Anda di halaman 1dari 29

FIELD QUALITY PLAN FOR

H. T. MOTORS
(ERECTION & COMMISSIONING)

FOR

MATRISHRI USHA JAYASWAL MEGA POWER PROJECT, CHANDWA


(2X270 MW, PHASE-I & 2X270, MW PHASE II) CUSTOMER: ABHIJEET INFRA LIMITED

BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR EASTERN REGION


DOC NO. :QPX:ABJ:270:EL:60 REV. NO. :R01
WI:QLY:03-F02/R0

FIELD QUALITY PLAN


FOR

HT MOTORS
(Erection & Commissioning)
FOR

UNIT CAPACITY --- 250 MW

PREPARED BY DGM/ QLY, PSER FQP NO. ORIGINAL DATE OF ISSUE REVISION NO. & DATE COPY NO. ISSUED TO DATE OF ISSUE CONTROLLED / INFORMATION COPY ISSUED BY (SIGNATURE & DESIGNATION)

APPROVED BY HEAD /QLY, PSER QPX:ABJ:270:EL:60 16/07/2012 R01 Dt. 17/07/2012

BHARAT HEAVY ELECTRICALS LIMITED POWER SECTOR EASTERN REGION


WI:QLY:03-F03/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 1 / 1 SHEETS

HT MOTORS
PSER

( ERECTION & COMMISSIONING )

CONTENTS
SL. NO. DESCRIPTION NO. OF SHEETS

1. 2. 3. 4. 5. 6. 7.

STATUS OF REVISIONS AUTHORISATION FOR DIFFERENT CATEGORIES OF CHECK STATEMENT OF CHECKS DOCUMENTS REFERRED IN FIELD QUALITY PLAN LOGSHEETS L-00 TO L-07 PROTOCOL FEEDBACK ON FIELD QUALITY PLAN

1 1 8 1 12 1 1

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 1 / 1 SHEETS

HT MOTORS
PSER

( ERECTION & COMMISSIONING )

STATUS OF REVISIONS

SL. NO.

REFERENCE OF SHEETS REVISED All

REVISION NO. & DATE 01 & 18.07.12

REMARKS

01

Customer comments included

WI:QLY:03-F05/R0

FIELD QUALITY PLAN FOR


PSER

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 1 / 1 SHEETS

HT MOTORS
( ERECTION & COMMISSIONING )

AUTHORISATION FOR DIFFERENT CATEGORIES OF CHECKS


Classification of Check -------------------------------Symbol Description A B C Legend : Critical Major Minor Checking Authority Accepting Authority

BHEL & Customer BHEL BHEL

Customer HOS BHEL

Customer : Customer or any other agency authorised by customer. BHEL HOS : Concerned engineers of BHEL Task Performer. : HEAD OF SECTION for BHEL

NOTE : 1. 2. 3. Quantum of check shall be 100% for all characteristics unless otherwise mentioned in reference documents. Customer shall witness A category checks. He is also authorised to carry out Surveillance in any of the B & C category of checks at his discretion. In case of non-conformity, accepting authority shall ensure dispositioning before accepting and the dispositioning shall be reflected in log sheets / protocols. Dispositioning of non-conformities to be authorised by Head/TSX with intimation to Head/Quality. Instruments with valid calibration to be used for measurements.

4.

WI:QLY:03-F06/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 1 / 8 SHEETS

HT MOTORS
PSER

( ERECTION & COMMISSIONING )

STATEMENT OF CHECKS

Capacity / Type : System : Sub-system : Area :

270MW H. T. Motors Horizontal and Vertical motors Erection & Commissioning

NOTES : 1. For checks where logsheets are not called for, suitable records should be maintained in the form of logsheets / protocols. 2. As an evidence of having carried out the work satisfactorily, a general purpose logsheet, L-00 shall be maintained for all the checks. 3. Abbreviations used in column Type of Check are : M : Measurement V : Visual R : Record Verifications

WI:QLY:03-F07/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET AREA : Erection


QUANTUM / FREQUENCY OF CHECK REFERENCE DOCUMENT/ ACCEPTANCE STANDARD FORMAT OF RECORD REMARKS

HT MOTORS
(STATEMENT OF CHECKS)
PSER

SHEETS

SYSTEM: H. T. MOTORS
S.NO. CHARACTERISTICS

SUB-SYSTEM : Horizontal Motor


TYPE OF CHECK INSTRUMENT CLASS

1 2 2.1 2.2 2.3 3 4 4.1 4.2 4.3

LUB OIL SYSTEM : Dimensions of the foundation. LUB OIL EQUIPMENT & PIPING: Maintain slope of return oil lines. Acid cleaning of oil lines if found rusted. Hydraulic test of oil coolers on water side MAIN MOTOR (HORIZONTAL) : The location of foundation with reference to axes. Minimum 90% contact area is present between : Bottom most packer and concrete Packer to packer Motor Sole plate (base plate) with topmost packer. Note: Total thickness of shims between motor feet and bedplate not to exceed 3 mm. Grouting as per drawing. Non-shrinking free flow high strength ready made grout mix to be used.

Tape

100%

Drawing

V V M M V Pressure Gauge Measuring Tape

B C B B A

100% 100% Once 100% 100%

Drawing Procedure/Drg Drawing Drawing -

5.

100%

Drawing

WI:QLY:03-F08/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET AREA : Erection


QUANTUM / FREQUENCY OF CHECK REFERENCE DOCUMENT/ ACCEPTANCE STANDARD FORMAT OF RECORD REMARKS

HT MOTORS
(STATEMENT OF CHECKS)
PSER

/ 8

SHEETS

SYSTEM: H. T. MOTORS
S.NO. CHARACTERISTICS

SUB-SYSTEM : Horizontal Motor


TYPE OF CHECK INSTRUMENT CLASS

6 6.1 6.2 6.3 6.4

ALIGNMENT AND CLEARANCES: Bearing clearances in case of sleeve bearings. Axial & radial run-out of the coupling The coupling gap and the vertical off-set. Usage of insulated bolts and washers for fixing the NDE capsule with end shields in case of insulated bearing. Air gap between stator & rotor ( if applicable) Termination of Power, control, space heater and RTD cables. Earthing of stator and terminal boxes. Earthing of DE pedestal with base plate if both the pedestal are insulated. After motor trial run, recheck alignment before coupling to driven side flange. Doweling after trial run. M M M V M V V V M V Dial Gauge Vernier/ Feeler gauge A A A A A A Feeler Gauge Dial Gauge Vernier A 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% Drawing Inst. Manual -doDrawing Drawing Schematic Drawing Drawing Drawing -Drawing L-01 L-02 L-02

6.5 7

9 10 11

WI:QLY:03-F08/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO. R 01 SHEET AREA : Erection


CLASS QUANTUM / FREQUENCY OF CHECK REFERENCE DOCUMENT/ ACCEPTANCE STANDARD FORMAT OF RECORD REMARKS

HT MOTORS
(STATEMENT OF CHECKS)
PSER

/ 8

SHEETS

SYSTEM: H. T. MOTORS
S.NO. CHARACTERISTICS

SUB-SYSTEM : Vertical Motor


TYPE OF CHECK INSTRUMENT

MAIN MOTOR (VERTICAL): 1 2 3 3.1 3.2 4 5 6 7 8 Packing/locking used for safe transportation is removed Horizontality of the motor stool (within 0.05 mm/metre) Radial & Axial alignment of coupling : For Rigid coupling Radial & Axial misalignment, 0.03 mm max. For Flexible coupling Radial & Axial misalignment, 0.05 mm max. Contact area between motor base and top of motor stool (minimum 90%) Clearance between guide bearing and shaft journal. Coupling gap in case of flexible coupling. Termination of HT, space heating and control cables. Earthing of main motor, base frame and terminal box. V M M V V Feeler Gauge Vernier Megger A A A A A 100% 100% 100% 100% 100% Drawing Drawing Schematics -doL-01 L-02 V M M Precision Level Dial gauge C B A 100% 100% 100% Instruction Manual Drawing L-02

WI:QLY:03-F08/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 5 / 8 SHEETS

HT MOTORS
(STATEMENT OF CHECKS)
PSER

SYSTEM: H. T. MOTORS
S.NO. CHARACTERISTICS/ITEM

SUB-SYSTEM : Horizontal & Vertical Motors


TYPE OF CHECK INSTRUMENT CLASS QUANTUM / FREQUENCY OF CHECK

AREA : Commissioning
REFERENCE DOCUMENT/ ACCEPTANCE STANDARD FORMAT OF RECORD REMARKS

1 1.1 1.2 2 3 3.1 3.1.1 3.1.2 3.2 3.3 3.4 3.5

LUB OIL UNIT (if applicable) Level of oil in the oil tank. Functioning of lub oil pump during trial run and setting of pressure switch. The freeness of motor rotor by manual rotation. IR value and K factor of the following: (Minimum IR value is (KV+1) Mohms.) Stator winding : Phase to phase Phase to earth H.T. Power Cable. Space heater and space heater cable RTD and RTD cables. Pedestal insulation
WI:QLY:03-F08/R0

V M V M 1 KV Megger Pressure Gauge

C A C A

100% 100% Once 100%

Inst Manual -do-do-doL-03

-do-do-do500 V Megger 500 V Megger 1 KV Megger

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 6 / 8 SHEETS

HT MOTORS
(STATEMENT OF CHECKS)
PSER

SYSTEM: H. T. MOTORS
S.NO. CHARACTERISTICS

SUB-SYSTEM : Horizontal & Vertical Motors


TYPE OF CHECK INSTRUMENT CLASS QUANTUM / FREQUENCY OF CHECK

AREA : Commissioning
REFERENCE DOCUMENT/ ACCEPTANCE STANDARD FORMAT OF RECORD REMARKS

3.6 4 5 6 7 8

NDE side bearing capsule (in case of motor fitted with end shield mounted insulated bearing) Dry out of motor ( In case IR values are less than required level ) Winding resistance of motor. Earthing of DE pedestal with base plate. Earthing of HT terminal box and space heater terminal box. IR measurement and HV test on HT cable after termination (After disconnecting the cable from motor) (Minimum value of IR is (KV + 1) Mohms. Check greasing of motor in case of end-shields mounted bearing. Setting of thermometers and speed switch. Direction of rotation of motor. Mounting of instrument in location. Tightening and locking of fasteners.
WI:QLY:03-F08/R0

1 KV Megger M M V V M HV Test Kit & 500V Megger Dry-out Kit Multimeter A A A A A Once Once 100% 100% Once Inst Manual Inst Manual Drawing Drawing. Inst Manual L-05 L-04 L-01

9 10 11 12 13

V V V V V

A A A A A

100% 100% Once 100% 100%

-doSchematics. Drawing Drawing Drawing

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 7 / 8 SHEETS

HT MOTORS
(STATEMENT OF CHECKS)
PSER

SYSTEM: H. T. MOTORS
S.NO. CHARACTERISTICS

SUB-SYSTEM : Horizontal & Vertical Motors


TYPE OF CHECK INSTRUMENT CLASS QUANTUM / FREQUENCY OF CHECK

AREA : Commissioning
REFERENCE DOCUMENT/ ACCEPTANCE STANDARD FORMAT OF RECORD REMARKS

14 15 16 17

Cable termination box is filled with recommended insulating compound after confirmation of direction of rotation. Verify testing of breaker & setting of all electrical protections prior to no-load run. Verify all interlocks, alarms and indications prior to load run. Record the following during no-load and on-load run :

V V V

A A A

100% 100% 100%

Drawing Schematics. -do-

17.1 17.2 17.3 17.4 17.5 17.6 17.7

Voltage Normal running current, starting current during load run. Maximum Winding temperature Maximum Bearing temperature Lub oil temp in case of sleeve bearings by RTD Vibration Starting Time

M M M M M M M

Control Panel Control Panel Control Panel Control Panel Control Panel Control Panel Stop-watch

A A A A A A A

100 % 100 % 100 % 100 % 100 % 100 % 100 %

Instruction Manual -do-do-do-do-do-do-

L-06 L-06 L-06 L-06

L-07 L-07

WI:QLY:03-F08/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 8 / 8 SHEETS

HT MOTORS
(STATEMENT OF CHECKS)
PSER

SYSTEM: H. T. MOTORS
S.NO. CHARACTERISTICS

SUB-SYSTEM : Horizontal & Vertical Motors


TYPE OF CHECK INSTRUMENT CLASS QUANTUM / FREQUENCY OF CHECK

AREA : Commissioning
REFERENCE DOCUMENT/ ACCEPTANCE STANDARD FORMAT OF RECORD REMARKS

17.8 18 19 20 21

Shaft voltage during load run Trial run of motor on no load for 8 hours. Operation of emergency push button. Interlock and protection trip check. Water leakage

M V V V V A A A A 100 % Once Once Once Instruction Manual -do-do-

L - 06

L-00

WI:QLY:03-F08/R0

FIELD QUALITY PLAN FOR

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 SHEET 1 / 1 SHEETS

HT MOTORS
PSER

( ERECTION & COMMISSIONING )

DOCUMENTS REFERRED IN FIELD QUALITY PLAN

SL. NO. 1. 2.

REFERENCE DOCUMENT Instruction Manual Acid cleaning instructions (for Lub Oil System ), if needed.

ISSUING AUTHORITY Supplying Unit PS-ER

WI:QLY:03-F09/R0

RECORD OF QUALITY CHECKS


PSER

SHEET NO. OF FQP

CHECK NO.

RESULTS ACHIEVED OK / NOT OK

DRAWING / DOCUMENT REFERENCE

FORMAT OF RECORD

INSPECTED BY SIGN. & DATE

CLEARED BY SIGN. & DATE

REMARKS

Note : Any protocol made is to be numbered & mentioned in Format of Record column. SYSTEM PROJECT UNIT NO. RATING
WI:QLY:03-F10/R0

SUB-SYSTEM

AREA

FQP NO. :QPX:ABJ:270:EL:60 REV. NO. R 01 LOG SHEET NO. L-00 SHEET / SHEETS

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

MOTOR CLEARANCES
A) AXIAL, SIDE AND TOP CLEARANCES BETWEEN SHAFT AND BEARING

B) CLEARANCE BETWEEN BEARING SLEEVE O.D. AND PEDESTAL COVER I.D. (SPHERICAL CLEARANCE) D.E.______________________________________ N.D.E.__________________________________________ THIS IS FOR MOTORS WITH JOURNAL BEARINGS ONLY. NAME PROJECT UNIT NO. RATING
WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-01 SHEET 1 / 2 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

BEARING CLEARANCES

BEARING TOP GUIDE BEARING BOTTOM GUIDE BEARING

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-01 SHEET 2 / 2 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

COUPLING ALIGNMENT

COUPLING DETAILS
TYPE ___________________ DIA________________

AXIAL 0.00

DETAILS OF DRIVEN MACHINE


M/C _________________ MAKE ____________________ TYPE___________________________________________ SL.NO. _________________________________________ AS PER DRAWING. COUPLING GAP _______________ ACTUAL COUPLING GAP

0.00 A1 ~ A2 RADIAL 0.00 0.00

TYPE OF COUPLING RIGID FLEXIBLE

MAXIMUM MISALIGNMENT RADIAL & AXIAL 0.03 mm 0.05 mm

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-02 SHEET 1 / 1 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

IR VALUES

Sl. No. 1.

Description 15 Sec STATOR WINDING a) Phase to Phase R-Y Y-B B-R b) Phase to Earth R - Earth Y - Earth B - Earth H.T. POWER CABLE a) Core to core Core 1 - 2 Core 2 - 3 Core 3 - 1 b) Core to earth Core 1 to Earth Core 2 to Earth Core 3 to Earth

IR Values 1 min

K Factor 10 min

PI value

xx xx xx

xx xx xx

2.

IR Values for 1 min.

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIG./DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-03 SHEET 1 / 2 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

IR VALUES 3. IR VALUES AT 1 MINUTE ( R60 ) Sl.No. 1. 2. POSITION Core to core Core to earth SPACE HEATER CABLE CONTROL CABLE RTD CABLE

4. WINDING RESISTANCES PHASE R Y B 5. PEDESTAL INSULATION NOTES : a) Absorption factor = IR Value after 1 Minute (K) IR Value after 15 seconds This value should not be less than 1.25 P.I. Value = IR Value after 10 Minutes IR Value after 1 Minute This value should not be less than 2 Note: PI value need not be measured with rated voltage 3.3KV & below. ________________________ MOhms RESISTANCE ( in milliOhms) Ambient temp/RTD temp ( C)

b)

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIG./DATE

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 LOG SHEET NO. L-03 SHEET 2 / 2 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

MOTOR DRY-OUT Sl. No. Date Time ( hrs ) Voltage ( Volts ) Current ( Amps ) RTDs readings ( oC ) IR Value with all phases combined ( M ohms ) 30 sec 1 min K factor

Remarks

NOTE : 1. Steady state temperature of winding with micalastic insulation to be limited to 60oC maximum in not less than 4 hours. 2. Winding current should be restricted to 50% of rated current

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-04 SHEET 1 / 1 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

H.V. TEST ON H.T. CABLES Sl. No. Cable Identification No. Equipment drive / panel IR Values w.r.t. Earth Before H.V. Test After H.V. test Core no. IR Value Core no. IR Value Test Voltage Core no. Voltage ( Volts ) Leakage Current ( mAmp ) Remarks

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-05 SHEET 1 / 1 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

RUNNING DATA 1) NO-LOAD AMBIENT TEMP : VOLTAGE ( Volts ) R-Y Y-B B-R CURRENT ( Amps ) R Y B FINAL CURRENT ( Amps ) STARTING TIME ( Seconds ) MAX. BRG. TEMP. DE NDE MAX. WINDING TEMPERATURE

Note : Coasting down time in seconds : _________________

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-06 SHEET 1 / 2 SHEETS

INSPECTED BY ACCEPTED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

RUNNING DATA

2) ON-LOAD AMBIENT TEMP : VOLTAGE ( Volts ) R-Y Y-B B-R CURRENT ( Amps ) R Y B FULL LOAD CURRENT ( Amps )
STARTING TIME STARTING CURRENT

( Seconds )

(Amp)

MAX. BRG. TEMP. DE NDE

MAX. WINDING TEMPERATURE

Note : Coasting down time in seconds : ______________

Shaft voltage: ________________

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-06 SHEET 2 / 2 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

VIBRATION MEASUREMENT HORIZONTAL MOTOR

LOCATION A: LOCATION B:

MOTOR COUPLING END (MAIN SHAFT EXTENSION) MOTOR FREE END BRG. (SECOND SHAFT EXTENSION)

HORIZONTAL-A POSITION MOTOR CONDITION UN-COUPLED COUPLED EMBEDDED PLATE UN-COUPLED COUPLED DISP VEL

VERTICAL-A DISP VEL

AXIAL-A DISP VEL

HORIZONTAL-B DISP VEL

VERTICAL-B DISP VEL

AXIAL-B DISP VEL

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-07 SHEET 1 / 2 SHEETS

INSPECTED BY ACCEPTED BY CUSTOMER

INSTRUMENT REG. NO./TAG NO. DATE OF INSPECTION PSER DRAWING / DOCUMENT REF.

VIBRATION MEASUREMENT VERTICAL MOTOR


DISP = DOUBLE AMPLITUDE OF DISPLACEMENTS (IN MICRONS) LOCATION A: LOCATION B: LOCATION C: MOTOR FREE END BEARING MOTOR COUPLING END MOTOR STOOL END

VEL = PEAK VELOCITY ( IN mm/sec )

LOCATION - A HORIZONTAL CONDITION NO LOAD LOAD ANY OTHER DISP VEL VERTICAL DISP VEL AXIAL DISP VEL HORIZONTAL DISP VEL

LOCATION - B VERTICAL DISP VEL AXIAL DISP VEL HORIZONTAL DISP VEL

LOCATION - C VERTICAL DISP VEL AXIAL DISP VEL

NAME PROJECT UNIT NO. RATING


WI:QLY:03-F11/R0

SIGNATURE / DATE

FQP NO. :QPX:ABJ:270:EL:60


REV. NO.: R01 LOG SHEET NO. L-07 SHEET 2 / 2 SHEETS

INSPECTED BY CLEARED BY CUSTOMER

INSTRUMENT REG. NO./TAG DATE OF INSPECTION


PSER

DRAWING / DOCUMENT REF.

PROTOCOL

NAME PROJECT UNIT NO. RATING WI:QLY:03-F12/R0 INSPECTED BY CLEARED BY CUSTOMER

SIGNATURE & DATE

FQP NO. :QPX:ABJ:270:EL:60 REV. NO.: R01 PROTOCOL NO. PAGE:

FEEDBACK ON FIELD QUALITY PLAN


PSER

In the Field Quality Plan, following checks / Logsheets may be added / rewritten / deleted (can not be carried out / not required) due to reasons as mentioned below: Check No. / Sheet no. Proposed Change / Reasons / Remarks Logsheet of FQP No.

PROJECT UNIT NO. RATING