MCset 1-2-3 Medium Voltage Switchgear Withdrawable circuit breaker 17.

5 kV User manual

MCset

Contents

General

Glossary Symbols Recommendations Standard tightening torques

2
2 2 3 3

General description

Warning for readers AD cubicle TT1, TT2 cubicles CL-GL cubicles RHB, RHC cubicles Withdrawable mobile part Identification Read the inscriptions on the front panel

4
4 4 5 5 6 6 9 9

Instructions for access to the inside of a cubicle


AD cubicle Removing front protection cover plates Removing the MV compartment separation sheet Removing the manhole sheet Removing and inserting fixed or withdrawable VTs Access to lower compartment (cables, CT, earthing switch, surge arresters) Accessing busbars Accessing plug-in pins

11
11 12 13 14 14 15 15 16

Installation and operation recommendation Steps for the tests


Voltage presence on MV cables MV cable tests

17 18
18 18

Operating Instructions

Extracting or inserting the mobile part Plugging in the mobile part Withdrawing the mobile part Closing the earthing switch Opening the earthing switch Plugging in VT fuses Withdrawing VT fuses Padlocking and preventing access using padlocks Locking using locks (option) Locking using an electromagnet (option)

20
20 24 25 26 28 30 31 32 34 35

Corrective maintenance

Forward Summary table Replacement of VT compartment fuses Replacing of a voltage indicator box Replacing the fans on 3600 A/ 4000 A cubicles Replacing the capacitor Putting back the new capacitor

36
36 36 37 40 41 41 42

Schneider Electric

07897302EN indice: C0 - 

General

Glossary

UF
AD CL-GL

Functionnal Unit (cubicle + mobile part + Sepam)


Incomming / outgoing cubicle Withdrawable line coupling cubicle Measurement and busbar earthing cubicle Bus riser cubicle through the top Cable riser cubicle through the top transition panel between an MCset cubicle and a MOTORPACT cubicle Fuse switch outgoing cubicle Voltage transformer Current transformer or current sensor Voltage Presence Indicating System Low voltage Voltage class, including levels 7.2 - 12 and 17.5 kV Earthing switch

Note: this document is available for all the MCset 1-2-3 units ordered from the 1st of March 2006.

TT RHB RHC MTP DI TT TC VPIS LV MV SMALT

Mobile part
LF Rollarc 400 EVOLIS CTV1 ERT Extraction table Withdrawable circuit-breaker with SF6 breaking which is used in AD and CL cubicles SF6 breaking withdrawable contactor equipping the AD1 cubicle Withdrawable circuit-breaker with vacuum breaking which is used in AD and CL cubicles Vacuum breaking withdrawable contactor equipping the AD1 cubicle Rack-in or rack-out and removal tool of the mobile parts on the ground Extraction or insertion table without the removal tool of the mobile parts on the ground

Symbols
SMALT operation

Plug-in prevention position. Locking possible.

Plug-in or withdrawal position.

Operation position.

Open earthing switch mechanical indicator light.

 - 07897302EN indice: C0

Schneider Electric

General

Closed earthing switch mechanical indicator light.

Position can be locked using paslocks.

Mobile part operation

Operation position.

Plugged-in position.

Withdrawn position.

Insertion / extraction position.

Recommendations
Height (H) of ceiling for installation of an anti-arc or IPX1 tunnel Installation above the switchboard Marking

It is necessary to have a height of ceiling H u 2.80 m to install a tunnel.

All type of equipment installation such as lamp or light are forbidden.

It is compulsory forbidden to walk on the parts bearing this marking.

It is compulsory forbidden to remove the parts bearing this marking when the equipment is energised.

Standard tightening torques


(non greased screws and bolts)

Screw
6 8 10 12 14

Torque in Nm
13 28 50 75 120

Application methods: The elastic washers placed on the external sides of the pads and busbars ensure better distribution of stress regarding screws tightened to the recommended torques.

Schneider Electric

07897302EN indice: C0 - 

General description

Warning for readers

As the MCset range is very extensive and presents a vast number of front panel options, we have decided to present a Functional Unit presentation equipped with the maximum switchgear.

AD cubicle
AD1 630/1250 A AD2 630/1250 A AD3 2500/3150/3600/4000 A
A: LV compartment door B: protection, monitoring, control by Sepam C: compartment door mobile part D: position inspection windows of the mobile part E: operation and locking plate of the mobile part F: voltage indicators G: earthing switch operation and locking plate and padlocking of the mobile part H: access panel to connection compartment of MV cables or withdrawable VT fuses J: visualisation windows of cables or of VT fuse position K: operation and padlocking plate of withdrawable VT fuses L: fan compartment (on 3600 A / 4000 A) M: cable compartment (on 3600 A / 4000 A) Incomer/outgoer without VT or with fixed VT Incomer/outgoer with withdrawable VT fuses

 - 07897302EN indice: C0

Schneider Electric

General description

TT1, TT2 cubicles


A: B: D: F: G: H: J: K: L: LV compartment door protection, monitoring, control by Sepam visualisation windows voltage indicators earthing switch operation and locking plate and padlocking of the mobile part access panel to connection compartment of MV cables or withdrawable VT fuses visualisation windows of cables or of VT fuse position operation and padlocking plate of withdrawable VT fuses compartment door fixed busbar bridge.

Voltage transformers with withdrawable fuses

Voltage transformers without VT or with fixed VT

CL-GL cubicles
With upstream and downstream VT with withdrawable fuses
A: LV compartment door B: protection, monitoring, control by Sepam C: compartment door mobile part D: position inspection windows of the mobile part E: operation and locking plate of the mobile part F: voltage indicators G: earthing switch operation and locking plate and padlocking of the mobile part J: visualisation windows of cables or of VT fuse position L: access panel to withdrawable VT fuses and to the lower busbar compartments M : operation and padlocking plate of withdrawable VT fuses N : compartment door fixed busbar bridge P : fan compartment (on 3600 A / 4000 A)

Circuit-breaker coupling cubicle

Bus riser cubicle

Schneider Electric

07897302EN indice: C0 - 

General description

RHB, RHC cubicles


RHB1, RHC1 630/1250 A RHB2, RHC2 630/1250 A RHB3, 2500/3150/3600/4000 A RHC3, 2500/3150 A
A: LV compartment door B: protection, monitoring, control by Sepam C: compartment door mobile part D: position inspection windows of the mobile part E: operation and locking plate of the mobile part F: voltage indicators G: earthing switch operation and locking plate and padlocking of the mobile part H : acces panel to the busbars or to the withdrawable VT fuses J : visualisation windows of cables or of VT fuse position K : operation and padlocking plate of withdrawable VT fuses L : connection through the top using busbars (RHB) or cables (RHC) M : fan compartment (on 3600 A / 4000 A)

Withdrawable mobile part


LF1

 - 07897302EN indice: C0

Schneider Electric

General description

LF2

LF3

Disconnector carriage
Note: available in 3 widths.

Busbar earthing carriage on circuit-breaker base


Note: option available in 3 widths.

Schneider Electric

07897302EN indice: C0 - 

General description

ROLLARC 400 CTV1

Evolis
Note: available in 3 widths.

Busbar earthing carriage on Evolis base


Note: available in 3 widths.

 - 07897302EN indice: C0

Schneider Electric

General description

Identification
Ex : AD functional unit A: B: C: name of the cubicle manufacturers label characteristics, designations and serial number.

LF withdrawable mobile part D: characteristics, designations and serial number. Rollarc or CTV1 withdrawable mobile part E: characteristics, designations and serial number. Evolis withdrawable mobile part F: G: characteristics, designations and serial number location of operating instructions (behind the cover).

Read the inscriptions on the front panel


A: B: C: D: procedure pictogram withdrawable mobile part earthing switch plate withdrawable fuse voltage transformer plate.

Schneider Electric

07897302EN indice: C0 - 

General description

Procedure pictogram
1: mobile part operation 2: earthing switch operation.

Mobile part
1: 2: 3: E: F: mechanical opening push-button mobile part position selector opening for inserting mobile part operating handle mechanical indicator light for indication of the mobile part position location for disconnector carriage lock (optional).

Cubicle
Earthing switch, voltage presence and plug-in prevention 4 : earthing switch position selector 5 : opening for the insertion of the earthing switch operating handle G : voltage presence H : plug-in prevention selector switch L : mechanical indicator of earthing switch status M : location for plug-in prevention lock N : location for earthing switch locks.

Withdrawable voltage transformer


6 : 7 : position selector switch for voltage transformer withdrawable fuses opening for the insertion of the voltage transformer withdrawable fuse operating handle.

10 - 07897302EN indice: C0

Schneider Electric

Instructions for access to the inside of a cubicle

AD cubicle

Markings
1 2 3 4 4 and 5 6 7 8

Access
To the lower compartment via the maintenance space or duct (access same as for CT)). Rear (dismantling is optional and has not been secured). Facilitates access to cables (AD cubicle ), through the front (access same as for CT). To the busbars (not possible for VT cubicle). To the rear inter cubicle fastening screws. This sheet must be reassembled before installation of busbars. To the lower compartment through the front (analogue access for VT and CT). To the mobile part. To low voltage compartment.

Schneider Electric

07897302EN indice: C0 - 11

Instructions for access to the inside of a cubicle

Removing front protection cover plates


Cubicle with or without fixed voltage transformer (VT)

Close earthing switch (see chapter Closing the earthing switch). It is recommended to padlock it in this position (see chapter Padlocking and preventing access using padlocks).

In the case of a cubicle equipped with a fixed VT. Open the protection switch of the VT secondaries which is located in the regrouping sleeve or in the LV compartment.

Closure To place back into operation, carry out operations in the reverse order of removal (closed earthing switch).

Dismantle the panel (10 screws).

Cubicle equipped with a withdrawable fusevoltage transformer

Withdraw VT fuses (see chapter Withdrawing VT fuses).

Close earthing switch (see chapter Closing the earthing switch). It is recommended to padlock it in this position (see chapter Padlocking and preventing access with padlocks).

12 - 07897302EN indice: C0

Schneider Electric

Instructions for access to the inside of a cubicle

Open the protection switch of the VT secondaries which is located in the regrouping sleeve or in the LV compartment.

Remove the access panel to VT mobile fuses (6 screws),as well as the U A angle bar ( 4 screws and 2 nuts ).

Closure To place back into operation, carry out operations in the reverse order of removal (closed earthing switch).

Remove the access panel to the connection compartment of MV cables (4 screws).

Removing the MV compartment separation sheet


Remove the circuit-breaker (see chapter Removing and inserting the mobile part).

Remove screws A and remove the separation sheet from the MV compartment. .

Closure

To place back into operation, carry out operations in the reverse order of the removal.

Schneider Electric

07897302EN indice: C0 - 13

Instructions for access to the inside of a cubicle

Removing the manhole sheet

On a cubicle equipped with VTs, remove them. Remove the screws and remove manhole sheet. Access to the connection compartment of MV cables is possible via the maintenance space at the cubicle manhole level. Likewise, it is possible to access the maintenance space or duct through the inside of the cubicle. See chapter Instructions for access to the inside of a cubicle.

Closure

To place back into operation, carry out operations in the reverse order of removal.

Removing and inserting fixed or withdrawable VTs

Fixed VTs On each VT, disconnect the connection rod, by unscrewing the nut, then removing the deflector, and raising the connection rod.

Similar operation whatever type of VT

Disconnect the VT low voltage connector.

Remove the VTs using the handle.

Closing the MV connection compartment

To place back into operation, carry out operations in the reverse order of removal.

For fixed VTs Tightening torque on VT: 30 Nm.

14 - 07897302EN indice: C0

Schneider Electric

Instructions for access to the inside of a cubicle

During the first VT insertion, cut and remove the connector immobilisation binding.

Connect the VT low voltage connector.

Access to lower compartment (cables, CT, earthing switch, surge arresters)


Safety rules

All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

Access to the MV cable connection compartement is possible through the maintenance space by removing the cubicle manhole sheet (see chapter Removing the manhole sheet).

Accessing busbars
Safety rules
All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

Upper

For access to busbars, see chapter Instructions for access to the inside of the cubicle.

Lower

Access to lower busbars is possible through the maintenance space by removing the cubicle manhole sheet. See chapter Instructions for access to the inside of the cubicle.

Schneider Electric

07897302EN indice: C0 - 15

Instructions for access to the inside of a cubicle

Accessing plug-in pins


Safety rules
All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

Opening and closing lower flaps

Using a screwdriver, raise the vane to release the locking. Push the ball into the link axis.

The flaps fall downwards up to locking. To close, pull the flaps upwards up to locking.

Opening and closing upper flaps

Using a screwdriver, raise the vane to release the locking. Push the ball into the link axis.

Push the flaps upwards up to locking. To close, pull the flaps downwards up to locking.

Before re-plugging in the mobile part, ensure that the shutters mechanisms have been put back into their initial position (locked closed). Failure to comply with this instruction may result in damage to the equipment.

16 - 07897302EN indice: C0

Schneider Electric

Installation and operation recommendation

the switchgears resistance to ageing in an MV substation depends on 3 main factors:

The necessity of correct implementation of connections: New cold retractable or slip-on technology offers ease of installation that favours resistance over time. Their design allows them to used in polluted environments with harsh climatic conditions. Impact of the relative humidity factor: Installing a heating device is essential in climates with high relative humidity levels and major temperature differences. Ensure that draughts and / or thermal shocks are avoided in all cubicle compartments in order to avoid the creation of dew points (sources of partial discharges).

The equipment must be installed in conformity with the relevant IEC standard. Outside of these normal usage conditions, we recommend contacting Schneider Electric to determine the operations to be carried out as well as their frequency according to the actual service conditions. Ventilation control: Grid size must be suited to the power dissipated in the substation. These grids must be placed exclusively in the vicinity of the transformer, in order to avoid air circulation on the LV switchboard.

Operation and maintenance

It is strongly advised to periodically carry out, (minimun every 2 years approximately), a few operation cycles on operating devices. Outside normal conditions of use, (between -5C and 40C , absence of dust, corrosive gas, etc.), it is recommended to examine, with our Schneider Electric services centre, the steps to be taken, in order to ensure correct functioning of the installation. After 6 to 12 month operations, we recommend you to check the busbars and MV cable connection tightening. It should be done with a calibrated torque spanner, adjust to lower torque compare to values indicated in page 4.

If no problems are detected and if the busbars and cable connections havent been modified, it will not necessary to do again this check. In case of dismantling, the elastic washers must be change and replace by new ones supplied by Schneider Electric. Our service centre is at your disposal at any time: - To undergo an installation diagnostic, - To offer you, if need be, suitable maintenance operations, - To offer you maintenance contracts, - to offer you adaptations.

b b

Version 3600 A / 4000 A: We strongly recommend that you clean the ventilation grids regularly (every 2 years): A : standard grids B : grids on RHB version. A fan monitoring system must be installed with the cubicle control and monitoring devices. Permanent operation of the following must be guaranteed: - 1 fan for version 3600 A - 2 fans for version 4000 A.

Schneider Electric

07897302EN indice: C0 - 17

Steps for the tests

Voltage presence on MV cables


Cubicle equipped with VPIS voltage indicator boxes
VPIS : Voltage Presence Indicating System, a box with 3 integrated lamps. Characteristics: The definite voltage presence indication is ensured on the voltage range stipulated by IEC 61958.

Instruction for use

VPIS must not be used as a VDS (Voltage Detecting Systems).

The indication of a VPIS alone does not suffice to ensure that the system is deenergised: if the operation rules require this, then suitable voltage detectors in compliance with IEC 61243 must be used for this.

A: B:

voltage presence indicator light (1 for each phase) connection points enabling a phase concordance unit to be connected.

Once the cables are energised, the voltage indicator lights should light up.

MV cable tests
Test condition
Open earthing switch. Cables connected to injection tools.

Voltage injections on MV cable heads


On outgoing cables(without VT)

Check voltage absence. Voltage indicator lights are not lit.

Close the earthing switch. See chapter Closing the earthing switch.

18 - 07897302EN indice: C0

Schneider Electric

Steps for the tests

Remove front protective cover plates. See chapter Instructions for access to the inside of a cubicle.

Connect the voltage injection circuit to cable lugs.

Open the earthing switch. See chapter Opening the earthing switch, then carry out the tests. At the end of the tests: - Close the earthing switch - Remove the accessories.

Schneider Electric

07897302EN indice: C0 - 19

Operating Instructions

Extracting or inserting the mobile part


Starting status
Cubicle + mobile partin a disconnected /test position.

Note: the following operations are described using the extraction and insertion tool application and the removal of mobile ERT parts ...

...the operating mode is identical when using the extraction table. These tools can be adjusted in width and height. See the corresponding manuals.

Extraction

Open the access door to the mobile part by pulling then turning the handle towards the right.

Disconnect the LV auxiliary cord by pressing on the red button and by pulling the socket lock (circuit-breaker or contactor).

Bring the ERT into position (the pins entered into the holes intended for this purpose on the cubicle).

Lock the latching mechanism by pushing in, then tipping the 2 OED notching operating mechanism handles to the right (check latching mechanism). Block the 2 ERT castors.

20 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

Change the position of selector switch 2 to and then, using handles A, remove the mobile part. Bring it up against to be butted against the ERT. Change the position of selector switch 2 back to . Note: moving the circuit-breaker on the ERT must be done near the ground.

Disconnect the ERT by turning the 2 notching operating mechanism handles towards the left then pulling them.

Unblock the ERT castors. Remove the ERT then place the mobile part on the ground by activating the handle.

Remove the ERT.

Before closing the access door to the mobile part, pull down the panel.

Close the access door to the mobile part by turning the handle towards the left, then pushing it.

Schneider Electric

07897302EN indice: C0 - 21

Operating Instructions

insertion

Open the access door to the mobile part by pulling then turning the handle towards the right.

Bring the ERT into position. (the pins entered into the holes intended for this on the cubicle). Block the 2 ERT castors.

Lock the latching mechanism by pushing in, then turning towards the right the 2 ERT notching operating mechanism handles (check latching mechanism).

Change the position of selector switch 2 to .

Push the mobile part into the cubicle until butted against it then change the position of selector switch 2 back to .

Disconnect the ERT by turning then pulling the 2 notching operating mechanism handles to the left. Unblock the 2 ERT castors and remove it.

Plug in the LV socket, to do so, push and keep pressing the red button located under the lock pressed down. Push the lock. Connect the cord and notch it.

22 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

Before closing the access door to the mobile part, lift the panel, and ensure that it is well notched at the top.

Close the access door to the mobile part by turning the handle to the left then pushing it.

Schneider Electric

07897302EN indice: C0 - 23

Operating Instructions

Plugging in the mobile part


Starting status
Door closed Selector switch 4 to (open earthing switch) Selector switch H in plug-in or drawout position to

Operation

Lower the protective flap of push-button 1. Press push-button 1, and while keeping it pushed down. Change the position of selector switch 2 to .

Insert the crank into opening 3. Plug in the mobile part by turning the crank (45 turns) clockwise until the position indicator changes status.

Change the position of selector switch 2 to .

In the case of a circuit-breaker or a contactor, the electric operation for charging the downstream part of installation is now possible.

The pictogram with a black background on the front plate is a reminder of the operations.

24 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

Withdrawing the mobile part


Starting status

The mobile part in the plugged-in position.

Operation

Press push-button 1 (which sends an order for the mechanical opening of the circuitbreaker). While keeping it pushed down, change the position of selector switch 2 to .

Insert the crank into opening 3. Withdraw the mobile part by turning the crank (45 turns) anti-clockwise until the position indicator changes status.

Change the position of selector switch 2 to .

The mobile part is withdrawn. The cubicle is in the disconnected position.

The pictogram with a black background on the front plate is a reminder of the operations.

Schneider Electric

07897302EN indice: C0 - 25

Operating Instructions

Closing the earthing switch


Starting status

The mobile part is in a disconnected position or in an extracted position, that is, absent from the cubicle. Check that the voltage presence lights are not lit. Any potential locks must enable the operation to be carried out.

Operation

Change the position of selectorswitch 4

to , by pulling it and turning it towards the right.

Insert the crank into the pin of operating axis 5, and turn it clockwise until the position indicator changes status. Closing is accompanied by a noise (sudden closing).

26 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

Change the position of selector switch 4 to , by pulling it and turning it towards the right.

The earthing switch is in the closed position. The MV cable heads are short-circuited and earthed.

The pictogram with a yellow background on the front plate, is a reminder of the operations.

Schneider Electric

07897302EN indice: C0 - 27

Operating Instructions

Opening the earthing switch


Starting status

Closed earthing switch Any potential locks must enable the operation to be carried out.

Operation

Change the position of selector switch 4

to , by pulling it and turning it towards the left.

Insert the crank into operating axis 5, and turn it anti-clockwise until the position indicator changes status. The change of status is accompanied by a sudden closing noise.

Change the position of selector switch 4 to by pulling it and turning it towards the left.

28 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

The earthing switch is in the open position.

The pictogram with a yellow background on the front plate, is a reminder of the operations.

Schneider Electric

07897302EN indice: C0 - 29

Operating Instructions

Plugging in VT fuses
Starting status
Assembled lower panel Selector switch 6 to

Operation

Change the position of selector switch 6

to , by pulling it and turning it towards the right.

Insert the crank into operating axis 7, and turn it clockwise until it is plugged in. Plug-in is completed when resistance can be felt (stop).

Change the position of selector switch 6 to , by pulling it and turning it towards the right.

The pictogram with a blue background on the front plate, is a reminder of the operations.

30 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

Withdrawing VT fuses
Starting status
Assembled lower pane Selector switch 6 to

Operation

Change the position of selector switch 6

to , by pulling it and turning it towards the left.

Insert the crank into operating axis 7, and turn it anti-clockwise until drawout.

Change the position of selector switch 6 to , by pulling it and turning it towards the left (this authorises the removal of the fuse access panel).

The pictogram on the front panel, is a reminder of the operations.

Schneider Electric

07897302EN indice: C0 - 31

Operating Instructions

Padlocking and preventing access using padlocks


Number of possible padlocks per cubicle type
Nota : used padlocks 6 to 8 mm. 3 padlocks on the plug-in prevention selector switch. 1 padlock on the protective flap of the mechanical opening push-button of the mobile part. 3 padlocks on the earthing selector switch in the opened or closed position. 3 padlocks on the selector switch of plug-in or drawout VT fuses. 1 padlock on the operating mechanism of each of the plug-in contact flaps

Preventing the plug-in of a mobile part

Place 1 to 3 padlocks on the plug-in prevention selector switch H. Plug-in prevention in

Preventing the opening of a compartment flap on the withdrawable part (option)


Close with padlock On the operating mechanism of the plug-in contact flaps, when they are closed.

The flap operating mechanism is located inside the cubicle, on the right side.

Press on the flap guide, and place the slides (1 and 2, 1 or 2) then place the padlocks in the holes.

40 kA/1s internal arc withstand: to get to the shutters mechanism, you must remove the metal sheet closing (2 screws A).

The metal sheet must be installed before to insert the circuit-breaker.

32 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

Preventing the mechanical opening order of a withdrawable part in an operational position


Can also serve as an additional plug-in and drawout lock out.

Place 1 padlock on the mechanical opening push-button protective flap 1.

Padlocking the earthing switch

Open earthing switch: place 1 to 3 padlocks on selector switch 4 to prevent closure.

Closed earthing switch: place 1 to 3 padlocks on selector switch 4 to prevent opening. This also prevents the plug-in of a mobile part.

Padlocking the operation of VT fuses

plugged-in fuses:place 1 to 3 padlocks on selector switch 6 to prevent drawout. This also prevents removalof the front panel.

Withdrawn fuses:place 1 to 3 padlocks on selector switch 6 to prevent plug-in.

Schneider Electric

07897302EN indice: C0 - 33

Operating Instructions

Locking using locks (option)


Number of possible locks

Mobile part in a drawn out position: 1 lock on the cubicle (2 O) or (2 C) or (1 O and 1 C) or (1 O) or (1 C): on earthing switch.

Disconnector carriage (withdrawable busbar bridges): 1 lock in the plugged-in position (on the disconnector).

Locking on a cubicle
Locking the plug-in prevention of a mobile part.

The wrench is only released when plug-in prevention is locked.

Locking the disconnector carriage in the plug-in position


Closed disconnector Plugged in disconnector carriage

The wrench is only released when the mobile part is in the plug-in and locked position.

Locking the earthing switchwith a lock

1 lock in closed position

1 lock in open position

Locking the earthing switchwith two locks

(2 O) or (2 F) or (1 O et 1 F) or (1 O) or (1 F).

34 - 07897302EN indice: C0

Schneider Electric

Operating Instructions

Locking using an electromagnet (option)


Locking the earthing switch
The electromagnet automatically locks the earthing switch in the open and closed position. A push-button located on the low voltage compartment authorises the operation of selector switch 4, if switchboard configuration is certain.

Locking on a cubicle
Electromagnetic locking prevents the plug-in of a mobile part.

The electromagnet automatically locks plug-in padlocking when it is activated. A push-button located on the low voltage compartment authorises unlocking, if switchboard configuration is certain.

Schneider Electric

07897302EN indice: C0 - 35

Corrective maintenance

Forward
Corrective maintenance operations allow for defective subassemblies to be replaced. The operations mentioned in the summary table here after can be carried out by the customeror by Schneider Electric After Sales agents. For any other intervention,call upon the nearest Schneider group agents. After each operation, carry out electric tests in compliance with the standards in force. Careful: during replacement, all the following accessories must absolutely be replaced by new equipment. - Nylstop (self-locking nut) - Contact washer - Stop rings - Mechanical pin.

Summary table
Description Replacement on FU (cubicle AD or CL) Busbar rating Earthing switch clamps and capacitive isolators Plug-in pins Upper and lower bushing Increase in the number of cables Flaps and flap operating mechanisms Extraction of a cubicle VT fuse VPIS voltage indicator box CT Anti-condensation resistor Earthing switch position auxiliary contact block Surge arrester Locking using plug-in padlocking lock(s) Plug-in padlocking electromagnetic locking Locking using earthing switch lock(1) Locking using earthing switch locks(2) Earthing switch electromagnetic lockin Locking using lock(s) for prevention of withdrawal Zero frequence toroid VT and VT compartment High voltage contacts on VT fuses MV handles Cable connection bar support isolators Circuit-breaker carriage position auxiliary contacts Withdrawable VT auxiliary contacts Withdrawable VT fuse blowing auxiliary contacts Printed circuit and relay support (STPI) Replacing the fans on 3600 A / 4000 A cubicles Cleaning ventilation grids on 3600 A / 4000 A cubicles Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ Customer/ See the following page See the following page See Kit no. 07897207 instructions Consult us See Kit no. 07897324 instructions Consult us See Kit no. 07897330 instructions See Kit no. 07897326 instructions See Kit no. 07897328 instructions See Kit no. 07897329 instructions See Kit no. 07897325 instructions Consult us See Kit no. 07897216 instructions See Kit no. 07897218 instructions See Kit no. 07897219 instructions See Kit no. 07897220 instructions Consult us See Kit no. 07897222 instructions Consult us See Kit no. 07897223 instructions Consult us See page 41 See page 17 For any intervention, call the nearest Schneider Electric agents. Execution Comments

36 - 07897302EN indice: C0

Schneider Electric

Corrective maintenance

Replacement of VT compartment fuses


Starting position

Withdrawn fuses and disconnected VT low voltage connector (see chapter Operating instructions).

Remove the protective panel (see chapter Instructions for access to the inside of a cubicle).

Removing

1: 2: 3: 4:

raise vane A disconnect the small vertical rod B pivot the striker pads C into a horizontal position carefully remove the pin from the striker pads D.

Schneider Electric

07897302EN indice: C0 - 37

Corrective maintenance

5: push wrench E and turn towards the left and let go. The fuse is unlocked. 6: Remove the wrench and the fuse.

Placing

Place the spring on the wrench and check that it is butted against the bottom of the wrench and positioned between the two clips indicated by the arrows.

Place the fuses, with the strikers on the outside. Fit the wrenches on the fuses (spring towards the bottom).

1: push wrench E 2: turn it towards the right and let go. The fuse is locked, check the wrench latching mechanism.

38 - 07897302EN indice: C0

Schneider Electric

Corrective maintenance

3: carefully insert the pin on the striker pads D. 4: raise vane A to place the striker pads C in a vertical position. 5: connect the small vertical rod B to ensure free operation of the small rod.

Operation

Connect the VT low voltage connector (see chapter Operating instructions).

Place protective panel (see chapter Instructions for access to the inside of a cubicle).

Schneider Electric

07897302EN indice: C0 - 39

Corrective maintenance

Replacing of a voltage indicator box

Removing
This operation can be carried out while the equipment is energised.

Remove the 2 fastening screws (A) from the voltage indicator box.

Remove the voltage indicator box (B) and disconnect the connector.

Placing

Check on the characteristics label (B) that the new box corresponds to the rated voltage of your network. - 1.7 kV to 3 kV - 3 kV to 7.2 kV - 10 kV to 24 kV.

Place the new voltage indicator box in the reverse order of removal. Tightening torque: 0.1 mdaN.

40 - 07897302EN indice: C0

Schneider Electric

Corrective maintenance

Replacing the fans on 3600 A / 4000 A cubicles


With or without capacitor

Removing withpower off.

1: disassemble the 10 screws (A) take off the cover. 2: disconnect the wires (D) mark the wires when disassembling.

3: disassemble the 8 screws (C) securing the fan to the cover of compartment (A).

Replacing the capacitor

With power off.

Remove the roof plate on each cubicle (6 screws).

To acc the capacitor.

Schneider Electric

07897302EN indice: C0 - 41

Corrective maintenance

Mark the wiring and disconnect (A).

Disassemble the nut and washer (B).

Putting back the new capacitor

Fit the fan and the capacitor (if necessary) in the opposite order to disassembly.

Check on the characteristics label that the new fan and capacitor match the rated voltage indicated. - 5 1237 333FA 220 Vac - 5 1237 333FB 110 Vac - 5 1237 333FC 48 VD.

42 - 07897302EN indice: C0

Schneider Electric

Schneider Electric

07897302EN indice: C0 - 43

44 - 07897302EN indice: C0

Schneider Electric

Schneider Electric group service centers are there to provide: - engineering and technical assistance, - commissioning, - training, - preventive and corrective maintenance, - adaptation work, - spare parts. Call your sales representative who will put you in touch with your nearest Schneider Electric group service center or directly call the following telephone number: +33 (0)4 76 57 60 60 Grenoble France.

Schneider Electric Industries SAS


89, boulevard Franklin Roosevelt F-92506 Rueil-Malmaison Cedex Tel: +33 (0)1 41 29 85 00 www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper. Publishing: Schneider Electric Industries SAS. Design: Profil. Printing:

07897302EN - REV. C0

10/2005

07897302EN - REV. C0 a Schneider Electric Industries SAS All rights reserved.

Anda mungkin juga menyukai