AC STATOR CORE TEST DATA

HP/KVA/KW PHASES HERTZ RPM VOLTS MFR. AMPS MODEL Back-iron depth B= FRAME SER# TYPE ID#

Core Dimensions Length less Air Ducts Inch mm L=

Inside diameter Slot depth D1= S=

Vs

POWER SUPPLY FOR TESTING WINDING EXTENSION DATA Volts f= Hz X= Y=

Use this section when core dimensions are in INCHES Mean Dia. - D Loop Turns Estimated Amperes Core Weight D1 + (2 x S) + B = (279 x Vs) / (f x L x B) = (28 x D) / (Loop Turns) = 0.82 x D x L x B = Mean Dia. - D (in.) Loop Turns Estimated Amperes Core Weight (lbs) Remarks

* Note: Weight calculation is based on back-iron only, and does not include teeth.

Use this section when core dimensions are in MILLIMETERS Mean Dia. - D Loop Turns Estimated Amperes Core Weight D1 + (2 x S) + B = (180000 x Vs) / (f x L x B) = (1.1 x D) / (Loop Turns) D x L x B / 43821= Mean Dia. - D (mm..) Loop Turns Estimated Amperes Core Weight (kg)

* Note: Weight calculation is based on back-iron only, and does not include teeth.

Lead Size Size AWG Selection Amperes Metric (mm^2)

18 16 14 12 10 8 18 22 25 30 40 50 1.0 1.5 2.5 4.0 6.0 10 F At End Rise

6 70 16

4 3 2 1 1/0 2/0 3/0 4/0 90 105 120 140 155 185 210 235 25 25 35 50 50 70 95 120 C TEST DATA

Lead Size

CORE TEMPERATURES Ambient At Start

Use only meters that read true RMS Volts Amps Watts

CORE ASSESSMENT (W2 / W1) DISPOSITION OF COR Watts/lb** Watts/lb** Watts/lb** Pass

0.00 Fail Watts/kg** Watts/kg** Watts/kg**

Hot Spot

Time

Before Stripping After Stripping FINAL

** Note: Weight calculation is based on back-iron only, and does not include teeth.

JOB

CUSTOMER

DATE

Tested By

Verified By