3Phase transformer calculation Transformer sl.

no 19602 Kva rating 16000 VA primary voltage 11000 Volts Secondry voltage 433 Volts Noload losses and current 72 watts Full load losses 394 Watts No load current 0.59 amps Impedance voltage 480 Volts Lv Avg resistance 219.16 m.Ohms Hv Avg resistance 215.33 Ohms Amb temparature 30 Deg c Hv rated current 0.839807 Amps Lv rated current 21.33458 Amps HV I2 R losses 227.8005 Watts LV I2R losses 149.6308 Watts Total I2R losses@amb temp stray loses@ Amb temp l I2R losses@75 temp stray loses@75 temp total full load loses@75 Impedavce @ Amb temp Total Resistance @ Amb temp = Reactance Resistance @ 75 temp = Impedance @ 75 temp = Percentage impedance Percentage resistance Percentage reacrance regulation @upf regulation @ 0 .8 pf Efficiency at upf 125% 100% 75% at 50% at25% Efficiency at .8 pf at 125% at 100% at 75% at 50% at 25% 377.4313 16.56875 441.5234 14.1636 455.687 989.9419 535.1543 832.8234 626.0296 1041.877 4.59 2.76 3.67 2.76 4.43 96.80 97.27 97.69 97.96 97.67 99.52 96.61 97.12 97.47 97.10 Watts Watts Watts Watts Watts Ohms Ohms Ohms Ohms Ohms % % % % % % % % % % % % % % %

TEST ENGINEER

VICTORY TRANSFORMERS &SWITCHGEARS LTD


3-Q TRANSFORMER CALCULATION SHEET
T/F SL.NO KVA rating of Transformer Primary voltage Secondary voltage No load losses No load current full load losses Impedance voltage L v resistance in milli ohms Hv resistance in ohms Amb temperature Full load current In hv side Lv full load current HV I2R losses = IR x1.5 = Lv IR losses = IR x .5x3 = IRLOSSES CALCULATION total I R lossses @ Amb temp = Hv losses+ Lv losses= stray losses @ Amb temp =Measured losses -I R losses = I R lossses @75 c temp = ((225+75) x losses) / (225+ Amb temp)= stray losses @ 75 c temp =((225+Amb temp)(Stray losses at amb))/300 Total full load losses at @75 c = IR losses at 75 c+Stray losses at 75 c= Impedance at amb temp =(Imp voltage x1.732)/Full load current= Total resistance at amb temp =IR losses/ I= Reactance =SQRT(Impedance --Resistance ) Resistancd at@ 75 c =(300 x resistance at amb ) /(225+Amb temp) Impedance at 75 c =SQRT(R at 75 + X)= percentage impedance =(Z at 75 c x I x 100)/V1 percentage resistance =( R 75 c x I x 100)/V1 percentage reactance =(X x I x 100)/V1 regulation @upf =(%R cos+%Xsin) regulation @ 0 .8 pf =(%R cos+%Xsin)+1/200(%R sin-%Xcos) 2 Efficiency at upf at125% =(Kva x 1.25 x 100)/((kva x 1.25)+(IR losses x 1.25)+(NLL)) at100% =(Kva x 100)/(kva +(IR losses )+(NLL)) at75% =(Kva x .75 x 100)/((kva x .75)+(IR losses x .75)+(NLL)) at 50% =(Kva x.5 x 100)/((kva x .5)+(IR losses x .5)+(NLL)) at25% =(Kva x .25 x 100)/((kva x .25)+(IR losses x .25)+(NLL)) Efficiency at .8 pf at125% =(Kva x 1.25x.8 x 100)/((kva x.8x 1.25)+(IR losses x 1.25)+(NLL)) at100% =(Kva x.8x 100)/(kva x.8 +(IR losses )+(NLL)) at75% =(Kva x .75 x.8x 100)/((kvax.8 x .75)+(IR losses x .75)+(NLL)) at 50% =(Kvax.8 x.5 x 100)/((kvax.8 x .5)+(IR losses x .5)+(NLL)) at25% =(Kvax.8 x .25 x 100)/((kvax.8 x .25)+(IR losses x .25)+(NLL)) 19602 16 11000 433 72 0.59 394 480 219.16 215.33 30 0.84 21.33 227.80 149.63 377.43 16.57 441.52 14.16 455.69 989.94 535.15 832.82 626.03 1041.88 4.48 2.76 3.67 2.76 4.43 96.80 97.27 97.69 97.96 97.67 99.52 96.61 97.12 97.47 97.10 Kva volts volts watts amps watts volts m ohms ohms deg c amps amps watts watts watts watts watts watts watts ohms ohms ohms ohms ohms % % %

% % % % % % % % % %

TEST ENGINEER

Anda mungkin juga menyukai