Anda di halaman 1dari 7

a. Berdasarkan psychrometric chart: Tdp = 50 oF T = 55 oF RH = 84% b.

Entalpi (H) = H terbaca di grafik + Deviasi terbaca di grafik Hin = 21,50 + (-0,01) = 21,49 Btu/lb dry Hout = 30,10 + (-0,19) = 29,91 Btu/lb dry Q = Hout Hin = 7,97 Btu/lb dry Specific volume udara masuk = 13,14 ft3/lb dry air Panas yg dimasukkan ke heater = c. Udara masuk heater: Tin (dry) = 90 oF = = 0,6065 Btu/ft3

win = 0,0076 lb water/lb dry air Udara keluar pengering: Tout (dry) = 70 oF Tdp = 63 oF wout = 0,0125 lb water/lb dry air Lb water (H2O) teruapkan = wout win = 0,0049 lb water/lb dry air d. Kandungan air dalam baju mula-mula: Airawal = Airakhir = = 56 lb = 17,8182 lb

Massa air yg harus diuapkan = 38,1818 lb Fin pengering = 1750 ft3/menit Uap air terbawa udara per ft3 (w)= Neraca massa air di pengering: = 0,000373 lb water/ft3

Asumsi air yang terbawa udara selalu tetap

Make-up water w = 0,022 lb H2O/lb dry air

T = 90 F RH = 65%

Adiabatic humidifying

a. Pembacaan psychrometric chart: Gambar titik keadaan udara masuk yaitu T = 90 oF dan RH = 65% (garis merah). Tarik garis horizontal dari nilai kelembaban udara keluar yg diinginkan (0,022 lb H2O/lb dry air) ke arah kiri (garis hijau). Tarik garis dari keadaan awal (T = 90 oF dan RH = 65%) mengikuti garis wet bulb/adiabatic cooling line hingga memotong garis horizontal yg dibuat sebelumnya (garis biru). Dari titik perpotongan tersebut ditarik garis vertikal ke bawah hingga didapat suhu udara keluar yaitu 82 oF b. Neraca massa total air di menara (chamber) keadaan steady state: Input output = 0 (Fin.win + make-up water) Fout.wout = 0 Dengan Fin = Fout = lb dry air/s (massa udara kering tetap) Make-up water = Fout.wout - Fin.win = Fin(wout - win) Dari psychrometric chart diketahui specific volume udara = 14,27 ft3/lb dry air pada keadaan udara masuk, Maka Fin = = 0,7008 lb dry air/s

Make-up water = 0,7008 lb dry air/s.(0,022-0,020)lb H2O/lb dry air = 0,0014 lb dry air/s = 5,0456 lb dry air/jam

Udara segar o T= 35 C o 95 F o Tdp= 20 C o 68 F T = 60 C o 140 F RH = 95%


o

T = 120 C o 248 F

Padatan 15% air 100 kg/jam

Padatan 2,5% air

Ditanyakan:

a. Jumlah udara segar b. Jumlah udara direcycle c. Beban heater

mair bahan masuk

= = 13,0435 kg/jam = 28,7557 lb/jam

mpadatan

= 100 13,0435 = 86,9565 kg/jam = 191,7043 lb/jam

mair bahan keluar

= = 4,7926 lb/jam

mair teruapkan = (28,7557 4,7926) = 23,9630 lb/jam

x z

x = jumlah udara kering recycle (lb dry air/jam) y = jumlah udara kering segar (lb dry air/jam) z = jumlah udara kering total masuk dryer (lb dry air/jam) Dari psychrometric chart: wx = 0,132 lb water/lb dry air wy = 0,015 lb water/lb dry air Neraca massa udara kering total: Input Output = 0 y (z-x) = 0 (z-x) = y Neraca massa total air keadaan steady state: Input Output = 0 (28,7557 + 0,015y) {4,7926 + 0,132(z-x)} = 0 23,9630 = 0,117y y = 204,8123 lb dry air/jam Misal kadar uap air dalam arus z = w, maka neraca massa air dalam dryer: (w.z + 28,7557) (0,132z + 4,7926) = 0 (0,132 w)z = 23,9630 z=

(1)

Ada 2 variabel yang masih belum diketahui, oleh karena itu butuh persamaan 1 lagi yg memberikan hubungan z dan w, yaitu neraca panas Neraca panas udara dalam dryer:

Jika proses adiabatic, maka: Hin = Hout (jika tidak adiabatic maka perlu diketahui nilai Q) H didekati dengan persamaan: H = cpdry airT + w(water+cpwater vaporT) (H dalam Btu/lb dry air, T dalam oF) = 0,24T + w(1025,34 + 0,45T) Hin = Hout {0,24(248) + w[1025,34+0,45(248)]}z = {0,24(140) + 0,132[1025,34+0,45(140)]}z 59,52 + 1136,9385w = 177,2607 w = 0,1036 z=

= 842,5649 lb dry air/jam Jumlah udara direcycle: x=zy x = 842,5649 - 204,8123 x = 637,7526 lb dry air/jam Menghitung beban panas heater:
y, Hy x, Hx Q z, Hz

(2)

Neraca panas di sekitar heater pada keadaan steady state: Hin Hout + Q W = 0 (y.Hy + x.Hx) z.Hz + Q = 0 Q = z.Hz - (y.Hy + x.Hx) Hz = 0,24(248) + 0,1036(1025,34+0,45(248)) = 177,3068 Btu/lb Hy = 0,24(95) + 0,015(1025,34+0,45(95)) (3)

= 38,8213 Btu/lb Hx = 0,24(140) + 0,132(1025,34+0,45(140)) = 177,2607 Btu/lb Q = (842,5649)( 177,3068) {(204,8123)(38,8213) + (637,7526)( 177,2607)} Q = 28392,97 Btu/jam

Anda mungkin juga menyukai