CT2400 RMU-Fault Indicator
CT2400 RMU-Fault Indicator
RMU-Indikator Gangguan
MV
RUANG INPUT FEEDER
948VDC
CONNECTOR
RMU-Indikator Gangguan
Mendeteksi:
Gangguan 1 fasa ke tanah (PTE) Gangguan 2 & 3 fasa ke fasa (PTP)
Indikasi:
LED untuk gangguan PTE & PTP NO relay contacts untuk remote signalling Output untuk indikasi eksternal
Reset:
Secara otomatis ketika Tegangan telah kembali
ATAU
Setelah waktu yang telah ditentukan (adjustable timeout) dari SCADA-system (closing relay-contact) Push-button pada panel
RMU-Indikator Gangguan
VPI = Indikasi tegangan*) Tombol Test/reset PTP = Indikasi Gangguan fasa ke fasa PTE = Indikasi gangguan Fasa ke tanah Penyesuaian untuk PTE trip level *) berkedip selama waktu inrush blocking menyala konstan setelah blocking timeout
RMU-Indikator Gangguan
Gangguan
Permanen:
Fault
Fast Auto Reclosing Last Reclosing Non-successful
VPI
Inrush blocking Verification time
INDICATION
LED-Indication
CLOSED
permanen:
Fault
Fast Auto Reclosing
Last Reclosing Non-successful
VPI
Inrush blocking
Verification time
INDICATION
LED-Indication
VPI
Inrush blocking Verification time Reset
LED-Indication
INDICATION
No relay-operation
SCADA-RTU
Reset of indicator
Test of LEDs Test of relays
uC
TEST/RESET
Description
Notes
13
14 15
PtP-Sensor 3
VPI-Input VPI-GND Capacitve testpoint or Low Voltage source
RMU-Indikator Gangguan
Parameter Io fixed Io cont.adjustable I> Timerreset Inrush blocking Delay volt.reset Delayed indication External reset activation time Testmode LED Testmode Relays Fault duration PTE Fault duration PTP LED flashing freq. 250A 2h 3 sec 60 sec 10 sec 0,5 sec > 3 sec > 7 sec 100 msec 100 msec 1Hz Default 10A Adj.range 5, 20, 40A 5 100A 100, 400, 500A 6, 12, 24h 3-15 sec 1 -> 1000 sec 1 -> 1000 sec > 10 msec > 1 sec > 5 sec 40-2000 msec 40-2000 msec < 1Hz Dip.switches Dip.sw/Pot.meter Dip.switces Dip.switches SW SW SW SW SW SW SW SW SW
Spesifikasi (gen.RMU-Ind)
Aplikasi: Prinsip deteksi gangguan: Phase-to-Earth fault det.level: Phase-to-Phase fault det.level: Inrush blocking: Verification time: 2 modes: 1. Imediate indication 2. Delayed indication Indikasi: Local: External: Remote:
Integration in Ring main Units (DIN 43 700) 50Hz steady state current detection Io: 5, 10, 20, 40 A (Depends on iron core) I>: 100, 250, 400, 500A 3 sec 100 msec Relay closes after verification of fault Relay closes after verif.time + 10 sec if cable de-energised 2 LEDs: PtE & PtP Ouptut for ext. LED (outdoor indication) 2 NO relay contacts PtP and PtE
Voltage Present Ind. (VPI) Reset: Automatic reset; Timer reset: Manuell: Remote Power Supply: Konsumsi arus:
Housing: DIN modular case Type A acc. To DIN 43 700 (96x48x86mm) (WxHxL) Polycarbonate (ABS), UV Resistant