Anda di halaman 1dari 1

ITB Review Sheet

Project Name: STC SM#1 Modernization Proposal No. 21-044-01 Vo. Par. Contents DOC. NO. : REV. NO. : Review / Clarification Div/Dept : GM: Reply / Action Date: Aug 02, 2013 LAE: Dept. Closed Date

4.4.3

Seismic load

Seismic load shall be calculated by the following equation which specified in the Korean Building Code 2005, Sec. 14 Detail shall be as per the requirements of Korean Building Code 2005. V=AxIxCxSxW/R Where V = Seismic load A = Area factor (0.12) I = Important factor (1.2 ~ 1.5) C = Dynamic factor C = 1 / 1.2T, (1.5 at max.) T = Natural periodic time S = Soil factor 1.0 (out area) or 1.5 (reclaimed area) Subject to Article 14.2(5) of Korean Building Code C x S 1.75 R = Response factor 2.0 to 6.0 subject to Article 14.2(6) of Korean Building Code W = Weight Earthquake load (STC Spec.) : Seismic factor, K=0.16

FORM : kef1sd003k-16a1-01(Apr.10))