TABLA DE CAPACIDADES DE CORRIENTE PARA CONDUCTORES AISLADOS TENSION 0 a 2000 V- 60 C a 90 C

60 75 FEPW RH RHW THW THWN XHHN USE ZW 85 90 TA,TBS SA AVB SIS FEB FEPB RHH THWN XHHW
COBRE

60

75 FEPW RH RHW THW THWN XHHN USE ZW

85

90 TA,TBS SA AVB SIS FEB FEPB RHH THWN XHHW

Tipo de aislante

Tipo de aislante

CALIBRE

TW UF

CALIBRE

TW UF

ALUMINIO O AL RECUBIERTO CON COBRE

18 16 14 12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900

20 25 30 40 55 70 95 125 145 165 195 215 240 260 280 320 355 385 400 410 435

20 25 30 40 65 85 115 150 175 200 230 255 285 310 335 380 420 460 475 490 520

18 25 30 40 55 70 95 125 165 190 215 250 275 310 340 365 415 460 500 515 535 565

14 18 25 30 40 55 75 95 130 170 195 225 260 290 320 350 380 430 475 520 535 555 585

12 10 8 6 4 2 1/0 2/0 3/0 4/0 250 300 350 400 500 600 700 750 800 900

20 25 30 40 55 75 100 115 130 150 170 190 210 225 260 285 310 320 330 355

20 25 30 50 65 90 120 135 155 180 205 230 250 270 310 340 375 385 395 425

24 30 40 55 75 100 130 145 170 195 220 250 270 295 335 370 405 420 434 465

25 35 45 60 75 100 135 150 175 205 230 255 280 305 350 385 420 435 450 480

TABLA DE FACTORES DE CORRECION PARA TEMPERATURA AMBIENTE SOBRE 30 C 60 TEMPERATURA AMBIENTE C 75 FEPW RH RHW THW THWN XHHN USE ZW 85 90 TA,TBS SA AVB SIS FEB FEPB RHH THWN XHHW
COBRE

60

75 FEPW RH RHW THW THWN XHHN USE ZW

85

90 TA,TBS SA AVB SIS FEB FEPB RHH THWN XHHW

Tipo de aislante

Tipo de aislante

TW UF

TW UF

ALUMINIO O AL RECUBIERTO CON COBRE

31-40 41-45 46-50 51-60 61-70 71-80

0.82 0.71 0.58

0.88 0.82 0.75 0.58 0.35

0.9 0.85 0.8 0.67 0.52 0.3

0.91 0.87 0.82 0.71 0.58 0.41

0.82 0.71 0.58

0.88 0.82 0.75 0.58 0.35

0.9 0.88 0.8 0.67 0.52 0.3

0.91 0.87 0.82 0.71 0.58 0.41

PARA CALCULAR LA MAXIMA CORRIENTE PERMITIDA POR UN CONDUCTOR A UNA TEMPERATURA MAYOR A 30C SE DEBE MULTIPLICAR LA CORRIENTE PERMITIDA POR EL CONDUCTOR A UNA TEMPERATURA A 30C POR EL FACTOR SEGN LA TEMPERATURA AMBIENTE

TABLA DE CORRIENTE PERMISIBLE DE CONDUCTORES EN DUCTO

NUMERO DE CONDUCTORES

PORCENTAJE DE VALORES POR AUMENTO DE CONDUCTORES

1 4 7 25 43

a a a a a

3 6 24 42 ms

100 80 70 60 50

% % % % %

LA POTENCIA CONSUMIDA SEGN LOS VALORES QUE ALCANCE EL CONDUCTOR, PROVOCARAN UN AUMENTO DE LA TEMPERATURA RESPECTO A LA DEL AMBIENTE CUANDO EL CABLE SE ENCUENTRE DENTRO DE UNA CANALIZACION CON OTROS CONDUCTORES SE HACE MAS DIFICIL LA DISIPACION DEL CALOR PROVOCANDO UN CALENTAMIENTO MUTUO A MEDIDA QUE AUMENTE EL NUMERO DE CONDUCTORES EN UN DUCTO, EL EFECTO JOULE SER ACUMULATIVO, DEBIENDOSE EN ESTE CASO REDUCIR LA CORRIENTE PARA NO PROVOCAR EL RECALENTAMIENTO DE LOS CONDUCTORES, QUE PUEDE DAAR SU AISLAMIENTO Y PRODUCIR UN CORTOCIRCUITO PARA EL CASO DE UNA BANCADA DE TUBERIAS, DONDE EN CADA UNA DE ELLAS HAY CONDUCTORES. LA DISIPACION DE CALOR SE PUEDE COMPLICAR CUANDO EL NUMERO DE TUBOS SEA MAYOR DE 4.