CT 2400 RMU-Indikator Gangguan

Untuk integrasi di Unit Ring Utama

RMU-Indikator Gangguan
MV
RUANG INPUT FEEDER

230V AC untuk Voltage signal


Autoreset & Inrush blocking blocking Reset & Inrush

SENSOR ARUS ELEMEN GANGGUAN TANAH

948VDC

EARTHING UNTUK CABLE SCREEN

CONNECTOR

EARTHING UNTUK SENSOR ARUS SUBSTATION EARTHING

Outputs ke RTU Outdoor indikasi


Gangguan tanah Ext.reset Gangguan hubung singkat

RMU-Indikator Gangguan

Mendeteksi:
Gangguan 1 fasa ke tanah (PTE) Gangguan 2 & 3 fasa ke fasa (PTP)

Indikasi:
LED untuk gangguan PTE & PTP NO relay contacts untuk remote signalling Output untuk indikasi eksternal

Reset:
Secara otomatis ketika Tegangan telah kembali

ATAU

Setelah waktu yang telah ditentukan (adjustable timeout) dari SCADA-system (closing relay-contact) Push-button pada panel

RMU-Indikator Gangguan

Ext.Power (9-48V terhubung)

VPI = Indikasi tegangan*) Tombol Test/reset PTP = Indikasi Gangguan fasa ke fasa PTE = Indikasi gangguan Fasa ke tanah Penyesuaian untuk PTE trip level *) berkedip selama waktu inrush blocking menyala konstan setelah blocking timeout

RMU-Indikator Gangguan
Gangguan

Permanen:
Fault
Fast Auto Reclosing Last Reclosing Non-successful

Mode: operasi Instant relay


Line current Line voltage
Energising of the line

VPI
Inrush blocking Verification time
INDICATION

LED-Indication

PTE or PTP Relay

CLOSED

RMU Indikator Gangguan


Gangguan

permanen:
Fault
Fast Auto Reclosing
Last Reclosing Non-successful

Mode: operasi Delayed relay


Line current
Line voltage
Energising of the line

VPI
Inrush blocking
Verification time
INDICATION

LED-Indication

PTE or PTP Relay

Delay (progr.: 10 - 60 sec)

RMU Indikator Gangguan


Gangguan

tidak permanen (Interm.faults):


Fault
Fast Reclosing successful

Mode: operasi delayed relay


Line current Line voltage
Energising of the line

VPI
Inrush blocking Verification time Reset

LED-Indication

INDICATION

PTE or PTP Relay

Delay (progr.: 10 - 60 sec)

No relay-operation

RMU Indikator Gangguan

Test/reset fungsi dapat dilakukan dari SCADA-system


SCADA-reset
Press time/ Relay closing time Action

SCADA-RTU

> 0,5 sec


> 3 sec > 7 sec

Reset of indicator
Test of LEDs Test of relays

uC

TEST/RESET

RMU Indikator Gangguan


Connections:
Input #
1 2 3 4 5 6 7 8 9 10 11 12 Ext DC Non-polarised External Indication output GND Relay common Phase-to-Earth Relay (Io) Phase-to-Phase Relay (I>>) External Reset Input GND Common PtP-sensors PtP-Sensors 1 PtP-Sensor 2 Polarised 3->1 connector Normally Open Normally Open Closed contact || Test/Reset button 9-48V DC LED-3

Description

Notes

13
14 15

PtP-Sensor 3
VPI-Input VPI-GND Capacitve testpoint or Low Voltage source

RMU-Indikator Gangguan
Parameter Io fixed Io cont.adjustable I> Timerreset Inrush blocking Delay volt.reset Delayed indication External reset activation time Testmode LED Testmode Relays Fault duration PTE Fault duration PTP LED flashing freq. 250A 2h 3 sec 60 sec 10 sec 0,5 sec > 3 sec > 7 sec 100 msec 100 msec 1Hz Default 10A Adj.range 5, 20, 40A 5 100A 100, 400, 500A 6, 12, 24h 3-15 sec 1 -> 1000 sec 1 -> 1000 sec > 10 msec > 1 sec > 5 sec 40-2000 msec 40-2000 msec < 1Hz Dip.switches Dip.sw/Pot.meter Dip.switces Dip.switches SW SW SW SW SW SW SW SW SW

SW: Field programable

Spesifikasi (gen.RMU-Ind)

Aplikasi: Prinsip deteksi gangguan: Phase-to-Earth fault det.level: Phase-to-Phase fault det.level: Inrush blocking: Verification time: 2 modes: 1. Imediate indication 2. Delayed indication Indikasi: Local: External: Remote:

Integration in Ring main Units (DIN 43 700) 50Hz steady state current detection Io: 5, 10, 20, 40 A (Depends on iron core) I>: 100, 250, 400, 500A 3 sec 100 msec Relay closes after verification of fault Relay closes after verif.time + 10 sec if cable de-energised 2 LEDs: PtE & PtP Ouptut for ext. LED (outdoor indication) 2 NO relay contacts PtP and PtE

Voltage Present Ind. (VPI) Reset: Automatic reset; Timer reset: Manuell: Remote Power Supply: Konsumsi arus:

Capacitive testvoltage (> 1pF @ 20kV or LowVoltage)


Return of voltage (if VPI connected) 2, 6, 12, 24 hours, Push button on frontpanel Closing contact from SCADA Ext. 9 48V DC +/1 20mA depending on LED-modes (electronics only: < 1mA)

Housing: DIN modular case Type A acc. To DIN 43 700 (96x48x86mm) (WxHxL) Polycarbonate (ABS), UV Resistant