Hz

Signal Inputs and Outputs


Analog Inputs - AI1:bipolar current/voltage mode -AI2 :unipolar current /voltage mode (can be used as digital inputs) Analog Outputs -AO:0 20mA Digital Inputs - DI1-DI4,optically isolated PNP/NPN selectable by terminal Digital Outputs -DO1:transistor output -DO2: relay output -250V AC 0.5A with resistive load - 30V DC 0.5A with resistive load

CONNECTION DIAGRAM

BUILT IN BOP

RESTORING TO DEFAULTS

QUICK COMMISIONING THROUGH PARAMETERS


PARAMETER P0003 FUNCTION User access level SETTING =0(user defined parameter list) =1(standard) =2(extended) =3(expert) =4(service) =1(quick commissioning)

P0010

Commissioning parameter

P0100

50/60Hz selection

=0(50Hz,KW in Europe) =1(60Hz,hp in north America) =2(60Hz, KW in north America)


Range 10..2000 Range 0.01.10000 Range 0.012000.0

P0304[0] P0305[0] P0307[0]

Rated motor voltage[V] Rated motor current[A] Rated motor power [KW/Hp]

QUICK COMMISIONING THROUGH PARAMETERS


PARAMETER P0308[0] P0310[0] FUNCTION Rated motor power factor SETTING Range 0.000..1.000

Rated motor frequency(Hz) Range 12.599

P0311[0] P0700[0..2]

Rated motor speed(RPM) Selection of command source

Range 040000 =0(Factory default setting) =1(Operator panel) =2(Terminal) =5(USS/MODBUS on RS485) Range 077(factory default 1) =0(no main set point) =1(MOP set point) =2(analog set point) =3(fixed frequency) =5(USS on RS485) =7(analog set point 2)
Range 0599(factory default=0)

P1000[0]

Selection of frequency set point

P1080[0]

Minimum frequency[Hz]

QUICK COMMISIONING THROUGH PARAMETERS


PARAMETER P1082[0] P1120[0] P1121[0] FUNCTION Maximum frequency[Hz] Ramp up time[s] Ramp down time[s] SETTING Range 0599 Range 0.00650.00(factory default=10) Range 0.00650.00(factory default=10)

P3900

End of commissioning Note: After completion of calculation, P3900 and P0010 are automatically reset to their original value 0. The inverter displays "8.8.8.8.8" which indicates that it is busy with internal data processing.

=0(no quick commissioning)-factory default =1(end of quick commissioning with factory reset) =2(end quick commissioning) =3(end of quick commissioning only for motor data)

P0700[1]-OPERATOR PANEL
Start Stop Multi-function button Hand/jog/auto Forward and reverse motor direction Speed up and speed down motor

PO700[2]-TERMINALS
Parameter P0701[0...2] Description Function of digital input 1 Range 0 - 99 Factory default 0 Acc. level 2

0
1 2 3 4

Digital input disabled


ON / OFF1 ON reverse/OFF1 OFF2-coast to standstill OFF3-quick ramp down

16
17 18 22 23

Fixed frequency selector bit1


Fixed frequency selector bit2 Fixed frequency selector bit3 Quick stop source1 Quick stop source2

Fault acknowledge

24

Quick stop override

PO700[2]- TERMINALS
Parameter Description 9 10 11 12 Range Fault acknowledge JOG right JOG left Reverse Factory default 24 25 27 29 Acc. level Quick stop override DC brake enable Enable PID External trip

13

MOP down(increase frequency)


MOP down(decrease frequency) Fixed frequency selector bit0

33

Disable additional freq set point


Enable BICO parameterization

14

99

15

PO700[2]- TERMINALS
Parameter P0702[0...2] Description Function of digital input 2 Range 0 - 99 Fa0ctory defa0ult 0 Acc. level 2

P0703[0...2]
P0704[0...2] P0712 [0...2] P0713[0...2]

Function of digital input 3


Function of digital input 4 Analog / digital input 1 Analog / digital input 2

0 - 99
0 - 99 0 - 99 0 - 99

9
15 0 0

2
2 2 2

FIXED FREQUENCY SELECTION


P1000=3(fixed frequency) P1016[0..2](Fixed frequency mode) =1(direct selection) =2(binary selection) If P1016=1 P0701=15(Fixed frequency selector bit 0) P0702=16(Fixed frequency selector bit 1) P0703=17(Fixed frequency selector bit 2) P0704=18(Fixed frequency selector bit 3) Frequency selected from-P1001 to P1004 If P1016=2 P1020[0]:DI1 P1021[0]:DI2 P1022[0]:DI3 P1023[0]:DI4 Assigning frequency to each inputP1001:Fixed frequency 1(Hz).. P1015:Fixed frequency 15(Hz)

ANALOG PARAMETERS
P1000=2(Analog set point)
Analog operation through BOP(P0700=1) P1000=12(analog set point + MOP set point) P1000=21(MOP set point + analog set point) Analog operation through Terminals(P0700=2) P1000=23(fixed frequency + analog set point)

MACROS
DEFINITION:

CONNECTION MACROS APPLICATION MACROS

CONNECTION MACRO

APPLICATION MACROS

Ease of Use
Energy consumption monitoring Automatic restart Parameter cloning USS/MODBUS communication Connection and application macro Customized default values

APPLICATION
Hibernation mode Slip compensation Keep running mode Kinetic buffering Flying start Motor staging BICO function Dual ramp Wobble function PID Controller Super torque mode Hammer start Blockage clearing mode