System Architecture and Installation
User Manual for Revisions 20/24.71. Each of the selectable buttons allows for easy access to your area of interest.
Basic Operation
Configuration and Advanced Operation
Modbus Database Addresses and Index Numbers
Technical Bulletins
Volume 5
Omni Flow Computers, Inc. is the worlds leading manufacturer and supplier of panel-mount custody transfer flow computers and controllers. Our mission is to continue to achieve higher levels of customer and user satisfaction by applying the basic company values: our people, our products and productivity. Our products have become the international flow computing standard. Omni Flow Computers pursues a policy of product development and continuous improvement. As a result, our flow computers are considered the brain and cash register of liquid and gas flow metering systems. Our staff is knowledgeable and professional. They represent the energy, intelligence and strength of our company, adding value to our products and services. With the customer and user in mind, we are committed to quality in everything we do, devoting our efforts to deliver workmanship of high caliber. Teamwork with uncompromising integrity is our lifestyle.
Omni flow computers Our products are currently being used world-wide at: u Offshore oil and gas production facilities u Crude oil, refined products, LPG, NGL and gas transmission lines u Storage, truck and marine loading/offloading terminals u Refineries; petrochemical and cogeneration plants.
Phone: Fax:
281-240-6161 281-240-6162
Getting User Support
Technical and sales support is available world-wide through our corporate or authorized representative offices. If you require user support, please contact the location nearest you or our corporate offices. Our staff and representatives will enthusiastically work with you to ensure the sound operation of your flow computer.
ALL.71+ 04/98
Manual Guide
Target Audience
As a users reference guide, this manual is intended for a sophisticated audience with knowledge of liquid and gas flow measurement technology. Different user levels of technical know-how are considered in this manual. You need not be an expert to operate the flow computer or use certain portions of this manual. However, some flow computer features require a certain degree of expertise and/or advanced knowledge of liquid and gas flow instrumentation and electronic measurement. In general, each volume is directed towards the following users: u Volume 1. System Architecture and Installation Installers System/Project Managers Engineers/Programmers Advanced Operators Operators u Volume 2. Basic Operation All Users u Volume 3. Configuration and Advanced Operation Engineers/Programmers Advanced Operators u Volume 4. Modbus Database Addresses and Index Numbers Engineers/Programmers Advanced Operators u Volume 5. Technical Bulletins Users with different levels of expertise.
ALL.71+ 04/98
Volume 5
Manual Structure
The User Manual comprises 5 volumes; each contained in separate binding for easy manipulation. You will find a detailed table of contents at the beginning of each volume.
This volume is application specific and is available in four separate versions (one for each application revision). It covers the essential and routine tasks and procedures that may be performed by the flow computer operator. Both US and metric units are considered. General computer-related features are described, such as: u u u u u Overview of keypad functions Adjusting the display Clearing and viewing alarms Computer totalizing Printing and customizing reports
The application-related topics may include: u u u u u Batching operations Proving functions PID control functions Audit trail Other application specific functions
Depending on your application, some of these topics may not be included in your specific documentation. An index of display variables and corresponding key press sequences that are specific to your application are listed at the end of each version of this volume.
ALL.71+ 04/98
Manual Guide
Volume 5 includes technical bulletins that contain important complementary information about your flow computer hardware and software. Each bulletin covers a topic that may be generic to all applications or specific to a particular revision. They include product updates, theoretical descriptions, technical specifications, procedures, and other information of interest. This is the most dynamic and current volume. Technical bulletins may be added to this volume after its publication. You can view and print these bulletins from our website.
Several typographical conventions have been established as standard reference to highlight information that may be important to the reader. These will allow you to quickly identify distinct types of information. CONVENTION USED Sidebar Notes / InfoTips
Example:
INFO - Sidebar notes are used to highlight important information in a concise manner.
DESCRIPTION
Sidebar notes or InfoTips consist of concise information of interest which is enclosed in a grayshaded box placed on the left margin of a page. These refer to topics that are either next to them, or on the same or facing page. It is highly recommended that you read them. Keys on the flow computer keypad are denoted with brackets and bold face characters (e.g.: the up arrow key is denoted as [ ]). The actual function of the key as it is labeled on the keypad is what appears between brackets. Keypress sequences that are executed from the flow computer keypad are expressed in a series of keys separated by a space (as shown in the example).
Screen Displays
Example:
Sample screens that correspond to the flow computer display appear surrounded by a dark gray border with the text in bold face characters and mono-spaced font. The flow computer display is actually 4 lines by 20 characters. Screens that are more than 4 lines must be scrolled to reveal the text shown in the manual.
ALL.71+ 04/98
Volume 5
DESCRIPTION
Sequential heading numbering is used to categorize topics within each volume of the User Manual. The highest heading level is a chapter, which is divided into sections, which are likewise subdivided into subsections. Among other benefits, this facilitates information organization and cross-referencing.
2. Chapter Heading
2.3. Section Heading
2.3.1. Subsection Heading
Figure Captions
Example: Fig. 2-3. Figure No. 3 of Chapter 2
Figure captions are numbered in sequence as they appear in each chapter. The first number identifies the chapter, followed by the sequence number and title of the illustration. Page numbering restarts at the beginning of every chapter and technical bulletin. Page numbers are preceded by the chapter number followed by a hyphen. Technical bulletins only indicate the page number of that bulletin. Page numbers are located on the outside margin in the footer of each page. The contents of Volume 1 and Volume 5 are common to all application revisions and are denoted as All.71. Content of Volumes 2, 3 and 4 are application specific and are identified with the application number. These identifiers are included on every page in the inside margin of the footer, opposite the page number. The publication/effective date of the manual follows the application identification. The date is expressed as month/year (e.g.: March 1998 is 03/98).
Page Numbers
Example:
Trademark References
The following are trademarks of Omni Flow Computers, Inc.: t Omni 3000 t Omni 6000 t OmniCom Other brand, product and company names that appear in this manual are trademarks of their respective owners.
ALL.71+ 04/98
Manual Guide
Important!
Product warranty and licenses for use of Omni Flow Computer Firmware and of OmniCom Configuration PC Software are included in the first pages of each Volume of this manual. We require that you read this information before using your Omni Flow Computer and the supplied software and documentation. If you have not done so already, please complete and return to us the product registration form included with your flow computer. We need this information for warranty purposes, to render you technical support and serve you in future upgrades. Registered users will also receive important updates and information about their flow computer and metering system.
ALL.71+ 04/98
Volume 1
Contents of Volume 1
Figures of Volume 1 ........................................................................................................ vi 1. Overview of Hardware and Software Features ....................................................... 1-1
1.1. Introduction.............................................................................................................1-1 1.2. Operators Panel.....................................................................................................1-2
1.2.1. LCD Display ........................................................................................................... 1-2 1.2.2. Electromechanical Totalizers................................................................................ 1-2 1.2.3. Diagnostic and Program LEDs ............................................................................. 1-2 1.2.4. Active Alarm LED................................................................................................... 1-2 1.2.5. Alpha Shift LED ..................................................................................................... 1-2 1.2.6. Operator Keypad ................................................................................................... 1-2
1.3. Passive Backplane Mother Board .........................................................................1-4 1.4. Back Panel Terminal Module .................................................................................1-6
1.4.1. Back Panel Terminations ...................................................................................... 1-6 1.4.2. Extended Back Panel ............................................................................................ 1-7
ALL.71+ w 04/98
Contents of Volume 1
1.7. Operating Power .................................................................................................. 1-17 1.8. Firmware and Software ........................................................................................ 1-19
1.8.1. Interrupt-Driven CPU............................................................................................ 1-19 1.8.2. Cycle Time............................................................................................................ 1-19 1.8.3. On-line Diagnostics and Calibration................................................................... 1-19 1.8.4. PC Communications Interface............................................................................. 1-19 1.8.5. OmniCom Configuration PC Software.............................................................. 1-20 1.8.6. Year 2000 Compliance ......................................................................................... 1-20
1.9. Initializing Your Flow Computer .......................................................................... 1-21 2. Process Input/Output Combination Module Setup............................................................. 2-1 2.1. Introduction ............................................................................................................ 2-1 2.2. Features of the I/O Combo Modules ..................................................................... 2-1
2.2.1. Setting the Address of the Combo Modules ........................................................2-2 2.2.2. Hardware Analog Configuration Jumpers ............................................................2-2 2.2.3. Process I/O Combo Module Addresses Versus Physical I/O Points..................2-2 2.2.4. Assigning Specific Signal Inputs..........................................................................2-3 2.2.5. Sample Omni Flow Computer Configuration Charts ...........................................2-4
2.5. The H Type Combo I/O Module............................................................................ 2-13 2.6. The HV Type Combo I/O Module ......................................................................... 2-15 2.7. The SV Type Combo I/O Module ......................................................................... 2-16 ii OMNI Flow Computers, Inc.
ALL.71+ w 04/98
Volume 1
5.5. Wiring of Honeywell ST3000 Transmitters .......................................................5-10 5.6. Wiring Micro Motion Transmitters.....................................................................5-11
5.6.1. Connecting Micro Motion RFT9739 Transmitter to A Type or E Type Process I/O Combination Modules ..................................................................... 5-11 5.6.2. Connecting Micro Motion RFT 9739 via RS-485 Serial Communications...... 5-12 5.6.3. Connecting Micro Motion RFT9739 via Serial RS-232-C to 485 Converter .... 5-13
ALL.71+ w 04/98
iii
Contents of Volume 1
6. Connecting Analog Outputs and Miscellaneous I/O Including Provers ............... 6-1
6.1. Analog Outputs....................................................................................................... 6-1 6.2. Digital Inputs/Outputs ............................................................................................ 6-2
6.2.1. Wiring a Digital Point as an Input or an Output ...................................................6-2 6.2.2. Connecting Various Digital I/O Devices................................................................6-4
7.3. Connecting to a Personal Computer and Modem ................................................ 7-4 7.4. Peer-to-Peer Communications and Multi-drop Modes......................................... 7-6
7.4.1. Peer-to-Peer RS-485 Two-wire Multi-drop Mode ..................................................7-6 7.4.2. Peer-to-Peer via RS-232-C Communications ........................................................7-7 7.4.3. Keying the Modem or Radio Transmitter Carrier in Multi-drop Applications.....7-7 7.4.4. RS-485 Four-wire Multi-drop Mode .......................................................................7-8
7.5. Connecting to a SCADA Device ............................................................................ 7-9 7.6. Interfacing the Fourth Serial Port to an Allen-Bradley KE Module................. 7-10
iv
ALL.71+ w 04/98
Volume 1
9.14. Operator Keypad ..................................................................................................9-5 9.15. LCD Display...........................................................................................................9-5 9.16. Electromechanical Counters................................................................................9-6 9.17. Operating Mode Indicator LEDs...........................................................................9-6 9.18. Security .................................................................................................................9-6
ALL.71+ w 04/98
Contents of Volume 1
Figures of Volume 1
Fig. 1-1. Features of the Operator Front Panel ....................................................................................1-3 Fig. 1-2. Passive Backplane Motherboard Omni 3000 .........................................................................1-4 Fig. 1-3. Passive Backplane Motherboard Omni 6000 .........................................................................1-5 Fig. 1-4. Back Panel Terminations Omni 6000 and Omni 3000............................................................1-6 Fig. 1-5. Extended Back Panel - Omni 6000 (left); Omni 3000 (right) ..................................................1-7 Fig. 1-6. Central Processor Module - Jumper Settings .........................................................................1-8 Fig. 1-7. Matching the I/O Modules to the Back Panel Terminations ....................................................1-9 Fig. 1-8. Photo-optical Isolation - How It Works ................................................................................. 1-10 Fig. 1-9. Digital I/O Module Model # 6011 - Jumper Settings ............................................................. 1-11 Fig. 1-10. RS-232/485 Module #68-6205 Showing Selection Jumpers and LED Indicators................. 1-12 Fig. 1-11. Layout of Jumper Blocks Showing RS-232/485 Formats.................................................... 1-13 Fig. 1-12. Back Panel Wiring of the RS-232/485 Module #68-6205.................................................... 1-14 Fig. 1-13. Dual RS-232 Serial I/O Module Model - Jumper Settings................................................... 1-15 Fig. 1-14. Power Supply Module Model # 68-6118............................................................................. 1-18 Fig. 2-1. Sample Configuration Chart (Blank) - Omni 3000 ..................................................................2-4 Fig. 2-2. Sample Configuration Chart (Blank) - Omni 6000 ..................................................................2-5 Fig. 2-3. The A and B Combo I/O Module - Configuration Jumpers .....................................................2-6 Fig. 2-4. A and B Combo Module - Non-Selectable / Selectable Address.............................................2-7 Fig. 2-5. A Type Combo Module - Flow Pulse Jumper Settings (Channel 3 or Channel 4) ...................2-8 Fig. 2-6. A Type Combo Module - Analog Input Jumper Settings.........................................................2-9 Fig. 2-7. B Type Combo Module - Jumper Settings - Frequency Densitometer Setup ........................ 2-10 Fig. 2-8. E/D Type Combo Module - Jumper Settings ........................................................................ 2-11 Fig. 2-9. E Type Combo Module - Jumper Settings ........................................................................... 2-12 Fig. 2-10. H Type Combo Module - Jumper Settings ......................................................................... 2-13 Fig. 2-11. HV Type Combo Module - Jumper Settings ....................................................................... 2-15 Fig. 2-12. Omni Multivariable Interface (SV Type Combo) Module Model 68-6203 - Jumper Settings 2-16 Fig. 3-1. Panel Mounting - Omni 6000 (upper), Omni 3000 (lower) ......................................................3-1 Fig. 3-2. Input Power Terminals - Omni 3000 (upper), Omni 6000 (lower) ...........................................3-4 Fig. 3-3. Input Power Terminals - Extended Back Panel (Omni 6000 only) ..........................................3-5 Fig. 3-4. Example of Typical Back Panel Assignments (Omni 6000)....................................................3-6 Fig. 3-5. Example of Typical Back Panel Assignments (Omni 3000)....................................................3-6 Fig. 3-6. Power Supply Module Model 68-6118....................................................................................3-7
vi
ALL.71+ w 04/98
Volume 1
Fig. 4-1. Connecting to a Turbine Pre-amp (A or B Combo Modules) .................................................. 4-1 Fig. 4-2. Wiring to Turbine Pre-Amps (E Type Combo Modules Only)................................................. 4-2 Fig. 4-3. Wiring of Faure Herman Pre-amp Using Omni 24 VDC......................................................... 4-3 Fig. 4-4. Wiring of Faure Herman Pre-amp Using External 24 VDC ................................................. 4-3 Fig. 4-5. Connecting Dual Coil Turbines for Pulse Fidelity Checking ................................................... 4-4 Fig. 5-1. Wiring the 4-20 mA Inputs (Input Channels 1 & 2 shown)...................................................... 5-1 Fig. 5-2. Wiring for Dry C Type Contact .............................................................................................. 5-2 Fig. 5-3. Wiring a 4-Wire RTD Temperature Probe ............................................................................. 5-3 Fig. 5-4. Wiring a Solartron Densitometer with Safety Barriers to a B Type I/O Combo Module ...... 5-4 Fig. 5-5. Wiring a Solartron Densitometer without Safety Barriers to a B Type I/O Combo Module . 5-5 Fig. 5-6. Wiring a Sarasota Densitometer with Safety Barriers to a B Type I/O Combo Module....... 5-6 Fig. 5-7. Wiring a Sarasota Densitometer without Safety Barriers to a B Type I/O Combo Module.. 5-7 Fig. 5-8. Wiring a UGC Densitometer with Safety Barriers to a B Type I/O Combo Module............. 5-8 Fig. 5-9. Wiring a UGC Densitometer without Safety Barriers to a B Type I/O Combo Module........ 5-9 Fig. 5-10. Wiring of a Honeywell Smart Transmitter ....................................................................... 5-10 Fig. 5-11. Wiring of a Micro Motion RFT9739 Field-Mount (Explosion-Proof) Transmitter .............. 5-11 Fig. 5-12. Wiring of a Micro Motion RFT9739 Field-Mount (Explosion-Proof) Transmitter Via Two-wire RS-485 Communications (Serial I/O Module #68-6205) ...................................... 5-12 Fig. 5-13. Wiring of a Micro Motion RFT9739 Field-Mount (Explosion-Proof) Transmitter Via Serial RS-485 Converter.............................................................................................................. 5-13 Fig. 6-1. Wiring Devices to the Flow Computers Analog Outputs........................................................ 6-1 Fig. 6-2. Wiring of a Digital I/O Point as an Input ................................................................................ 6-2 Fig. 6-3. Wiring of a Digital I/O Point as an Output.............................................................................. 6-3 Fig. 6-4. Connecting Digital I/O Devices to the Flow Computer ........................................................... 6-4 Fig. 6-5. Wiring to a Brooks Compact Prover ................................................................................... 6-5 Fig. 6-6. Controlling the Plenum Pressure of a Brooks Compact Prover ........................................... 6-6
ALL.71+ w 04/98
vii
Contents of Volume 1
Fig. 7-1. Connecting a Printer to Serial Port #1 of the Flow Computer .................................................7-2 Fig. 7-2. Connecting Several Flow Computers to a Shared Printer ......................................................7-3 Fig. 7-3. Direct Connect to a Personal Computer - DB25 Female Connector (Using Port #2 as an example)................................................................................................................................7-4 Fig. 7-4. Direct Connect to a Personal Computer - DB9 Female Connector .........................................7-5 Fig. 7-5. Connecting Port #2 to a Modem ............................................................................................7-5 Fig. 7-6. Wiring of Several Flow Computers using the Peer-to-Peer Feature via RS-485 Communications in Two-wire Multi-drop Mode .......................................................................7-6 Fig. 7-7. Wiring of Several Flow Computers in the Peer-to-Peer Mode using RS-232-C Communications. ...................................................................................................................7-7 Fig. 7-8. Wiring of Multiple Flow Computers to a PLC Device Via RS-485 Communications in Four-wire Multi-drop Mode .....................................................................................................7-8 Fig. 7-9. Typical Wiring of Port #3 to a SCADA Device via Modem .....................................................7-9 Fig. 7-10. Wiring Serial Port #4 to Allen-Bradley KE Communications Module................................ 7-10 Fig. 8-1. Figure Showing Calibration of RTD Input Channel.................................................................8-6
viii
ALL.71+ w 04/98
Volume 1
Introduction
Omni 3000 and Omni 6000 Flow Computers are reliable, easy to use, uniquely versatile measurement instruments. They are factory-programmed for single or multiple meter run configurations to measure crude oils, refined products, NGLs, LPGs, ethylene, propylene, natural gas, and specialty gases. Measurement of other flowing products can also be provided. Extensive communications capability enables the Omni 6000 to be used in a variety of Master/Slave configurations for high-speed data transfer applications, and as a large communication submaster. The flow computer can also be hardware configured as a medium-size Remote Terminal Unit (RTU) with significant digital I/O capability. Your Omni Flow Computer connects to various sensors monitoring pipeline flow in your transmission, petrochemical or process measurement application. It calculates, displays and prints data that will be used for operational or billing functions. The computer is configured to match your piping system requirements. Its nonrestrictive bus design permits any combination of inputs and outputs to meet most metering, flow and valve control, and communication requirements. Plug-in modules furnish the input and output channels as needed and provide an assurance of maximum product life by higher accuracy measurement technologies such as meter pulse fidelity checking, and Rosemount and Honeywell digital transmitter interface modules. Up to 4 serial ports in some models are available for printing reports and other communications tasks. All I/O modules are quality tested and temperature trimmed to optimize the 14-bit analog resolution, and burned-in before shipment for field installation.
ALL.71+ w 04/98
1-1
1.2.
BASIC FEATURES (Continued) q Data archive and report storage q Modbus peer-to-peer communications to 38.4kbps for PLC/DCS q Real-time dial-up for diagnostics q International testing q Includes OmniCom configuration software q Three year warranty
Operators Panel
The operators panel shown (Fig. 1-1) is standard for all applications and is used to display and enter all data. All data can also be accessed via any of the serial ports.
1.2.1.
LCD Display
The 4-line by 20-alpha-numeric character, back-lit Liquid Crystal Display is updated every 200 ms. It displays all messages and system variables in English language engineering units. Backlighting and display viewing angle are adjustable from the keypad (press [Setup] then [Display] and follow the displayed instructions).
1.2.2.
Electromechanical Totalizers
Three non-resetable, 6-digit electromechanical counters are included on the front panel for non-volatile backup totalizing. They can be programmed to count gross, net, mass or energy units at any rate up to 10 counts per second.
1.2.3.
These dual-color LEDs indicate when the user is in the Diagnostic Mode calibrating the I/O modules, or when in the Program Mode changing the configuration of the computer. The LEDs change from green to red after a valid password is requested and entered. The computer is in the normal Display Mode when neither of these LEDs are on.
1.2.4.
New unacknowledged alarms cause this LED to glow red. This changes to green as soon as the alarm is acknowledged by pressing the [Cancel/Ack] key on the keypad.
1.2.5.
INFO - Pressing the [Alpha Shift] key twice will put the shift lock on. The shift lock is canceled by pressing one more time or automatically after the [Display/Enter] key is pressed. Help System - These computers are equipped with a powerful context-sensitive help system. Press the [Help] key (bottom right) twice to activate the help displays. Cancel the help screens by pressing the [Prog] key.
This LED glows green to show that the next key only will be shifted. A red LED indicates that the shift lock is on.
1.2.6.
Operator Keypad
Control of the flow computer is via the 34-button alphanumeric membrane keypad, with tactile domes and audio feedback. Through the keypad you have the capability to configure your system, access and modify calibration data online, and view or print process data. Configuration data can also be entered remotely by serial port and is stored in battery backed-up CMOS SRAM memory. Passwords and an internal program inhibit switch provide tamperproof security.
1-2
ALL.71+ w 04/98
Volume 1
DIAGNOSTIC LED Glows green when in the Diagnostic Mode. Glows red when a valid password is entered.
LCD DISPLAY Is 4 lines by 20 characters. Backlight and viewing angle are adjustable via the keypad.
PROGRAM LED Glows green when in the Program Mode. Glows red when a valid password is entered.
THREE 6-DIGIT, ELECTROMECHANICAL COUNTERS These non-resetable counters are assigned via the keypad.
Total A
DIAG/PROG KEY Used to access Diagnostic and Program Modes.
Total B
Total C
000682
Diagnostic
009456
023975
Active Alarm Alpha Shift
Program
ARROW KEYS Used to move the cursor and scroll displays. Also used as software zero and as span control during calibration.
ACTIVE ALARM LED Glows red when a new alarm occurs. Glows green when an acknowledged alarm exists.
Diag Prog
Gross Net Mass Energy SG/API
Alpha Shift
Control
A & %
Temp
F /
Meter
7
Density
8
D.P.
9
Orifice
ALPHA SHIFT LED Glows green for a single character shift. Glows red when the shift lock is on.
OPERATOR KEYPAD Has 34 keys, domed membrane with tactile and audio feedback.
Press
G #
Time
H $
Counts
4
Factor
5
Preset
6
Batch
*
Analysis
R =
Setup
SPACE/CLEAR / CANCEL/ACK KEY Used to clear data and insert spaces in the Program Mode. It is also used to cancel key press sequences and, in the Display Mode, acknowledge alarms.
:
Print
Prove
1
Status
2
Alarms
3
Product
,
Cancel / Ack
0
Input
.
)
X +
Help
Output
Space Clear
Y (
Display Enter
DISPLAY/ENTER / HELP KEY Used to enter a key press sequence and to access the Help System.
Fig. 1-1.
ALL.71+ w 04/98
1-3
1.3.
INFO - Passive backplane simply means that no active circuitry is contained on it. The active circuitry is contained on the modules that plug into it.
Mounted on the passive backplane are DIN standard connectors which are bussed in two sections. The front section is a high performance, 16-bit bus which accepts the Central Processor Module. The Omni 6000 computer has 3 other connectors available in this section to accept memory expansion and future product enhancements. The rear 8-bit I/O bus section comprises 10 connectors on the Omni 6000 and 4 on the Omni 3000, which can accept any type of optically isolated I/O module manufactured by Omni. The rearmost connector on both computers accepts the system AC/DC power supply module. Dual ribbon cable assemblies (Omni 6000) and a single ribbon cable (Omni 3000) connect the I/O connectors on the backplane to the back panel terminals. (See Fig. 1-2 below and Fig. 1-3 on facing page.)
CAUTION!
These units have an integral cabinet latching mechanism which first must be disengaged by lifting the bezel upwards, before withdrawing the unit from the case.
Fig. 1-2.
1-4
ALL.71+ w 04/98
Volume 1
CAUTION!
These units have an integral cabinet latching mechanism which first must be disengaged by lifting the bezel upwards, before withdrawing the unit from the case.
Fig. 1-3.
ALL.71+ w 04/98
1-5
1.4.
The AC receptacle of the Omni 6000 and Omni 3000 back panel is a power line filter with a separate AC fuse holder. The AC power is contained on a separate four-conductor cable which plugs into the power supply. The power supply used with this version is a Model 68-6118; no physical fuses (see 1.7. Operating Power).
1.4.1.
The Omni 6000 terminal blocks are identified TB1 through TB10 with terminals marked 1 through 12 for each block. These provide 120 circuit paths to the passive backplane. The DC terminals are on TB11. The Omni 3000 terminal blocks are identified as TB1 through TB4, with terminals marked 1 through 12 for each block. These provide 48 circuit paths to the passive backplane. The DC terminal is on TB5.
Back Panel Fuses - All DC fuses are 3 amp fast-blow manufactured by Littlefuse, Model 225.003. All AC fuses are amp slow-blow manufactured by Littlefuse, Model 229.500.
Fig. 1-4.
1-6
ALL.71+ w 04/98
Volume 1
1.4.2.
Several flow computer mounting options are available with the extended back panel. Screw type terminals are provided for AC and DC power. Extended 64conductor ribbon cables and the AC cables are provided with a standard length of 5 feet. For the Omni 6000 (dimensions: 3 x 18), this panel incorporates all the terminal blocks TB1 through TB10, with terminals marked 1 through 12. In addition to the terminal blocks, extra DC (fused), return and shield terminals are provided for TB1 through TB8. The Omni 3000 extended back panel (dimensions: 3 x 8) also incorporates all the terminal blocks TB1 through TB4, with terminals marked 1 through 12. In addition to the terminal blocks, extra DC (fused), return and shield terminals are provided for TB1 and TB2.
Extended Back Panel AC/DC Fuses - All DC fuses are amp fast-blow manufactured by Littlefuse, Model 225.250. The AC fuse is amp slow-blow manufactured by Littlefuse, Model 239.500. The fuse for the back panels AC receptacle is a 5x20mm, amp slow-blow.
Fig. 1-5.
ALL.71+ w 04/98
1-7
1.5.
This module contains the Motorola 16/32-bit microprocessor operating at 16 MHz, a maximum of 512 kbytes of SRAM memory, 1 Mbyte of EPROM program memory, math coprocessor and time of day clock. Positions U3 and U4 on the Central Processor Module contain the program EPROMs. The hardware real-time clock will continue to operate even when power loss to the computer occurs. Time of power failure is logged and printed when the power is restored.
CAUTION!
POTENTIAL FOR DATA LOSS! RAM Battery Backup Omni flow computers leave the factory with a fully charged Ni-Cd battery as RAM power backup. RAM data, including user configuration and I/O calibration data, may be lost if the flow computer is disconnected from external power for more than 30 days. Observe caution when storing the flow computer without power being applied for extended periods of time. The RAM back-up battery is rechargeable and will be fully charged after power has been applied for 24 hours.
Math Processor
Central Processor
Program EPROM
Program RAM
Archive RAM
Backup Batttery
J1
J2
J3
Fig. 1-6.
1-8
ALL.71+ w 04/98
Volume 1
1.6.
Omni flow computers utilize an I/O bus system. All I/O is modular and plug-in for easy field maintenance and replacement. I/O circuitry is also photo-optically isolated from all field wiring which makes it relatively immune to electrical noise and prevents damage to the electronics. Your Omni Flow Computer has a combination of 3 types of I/O modules: o Digital I/O Modules o Serial I/O Modules o Process I/O Combo Modules A and B Type Combo Modules E and E/D Type Combo Modules H Type Combo Modules Almost any combination of I/O mix can be accommodated in the flow computer. The only limitations are the number of I/O connectors (4 on Omni 3000, 10 on Omni 6000) and the number of wires connecting them to the back panel field wiring terminals (48 for Omni 3000, 120 for Omni 6000). Your Omni Flow Computer has a standard order in which the modules are plugged-in (Fig. 1-7; also see Fig. 1-2 and Fig. 1-3). This provides a standard termination layout.
INFO - Mother board connectors do not have a specific address. These are pre-established at the factory. Each Omni Flow Computer will be supplied with a termination diagram indicating these settings.
Omni 6000
TB1 TB2 TB3 TB4 TB5
Omni 3000
TB1 TB2
Digital I/O 1 - 12
Combo I/O # 5
Combo I/O # 6
Combo I/O # 2
Combo I/O # 3
Combo I/O # 4
24
TB6 TB7 TB8 TB9 TB10
24
TB3 TB4
Fig. 1-7.
ALL.71+ w 04/98
Combo I/O # 1
Combo I/O # 2
12 13
12 13
Combo I/O # 1
1-9
1.6.1.
Photo-Optical Isolation Transducer signals are converted by the LED into high frequency pulses of light. These are sensed by the photo-transistor which passes the signal to the flow computer. Note that no electrical connection exists between the transducers and the computer circuits.
Photo-Optical Isolation
The microprocessor circuitry is isolated via photo-optical devices from all field wiring to prevent accidental damage to the electronics, including that caused by static electricity. Photo-optical isolation also inhibits electrical noise from inducing measurement errors. Independent isolation of each process input provides high common-mode rejection, allowing the user greater freedom when wiring transmitter loops. Furthermore, it minimizes ground loop effects and isolates and protects your flow computer from pipeline EMI and transients.
Opto Coupler IC
LED
Photo Transistor
1-10
ALL.71+ w 04/98
Volume 1
1.6.2.
INFO - Only 1 digital I/O module can be used on the Omni 3000 and a maximum of 2 on the Omni 6000.
Inputs and outputs are provided for control of prover functions, remote totalizing, sampler operation, tube control or injection pump control. A digital I/O module is used, providing a total of 12 digital I/O points. Each point can be configured independently as an input or output. It is individually fused and includes LEDs indicating that the point is active or if the fuse is blown. Sequence and control is provided by assigning outputs to user programmable Boolean variables using simple logic statements involving internal and external events, including delay-on timers and delay-off timers. The digital I/O module normally occupies I/O Slots 1 and 2 on the Omni 6000 backplane, and I/O Slot 1 on Omni 3000.
Select D1
I/O Point LEDs - Each digital I/O point has 2 LEDs (green and red) which indicate its status. A solid glowing green LED means that the digital point is assigned as an input and is receiving a signal. A blinking green LED indicates it is assigned as an output and that it is actively communicating. A solid glowing red LED denotes that the fuse for that I/O point is blown.
A5
Select D2
A5
F3
F2
F1
F6
F5
F4
F9
F8
F7
F12
F11
F10
#12
Fig. 1-9.
ALL.71+ w 04/98
1-11
1.6.3.
Serial I/O Module # 68-6205 is capable of handling two communications ports Each serial communication port is individually optically isolated for maximum common-mode and noise rejection. Although providing RS-232C signal levels, the tristate output design allows multiple flow computers to share one serial link. Communication parameters such as baud rate, stop bits and parity settings are software selectable. In addition to RS-232, jumper selections have been provided on each port to allow selection of RS-485 format. With this option, a total of two RS-485 ports are available on each module.
Multivariable Transmitting Devices - In addition to the Serial I/O Module # 68-6205, the flow computer must also have an SV Module to communicate with multivariable transmitters. This serial module is jumpered to IRQ 3 when used in combination with an SV Module. Without an SV Module, the jumper is placed at IRQ 2. The SV Module can only be used with this serial module (68-6205) and is not compatible with the Serial I/O Module # 68-6005. For more information, see Technical Bulletin # TB980303.
Address S2 Selected
LED Indicators
IRQ 2 Selected
Port #2 Jumpers
Port #1 Jumpers
Fig. 1-10. RS-232/485 Module #68-6205 Showing Selection Jumpers and LED Indicators
1-12
ALL.71+ w 04/98
Volume 1
RS-232
JB1 or JB4 JB2 or JB5 JB3 or JB6
RS-485
RS-232
RS-232/485 4-WIRE
RS-485 TERMINATED
ALL.71+ w 04/98
1-13
RS-485 4-Wire TX-B RX-A GND TX-A RX-B TX-B RX-A GND TX-A RX-B
3 4 5 6 7 8
9 10 11 12
1-14
ALL.71+ w 04/98
Volume 1
System Architecture and Installation Dual RS-232-Compatible Serial I/O Module Model # 68-6005
INFO - Up to 12 flow computers can be multidropped to one RS-232C serial device. Typically, one serial I/O module is used on the Omni 3000, providing two ports. A maximum of two serial modules can be installed in the Omni 6000, providing four ports.
Dual channel serial communication modules can be installed providing two RS232-C ports. Each serial communication port is individually optically isolated for maximum common-mode and noise rejection. Although providing RS-232C signal levels, the tristate output design allows multiple flow computers to share one RS-232 device. Communication parameters such as baud rate, stop bits and parity settings are software selectable.
Serial Ports 1 & 2 Use the S1 Module Setting Serial Ports 3 & 4 Use the S0 Module Setting
Chan. B Chan. A
LED Indicators
Chan. A Chan. B
Fig. 1-13. Dual RS-232 Serial I/O Module Model - Jumper Settings
ALL.71+ w 04/98
1-15
1.6.4.
Meter runs utilize plug-in modules which include all necessary analog/digital (A/D) converters and control circuitry. User selection of process I/O is available with combo cards that can be a mix of meter pulse, frequency densitometer, 4-20 mA, 4-wire 100 ohm RTD inputs, and 4-20 mA outputs. All process measurements such as temperature, pressure, density, and flow are input via these process I/O combo modules. Each module will handle 4 inputs of a variety of signal types and provides one or two 4-20 mA analog outputs (except the SV Module which has six 4-20 mA outputs). Seven types of combo I/O modules are available: A, B, E, E/D, H, HV and SV. All modules accept analog and pulse frequency type inputs, except for the H and HV Modules which interface digitally with Honeywell Smart Transmitters, and the SV Module which interfaces serially with RS-485 compatible multivariable transmitters. The A and B Types use identical I/O boards. Likewise, the E and E/D Modules are also identical, except for the position of a configuration jumper which selects the type and address of each module.
INFO - The flow computer allocates the physical I/O point numbers according to the module IDs, not the position occupied on the backplane.
Each of the combo modules installed must have a different identity i.e., you cannot have two or more modules of the same type and address. Valid IDs are: A1 through A6, B1 through B6, E/D-1 through E/D-6, E1 through E6, H1 through H6, and SV1 through SV2. Only one HV Module can be installed. Modules are plugged into DIN type connectors on the passive backplane. Each backplane connector has 12 circuits which connect to the back panel terminal strips via ribbon cables. Combo I/O modules are plugged into the backplane starting at I/O Position #5 (Omni 6000) or I/O Position #3 (Omni 3000) and working towards Position #10 (Omni 6000) or Position #4 (Omni 3000). The preferred order is lowest number A Type to highest number H Type, them SV and HV Modules. The following chapter deals in more detail with process I/O combo modules and includes illustrations and jumper settings. (See Chapter 2 Process I/O Combo Module Setup.)
1-16
ALL.71+ w 04/98
Volume 1
1.7.
Operating Power - The indicated power is maximum and includes the power used by transmitter loops, etc. It will vary depending on the number of modules installed, the number of current loops and any digital output loads connected.
Operating Power
Omni flow computers can be AC or DC powered. When AC powered, 120 VAC 50 Watts is applied to the AC plug. For powering transmitter loops when AC powered, approximately 500 mA at 24 VDC is available from the DC terminal block. The flow computer can be special ordered for operation on 220-250 VAC supplies. This requires a modified power supply unit and a different cord set. AC power to the unit is fused by a 0.5 Amp (5x20 mm) slow-blow fuse located in the AC power receptacle. To DC power the flow computer, apply 18 to 30 VDC, 50 Watts to the DC terminal block. DC power into or out of the back panel DC power terminals is fused by a 3 Amp, 2 AG fast-blow fuse located on the back panel next to the DC power terminals. All analog and digital circuits within the flow computer are powered from a 5volt switching regulator located on the power supply module. This is located in the rear most connector on the computer backplane. The DC power which supplies the switching regulator either comes directly from the DC terminals on the back panel of the flow computer (18-30 VDC) or by rectifying the output of the integral 120 VAC (240 VAC) to 20 VAC transformer. Regulated 5-volt power is monitored by a 3-4 second shutdown circuit located on the power supply module. When power is applied to the computer there will be a delay of 3 to 4 seconds before the unit powers up. A recommended maximum of 500 mA of transducer loop power is available with a fully loaded Omni system of 6 combo I/O modules, 2 digital I/O modules and 2 dual serial I/O modules. The Omni must be DC powered if this 500 mA limit is to be exceeded. The maximum system configuration of the Omni is 24 process inputs, 12 process outputs, 24 digital I/O points, and 4 serial I/O channels dissipates approximately 24 Watts. This causes an internal temperature of 15F (8.33C) over the ambient. The unit should not be mounted in a cabinet or panel where the ambient inside the cabinet will exceed 110F (43.33C).
CAUTION!
POTENTIAL FOR DATA LOSS! RAM Battery Backup Omni flow computers leave the factory with a fully charged Ni-Cd battery as RAM power backup. RAM data, including user configuration and I/O calibration data, may be lost if the flow computer is disconnected from external power for more than 30 days. Observe caution when storing the flow computer without power being applied for extended periods of time. The RAM back-up battery is rechargeable and will be fully charged after power has been applied for 24 hours.
ALL.71+ w 04/98
1-17
CAUTION
The Power Low and +5 v Adjust are factory adjustments that require the use of special equipment. DO NOT attempt to adjust.
AC Connector
1-18
ALL.71+ w 04/98
Volume 1
1.8.
Omni flow computers are supplied with pre-programmed firmware and PC configuration software which permit a single unit to perform a great diversity of combined flow measurement tasks, such as: o Multiple Meter Run Totalizing, Batching, Proving, and Data Archiving o Flow and Sampler Control o Direct Interface to Gas Chromatographs and Smart/Multivariable Transmitters o Selectable Communications Protocols to Directly Interface to DCS, PLC and SCADA Host Systems The flow computer database numbers thousands of data points and provides the tightest communications coupling yet between SCADA and the metering system.
1.8.1.
Interrupt-Driven CPU
This is a very important aspect to firmware. It provides for a multi-tasking environment in which priority tasks can be undertaken concurrently with unrelated activity. This provides for high-speed digital signals to be output at the same time as measurement computations and serial communications to a printer or host computer, without degradation in speed or tasking. All custody transfer measurement programs are stored in EPROM or Flash Memory. This prevents damage due to electrical noise, or tampering with the integrity of calculation specifications. SRAM programming can also be accommodated.
1.8.2.
Cycle Time
All time-critical measurement functions are performed by the flow computer every 500 msec. This provides greater accuracy of measurement calculations and permits a faster response by pipeline operations in critical control functions, such as opening or closing valves.
1.8.3.
Extensive diagnostic software is built into the system which allows the technician to locally or remotely debug a possible problem without interrupting on-line measurement. Calibration of analog signals is performed through the keypad and software. The system has only two potentiometers, both of which are on the power supply and are factory set and need no adjustment.
1.8.4.
PC Communications Interface
The wide use of PCs and video display units makes it possible to provide software for off-line/on-line access to measurement, configuration and calibration data. Collection of historical reports, including alarms, interval reports of any time sequence, liquid batch and prove reports, and full remote technical intervention capabilities are also provided.
ALL.71+ w 04/98
1-19
1.8.5.
INFO - Full details about the OmniCom configuration program are documented in Appendix C.
On-line or off-line configuration of your Omni Flow Computer is possible using an IBM PC compatible running the OmniCom program supplied with your flow computer. This powerful software allows you to copy, modify and save to disk entire configurations. The program also allows you to print customized reports by inputting report templates that are uploaded to the flow computer.
1.8.6.
INFO - The current firmware has been fully tested and assured to be in conformance to Year 2000 requirements. For more information, please contact our technical support staff.
Omni flow computer firmware has been tested in conformance to Year 2000 requirements. It will accurately process time- and date-related data after December 31st, 1999. Software and hardware designed to be used before, during and after the calendar year 2000 will operate appropriately relating to date information. All calculating and logic of time-related data will produce the expected results for all valid date values within the application.
1-20
ALL.71+ w 04/98
Volume 1
1.9.
CAUTION!
A processor reset signal is automatically generated when: 1) Power is applied. 2) The processor reset switch at the rear of the front panel is toggled. 3) The watchdog timer fails to be reset by firmware every 100 milliseconds. The flow computer will perform a diagnostic check of all program and randomaccess memory whenever any of the above events occur. The program is stored with a checksum in Non-volatile Read-only Memory. The program alarms if the calculated checksum differs from the stored checksum. The most obvious cause of such a problem would be a bent pin on a program memory chip. The validity of all data stored in RAM memory is checked next. This data includes totalizers, configuration data and historical data. Any problems here will cause the computer to initialize the RAM and display the following message: RAM Data Invalid Reconfigure System Using OMNI as Initial Password If due to the RAM area in the computer not agreeing with the checksum area, the computer will display the following message: RAM & Calibrate Data Invalid, Reconfigure & Re-calibrate Using OMNI as Password Assuming that the EPROM memory and RAM memory are valid, the flow computer then checks the software configuration against the installed I/O modules and displays a screen similar to the following:
POTENTIAL FOR DATA LOSS! RAM Battery Backup Omni flow computers leave the factory with a fully charged Ni-Cd battery as RAM power backup. RAM data, including user configuration and I/O calibration data, may be lost if the flow computer is disconnected from external power for more than 30 days. Observe caution when storing the flow computer without power being applied for extended periods of time. The RAM back-up battery is rechargeable and will be fully charged after power has been applied for 24 hours.
Module S-Ware H-Ware A-1 Y Y B-1 Y N D-1 Y Y S-1 N Y Revision No. 023.70 EPROM Checksum 1B36 A N in the hardware column indicates that a module has been removed since the software was configured. A N in the software column indicates that a module has been added. In either case you should make the columns agree by adding or removing modules or re-configuring the software.
ALL.71+ w 04/98
1-21
Volume 1
2.1.
Introduction
All process measurement signals are input via the process I/O combination (or combo) modules plugged into the backplane of the computer. There currently are 7 types of combo modules available: A, B, E, E/D, H, HV, and SV Types. The 7 types of modules are actually manufactured using only 4 types of printed circuit modules. The first can be configured as either an A or B Module; the second is used for an E or E/D Module; the third printed circuit is used for an H or HV Type Module; and the fourth for an SV Module.
2.2.
Each combo module (except the SV Module) will handle 4 inputs of a variety of signal types and provides one or two 4-20 mA analog outputs. The SV Module has two ports and six 4-20 mA analog outputs. Only the E Combo Module has Level A pulse fidelity checking and double chronometry proving capabilities. The input/output capabilities and some of the features of the combo modules are expressed in the following table.
PROVING A B E/D E H HV 1-5v; 4-20mA; RTD 1-5v; 4-20mA; RTD 1-5v; 4-20mA; RTD 1-5v; 4-20mA; RTD 1-5v; 4-20mA; Flow Pulses 1-5v; 4-20mA Flow Pulse Frequency Density No No No Yes No No No No No Yes No No
SV
No
No
ALL.71+ w 04/98
2-1
Chapter 2
2.2.1.
Jumpers are provided on each combo module which allow the user to select the address needed to access the module. Changing the software functions of the module is also done by moving the appropriate jumper; i.e., A or B Type, E or E/D Type.
2.2.2.
Other jumpers are provided on each module which select the correct hardware analog configuration for the type of signal that each input channel will accept. This allows the same basic hardware module to accept signals such as 4-20 mA, 1-5 VDC, 100 ohm RTD probes and voltage or current pulses from a turbine, PD meter or digital densitometer.
2.2.3.
IMPORTANT!
Combo I/O modules are sorted alphabetically and by low- to-high address. Adding or removing cards may change the existing sort if the Check I/O function is executed.
A flow computer will usually have several combo modules installed depending on the number of flowmeter runs to be measured. If for example, 2 A Type, 2 B Type, 1 E/D Type and 1 E Type Modules were installed, they would normally be numbered A1, A2, B1, B2, E/D1 and E1. Other address combinations are acceptable (e.g.: A2, A3, B1, B4, E/D2 & E2 ) as long as each has a unique identity. In the above example where 6 modules (A1, A2, B1, B2, E/D1 & E1) are installed, the physical I/O points are mapped as follows. (Note that E/D modules come before the E modules!) To standardize, Omni recommends that combo modules should always be installed starting with the lowest number A Type Module in I/O Slot #5 (Slot #3 in Omni 3000) as shown, with additional modules being installed in ascending order towards Slot #10 (Slot #4 in Omni 3000).
2-2
ALL.71+ w 04/98
Volume 1
2.2.4.
The Omni factory pre-assigns the physical I/O points of each flow computer based on information supplied at time of order. This configuration information is stored in battery backed-up static CMOS RAM. If you wish to change or add to these assignments, refer to the section Program Setup in Volume 3, Chapter 2 Flow Computer Configuration and follow these basic rules: 1) Digital densitometer signals can only be assigned to the fourth channel of each B Type Combo Module, or the third and fourth channel of each E/D Module. 2) RTD signals can only be assigned to the first or second channel of each A, B, E/D or E combo module. Whenever possible, avoid using the second RTD excitation current source of an A Type Combo Module as this makes the second 4-20 mA output on that module inaccessable.
rd 3) Pulse signals from flowmeters can be assigned only to the 3 channel of th each combo module and/or the 4 channel of each A Combo Module and E Combo Module (E/D Combo Modules excepted).
4) Pulse signals to be used for Pulse Fidelity Checking must be connected rd th to the 3 and 4 channel of an E Combo Module with the third channel assigned as the flow input.
rd th 5) Use the 3 and 4 input channels of an E Combo Module for double chronometry proving.
INFO - The message I/O Type Mismatch is displayed if you try to assign the same physical I/O point to more than one type of variable.
6) Physical I/O points may be assigned to more than one variable (i.e., common temperature or pressure sensors) but variable types cannot be mixed (i.e., the same physical point cannot be assigned to temperature and pressure, for example).
ALL.71+ w 04/98
2-3
Chapter 2
2.2.5.
The charts (below and facing page) are examples of the configuration chart supplied with your flow computer. It shows the type of combo modules installed, the assigned process variables, the I/O point numbers and the jumper settings for each input channel. To avoid confusion, we recommend that you plan any changes to the physical I/O setup on such a chart before making any changes.
Fig. 2-1.
2-4
ALL.71+ w 04/98
Volume 1
Fig. 2-2.
ALL.71+ w 04/98
2-5
Chapter 2
2.3.
All I/O signals of the combo module are converted to the form of high frequency pulse trains (0 to 25 kHz). These pulse trains are passed through opto-couplers providing electrical isolation. All 4 process inputs can accept analog input voltages which are first buffered with a 1 megohm input buffer and then converted to pulse frequencies using precision voltage-to-frequency converters. With 2 averaged 500 millisecond samples, analog conversion resolution is 14 binary bits. Linearity is typically 0.01% and the temperature coefficient is trimmed to better than 15 PPM/F. Current inputs such as 4-20 mA are converted to 1-5 VDC by jumpering-in a 250 ohm shunt resistor. The conversion gain of Input Channels 1 and 2 can also be increased by a factor of 10, allowing low level RTD signals (0.20 - 0.55 VDC) to be accepted. Input Channels 3 and 4 can also be jumpered to accept pulse signals (0-12 kHz). In this case, the input stage is configured as Schmitt Trigger, whose threshold is 3.5 VDC and hysteresis 0.5 VDC. The voltage-to-frequency converter is bypassed in this mode. Input Channel 4 can also be jumpered for AC coupling and a 1-volt trigger threshold, making it suitable for interfacing to Solartron type densitometers. Analog Outputs #1 and #2 are obtained in the reverse fashion. A softwarecontrolled pulse train (100 Hz to 5.0 kHz) is passed through opto-couplers and converted to a current using precision frequency-to-current converters. Resolution of these outputs is approximately 12 binary bits. The second analog output is not available when the module is jumpered as a B Type.
Input Channel #4
Input Channel #3
Input Channel #2
Input Channel #1
Module Address Jumpers 2nd. RTD Excitation Source or 2nd Digital-Analog Output Input Type Select Jumpers
Fig. 2-3.
2-6
ALL.71+ w 04/98
Volume 1
2.3.1.
The Combo Type A or B Module can either have a non-selectable address or a selectable Address. The non-selectable address type is featured in older versions of the Omni Flow Computer. The address is programmed into the Programmable Array Logic (PAL) integrated circuit and is factory set. The module address can only be changed by replacing the PAL chip. The selectable type address is featured in current versions of the Omni. Normally, it is preset at the factory, however it allows the user to change the address simply by selecting the correct type and address on the selection jumpers.
Non-Selectable Address
Selectable Address
Fig. 2-4.
ALL.71+ w 04/98
2-7
Chapter 2
2.3.2.
INFO - The second analog output is not available in cases where JP12 is used to select the second RTD excitation current source. You may be able to avoid using the second RTD excitation source and save losing an analog output by using an unused excitation source on another combo module.
The A Type Module is the most common configuration. It accepts 4 process inputs and provides two 4-20 mA analog outputs. Each module is connected to the back panel terminal blocks via 12 wires on the ribbon cables. The actual terminal block used depends upon which backplane connector (?) the module is plugged into. A Combo Module Back Panel Terminal Assignments
TB? Terminal 1 TB? Terminal 2 TB? Terminal 3 TB? Terminal 4 TB? Terminal 5 TB? Terminal 6 TB? Terminal 7 TB? Terminal 8 TB? Terminal 9 TB? Terminal 10 TB? Terminal 11 TB? Terminal 12 Input Channel #1 (1-5v, 4-20mA, RTD) Input Channel #1 (Isolated Signal Return) Input Channel #2 (1-5v, 4-20mA, RTD) Input Channel #2 (Isolated Signal Return) Input Channel #3 (1-5v, 4-20mA, Flowmeter Pulses) Input Channel #3 (Isolated Signal Return) Input Channel #4 (1-5v, 4-20mA, Flowmeter Pulses) Input Channel #4 (Isolated Signal Return) RTD Excitation Current Source #1 Signal Return Terminals 9, 11 & 12 (Internally connected to DC power return) Analog Output #1 (4-20mA) Analog Output #2 (4-20mA) or RTD Excitation Current Source #2 (See JP12 Setting)
JP11
Chan 4 Threshold JP11 In = 3.5 VDC 4-20mA Jumper Out (Pulse Type Input)
JP11
Address Select (Address #2 Shown) Module A0 A1 A2 #1 Out Out Out #2 In Out Out #3 Out In Out #4 In In Out #5 Out Out In #6 In Out In
JP12
RTD2
Fig. 2-5.
2-8
ALL.71+ w 04/98
Volume 1
JP11
Configured for Configured for Configured for 4-20 mA Input 1-5 VDC Input RTD Input
Fig. 2-6.
ALL.71+ w 04/98
2-9
Chapter 2
2.3.3.
INFO - You will need either a B Type Combo Module or E/D Type Combo Module when using digital densitometers connected to the flow computer. With a B Type Combo Module, Analog Output #2 is never available because the periodic time function uses the internal timer counter that is normally used to generate the second analog output.
The B Type Combo Module also handles 4 process inputs but Input Channel 4 is now used to measure the periodic time of a digital densitometer. The module always has Input Channel 4 jumpered as a frequency input. Signal coupling can be AC or DC with trigger threshold adjustable for 1.5 or 3.5 Vpp sensitivity. Each module is connected to the back panel terminal blocks via 12 wires on the ribbon cables. The actual terminal block used depends upon which backplane connector (?) the module is plugged into. B Combo Module Back Panel Terminal Assignments
TB? Terminal 1 TB? Terminal 2 TB? Terminal 3 TB? Terminal 4 TB? Terminal 5 TB? Terminal 6 TB? Terminal 7 TB? Terminal 8 TB? Terminal 9 TB? Terminal 10 TB? Terminal 11 TB? Terminal 12 Input Channel #1 (1-5v, 4-20mA, RTD) Input Channel #1 (Isolated Signal Return) Input Channel #2 (1-5v, 4-20mA, RTD) Input Channel #2 (Isolated Signal Return) Input Channel #3 (1-5v, 4-20mA, DC Coupled Flowmeter Pulses) Input Channel #3 (Isolated Signal Return) Input Channel #4 (AC Coupled Densitometer Frequency) Input Channel #4 (Isolated Signal Return) RTD Excitation Current Source #1 Signal Return Terminals 9, 11 & 12 (Internally connected to DC power return) Analog Output #1 (4-20mA) RTD Excitation Current Source #2
JP11
JP11
Address Select (Address #2 Shown) Module A0 A1 A2 #1 Out Out Out #2 In Out Out #3 Out In Out #4 In In Out #5 Out Out In #6 In Out In
JP12
RTD2
D/A2 JP12 In RTD2 Position Pulse (Frequency) Type Densitometer Requires AC Coupling - Channel 4
Fig. 2-7.
2-10
ALL.71+ w 04/98
Volume 1
2.4.
The hardware of E/D and E Combo Modules are similar to that of the A and B Modules (discussed previously) except that these modules provide 2 analog input channels which can be configured by jumpers for 1-5 volt, 4-20 mA or 4wire RTDs, and 2 pulse input channels which can be used to input flowmeter pulses or densitometer frequency signals. Two 4-20 mA analog outputs are always available on these modules. The module hardware can also be configured by the application software to provide Level A Pulse Fidelity Checking on the two pulse input channels.
2.4.1.
The E/D Type Combo Module is simply an E Combo Module with the JPD jumper in place. Input Channels 1 and 2 are analog input channels which can be configured by jumpers for 1-5 volt, 4-20 mA, or 4-wire RTDs. Input Channels 3 and 4 are always configured to measure periodic time and accept pulse signals from digital densitometers. Each module is connected to the back panel terminal blocks via 12 wires on the ribbon cables. The actual terminal numbers used depend upon which backplane connector (?) the module is plugged into. E/D Combo Module Back Panel Terminal Assignments
TB? Terminal 1 TB? Terminal 2 TB? Terminal 3 TB? Terminal 4 TB? Terminal 5 TB? Terminal 6 TB? Terminal 7 TB? Terminal 8 TB? Terminal 9 TB? Terminal 10 TB? Terminal 11 TB? Terminal 12
Input Threshold Select JP8 In = +1.2 Volt DC JP* Out = +3.2 Volt DC Select Module Type JPD In = E/D Module
Input Channel #1 (1-5v, 4-20mA, RTD) Input Channel #1 (Isolated Signal Return) Input Channel #2 (1-5v, 4-20mA, RTD) Input Channel #2 (Isolated Signal Return) Input Channel #3 (AC or DC Coupled Digital Densitometer Pulses) * Input Channel #4 (AC or DC Coupled Digital Densitometer Pulses) * Not Used RTD Excitation Current Source #2 * RTD Excitation Current Source #1 * Signal Return for signals marked (*) (Internally connected to DC power return) Analog Output #1 (4-20mA) * Analog Output #2 (4-20mA) *
JP8 THRES
JP5
JP6
JP3 JP4
JP6
JP2 AC DC AC INPUT 4
JP7 AC DC AC INPUT 3
Address Select (Address #2 Shown) Module #1 #2 #3 #4 #5 #6 A0 Out In Out In Out In A1 Out Out In In Out Out A2 Out Out Out Out In In JP2 JP7 AC DC AC INPUT 4 AC Coupling Select AC DC AC INPUT 3
JP5
JP6
DC Coupling Select
Fig. 2-8.
ALL.71+ w 04/98
2-11
Chapter 2
2.4.2.
The E Type Combo Module is simply an E/D Combo Module with the JPD jumper out. Double chronometry timers are provided in this module configuration, allowing either pulse train to be proved. Input Channels 1 and 2 are analog input channels which can be configured by jumpers for 1-5 volt, 4-20 mA, or 4-wire RTDs. Input Channels 3 and 4 are always configured to accept flowmeter pulses. Both RTD excitation current sources are also always available. Each module is connected to the back panel terminal blocks via 12 wires on the ribbon cables. The actual terminal numbers used depend upon which backplane connector (?) the module is plugged into.
Input Threshold Select JP8 In = +1.2 Volt DC JP* Out = +3.2 Volt DC Select Module Type JPD Out = E Module
JP8 THRES
JP5
JP6
JP3 JP4
JP6
JP2 AC DC AC INPUT 4
JP7 AC DC AC INPUT 3
Address Select (Address #2 Shown) Module #1 #2 #3 #4 #5 #6 A0 Out In Out In Out In A1 Out Out In In Out Out A2 Out Out Out Out In In JP2 JP7 AC DC AC INPUT 4 AC Coupling Select AC DC AC INPUT 3
JP5
JP6
DC Coupling Select
Fig. 2-9.
2-12
ALL.71+ w 04/98
Volume 1
2.5.
The H Type Combo Module is a special module which is used to communicate using the Honeywell DE Protocol with 4 Honeywell Smart Transmitters. It operates on a point-to-point basis. Honeywell Model ST3000 temperature, pressure and differential pressure transmitters can be used. Transmitters operating in the analog mode are automatically given a wake-up pulse and switched into the DE Mode, as soon as they are connected and assigned a meter run function. Two analog outputs are always available on this module. Each module is connected to the back panel terminal blocks via 12 wires on the ribbon cables. The actual terminal numbers used depend upon which backplane connector (?) the module is plugged into.
Green LED Indicates Any Activity Red LED Indicates OMNI is Transmitting
ALL.71+ w 04/98
2-13
Chapter 2
The flow computer will not allow any other devices to alter these variables. Should they be altered, by the Honeywell Smart Field Communicator (SFC) for example, they will be restored to their original value as shown in the flow computer (transducer tag name excepted).
2-14
ALL.71+ w 04/98
Volume 1
2.6.
The HV Type Combo Module is simply an H Module with the JP1, JP2 and JP3 address jumpers in the right-most setting (Address 15). The HV Combo Module is used to communicate with Honeywell SMV3000 multivariable transmitters via the DE Protocol. Operation of the LEDs is similar to the normal H Module. Since only one multivariable transmitter is needed per meter run and since there are a maximum of four meter runs, there will never be a need for more then one HV Combo I/O Module. Two analog outputs are always available on this module. Each module is connected to the back panel terminal blocks via 12 wires on the ribbon cables. The actual terminal numbers used depend upon which backplane connector (?) the module is plugged into. HV Combo Module Back Panel Terminal Assignments
TB? Terminal 1 TB? Terminal 2 TB? Terminal 3 TB? Terminal 4 TB? Terminal 5 TB? Terminal 6 TB? Terminal 7 TB? Terminal 8 TB? Terminal 9 TB? Terminal 10 TB? Terminal 11 TB? Terminal 12 Input Channel #1 (Transmitter Positive Terminal) Input Channel #1 (Transmitter Negative Terminal) Input Channel #2 (Transmitter Positive Terminal) Input Channel #2 (Transmitter Negative Terminal) Input Channel #3 (Transmitter Positive Terminal) Input Channel #3 (Transmitter Negative Terminal) Input Channel #4 (Transmitter Positive Terminal) Input Channel #4 (Transmitter Negative Terminal) Not Used Signal Return for signals marked (*) return) Analog Output #1 (4-20mA) * Analog Output #2 (4-20mA) * (Internally connected to DC power
Green LED Indicates Any Activity Red LED Indicates OMNI is Transmitting
ALL.71+ w 04/98
2-15
Chapter 2
2.7.
The SV I/O Combo Module has two RS-485 serial ports which are used to communicate with devices such as Rosemount 3095 multivariable transmitters via the Modbus Protocol. Dual LEDs on each port provide status of the communications. The module also has six 4-20 mA outputs.
SV Modules and Other Combo Module Types The flow computer can handle only two SV Modules and three other A, B, E/D, E or H I/O Combo Modules. An HV module can also be installed in lieu of one of these I/O combo modules.
LED Indicators
PORT 1 (3)
PORT 2 (4)
Fig. 2-12. Omni Multivariable Interface (SV Type Combo) Module Model 68-6203 - Jumper Settings
2-16
ALL.71+ w 04/98
Volume 1
Omni offers a variety of enclosure options which can all be customized based on customer specified requirements: q Panel Mounting q NEMA 4/4X q NEMA 7
3.1.1.
Panel Mounting - Panels less than 1/8 inch thick can be used but will require that the rear of the computer be supported.
Panel Mounting
A panel with the correct size cut out as dimensioned below is required. Panels should be a minimum of 1/8 inch thick. Use the two keyed nuts and clamping bars provided to mount the flow computer to the panel.
CAUTION!
These units have an integral latching mechanism which first must be disengaged by lifting the bezel upwards before withdrawing the unit from the case.
IMPORTANT!
The maximum length of the ribbon cable that connects the keypad to the CPU module is 18 inches. The operation of the Central Processor Module (CPU) will be significantly affected if this length is exceeded.
Fig. 3-1.
ALL.71+ w 04/98
3-1
Chapter 3
3.1.2.
Nema 4 / 4X Configurations
Both the NEMA 4 and NEMA 4X are weather-proof enclosures. The NEMA 4 is a standard steel enclosure, whereas the NEMA 4X is a stainless steel enclosure. Both Omni 6000 and Omni 3000 flow computers can be mounted inside the NEMAs on a sturdy swing frame. The NEMAs also include a 5 x 3 viewing window with a lexan plate to allow easy viewing. Custom enclosures are available. NEMA 4 / 4X FOR OMNI 6000 / 3000
Dimensions 24 in x 24 in x 12 in (610 mm x 610 mm x 305 mm) Weight 80 lbs (36 kg) Compliance q NEMA 4, -12 & -13 q UL 50, Type 4 q CSA Enclosure 4 q IEC 529, IP66
3.1.3.
Nema 7 Specification
The NEMA 7 is an explosion-proof enclosure which allows switch or pushbutton options for manipulating the contained flow computer. The viewing window is sustained by a 3 circular glass thick. Both the Omni 6000 and Omni 3000 flow computers can be mounted in the NEMA 7 with minimal specification variances. Custom enclosures are available. NEMA 7
Dimensions
FOR OMNI 6000
Compliance
Division 1 & 2 Class I; Groups B, C & D Class II; Groups E, F & G Class III q IEC
Compliance
Division 1 & 2 Class I; Groups B, C & D Class II; Groups E, F & G Class III q IEC
3-2
Volume 1
3.2.
INFO - A recommended maximum of 500mA of transducer loop power is available with a fully loaded system of 6 combo I/O modules, 2 digital I/O modules and 2 dual serial I/O modules. The computer must be DC powered if this 500 mA limit is to be exceeded.
Input Power
AC Power
3.2.1.
When AC powered, 120 VAC, 50 Watts is applied to the AC terminal block. Approximately 500 mA at 24 VDC is always available from the DC terminal block to drive transducer loops, pre-amplifiers, and digital I/O loads when the unit is powered by AC. The flow computer can be special ordered for operation on 220-250 VAC supplies. This requires a modified power supply unit and a different cord set.
CAUTION!
POTENTIAL FOR DATA LOSS! RAM Battery Backup Omni flow computers leave the factory with a fully charged Ni-Cd battery as RAM power backup. RAM data, including user configuration and I/O calibration data, may be lost if the flow computer is disconnected from external power for more than 30 days. Observe caution when storing the flow computer without power being applied for extended periods of time. The RAM back-up battery is rechargeable and will be fully charged after power has been applied for 24 hours.
3.2.2.
DC Power
When DC powered, 18 to 30 volts at 24 Watts is applied to the DC terminal block (this wattage figure does not include power sourced from the digital output terminals).
3.2.3.
Safety Considerations
To ensure continued protection against fire, the AC fuse must always be replaced with a 0.5 amp (5x20 mm) slow blow fuse. The DC fuse must be replaced by a 3 amp, 2 AG fast blow. Power should be connected via a suitable power disconnect switch certified as being safe for the area (for grounding requirements, see sidebar note on facing page).
ENVIRONMENTAL - The maximum system configuration of 24 process inputs, 12 process outputs, 24 digital I/O points and 4 serial I/O channels dissipates approximately 24 Watts. This causes an internal temperature rise of 15F over the ambient. The unit should not be mounted in a cabinet or panel where the ambient inside the cabinet will exceed 110F.
ALL.71+ w 04/98
3-3
Chapter 3
3.3.
3.3.1.
Power Terminals
CE Equipment Power Terminals
In this current version of the Omni 3000 and Omni 6000 back panel the AC receptacle is a power line filter with a separate AC fuse holder. The AC power is connected via a separate 4-wire conductor cable which plugs into the power supply. The DC terminal is on TB 11 (for Omni 6000) and on TB5 (for Omni 3000). The power supply used with this version is a Model 68-6118; no fuses.
Back Panel Fuses - All DC fuses are 3 amp, fast-blow Model 225.003, manufactured by Littlefuse. All AC fuses are amp, slow-blow Model 229.500, manufactured by Littlefuse
Earth Ground Requirements -To minimize the effects of electrical transients, the outer case of the flow computer should be connected to a high quality earth ground using the grounding stud located on the back of the unit (see Fig. 3-2). Connect the shields of all wiring to the same grounding stud. To eliminate earth loop currents, shields should be left unconnected and taped back at the other end.
Fig. 3-2.
3-4
ALL.71+ w 04/98
Volume 1
3.3.2.
Several mounting options are now available with the Omni 6000 flow computer by requesting the Extended Back Panel Termination option. This panel incorporates all the terminal blocks of Versions 2 and 3, TB1 through TB10 with terminals marked 1 through 12. Screw type terminals are provided for AC and DC power. In addition to TB1 through TB10, extra DC (fused), return and shield terminals are provided for TB1 through TB8. Extended 64-conductor ribbon cables and the AC cables are provided with a standard length of 5 feet.
Amp
Extended Back Panel Fuses - All DC fuses are amp fast-blow manufactured by Littlefuse, Model 225.250. The main DC fuse is 3 amp. The AC fuse is amp slowblow manufactured by Littlefuse, Model 239.500. The fuse for the back panels AC receptacle is a 5x20mm, amp slow-blow.
amp
3 Amp
Fig. 3-3.
ALL.71+ w 04/98
3-5
Chapter 3
Fig. 3-4.
Fig. 3-5.
3-6
Volume 1
3.4.
All analog and digital circuits within the flow computer are powered from a 5volt switching regulator located on the power supply module. This is located in the rear most connector on the computer backplane. The DC power which supplies the switching regulator either comes directly from the DC terminals on the back panel of the flow computer (18-30 VDC) or by rectifying the output of the integral 120 VAC (240 VAC) to 20 VAC transformer. DC power into or out of the back panel DC power terminals is fused by a 3 Amp, 2 AG fuse located on the back panel next to the DC power terminals. Regulated 5-volt power is monitored by a 3 to 4 second shutdown circuit located on the power supply module. When power is applied to the computer there will be a delay of 3 to 4 seconds before the unit powers up.
CAUTION
The Power Low and +5 v Adjust on the Power Supply Module are factory adjustments that require the use of special equipment. DO NOT attempt to adjust
Fig. 3-6.
ALL.71+ w 04/98
3-7
Volume 1
4. Connecting to Flowmeters
4.1. Turbine Flowmeter (A or B Combo Module)
Input Channels 3 and 4 can be independently jumpered to accept pulse signals. Channel 3 on the A and B Combo Modules and Channel 4 on the A Combo Module can be used to input turbine or positive displacement flowmeters. The input threshold is 3.5 volts; hysteresis 1/2 volt.
Fig. 4-1.
ALL.71+ w 04/98
4-1
Chapter 4
Connecting to Flowmeters
4.2.
Input Channels 3 and 4 of each E Type Combo Module are used to input signals from turbine or PD flowmeters. Both channels share a common signal return at the Omni terminals. Input threshold can be jumpered for +1 or +3.5 volt. Input coupling can be AC or DC (see Chapter 2). Hysteresis is approximately 0.5 volt.
Fig. 4-2.
4-2
ALL.71+ w 04/98
Volume 1
4.3.
Faure Herman Turbine Meters are used in liquid applications only. For these flowmeters, high threshold jumpers JP1 and JP8 on the E Type Combo Module must be installed.
Fig. 4-3.
Fig. 4-4.
ALL.71+ w 04/98
4-3
Chapter 4
Connecting to Flowmeters
4.4.
A flowmeter with dual channel out-of-phase outputs can be connected as shown. The flow computer can be configured to continuously compare the signals for frequency and sequence on a pulse-to-pulse basis, and alarm and log any differences. (See Volume 5, Technical Bulletin TB-970901 for more information on Pulse Fidelity Checking.)
Fig. 4-5.
4-4
ALL.71+ w 04/98
Volume 1
5.
Because of the high density of connections on the back panel terminal, it is recommended that wiring to the terminals be made with 18-22 gauge wire wherever possible. Transducers should be wired using twisted pairs of 18 gauge shielded wire. The shields should be connected together and grounded at the flow computer end. To prevent ground loops, shields should be taped back and insulated at the transducer end. Each of the 4-20 mA process input channels are individually optically isolated. The transducer may be connected in series with either the power or return line of the transducer current loop. The figure shown below shows a transducer wired in the power leg of the loop.
Fig. 5-1.
ALL.71+ w 04/98
5-1
Chapter 5
5.2.
Certain types of flowmeter photo-pulsers produce a low frequency contact pulse output (typical 1 pulse per barrel). To accommodate these low frequencies, they can be wired to any pulse input on A or E Type Combo Modules, as shown below.
Fig. 5-2.
5-2
ALL.71+ w 04/98
Volume 1
5.3.
INFO - Each A or B Type Combo Module always has 1 RTD excitation current source available at Terminal 9. A second source is always available on B Types at Terminal 12.
Channels 1 and 2 of each combo I/O module can be jumpered to accept a signal from a 100 ohm RTD probe. The flow computer can be configured for the DIN 43-760 curve (= 0.00385) or the American curve (=0.00392). The probe is wired in a 4-wire configuration as shown below.
TIP - The excitation current source for an RTD need not come from the same combo module from which the signal is input. You will need to recalibrate the input channel if you choose to use an excitation source from another combo module.
Fig. 5-3.
ALL.71+ w 04/98
5-3
Chapter 5
5.4.
5.4.1.
INFO - Because the density pulse signal can be a small AC signal with a large DC offset, you must select AC coupling and low trigger threshold for the combo module channel used; i.e.: on the B Type Combo Modules, JP13 in the AC position and JP11 out; on E/D Combo Modules, JP2 and JP7 in the AC positions and JP1 and JP8 out. Input impedance will be 10kohms; 1.5Vpp is required from the densitometer to reliably trigger the input.
Wiring Densitometers
Wiring Densitometer Signals to an E/D Type Combo Module
Two independent densitometers with RTD probes can be wired directly to an E/D type combo module. For example, Solartron and UGC densitometers can be wired to the same E/D Type Module.
5.4.2.
Solartron Densitometers
Connecting to a Solartron Digital Densitometer actually involves two devices: the densitometer current pulse signal and the densitometer 4-wire RTD probe attached to the vibrating tube. The pulse signal is connected to Channel 4 of a B Type Combo Module. The RTD is connected to Channel 1 or Channel 2. The device can be connected with or without safety barriers, depending on the needs of the application.
INFO - When configuring the flow computer, select the DIN curve for this RTD temperature point.
Fig. 5-4.
Wiring a Solartron Densitometer with Safety Barriers to a B Type I/O Combo Module
5-4
ALL.71+ w 04/98
Volume 1
NOTICE!
Diagrams shown are based on published manufacturers, data. Omni accepts no responsibility for wiring or installation of equipment in a hazardous area. Equipment must always be installed in compliance with local and national safety standards.
Fig. 5-5.
Wiring a Solartron Densitometer without Safety Barriers to a B Type I/O Combo Module
ALL.71+ w 04/98
5-5
Chapter 5
5.4.3.
INFO - Because the density pulse signal can be a small AC signal with a large DC offset, you must select AC coupling and low trigger threshold for the combo module channel used; i.e.: on the B Type Combo Modules, JP13 in the AC position and JP11 out; on E/D Combo Modules, JP2 and JP7 in the AC positions and JP1 and JP8 out. Input impedance will be 10kohms; 1.5Vpp is required from the densitometer to reliably trigger the input.
Sarasota Densitometers
The Sarasota Densitometer provides a voltage pulse signal representing density and also a 4-wire 100 ohm RTD probe monitoring the temperature of the device. The pulse signal is connected to Channel 4 of a B Type Combo Module. The RTD is connected to Channel 1 or Channel 2 of any module. The device can be connected with or without safety barriers, depending on the needs of the application.
Fig. 5-6.
Wiring a Sarasota Densitometer with Safety Barriers to a B Type I/O Combo Module
INFO - When configuring the flow computer, select the DIN curve for this RTD temperature point.
5-6
ALL.71+ w 04/98
Volume 1
NOTICE!
Diagrams shown are based on published manufacturers, data. Omni accepts no responsibility for wiring or installation of equipment in a hazardous area. Equipment must always be installed in compliance with local and national safety standards.
Fig. 5-7.
Wiring a Sarasota Densitometer without Safety Barriers to a B Type I/O Combo Module
ALL.71+ w 04/98
5-7
Chapter 5
5.4.4.
INFO - Because the density pulse signal is a large DC pulse signal with little or no DC offset, you must select DC coupling with normal trigger threshold for the combo module channel used; i.e.: on the B Type Combo Modules, JP13 in the DC position and JP11 in; on E/D Combo Modules, JP2 and JP7 in the DC positions and JP1 and JP8 in. Input impedance will be 1Mohms; <3.0Vfor low level and >4V.0 for high level is required from the densitometer to reliably trigger the input.
UGC Densitometers
The UGC Densitometer output provides an open collector transistor that requires an external pull-up resistor to 24 volts DC. The densitometer provides a 24 volt DC pulse output in the range of 1 to 2 kHz. The pulse signal is connected to Channel 4 of a B Type Combo Module and can be connected with or without safety barriers, depending on the application requirements.
Fig. 5-8.
Wiring a UGC Densitometer with Safety Barriers to a B Type I/O Combo Module
5-8
ALL.71+ w 04/98
Volume 1
NOTICE!
Diagrams shown are based on published manufacturers, data. Omni accepts no responsibility for wiring or installation of equipment in a hazardous area. Equipment must always be installed in compliance with local and national safety standards.
Fig. 5-9.
Wiring a UGC Densitometer without Safety Barriers to a B Type I/O Combo Module
ALL.71+ w 04/98
5-9
Chapter 5
5.5.
Up to four Honeywell Smart Transmitters can be wired to each H Type Combo I/O Module. Loop power is provided by the combo module. No external power is required.
5-10
ALL.71+ w 04/98
Volume 1
5.6.
5.6.1.
The frequency/pulse output that represents the volume flow from the RFT9739 Transmitter can be wired directly into either Frequency Channel 3 or 4 on A Type or E Type Combo Modules. (See Technical Bulletin TB-980401.)
ALL.71+ w 04/98
5-11
Chapter 5
5.6.2.
Serial communication via RS-485 can be accomplished using the Peer-to-Peer Mode via Omni Serial Port #2 of the RS-232-C/485 Serial Module # 68-6205, with selection jumpers in the RS-485 position. (See Technical Bulletin TB980401.)
OMNI BACK PANEL TERMINALS SERIAL PORT #2 (PEER-TO-PEER) RS-485 MODE SELECTED 7 (B) 8 9 10 11 (A)
Fig. 5-12. Wiring of a Micro Motion RFT9739 Field-Mount (Explosion-Proof) Transmitter Via Two-wire RS-485 Communications (Serial I/O Module #686205)
5-12
ALL.71+ w 04/98
Volume 1
5.6.3.
Serial communication via RS-485 can also be accomplished utilizing the Peerto-Peer Mode via RS-232-C. (See Technical Bulletin TB-980401.)
Fig. 5-13. Wiring of a Micro Motion RFT9739 Field-Mount (Explosion-Proof) Transmitter Via Serial RS-485 Converter
ALL.71+ w 04/98
5-13
Volume 1
Analog outputs are available for remote terminal units, flow controllers, and recording devices. The analog outputs source 4-20 mA into a load wired to the DC power return. Maximum load resistance is 1000 ohms at 25 VDC. Digital-toAnalog conversion is accomplished with a 12-bit binary resolution. Two outputs are available on each A Type Combo Module. One output is available on each B Type Combo Module. To calibrate, each of the outputs is set to 4.00 and 20.00 mA and the software zero and span adjusted while in the Diagnostic Mode (described later). Any value between 2.5 and 23.0 mA may be output. Each output is assigned via the keypad or serial link to one of the many variables available (see Volume 3).
Fig. 6-1.
ALL.71+ w 04/98
6-1
Chapter 6
6.2.
6.2.1.
Digital Inputs/Outputs
Wiring a Digital Point as an Input or an Output
Digital I/O modules handle 12 digital points. Each point can be independently configured as either an input or output via the keypad or via a serial port. The power and returns for all digital I/O signals are common with the DC power terminals. Digital output loads are connected between the I/O terminal and DC power return. An approximate total load of 500 mA per module (per 12 points) is allowed although an individual point can handle 200 mA. Voltages applied to I/O points used as inputs must not exceed the DC supply voltage at the DC terminal, or the protective fuse for that point on the digital I/O module may blow.
Fig. 6-2.
6-2
ALL.71+ w 04/98
Volume 1
Fig. 6-3.
ALL.71+ w 04/98
6-3
Chapter 6
6.2.2.
On the Omni 6000, Digital I/O Module #1, handling points 1 through 12, is plugged into the backplane connector marked I/O Module #1. This in turn is connected to Terminal Strip TB1-1 through 12. Digital I/O Module #2, handling points 13 through 24, is plugged into the backplane connector marked I/O Module #2 which is connected to Terminal Strip TB2-1 through 12. The Omni 3000 has only one digital I/O module which is connected to Terminal TB1-1 through 12 on the back panel. The diagram below shows the typical wiring required to interface to other devices, such as: switches, relays, provers, programmable logic controllers, among other devices.
Fig. 6-4.
6-4
ALL.71+ w 04/98
Volume 1
6.3.
6.3.1.
INFO - The prover detector switch signal activates an interrupt request into the computer. Jumpers JP1 and JP2 on the digital I/O module (Fig. 1-5) control which edge of the signal will cause the interrupt. Pulse counting should start when the sphere first activates the detector switch. Install JP1 in cases where the detector switchs normally opened contacts are used (Fig. 1-9). Install JP2 in cases where the detector switchs normally closed contacts are used.
Provers
Connecting Pipe Prover Detector Switches
Pipe prover detector switches are the only I/O signal that must be connected to a specific I/O point. They must be wired as shown in Fig. 6-4 to Digital I/O Point #1, and the point assigned to Boolean 1700 in the software configuration (see Volume 3). This is because Digital I/O Point #1 is internally jumpered to cause a high priority interrupt of the computer used to start and stop prover counting. Digital I/O Point #1 can still be used as a normal I/O point if pipe proving is not needed.
6.3.2.
The Omni Flow Computer interfaces to the basic Brooks Compact Prover Skid Electronics (the Brooks Control Box is not used). The control interface involves one digital output to control the piston launch, a digital input point to monitor the position of the piston, and a detector switch signal shared between each meter run to be proved. Compact provers use the Pulse Interpolation Method of measuring the flowmeter counts between the detector switches. The interpolation method requires that the detector switches activate high speed hardware timers on the Omnis combo I/O module. The detector switch signals called first and final pickoff by Brooks are connected to the Detector Switch input of each E Type Combo Module installed in the flow computer. The following diagram shows the complete installation, including 4-20 mA signals representing the temperature and pressure of the prover tube as well as the nitrogen plenum chamber. The 12-volt DC power supply is user supplied.
Note: When using double chronometry proving, the detector switch input is on Terminal 7 of an E Type Combo I/O Module.
Fig. 6-5.
ALL.71+ w 04/98
6-5
Chapter 6
6.3.3.
The plenum chamber pressure is used as a spring to close the poppet valve of the piston and cause the piston to be moved forward by the flowing liquid. The pressure required to close the poppet valve varies with pipeline pressure. Too high a plenum pressure causes the piston to be pushed downstream by this excess pressure and can lead to inaccurate provings. The Omni Flow Computer can monitor the plenum pressure and line pressure, and automatically charge or vent nitrogen from the plenum chamber. Before commencing a proving run, the Omni Flow Computer plenum pressure versus the required pressure and activates either or vent solenoid valve. The pressures will be matched within entered deadband percent. The Omni activates the solenoids via relays (not shown). checks the the charge some user low voltage
An additional enhancement shown is a pressure switch signaling low nitrogen bottle pressure. In this case, the prove attempt would be aborted if it became impossible to achieve the correct plenum pressure.
Fig. 6-6.
6-6
ALL.71+ w 04/98
Volume 1
The total number of serial communication ports depends on the number of dual port serial I/O modules installed. The Omni 6000 accepts 2 serial I/O modules; the Omni 3000 accepts 1. Two optional serial communication I/O modules are available with your flow computer (see Chapter 1): the RS-232-C (compatible) Model #68-6005, and the RS-232-C/485 Model #68-6205. The older Model #686005 is only capable of RS-232 compatible serial communications. The newer Model #68-6205 is capable of either RS-232 or RS-485 communications via a selection jumper. When jumpered for RS-232, the characteristics and functionality of this module is identical to that of the older RS-232-C module, providing 2 optically isolated RS-232-C serial ports which can operate from 0.3 to 38.4 kbps. These ports are used for printers, personal computers, and SCADA devices. Although the output voltage levels are compatible with the RS-232 standard, the output is actually tristated when not sending data. This allows the transmit output from multiple flow computers to be bussed. A terminating resistor is provided at the back panel connections to pull down the transmitter signal to a mark (-9V). Hence, a short jumper is required in many cases from TX (Out) to Term. RS-485 communications allows interconnecting multiple flow computers, programmable logic controllers, multivariable transmitters, and other serial devices in either four-wire multi-drop mode or peer-to-peer two-wire multi-drop mode.
RS-485 Communications with an RS-232-C Serial I/O Module #68-6005 - When connecting to RS-485 serial devices using Serial I/O Module #68-6005, a RS-232to-485 Converter device must be used.
Multivariable Transmitting Devices - In addition to the Serial I/O Module # 68-6205, the flow computer must also have an SV Module to communicate with RS-485 compatible multivariable transmitters. This serial module must be jumpered to IRQ 3 when used in combination with an SV Module. Without an SV Module, the jumper must be placed at IRQ 2. The SV Module can only be used with this serial module (68-6205) and is not compatible with the Serial I/O Module # 686005. For more information, see Technical Bulletin # TB980303.
ALL.71+ w 04/98
7-1
Chapter 7
7.2.
7.2.1.
INFO - The speed that data can be accepted by the printer depends on the size of the input buffer (if any) and the print mode (draft or near letter quality). Typical printers provide about 120 printed characters/second.
Connecting to Printers
Connecting to a Dedicated Printer (Port 1)
The following diagram shows the Omni Flow Computer connected to a dedicated printer. The hardware handshake wire connected to Pin 20 of the DB25 connector is optional, as the computer can be made to insert null characters after each carriage return to match the computer data transmission rate to the printer speed.
TIP - Most printers default to the draft mode. Leave it there for maximum performance. Because of impact printer limitations, no speed improvement is obtained by selecting baud rates over 2.4kbps.
Fig. 7-1.
7-2
ALL.71+ w 04/98
Volume 1
7.2.2.
Up to 12 Omni flow computers can share a printer. They are connected as shown. One flow computer is assigned as the master and manages all traffic to the printer. Each computer monitors the data transmitted to the printer by having its TX terminal jumpered to its RX terminal. Resident firmware ensures that only one computer will attempt to access the printer at any one time.
Fig. 7-2.
7.2.3.
Note: Refer to Volume 3, Chapter 2 for Printer Settings.
Most problems associated with printer sharing show up as garbled reports or locked up printers. This is usually caused by one or more computers sending data to the printer at the same time. Check your wiring to the figure above and consult the following checklist if you experience problems: 1) Check that all computers are set to the same baud rate, stop bits, and parity settings as the printer. 2) All computers must have the Transmitter Key Delay set to zero (0). 3) One and only one computer must have its Printer Priority Number set to 1. All computers must have a different priority number. 4) Some printers provide jumpers or switches which set the polarity of the Printer Ready signal on Pin 20. This signal must be positive when the printer is ready. 5) When not using the Printer Ready signal (Pin 20), ensure that you have entered enough NULs to prevent overrunning the printer buffer.
ALL.71+ w 04/98
7-3
Chapter 7
7.3.
Note:
Ports #1 and #2 (Ports #3 and #4* of an Omni 6000) can provide access to the computers database using a Modbus protocol interface. This port is usually connected to a PC running the OmniCom configuration software. Up to 12 Omni flow computers can be connected to 1 PC. The Modbus protocol includes an address field which ensures that only 1 unit will transmit at a time.
Fig. 7-3.
Direct Connect to a Personal Computer - DB25 Female Connector (Using Port #2 as an example)
7-4
ALL.71+ w 04/98
Volume 1
Fig. 7-4.
Fig. 7-5.
ALL.71+ w 04/98
7-5
Chapter 7
7.4.
Peer-to-Peer Communications - The peer-to-peer communication feature allows you to multidrop up to 32 flow computers and other devices in RS-485 serial communications mode, and up to 12 using RS-232-C communications.
Serial Port #2 can also be configured by the application software to act as a peer-to-peer Modbus master port. This is a half duplex/simplex link which allows any Omni Flow Computer to communicate with any other flow computer or Modbus slave device. That data link can operate at up to 38.4 kbps and uses a proprietary token passing scheme. Interconnecting multiple flow computers and or multiple serial devices can be accomplished via RS-232-Compatible or RS-485 communications.
Peer-to-Peer Redundancy Schemes - Redundancy schemes allows for uninterrupted measurement and control functionality by interconnecting two identically equipped and configured flow computers (see Technical Bulletin TB980402).
7.4.1.
The diagram below shows the wiring requirements for multi-dropping two or more flow computers via RS-485 in two-wire mode. This option is available only with the Omni Serial I/O Module #68-6205. (See Technical Bulletin #TB980401.)
OmniCom and Peer-toPeer - The OmniCom Configuration PC Software package supplied with your Omni Flow Computer cannot be used on Serial Port #2 when it is being used as a peer-to-peer link.
UP TO 32 FLOW COMPUTERS
GND
Fig. 7-6.
Wiring of Several Flow Computers using the Peer-to-Peer Feature via RS-485 Communications in Two-wire Multi-drop Mode
7-6
ALL.71+ w 04/98
Volume 1
7.4.2.
The diagram below shows the wiring requirements for multi-dropping two or more flow computers in RS-232 C (compatible) mode. When multi-dropping two or more flow computers with other serial devices via the RS-232-C mode, an RS-232-to-RS-485 standard converter may be required. (See Technical Bulletin #TB-980401.)
Fig. 7-7.
Wiring of Several Flow Computers in the Peer-to-Peer Mode using RS-232-C Communications.
7.4.3.
Note: Refer to Volume 3, Chapter 2 Flow Computer Configuration.
Use the RTS signal to key the modem or radio transmitter carrier in a multi-drop application. A delay between activating the RTS signal and actually sending data is provided to allow for carrier acquisition at the remote end. This delay can be selected as 0.0 msec, 50 msec, 100 msec, or 150 msec.
ALL.71+ w 04/98
7-7
Chapter 7
7.4.4.
The diagram below shows the wiring requirements for multi-dropping two or more flow computers via RS-485 in four-wire mode to a third party PLC type device. Note that in the wiring example shown below, the PLC acts as a master and can communicate with either flow computer. A four-wire wiring system does not allow communications between slaves; i.e., data can only be transferred between master and slaves. The RS-485 option is available only with the Omni Serial I/O Module #68-6205.
TX-B
A GND B TX
TX-A
RS-485 TERMINATED
Fig. 7-8.
Wiring of Multiple Flow Computers to a PLC Device Via RS-485 Communications in Four-wire Multi-drop Mode
7-8
ALL.71+ w 04/98
Volume 1
7.5.
When using an Omni 6000 with 2 serial I/O modules installed, a second Modbus port (Physical Port #3 used as an example) can provide access to the computers database. This port can also be connected to a PC or any SCADA device either directly, via modem, or via radio link.
Fig. 7-9.
ALL.71+ w 04/98
7-9
Chapter 7
7.6.
Port #4 is available on Omni flow computers with the second serial module fitted. This port can be selected to communicate with Allen-Bradley devices using DF1 full duplex or half duplex protocol, or set up for Modbus devices. The example below assumes that the Allen-Bradley Protocol has been selected.
7-10
ALL.71+ w 04/98
Volume 1
In the diagnostic mode you can verify that the I/O modules and transducers are working and are calibrated to specification. The actual process transducers used may provide a variety of signal types, ranging from voltage or current pulses of various levels, to linear analog signals such as 4-20 mA., 1-5V, 0-1V or RTD elements. In the case of pulse inputs, the input module provides amplification and/or level shifting, Schmitt triggering and opto-isolation. When analog signals are used the input module provides all signal conditioning, opto-isolation, and converts the analog signal to a high frequency pulse train, in the range of 0 - 20 kHz. By using a precision voltage to frequency converter, typical linearity of +/-0.01 % is obtained. Certain diagnostic displays are always available while in the Display Mode. For example pressing [Input] then [Display] will display the raw frequency input from each process input point. The up/down arrow keys can be used to scroll through all inputs. A typical display shows:
INFO - When viewing an analog input point, the frequency displayed approximates 1000Hz/mA. When viewing a turbine or photo pulsar signal, the display is the actual input frequency.
Input % Freq/Period #1 2530 Input % /Freq/Period #2 3021 Pressing [Output] [Status] [Display] shows the current percentage output for each of the digital to analog 4-20 mA outputs.
ALL.71+ w 04/98
8-1
Chapter 8
8.2.
INFO - The Diagnostic LED glows red after a valid password has been asked for and entered.
In the Diagnostic Mode the user selects a specific process variable to calibrate or view. The display shows the input channel and combo module used for the variable. Calibration override values can be input and the input signals can be viewed simultaneously as engineering values % span, input voltage and current. Analog outputs and digital I/O points can also be viewed and manipulated.
8.2.1.
To enter the diagnostic mode proceed as follows press the [Alpha Shift] key, then the [Diag] key.
INFO - The Select Input/Output screen must be displayed when making a new selection while in the Diagnostic Mode. Return to this screen by pressing the [Diag] key once.
The front panel diagnostic LED will glow green and the following will be displayed on the first three lines of the LCD Display: Select Input/Output to Calibrate, Press "Diag" to Exit
8-2
ALL.71+ w 04/98
Volume 1
8.2.2.
INFO - Each input channel of each combo module has had its temperature coefficient trimmed to 10 ppm/F. To avoid temperature gradient effects and for best results, always allow the internal temperature of the computer to stabilize before making your final calibration adjustments.
To display an input or output variable to calibrate, select from the following display groups and associated key presses or select the I/O number if known, (usually supplied on a separate sheet).
DISPLAY VARIABLES
All of the following key presses are valid in the Diagnostic Mode. To enter the Diagnostic Mode, these key presses must be preceded by the [Alpha Shift] [Diag] keys. Input Channels
(n = 1 through 24) (n = 1 through 4) [Input] or [Input] [n] [Temp] or [Temp] [Meter] [n] [Press] or [Press] [Meter] [n] [Density] or [Dens] [Meter] [n] [Density][Temp] or [Density][Temp][Meter][n] [Density][Press] or [Density][Press][Meter][n] [Prove} [Temp] [Prove} [Temp] [Output] [n] [Status] [n]
(n = 1 through 4)
(n = 1 through 4)
Meter Density Temp (n = 1 through 4) Meter Dens Pressure (n = 1 through 4) Prover Temperature (Left, Right) Prover Pressure (Left, Right) Output Channels Digital I/O
(n = 1 through 24)
(n = 1 or 2)
8.2.3.
Once you are done viewing and/or modifying the calibration settings, press [Diag] to return to the selection screen below: Select Input/Output to Calibrate, Press "Diag" to Exit
Press the [Diag] key again to return to the Display Mode (Diagnostic LED will turn off).
ALL.71+ w 04/98
8-3
Chapter 8
8.3.
8.3.1.
Note: You can also calibrate the input and output of your choice by entering the number of that input or output; e.g.: Press [Input] [1] [Enter]; press [Output] [4] [Enter]. With this method you can calibrate the inputs and outputs to the computer without having them assigned to any I/O point numbers.
Calibration Instructions
Calibrating A Voltage or Current Analog Input
While the above display is shown select the input variable to calibrate. For example to calibrate Meter Run #1 Temperature, press [Meter] [1] [Temp] (or the input # if known). The display shows: Select Input/Output to Calibrate, Press "Diag" to Exit Meter 1 Temp Other key press combinations work. [Temp] [Meter] [1] means the same to the computer as [Meter] [1] [Temp]. Pressing [Temp] without a meter number allows all of the temperatures to be scrolled through and calibrated. Now enter the selection by pressing [Display] and the following is displayed: Temperature #1 Input# & Module 1-a1 Override 60.0 Calibrate Input ? _
INFO - Unless previously entered, a request for a valid password is made at this point. The calibrate override value entered will be substituted for all process variables assigned to this physical I/O point when the user answers [Y] to Calibrate Input ?. It is automatically removed when the user presses the [Diag] key to exit or make a new selection.
The display shows the process variable name, the input channel number and combo module used. This example shows Temperature Meter Run #1 connected to Channel 1 of Combo Module A1. Before calibrating an input the user should enter a Cal Override value to be used in all calculations in place of the live value. Answer [Y] to the 'Calibrate Input ?' question and the following is displayed: Meter 1 % Value Input Volts mA Value 27.5 50.00 3.000 12.00
8-4
ALL.71+ w 04/98
Volume 1
INFO - Each input channel of each combo module has had its temperature coefficient trimmed to 10 ppm/F. To avoid temperature gradient effects and for best results, always allow the internal temperature of the computer to stabilize before making your final calibration adjustments. INFO - The []/[] keys are used as a software Zero potentiometer. Adjustments made when the Shift LED is on are approximately ten times more sensitive. Holding the arrow keys longer than two seconds speeds up the rate of adjustment.
1) Disconnect the transducer signal and replace it with a stable current or voltage source capable of inputting 4.000 to 20.000 mA or 1.000 to 5.000 V signal. 2) Set the input signal to 4.000 mA or 1.000 V as applicable. 3) Using the Up/Down arrow keys adjust the displayed value so it reads 4.000 mA / 1.000 V. 4) Set the input signal to 20.000 mA or 5.000 V as applicable. 5) Using the Left/Right arrow keys adjust the displayed value so it reads 20.000 mA / 5.000 V. 6) Recheck step 2) No further adjustment is normally needed if the Zero is adjusted at exactly 4.0 mA. 7) Disconnect the calibrator signal and reconnect the transducer signal. 8) Press the [Diag] key to return to the selection screen.
TIP - The Span adjustment has no effect at 4mA or 1v. Always adjust the Zero first at exactly 4mA or 1v.
8.3.2.
Leaving the Diagnostic Mode - In the Select Input/Output screen, press the [Diag] key to return to the Display Mode (Diagnostic LED will turn off).
While the above screen is being displayed select a process variable which is assigned as an RTD probe input. For example, assuming a pulse type densitometer is installed, pressing [Meter] [1] [Density] [Temp] (or the input # if known), selects the input channel used to process Meter Run #1's Densitometer integral RTD. Other key press combinations will work, and [ Density] [Meter] [1] [Temp] all mean the same. Pressing [Density] [Temp] allows the user to scroll through all density temperature channels. Now enter the selection by pressing [Display] and the following is displayed:
ALL.71+ 04/98
8-5
Chapter 8
INFO - Each input channel of each combo module has had its temperature coefficient trimmed to 10 ppm/F. To avoid temperature gradient effects and for best results, always allow the internal temperature of the computer to stabilize before making your final calibration adjustments.
1) Disconnect the RTD probe and connect precision decade resistance box. capable of inputting 25.00 to 150.00 Ohms as shown below. 2) Set the decade box to 25.00 Ohms. 3) Using the Up/Down arrow keys adjust the displayed value so it reads 25.00 Ohms. 4) Set the decade box to 150.00 Ohms. 5) Using the Left/Right arrow keys adjust the displayed value so it reads 150.00 Ohms. 6) Recheck step 2). No further adjustment is normally needed if the Zero is adjusted at exactly 25 Ohms. 7) Disconnect the decade box and reconnect the RTD probe. 8) Press the [Diag] key to return to the selection screen. Select Input/Output to Calibrate, Press "Diag" to Exit
INFO - Installing the decade box at the actual RTD probe location provides maximum accuracy, but can be inconvenient. The errors introduced by installing the decade box at the back panel terminals of the flow computer are approximately 0.01% per 100 ohms of field wiring resistance.
TIP - The Span adjustment has no effect at 4mA or 1v. Always adjust the Zero first at exactly 4mA or 1v.
Leaving the Diagnostic Mode - In the Select Input/Output screen, press the [Diag] key to return to the Display Mode (Diagnostic LED will turn off).
Fig. 8-1.
8-6
ALL.71+ w 04/98
Volume 1
8.3.3.
Each of the analog outputs can be calibrated by monitoring the loop current with an accurate milliamp meter and setting the output current to 4.00 mA and 20.00 mA. For example to calibrate Analog Output #1 proceed as follows: While the 'Select Input/Output' screen is displayed, press [Output] [1] [Display]. The display shows: Analog Output #1 0%=4mA, 100%=20mA Override % 0.00 Calibrate Output ? _
CAUTION!
Answer [Y] to the 'Calibrate Output ?' question and the display shows: Analog Output #1 0%=4mA, 100%=20mA Override % 0.00 Override Now Active To calibrate the output channel follow these steps: 1) Connect an accurate milliamp meter in series with the load. 2) Input 0.00 % (4.00 mA) as the output override. 3) Using the Up/Down arrow keys adjust the output current until the milliamp meter indicates 4.00 mA. 4) Input 100.00 % (20.00 mA) as the output override. 5) Using the Left/Right arrow key adjust the output current until the milliamp meter indicates 20.00 mA. 6) Repeat steps 2) through 5) until no further improvement can be obtained. 7) Remove the milliamp meter and reconnect the load. 8) Press the [Diag] key to return to the selection screen.
At this point, the analog output reflects the value of the currently displayed override, not the assigned variable. The user must ensure that any equipment using the output signal will not cause an unsafe condition to arise or cause erroneous results to be generated.
Leaving the Diagnostic Mode - In the Select Input/Output screen, press the [Diag] key to return to the 'Display Mode' (Diagnostic LED will turn off).
ALL.71+ w 04/98
8-7
Chapter 8
8.3.4.
The digital I/O points can be manipulated as a group by pressing [Status] [1] for digital points 1 through 12 or [Status] [2] for digital points 13 through 24. Pressing [Status] will allow the user to scroll to either group. Press [Display] and a screen similar to the following is displayed: Digital#1 I/O Points Input 001011001011 Overide 101010101010 Force To Output ? _
CAUTION!
After answering [Y], the digital outputs will reflect the value of the currently displayed override, not the assigned variable. The user must ensure that any equipment using the output signal will not cause an unsafe condition to arise or cause erroneous results to be generated.
The second line shows the status of the I/O points frozen at the time that the screen was displayed. The points are numbered left to right (1 to 12) with a '0' indicating that a point is off and a '1' indicating that a point is on. The third line shows the override bit values that will be forced to the output port when the user answers [Y] to the 'Force To Output ?' question. A screen similar to the following is displayed: Digital#1 I/O Points Input 101110001101 Overide 101010101010 Override Now Active The override '1's and '0's can be changed at any time while the 'Override Now Active' line is displayed. The input status displayed on the second line should always agree with the green LEDs on the edge of the digital I/O module. Red LEDs lit indicate blown fuses on the digital I/O module. Outputs on this I/O module that are assigned as totalizer outputs will stop counting while the 'Override Now Active' line is displayed. Pulses to be output are accumulated and are output at the maximum allowed rate as soon as the [Diag] key is pressed. Press [Diag] to return to the selection screen below:
INFO - To avoid a hardware conflict, only points that have been assigned as outputs will accept an override of 1; i.e., entering a 1 at an input position will be ignored and displayed as a 0.
Leaving the Diagnostic Mode - In the Select Input/Output screen, press the [Diag] key to return to the Display Mode (Diagnostic LED will turn off).
8-8
ALL.71+ w 04/98
Volume 1
Environmental
Operating Temperature : q -15C to +65C Storage Temperature : q -20C to +75C Relative Humidity : q 80% non-condensing maximum
9.2.
Electrical
Supply Voltage : q 120 VAC, 50-500 Hz; or 18-30 VDC, 10-20 Watts (excluding transducer loops) q Optional: 220-250 VAC, 50-500 Hz; or 1830 VDC, 10-20 Watts (excluding transducer loops) Transducer Output Power : q 24 VDC at 400 mA+ for configurations (when AC powered) most
Isolation : q All analog inputs and outputs are optically isolated from computer logic supply q Maximum common mode voltage on any input or output is 250 VDC to chassis ground.
9.3.
Microprocessor CPU
Type : q Motorola MC68HC000FN16 q Clock Speed: 16 MHz, 0 wait state; Throughput 4,000,000 instructions/sec Coprocessor : q Motorola MC68HC881/82FN16B q Clock Speed: 16 MHz; Throughput 50,000 floating point operations/sec EPROM Memory : q 1 Mbyte. expandable to 2 Mbytes max. RAM Memory : q 512 bytes standard; Expandable to 1 Mbytes max. Real Time Clock : q Battery backed-up, time of day; programmable interval down to 1 msec q Maintains time during power loss q Reports downtime on power-up Logic Voltage : q 5 VDC Over-voltage Protection : q Crowbar on power supply fires at 6.25 VDC approx. Transient Protection : q Transorbs on power supply module RAM Memory Battery Backup : q 3.6 VDC Ni-Cad; rechargeable
9-1
Chapter 9
9.4.
NOTICE!
Omni Flow Computers, Inc., pursuant to a policy of product development and improvement, may make any necessary changes to these specifications without notice.
Backplane
Type : q Passive; configured connectors Number of I/O Module Slots : q Omni 3000: 4 slots q Omni 6000: 10 slots with plug-in DIN
9.5.
TYPE
ADDITIONAL FEATURES
1-5v; 4-20mA; Flow Pulses 1-5v; 4-20mA Flow Pulse Frequency Density
Pipe Proving
Pipe Proving
E/D
Frequency Density
Flow Pulses
Honeywell DE Protocol
HV
SV
Six 4-20mA
9.6.
Positive Going Trigger Threshold : q +4.0 Volts Negative Going Trigger Threshold : q +2.0 Volts Input impedance : q 1 M Ohm Configuration : q Differential input (E module inputs are single ended referenced to DC ret.) Common Mode Voltage : q 250 VDC to chassis ground Pulse Fidelity Check : q Channels are continuously compared for frequency and sequence. E Module Only : q Complete failure of either A or B channel will not effect totalizing q Simultaneous noise pulses are rejected with 85% certainty
9-2
ALL.71+ w 04/98
Volume 1
9.7.
NOTICE!
Omni Flow Computers, Inc., pursuant to a policy of product development and improvement, may make any necessary changes to these specifications without notice.
9.8.
9.9.
Analog Inputs
Input Type : q 4 - 20 mA or 1-5 V Input Impedance : q 1 MegOhm (250 Ohms) (4-20 mA range selected by installing shunt resistor) Resolution : q 14 Binary Bits, w/ 500 msec sample Linearity : q 0.020% F.S. typical 1 Digit Temperature Drift : q Less than 15 ppm/OF Common Mode Voltage : q 250 VDC to chassis ground
ALL.71+ w 04/98
9-3
Chapter 9
Resolution : q 12 Binary Bits Output : q Current source 4-20 mA (referenced to transducer power return terminal) Common Mode : q 250 Volts to chassis ground Max./Min. Working Loop Voltage : q 30 VDC to 18 VDC Loop Resistance : q 900 Ohm with 24 VDC Power q 1.2 k Ohm with 30 VDC Power Update Rate : q Each 500 milliseconds
9-4
ALL.71+ w 04/98
Volume 1
9.13.2. RS-485
(2 per Module)
Serial Data Output Voltage : q 5 Volts differential driver Recommended Load Impedance : q 120 Ohm Short Circuit Current : q 20 mA Input Low Threshold : q 0.8 Volts Baud Rate : q Software selectable q Range 1.2, 2.4, 4.8, 9.6, 19.2, 38.4 k bps Common Mode Voltage : q 250 Volts to chassis ground LEDs : q Indicator LEDs for each channel input, output and handshaking signals
ALL.71+ w 04/98
9-5
Chapter 9
Quantity : q Three, with programmable function Display : q 6-digit, non-resetable Character Height : q 5 mm Maximum Count Rate : q 10 counts per second
or
Green: to indicate Alpha Shift Lock Mode is active Red: to indicate alpha shift next key only
9.18. Security
Hardware : q Optional lock on housing and internal keyboard program lockout Software : q Multi-level password control
9-6
ALL.71+ w 04/98
Volume 2a
Basic Operation
BASIC OPERATION
Contents of Volume 2
Figures of Volume 2 ........................................................................................................ iii 1. Basic Operating Features......................................................................................... 1-1
1.1. Overview of the Keypad Functions .......................................................................1-1 1.2. Operating Modes ....................................................................................................1-2
1.2.1. Display Mode ......................................................................................................... 1-2 1.2.2. Keypad Program Mode.......................................................................................... 1-2 1.2.3. Diagnostic and Calibration Mode ......................................................................... 1-2 1.2.4. Field Entry Mode ................................................................................................... 1-2
1.4. Adjusting the Display..............................................................................................1-5 1.5. Clearing and Viewing Alarms .................................................................................1-6
1.5.1. Acknowledging (Clearing) Alarms........................................................................ 1-6 1.5.2. Viewing Active and Historical Alarms .................................................................. 1-6 1.5.3. Alarm Conditions Caused by Static Discharges.................................................. 1-6
20/24.71+ w 04/98
Contents of Volume 2
2.4. PID Control Remote Setpoint ................................................................................ 2-4 2.5. Using the PID Startup and Shutdown Ramping Functions.................................. 2-5 2.6. Startup Ramp/Shutdown Ramp/Minimum Output Percent .................................. 2-5 2.7. PID Control Tuning................................................................................................. 2-6
2.7.1. Estimating The Required Controller Gain For Each Process Loop ....................2-6 2.7.2. Estimating The Repeats / Minutes And Fine Tuning The Gain ...........................2-7
3.5. Recalculate and Reprint a Previous Batch Ticket ............................................... 3-4 3.6. Batch Preset Counters........................................................................................... 3-5
3.6.1. Batch Preset Flags.................................................................................................3-5 3.6.2. Batch Warning Flags .............................................................................................3-5
3.7. Adjusting the Size of a Batch ................................................................................ 3-5 3.8. Automatic Batch Changes Based on Product Interface Detection..................... 3-6
ii
20/24.71+ w 04/98
Volume 2a
Basic Operation
6.2. Full Sized Provers (Unidirectional and Bi-directional) .........................................6-2 6.3. Brooks Compact Prover.........................................................................................6-3
6.3.1. Proving Reports for Brooks Compact Provers ................................................... 6-4
Figures of Volume 2
Fig. 1-1. Flow Computer Front Panel Keypad ..................................................................................... 1-1 Fig. 1-2. Block Diagram Showing the Keypad and Display Modes....................................................... 1-3 Fig. 2-1. Typical PID Control Application - Single Loop ....................................................................... 2-1
20/24.71+ w 04/98
iii
Volume 2a
Basic Operation
Thirty-four keys are available. Eight special function keys and twenty-six dedicated to the alphanumeric characters A through Z, 0 through 9 and various punctuation and math symbols. The [Display/Enter] key, located at the bottom right, deserves special mention. This key is always used to execute a sequence of key presses. It is not unlike that the Enter key of a personal computer. Except when entering numbers in a field, the maximum number of keys that can be used in a key press sequence is four (not counting the [Display/Enter] key).
Fig. 1-1.
20/24.71+ w 04/98
1-1
Chapter 1
1.2.
Operating Modes
Keyboard operation and data displayed in the LCD display depends on which of the 3 major display and entry modes are selected.
1.2.1.
Display Mode
This is the normal mode of operation. Live meter run data is displayed and updated every 200 msec. Data cannot be changed while in this mode.
1.2.2.
Configuration data needed by the flow computer can be viewed and changed via the keypad while in this mode. When the Program Mode is entered by pressing the [Prog] key, the Program LED glows green. This changes to red when a valid password is requested and entered.
1.2.3.
The diagnostic and calibration features of the computer are accessed by pressing the [Diag] key ([Alpha Shift] then [Prog]. This mode allows you to check and adjust the calibration of each input and output point. The Diagnostic LED glows green until a valid password is requested and entered.
1.2.4.
You are in this mode whenever the data entry cursor is visible, which is anytime the user is entering a number or password while in the Program Mode or Diagnostic Mode.
1-2
20/24.71+ 04/98
Volume 2a
Basic Operation
Fig. 1-2.
20/24.71+ w 04/98
1-3
Chapter 1
1.3.
1.3.1.
Special Keys
Display/Enter (Help) Key
This key is located bottom-right on the keypad. Pressing once while in the Field Entry Mode will store the data entered in the field to memory. Pressing twice within one second will cause the contextsensitive Help to be displayed. The Help displays contain useful information regarding available variable assignments and selections. When in other modes, use it at the end of a key press sequence to enter the command.
1.3.2.
These keys are located top-center on the keypad. When in the Display Mode, the [ ]/[ ] keys are used to scroll through data relevant to a particular selection. When in the Program Mode, they are used to scroll through data and position the cursor on data to be viewed or changed. In the Diagnostic Mode, The up/down arrow keys are initially used to position the cursor within the field of data being changed. Once you select an input or output to calibrate or adjust, the up/down arrow keys are used as a software zero potentiometer.
1.3.3.
These keys are located top-center on the keypad; to the left and right respectively of the Up/Down Arrow Keys. The [ ]/[ ] keys have no effect while in the Display Mode. When in Program Mode, they are used to position the cursor within a data field. In the Diagnostic Mode, they are initially used to position the cursor within the field of data to be changed. Once you select an input or output to calibrate or adjust, the left/right arrow keys are used as software span potentiometer.
1.3.4.
This key is located top-right on the keypad. Pressing the [Alpha Shift] key while in the Field Entry Mode causes the Alpha Shift LED above the key to glow green, indicating that the next valid key press will be interpreted as its shifted value. The Alpha Shift LED is then turned off automatically when the next valid key is pressed. Pressing the [Alpha Shift] key twice causes the Alpha Shift LED to glow red and the shift lock to be active. All valid keys are interpreted as their shifted value until the [Alpha Shift] key is pressed or the [Display/Enter] key is pressed. When in the Calibrate Mode, zero and span adjustments made via the arrow keys are approximately ten times more sensitive when the Alpha Shift LED is on.
1-4
20/24.71+ 04/98
Volume 2a
Basic Operation
1.3.5.
This key is located top-left on the keypad. While in the Display Mode, pressing this key changes the operating mode to either the Program or Diagnostic Mode, depending on whether the Alpha Shift LED is on. When in other modes, it cancels the current entry and goes back one menu level, eventually returning to the Display Mode.
1.3.6.
Static Discharges - It has been found that applications of electrostatic discharges may cause the Active Alarm LED to glow red. Pressing the [Space/Clear] key will acknowledge the alarm and turn off the red alarm light.
This key is located bottom-left on the keypad. Pressing this key while in the Display Mode acknowledges any new alarms that occur. The Active Alarm LED will also change from red to green indicating an alarm condition exists but has been acknowledged. When in the Field Entry Mode, unshifted, it causes the current variable field being changed to be cleared, leaving the cursor at the beginning of the field awaiting new data to be entered. With the Alpha Shift LED illuminated, it causes the key to be interpreted as a space or blank. When in all other modes, it cancels the current key press sequence by flushing the key input buffer.
1.4.
Once the computer is mounted in its panel you may need to adjust the viewing angle and backlight intensity of the LCD display for optimum performance. You may need to re-adjust the brightness setting of the display should the computer be subjected to transient electrical interference. While in the Display Mode (Program LED and Diagnostic LED off), press [Setup] [Display] and follow the displayed instructions: Use Up/Down Arrows To Adjust Contrast; Left, Right Arrows To Adjust Backlight
20/24.71+ w 04/98
1-5
Chapter 1
1.5.
TIP - Alarm flags are latched while the red LED is on. To avoid missing intermittent alarms, always press [Alarms] [Display] to view alarms before pressing [Cancel/Ack].
1.5.1.
New alarms cause the Active Alarm LED to glow red. Pressing the [Cancel/Ack] key (bottom left), or setting Boolean Point 1712 via a digital I/O point or via a Modbus command, will acknowledge the alarm and cause the Active Alarm LED to change to green. The LED will go off when the alarm condition clears.
1.5.2.
To view all active alarms, press [Alarms] [Display] and use the [ ]/[ ] arrow keys to scroll through all active alarms.
The last 500 time-tagged alarms that have occurred are always available for printing (see Historical Alarm Snapshot Report in this chapter).
1.5.3.
It has been found that applications of electrostatic discharges may cause the Active Alarm LED to glow red. Pressing the [Space/Clear] key will acknowledge the alarm and turn off the red alarm light.
1.6.
Computer Totalizing
Two types of totalizers are provided: 1) Three front panel electromechanical and non-resetable; and 2) Software totalizers maintained in computer memory. The electromechanical totalizers can be programmed to count in any units via the Miscellaneous Setup Menu (Volume 3). The software totalizers provide batch and daily based totals, and are automatically printed, saved and reset at the end of each batch or the beginning of each contract day. Daily flow or time weighted averages are also printed, saved and reset at the end of each day. Batch flow weighted averages are also available in liquid application flow computers. Software cumulative totalizers are also provided and can only be reset via the Password Maintenance Menu (Volume 3). View the software totalizers by pressing [Gross], [Net] or [Mass]. Pressing [Meter] [n] [Gross], [Net] or [Mass] will display the software for Meter Run n.
1-6
20/24.71+ 04/98
Volume 2a
Basic Operation
Four independent control loops are available. Each loop is capable of controlling a primary variable (usually flow rate) with a secondary override variable (usually meter back pressure or delivery pressure). The primary and secondary set points can be adjusted locally via the keypad and remotely via a communication link. In addition, the primary set point can be adjusted via an analog input to the computer. Contact closures can be used to initiate the startup and shutdown ramp function which limits the control output slew rate during startup and shutdown conditions. A high or low 'error select' function causes automatic override control by the secondary variable in cases where it is necessary either to maintain a minimum secondary process value or limit the secondary process maximum value. Local manual control of the control output and bumpless transfer between automatic and manual control is incorporated.
Fig. 2-1.
20/24.71+ w 04/98
2-1
Chapter 2
2.2.
INFO - Select PID Loop 1 through 4 by entering n as 1, 2, 3 or 4.
While in the Display Mode press [Control] [n] [Display]. Press the Up/Down arrow keys to display the following screens: Screen #1 PID #1 VALVE STATUS Open 50.00 Auto/Manual Auto Primary Controlling
Setpoint
20.00
Setpoint
20.00
Screen #4
INFO - Data such as set points or operating mode cannot be changed while in the Display Mode.
PID #1 SET POINT Source is Local Remote S.P. Input Value is 20.00
2-2
20/24.71+ w 04/98
Volume 2a
Basic Operation
2.3.
INFO - Select PID Loop 1 through 4 by entering n as 1, 2, 3 or 4. To access the next two screens you must enter the [Y] to select Manual Valve or Local Setpoint even if a Y is already displayed. To cancel the Manual Mode or Local Setpoint Mode, enter [N].
Press [Prog] [Control] [n] to display the following screen: PID#1 OPERATING MODE Manual Valve(Y/N) N Local Set.Pt(Y/N) N Sec Set.Pt 750.0
2.3.1.
To change to manual valve control enter [Y] at the 'Manual Valve (Y/N)' prompt and the following screen is displayed: PID #1 MANUAL VALVE Up/Down Arrow to Adj Measurement 20.00 Open % 50.00
The switch from Auto to Manual is bumpless. Use the Up/Down arrow keys to open or close the valve. Press [Prog] once to return to the previous screen. PID#1 OPERATING MODE Manual Valve (Y/N) Y Local Set.Pt(Y/N) N Sec Set.Pt 750.0
2.3.2.
To change from manual to automatic valve control, enter [N] at the 'Manual Valve (Y/N)' prompt. The switch to automatic is bumpless if local setpoint is selected.
20/24.71+ w 04/98
2-3
Chapter 2
2.3.3.
Enter [Y] at the 'Local Set. Pt. (Y/N)' prompt and the following screen is displayed: PID#1 LOCAL SETPOINT Up/Down Arrow to Adj Measurement 20.00 Setpoint 20.00
The switch from Remote to Local is bumpless. Use the Up/Down arrow keys to increase or decrease the setpoint. Press [Prog] once to return to the previous screen.
Notice you are now in Automatic with Local Valve Control
PID#1 OPERATING MODE Manual Valve(Y/N) N Local Set.Pt(Y/N) Y Sec Set.Pt 750.0
2.3.4.
To change from local setpoint to remote setpoint, enter [N] at the 'Local Set. Pt.(Y/N)' prompt. The switch to remote setpoint may not be bumpless, depending upon the remote set point source.
2.3.5.
Move the cursor to the bottom line of the above display, press [Clear] and then enter the new setpoint.
2.4.
IMPORTANT!
You must assign a remote setpoint input even if one will not be used. The 4-20mA scaling of this input determines the scaling of the primary controlled variable.
As described above, the PID control loop can be configured to accept either a local setpoint or a remote setpoint value for the primary variable. The remote setpoint is derived from an analog input (usually 4-20 mA). This input is scaled in engineering units and would usually come from another device such as an RTU. High/Low limits are applied to the remote setpoint signal to eliminate possible problems of over or under speeding a turbine meter (see Volume 1, Chapter 8 for more details).
2-4
20/24.71+ w 04/98
Volume 2a
Basic Operation
2.5.
These functions are enabled when a startup and/or shutdown ramp rate between 0 and 99 percent is entered (see section PID Setup in Volume 3). Commands are provided to Start the valve ramping open, Shutdown to the minimum percent open valve or Stop the flow by closing the valve immediately once it has been ramped to the minimum percent open. These commands are accessed using the keypad by pressing [Prog] [Batch] [Meter] [n], which will display the following: Mtr1 Batch Start Y ? Shutdown to Min% ? Batch Stop ? Print & Reset ?
2.6.
Inputs are provided for startup/shutdown ramp rates and minimum output % settings. When these startup/shutdown ramp rates are applied the control output, movements will be limited to the stated % movement per second (see Volume 3). On receipt of a shutdown signal, the output will ramp to the minimum output % for topoff purposes.
20/24.71+ w 04/98
2-5
Chapter 2
2.7.
IMPORTANT!
PID Control Tuning - The primary variable must be tuned first. When tuning the primary variable loop, you must set the secondary setpoint high or low enough to the point where it will not take control. Otherwise, the PID loop will become very unstable and virtually impossible to tune. Adjust the primary gain and integral repeats per minute until you achieve stable control. Likewise, when tuning the secondary setpoint, the primary must be set so it cannot interfere. Once you have achieved stable control of both loops, you can then enter the setpoints established for each loop at normal operating conditions.
Individual control of gain and integral action are provided for both the primary and secondary control loops. Tune the primary variable loop first by setting the secondary setpoint high or low enough to stop the secondary control loop from taking control. Adjust the primary gain and integral repeats per minutes for stable control. Reset the primary and secondary set points to allow control on the secondary variable without interference from the primary variable. Adjust the secondary gain and integral repeats per minute for stable control of the secondary variable.
2.7.1.
Each process loop will exhibit a gain function. A change in control valve output will produce a corresponding change in each of the process variables. The ratio of these changes represents the gain of the loop (For example: If a 10 % change in control output causes a 10% change in the process variable, the loop gain is 1.0. If a 10 % change in control output causes a 20 % change in process variable, the loop gain is 2.0). To provide stable control the gain of each loop with the controller included must be less than 1.0. In practice the controller gain is usually adjusted so that the total loop gain is between 0.6 and 0.9. Unfortunately the gain of each loop can vary with operating conditions. For example: A butterfly control valve may have a higher gain when almost closed to when it is almost fully open. This means that in many cases the controller gain must be set low so that stable control is achieved over the required range of control. To estimate the gain of each loop proceed as follows for the required range of operating conditions: (1) In manual, adjust the control output for required flowing conditions and note process variable values. (2) Make a known percentage step change of output (i.e., from 20% to 22% equals a 10% change). (3) Note the percentage change of each process variable (i.e., 100 m3/hr to 110 m3/hr equals a 10% change).
INFO - The primary gain interacts with the secondary gain. The actual secondary gain factor is the product of the primary gain and secondary gain factors.
(4) Primary Gain Estimate = 0.75 / (Primary Loop Gain). (5) Secondary Gain = Estimate). 0.75 / (Secondary Loop Gain x Primary Gain
2-6
20/24.71+ w 04/98
Volume 2a
Basic Operation
2.7.2.
(1) Set the 'repeats / minute' to 40 for both primary and secondary loops. (2) Adjust set points so that only the primary (sec) loop is trying to control. (3) While controlling the primary (sec) variable, increase the primary (sec) gain until some controlled oscillation is observed. (4) Set the primary (sec) 'repeats/minute' to equal 0.75 / (Period of the oscillation in minutes). (5) Set the primary (sec) gain to 75% of the value needed to make the loop oscillate. (6) Repeat (2) through (5) for the secondary variable loop.
20/24.71+ w 04/98
2-7
Volume 2a
Basic Operation
A complete set of software batch totalizers and flow weighted averages are also provided in addition to the daily and cumulative totalizers. These totalizers and averages can be printed, saved and reset automatically, based on the number of barrels or cubic meters delivered, change of product or on demand. The Omni flow computer can keep track of 4 independent meter runs running any combination of 16 different products. Flowmeter runs can be combined and treated as a station. The batch totalizers and batch flow weighted averages are printed, saved and reset at the end of each batch. The next batch starts automatically when the pulses from the flowmeter exceed the meter active threshold frequency. Pulses received up to that point which do not exceed the threshold frequency are still included in the new batch, but the batch start time and date are not captured until the threshold is exceeded.
3.2.
Batch Status
The batch status appears on the Status Report and is defined as either: o In Progress ------- Batch is in progress with the meter active. o Suspended ------- Batch is in progress with the meter not active. o Batch Ended ----- Batch End has been received, meter not active.
20/24.71+ w 04/98
3-1
Chapter 3
3.3.
When running independent products on each meter run, each flowmeter run has a batch schedule stack which stores the setup information for up to 5 future batches. The setup information is popped off the appropriate stack by the computer at the beginning of each batch. When all meter runs are running the same product, the individual meter run batch schedule stacks are combined and organized to store up to the next 23 future station batches.
3.3.1.
TIP - When ending a batch with flow occurring, remember that the next batch will start immediately after you end the current one. You should check that the batch schedule contains the correct setup information for that batch.
The flow computer will use the batch setup data for the batch last completed if the meters batch schedule stack is empty at the beginning of a new next batch.
3.3.2.
Pressing [Prog] [Batch] [Setup] or [Prog] [Meter] [n] [Batch] [Setup] displays the screen similar to that shown below. The screen shows information regarding the current running batch. The 16 character batch ID number appears on all reports and can be edited at any time during a batch. The starting size of the batch in net barrels is used to determine the value of the batch preset counter. It can be changed at any time during a batch and the batch preset counter will be adjusted accordingly. MTR #1 CURRENT BATCH ID: Butane 5010 Running Product 1 Size BBl 100
By using the []/[] keys you can scroll through and modify any one of the 6 batch setups (in Independent Batch Stack) and 24 (in Common Batch Stack) in the Batch Schedule Stack. M1:1 I=Ins D=Del ? ID: EP-001-021-BUT Product to Run? 0 Size BBl 0
The number on the left on Line 1 is the flowmeter run number and stack position; i.e., M2:1 will be the next batch setup run for Meter #2, M2:2 the next and so on. Batch setups can be inserted before the displayed position or the displayed setup and can be deleted by entering I or D on Line 1. Press [Prog] twice to return to the Display Mode.
3-2
20/24.71+ w 04/98
Volume 2a
Basic Operation
3.4.
Ending a Batch
A batch in progress is ended by setting the appropriate End Batch Flag in the computers database. This can be done manually from the keypad, on a timed basis, through a digital I/O point or via a Modbus command.
3.4.1.
Batches can be ended and products changed by using the Product Change Strobes (Boolean 1707 and 1747 through 1750). Setting any of these Boolean commands, either through a digital input or writing it through a Modbus port, will cause the flow computer to: (1) End the batch in progress and print a batch report. (2) Determine what the next product to run will be by decoding the binary coded Product Select Input flags (Booleans 1743 through 1746). (3) Write the number of the selected product into the next batch stack position. (4) Pop the batch setup off the stack and start a new batch.
3.4.2.
Press the [Prog] [Batch] [Meter] [n] or [Prog] [Meter] [n] [Batch] keys and a screen similar to the following will be displayed: METER #1 BATCH Print & Reset ?
Pressing [Prog] [Batch] and [Enter] (i.e., not specifying a meter run) will display the following: STATION BATCH Print & Reset ?
Enter [Y] to the Print & Reset ? question and enter your password when requested. The batch will be ended immediately and a Batch Report printed out. The above displays will vary if the PID ramping functions are enabled (see the following section).
20/24.71+ w 04/98
3-3
Chapter 3
3.5.
Recalculating a Previous Batch - For more information on this topic, see Technical Bulletin TB-980202 Recalculating a Previous Batch within the Flow Computer included in Volume 5.
To recalculate and reprint a previous batch, you must do the following: (1) Press [Prog] [Batch] [Meter] [n] [Enter] (n = meter run number). The Omni LCD screen will display: METER #1 BATCH Print & Reset ? Select Prev# Batch 1 Enter API60 .0 Enter SG60 .0000 Enter %S&W .00 Recalculate&Print?
(2) Select which previous batch you wish to recalculate. The Omni stores the last 4 completed batches numbered as: 1 = last batch completed to 4 = oldest batch completed. (3) Press [] to scroll down to Select Prev # Batch and enter a number between 1 and 4, depending upon which batch is to be recalculated. The flow computer moves the selected previous batch data to the previous batch data points within the database (see explanation in Technical Bulletin TB-980202) (4) Enter Password when requested. Scroll to either Enter API60 or Enter SG60. Type in a valid value and press [Enter]. (5) Scroll to Recalculate & Print?. Press [Y] and then [Enter]. At this time the flow computer will recalculate the batch data and send the report to the printer and the Historical Batch Report Buffer in RAM memory. The default batch report shows the batch number as XXXXXX-XX where the number ahead of the - is the batch number and the number after the - is the number of times that the batch has been recalculated.
3-4
20/24.71+ w 04/98
Volume 2a
Basic Operation
3.6.
INFO - In order to activate the batch preset counter you must have entered a batch size other than zero before the batch started (i.e., starting with a batch size of zero disables the preset counter feature). Batch presets can be selected for gross, net or mass units (see Volume 3; 2.7. Configuring the Meter Station).
Independent batch preset counters are provided for each meter run when in the Independent Batch Stack Mode. Each batch preset counter is pre-loaded with the batch size taken from the appropriate batch schedule stack. The counter is automatically reduced by the meter runs net flow. Press [Batch] [Preset] [Meter] [n] or [Meter] [n] [Batch] [Preset] to see the current value of the counter for a particular meter run: Meter#1 Batch Preset barrels 49978 Mtr#1 Preset Warning barrels 100
3.6.1.
The batch preset flags are Boolean variables within the database which are automatically set whenever the appropriate batch preset counter reaches zero. They are available for use in programmable Boolean equations and digital I/O functions.
3.6.2.
The batch warning flags are Boolean variables within the database which is automatically set whenever the appropriate batch preset counter is equal or less than the programmed batch warning value. It is available for use in programmable Boolean equations and digital I/O functions.
3.7.
INFO - The batch preset counter can be selected for gross, net or mass units (see Volume 3; 2.7. Configuring the Meter Station).
The size of a running batch may change several times during the progress of the batch. This is usually due to product take-off or injection upstream of the metering station. While in the Display Mode, press [Prog] and then [Batch] [Preset] [Meter] [n] or [Meter] [n] [Batch] [Preset]. This will show the following screen. ADJUST #1 BATCH SIZE Enter Amount to Adjust 0 Size Now 100000
Press [Clear] and enter the number of barrels/cubic meters (lbs or kgs) that you wish to add to the size of the batch. Enter a minus number to reduce the size of the batch.
20/24.71+ w 04/98
3-5
Chapter 3
3.8.
Automatic batch changes can be made by the computer by monitoring the rate of change of the products specific gravity/density during the final moments of a batch. For example, a Boolean point can be programmed to be active whenever the specific gravity rate of change flag is set and the batch warning flag is set. A digital output can then be assigned to this interface detected Boolean flag and can be used to cause a batch end command. Specific gravity disturbances which may occur during the batch will be alarmed but will not be used to end a batch unless the batch warning flag has been reached.
3-6
20/24.71+ w 04/98
Volume 2a
Basic Operation
The specific gravity/density rate of change alarm flag is a flag within the database which is set whenever the rate of change of the station gravity/density with respect to flow (SG or Dens see sidebar) exceeds the preset limit. It is used to detect a change in flowing product and is available for use in programmable Boolean equations and digital I/O functions.
4.2.
In many cases the densitometer or gravitometer used to detect the product interface is mounted many Bbls (m3 or liter3) ahead of the valve manifold used to cut the product and end the batch. A second gravity/density rate of change flag which is delayed by the amount of line pack Bbls or m3 provides an accurate indication of when the interface reaches the actual valve manifold. Next Interface Due Barrels 156 The 'Next Interface Due' counter shows the number of Bbls or m3 of line pack remaining before the leading edge of the product interface reaches the valve manifold. A minus number indicates that the leading edge has passed. Up to three interfaces can be tracked between the interface detector and the valve manifold.
20/24.71+ w 04/98
4-1
Chapter 4
4.3.
SG & Dens - Delta Specific Gravity (SG) refers to U.S. customary units and is measured per barrel. Delta Density (Dens) refers to metric units and is measured per cubic meter. The SG (or Dens) function is the smallest difference in specific gravity (or density) between two products that will form the product interface.
To accurately detect the product interface it is important to set the gravity rate of change limits correctly. This limit is expressed as change in Specific Gravity per Net Bbl or m3 (SG/Bbl or Dens/m3 see sidebar) and as such is flow rate independent. Too small a limit will cause minor disturbances to be detected and too large will cause the interface to be missed. For example: A pipeline runs ISO-Butane (0.565), N-Butane (0.585) and Propane (0.507). The smallest SG in this case is 0.585 minus 0.565, which equals 0.020 SG units. It was observed that once an interface was detected, 33 Bbls passed before the specific gravity stabilized at the new gravity. The actual gravity rate of change limit for this example is calculated as: 0.20 / 33 = 0.0006 ( SG/Bbl)
To ensure that we reliably detect the gravity rate of change, we set the rate of change limits to one third of the actual expected rate of change (i.e., 0.0006/2) which is 0.0002. To enter this value, press [Prog] [Meter] [Enter]. Scroll down to 'Grav Change' and enter 0.0006. Meter Station Grav Change Line Pack
.0006 250
4-2
20/24.71+ w 04/98
Volume 2a
Basic Operation
5. Meter Factors
5.1. Changing Meter Factors
To do this you must edit the product file information by pressing [Prog]. Then press [Product] [Enter] to scroll through all 16 sets of product data. Pressing [Product] [n] [Enter], where n is 1-16, will allow you to go directly to data for a specific product number. A display similar to the following can be scrolled through: PRODUCT #5 Name PROPANE Table Select 2 Override API 150.9 Override Dens 5010 M.F. #1 1.0099 M.F. #2 1.0034 M.F. #3 1.0023 M.F. #4 .9995
Move the cursor to the appropriate meter factor, press [Clear] and re-enter the required meter factor. Note that only numbers greater than 0.8000 and less than 1.2001 are allowed. The Retroactive Barrels question will not be prompted unless the meter factor you want to modify is being used at the time.
20/24.71+ w 04/98
5-1
Chapter 5
Meter Factors
5.2.
Enter the Program Mode by pressing [Prog]. Then press [Factor] [Enter]; this will allow you to scroll through all meter factors; or press [Meter] [n] [Factor] [Enter] to go directly to the meter factor for Flowmeter n (n = 1, 2, 3 or 4). Flowmeter #1 Meter Factor
1.0000
Press [Clear] and then enter the required meter factor. You will be prompted to enter the number of retroactive gross barrels (or cubic meters) that the new meter factor will be applied to. Flow Meter #1 Meter Factor 1.0050 Retro Bbls ? 1000
Note that only numbers greater than 0.8000 and less then 1.2001 are allowed as meter factors. The meter factor will automatically replace the previous meter factor in the appropriate product information file.
5.3.
Whenever a flowmeter is proved, the new meter factor is compared against the current meter factor. Additional data such as the flow rate and a time tag is needed in order for this data to be meaningful. This Previous Meter Factor data is saved with the meter factor automatically whenever a meter factor is implemented after a prove or entered manually while it is being used.
5-2
20/24.71+ w 04/98
Volume 2a
Basic Operation
6. Proving Functions
6.1. Auto-Prove Mode
The auto prove mode requires that a prover is available on a continuous basis with motorized actuators on the appropriate valves. Flowmeters can be automatically proved whenever the flow rate varies more than a certain amount from the flow rate that existed when the flowmeter was last proved or when the meter factor was manually entered. Flowmeters can also be proved whenever a certain amount of flow has been measured without a proving, or after a meter has been shut-in for more than a certain period of time and flow has been started. Entries are provided in the [Prog] [Prove] [Setup] menu to: q Enter the percentage change in flow rate which will trigger an auto-prove request. q Enter a minimum number of Bbls (or m3)/hr flow rate change to trigger an auto-prove request (needed at the lower flow rates where the percentage change would be a very small volume change). q Specify the period of time that the flow must remain at the new changed rate before a prove sequence is started. q Specify the period of time that a meter must be shut in before the need for a prove sequence is flagged. q Specify the maximum amount of flow between proves. An additional entry in the [Prog] [Meter] [n] menu is required to activate or put a meter run into the Auto-prove Mode.
6.1.1.
If 10 consecutive prove aborts occur when trying to auto-prove a specific meter, auto-prove for that meter will be disabled (each prove abort reason will also be logged into the historical alarm stack). If during the Auto-prove Mode, a prove is completed and the meter factor is not implemented because of an unexpected meter factor shift. The computer will wait the allowed time (Inactive Timer under Prove Setup) before trying another prove run. If the second completed run cannot implement the meter factor, then the Auto-prove Mode for that meter will be disabled.
20/24.71+ w 04/98
6-1
Chapter 6
Proving Functions
6.2.
Proving functions are accessed via the Program Mode. Press [Prog] [Prove] [Enter] and the following selection menu is displayed: * Prover Operation * Trial Report (Y/N) Trial Prove Mtr"n" _ Prove Meter "n" Abort Prove ? (Y) For a single 'Trial Prove', enter the meter number to be proved on the 2nd line. To disable a trial prove report, enter [Y] on line one. For a prove sequence enter the number of the meter to be proved on the 3rd line. To abort a prove in progress enter [Y] on the 4th line. After making your entry the flow computer will automatically return you to the Display Mode and select the 'Prove Counts Display': Counts 0 Prove Run 1 Meter Selected 2 Check Temp Stability
The bottom line of this display shows the current status of the prover. As the prove sequence proceeds the 4th line is updated with the current status: Ball Launched Fwd. 1st Detector Switch In Flight Forward 2nd Detector Switch Over Travel Forward Ball Launched Reverse 1st Detector Switch In Flight Reverse 2nd Detector Switch Over Travel Reverse
The 'Prove Run' number on line 2 increments as each run is completed. Assuming a successful prove the 4th line indicates:
Prove Completed
6-2
20/24.71+ w 04/98
Volume 2a
Basic Operation
When the required number of consecutive runs within the run deviation limits are accumulated. The run data are averaged and the prove calculations are performed. The resultant meter factor is compared against the current meter factor and if it is within acceptable limits can be automatically stored in the appropriate product file and implemented retroactively for the current batch.
6.3.
Proving functions are accessed the same as with full sized provers; via the Program Mode. Press [Prog] [Prove] [Enter] and the following selection menu is displayed: *PROVER OPERATION* Invar Rod Deg.F 75.5 Trial Report (Y/N) Trial Prove Mtr"n" Prove Meter "n" Abort Prove ? (Y)
An additional entry is included for a Brooks prover (Invar Rod temperature). The invar rod is part of the detector switch mechanism of the prover and is usually close to ambient temperature. Enter the correct temperature to enable the computer to correct for any thermal expansion. For a single 'Trial Prove' enter the meter number to be proved on the 3rd line. For a prove sequence enter the number of the meter to be proved on the 4th line. To abort a prove in progress press the down arrow and enter [Y] on the 5th line. After making your entry the flow computer will automatically return you to the Display Mode and select the 'Prove Counts Display' : Counts 0 Prove Run 1 Meter Selected 2 Check Temp Stability
As with the full sized prover the bottom line of this display shows the current status of the prover. Two additional status states will appear.
While the computer is checking for temperature stability it is also checking and adjusting the plenum chamber pressure. The status line above will only show if the plenum pressure is still not within the selected dead band by the time the temperature is stable. Piston Downstream
20/24.71+ w 04/98
6-3
Chapter 6
Proving Functions
This status display occurs while the prover is returning the piston to the upstream position ready to launch. Use the arrow keys to scroll down the display. A second screen is relevant to the pulse interpolation method of accumulating prove pulse counts. Prove Counts 1034 Tdvol 2.234122 Tdfmp 2.202312 Piston Downstream The 1st line shows the integer counts. Tdvol is the time between detectors and Tdfmp is the time between the 1st flowmeter pulse after each of the detectors. A pass report is printed at the end of each set of passes.
6.3.1.
As the compact prove sequence progresses the flow computer will print the Pass Summary Report. This report is printed for each sequence of passes that comprise a prove run. The number of passes made per run is selectable from 1 to 25 (see Prover Setup in Volume 3. Note: an entry of 1 will disable this report). On completion of a successful prove a Meter Proving Report will be printed. This report is user configurable via the OmniCom configuration program.
6.4.
The following reports are also available with this application: o Prove Abort Report o Meter Proving Report For Master Meter Method o Mass Proving Report
6-4
20/24.71+ w 04/98
Volume 2a
Basic Operation
7. Printed Reports
-
7.1.
Several reports use a fixed format (i.e., cannot be changed by the user). These are described below: q Status Report
20/24.71+ w 04/98
7-1
Chapter 7
Printed Reports
7.2.
The following reports are user-configurable via the OmniCom configuration program. q q q q
7.3.
INFO - Entering a number between 1 and 500 at the Hist Alarm ? line will cause many previous alarms to be printed. When requesting reports, such as previous daily, batch or prover reports, you must enter a number between 1 and 8; 1 refers to the last report generated and 8 refers to the oldest report. Up to 150 previous data entry changes can be printed when the Audit Trail is requested. Note: ** These entries only show up when the archive ram is installed.
Printing Reports
A Snapshot Report can be printed by pressing [Print] [Enter] and can also be printed automatically on timed intervals (see 9. Print Setup in Chapter 9). Other printed reports are accessed from the Program Mode. Press [Prog] [Print] [Enter] and the following selection menu will be displayed: *PRINT REPORT MENU* Snapshot Report ? Previous Snapshot? Status Report ?(Y) Prev. Batch (1-8) Prev. Ticket ? Prev. Daily (1-8) Prev. Prove (1-8) Hist Alarm ? Audit Trail ? (Y) ** Arch Starts ** # of Arc Days Product File ?(Y) Config Report ?(Y)
Move the cursor to the report required and enter [Y] or the number of the historical report you wish to print ([1] refers to the latest, [2] refers to the next to latest etc). Press [Prog] twice to return to the Display Mode.
7-2
20/24.71+ w 04/98
Volume 2a
Basic Operation
7.4.
7.4.1.
Audit Trail
Audit Trail Report
A fixed format report provides an audit trail of changes made to the flow computer database. The number of changes that can be reported depends on the type of changes made. The last 150 items are recorded. Each record consists of a unique event number, time & date tag, database index number for the variable changed and the new and old value of the variable, The starting index number and the number of points changed is recorded when changes are made remotely via a Modbus port, using OmniCom for instance.
Note1: Password entries are recorded in this field. A threedigit code signifies the password source and level of the password entered. These codes are as follows: PIPELINE COMPANY NAME Audit Trail Report Time: xx:xx:xx Date xx/xx/xx Index Number1 xxxxx Page: 1 Computer ID: REV2271 New Value/ Serial Port x.xxxxxxxxxxx
7.4.2.
The Audit Trail Report is stored within the flow computer and is used to document and time and date stamp changes made to the flow computer database, either via the local keypad or via password protected serial port access. The report is formatted in columns as shown above:
PASSWORD CODES
100 101 102 103 104 105 108 200 201 202 Privileged Level Password entered at the keypad Level 1 Password entered at local keypad Level 2 Password entered at local keypad Serial Port #2 Level A Password entered at local keypad Serial Port #3 Level A Password entered at local keypad Serial Port #4 Level A Password entered at local keypad Level 1A Password entered at local keypad Level A Password entered via Serial Port #2 Level B Password entered via Serial Port #2 Level C Password entered via Serial Port #2 300 301 302 400 401 402 500 501 502 503 Level A Password entered via Serial Port #3 Level B Password entered via Serial Port #3 Level C Password entered via Serial Port #3 Level A Password entered via Serial Port #4 Level B Password entered via Serial Port #4 Level C Password entered via Serial Port #4 Level A Password entered via Serial Port #1 Level B Password entered via Serial Port #1 Level C Password entered via Serial Port #1 Serial Port #1 Level A Password entered at local keypad
20/24.71+ w 04/98
7-3
Volume 2a
Basic Operation
Batch Totalizers are displayed by including the [Batch] key before the key presses shown below:
Daily & Cumulative Uncorrected Gross (IV) Batch Uncorrected Gross (IV) Daily & Cumulative Corrected Net (GSV) Daily & Cumul. S&W Corrected Net (NSV) Batch Corrected Net Batch S&W Corrected Net (NSV) Daily & Cumulative Mass Batch Mass Daily & Cumulative Energy Total @ Second Reference Temperature [Gross] or [Gross] [Meter] [n] [Batch] [Gross] or [Batch] [Gross] [Meter] [n] [Net] or [Net] [Meter] [n] [Net] [Net] [Meter] [n] or [Meter] [n] [Net] [Net] [Batch] [Net] or [Batch] [Net] [Meter] [n] [Net] [Net] [Batch] or [Batch] [Net] [Net] [Mass] or [Mass] [Meter] [n] [Batch] [Mass] or [Batch] [Mass] [Meter] [n] [Energy] or [Energy] [Meter] [n] [Net] or [Net] [Meter] [n]
20/24.71+ w 04/98
8-1
Chapter 8
Batch Totalizers are displayed by including the [Batch] key before the key presses shown below.
Volume Correction Factors (VCF) Pressure Correction Factors (Cpl) Batch FWA Meter Factors [Temp] [Factor] or [Temp] [Factor] [Meter] [n] [Press] [Factor] or [Press] [Factor] [Meter] [n] [Batch] [Meter] [n] [Factor]
Alarm Information
Active Alarms Transducer High/Low Alarm Limits [Alarms] [Meter] or [Meter] [n]
Product Information
Product Number and Name Override API & SG Gravity Meter Factors Calculation Mode [Product] or [Product] [n] Note: n = 1-16
Miscellaneous Displays
Current Time & Date Power Last Applied Time & Date Power Last Lost Time & Date Task Timing Display Display of Raw Input Signals Display of Raw Output Signals Hardware Inventory / Software Version Honeywell Module Status
8-2
20/24.71+ w 04/98
Volume 2a
Basic Operation
[Control] [n]
User Displays
Up to eight additional displays can be programmed by the user (See Volume 3 for more details).
20/24.71+ w 04/98
8-3
Firmware Revisions 20.71/24.71
Volume 3
Contents of Volume 3
Figures of Volume 3 ....................................................................................................... ix 1. Overview of Firmware Revisions 20.71/24.71 ......................................................... 1-1
1.1. Number of Meter Runs - Type of Flowmeters .......................................................1-1 1.2. Product Configuration............................................................................................1-1 1.3. Configurable Sensors per Meter Run....................................................................1-2 1.4. Configurable Sensors per Prover..........................................................................1-2 1.5. Temperature............................................................................................................1-2 1.6. Densitometers.........................................................................................................1-2 1.7. Station Capability....................................................................................................1-2 1.8. Auxiliary Inputs .......................................................................................................1-2 1.9. Number of products - Information Stored/Product...............................................1-2 1.10. Type of Products Measured.................................................................................1-2 1.11. Batching and Interface Detection ........................................................................1-3 1.12. Auto Proving Features..........................................................................................1-3 1.13. Retroactive Meter Factors and Override Gravity ................................................1-3 1.14. Retroactive Density Correction Factor................................................................1-3 1.15. Flow Rate/Viscosity Linearizing...........................................................................1-3 1.16. PID Control Functions ..........................................................................................1-4 1.17. Flow Weighted Averages......................................................................................1-4
20/24.71 w 04/98
Contents of Volume 3
1.18. User-Programmable Digital I/O............................................................................ 1-4 1.19. User-Programmable Logic Functions ................................................................. 1-4 1.20. User-Programmable Alarm Functions................................................................. 1-4 1.21. User-Programmable Variables ............................................................................ 1-4 1.22. User Display Setups............................................................................................. 1-4 1.23. User Report Templates ........................................................................................ 1-5 1.24. Serial Communication Links................................................................................ 1-5 1.25. Peer-to-Peer Communications ............................................................................ 1-5 1.26. Archive Data ......................................................................................................... 1-5 1.27. OmniCom Software Communications Package .............................................. 1-5 1.28. OmniView Software Communications Package .............................................. 1-5
2.3. Getting Help ............................................................................................................ 2-4 2.4. Program Inhibit Switch........................................................................................... 2-4 2.5. Configuring the Physical Inputs / Outputs ........................................................... 2-6
2.5.1. Miscellaneous Configuration (Misc. Setup Menu) ...............................................2-6 2.5.2. Physical I/O Points not Available for Configuration ............................................2-7 2.5.3. Password Maintenance Settings...........................................................................2-7 2.5.4. Entries Requiring a Valid Privileged Password ...................................................2-8 2.5.5. Module Settings .....................................................................................................2-8 2.5.6. Meter Station Settings ...........................................................................................2-9 Auxiliary Input Assignment ....................................................................................... 2-10 2.5.7. Meter Run Settings .............................................................................................. 2-10 2.5.8. Prover Settings .................................................................................................... 2-12
ii
20/24.71 w 04/98
Volume 3
20/24.71 w 04/98
iii
Contents of Volume 3
2.9.2. Meter Temperature Settings ................................................................................ 2-41 2.9.3. Meter Density Temperature Settings .................................................................. 2-42 2.9.4. Prover Temperature Settings .............................................................................. 2-42 2.9.5. Prover Density Temperature Settings................................................................. 2-43
iv
20/24.71 w 04/98
Volume 3
20/24.71 w 04/98
Contents of Volume 3
3.2.10. Miscellaneous Meter Station Alarm and Status Points.................................... 3-25 3.2.11. Commands Which Cause Custom Data Packets to be Transmitted Without a Poll ................................................................................................................... 3-25 3.2.12. Commands Needed To Accomplish a Redundant Flow Computer System ... 3-26 3.2.13. Commands to Recalculate and Print Selected Batch ...................................... 3-26 3.2.14. Station Totalizer Roll-over Flags....................................................................... 3-26 3.2.15. Station Totalizer Decimal Resolution Flags ..................................................... 3-27 3.2.16. Status Booleans Relating to Redundant Flow Computer Systems................. 3-29 3.2.17. More Station Totalizer Decimal Resolution Flags ............................................ 3-29
vi
20/24.71 w 04/98
Volume 3
4.6. Custom Data Packets ...........................................................................................4-14 4.7. Peer-to-Peer on the Modbus Link .....................................................................4-15 4.8. Half Duplex Wiring Configuration Required........................................................4-15 4.9. Active Master.........................................................................................................4-15 4.10. Error Recovery....................................................................................................4-15
20/24.71 w 04/98
vii
Contents of Volume 3
5.1.8. Equivalencies .........................................................................................................5-4 For Uni- or Bi-Directional Prover ................................................................................5-4 For Compact Prover...................................................................................................5-4 When Using Pulse Interpolation Method .....................................................................5-5 When Proving Propylene Product...............................................................................5-5 When Proving Ethylene Product.................................................................................5-5 5.1.9. PID Control .............................................................................................................5-5 5.1.10. Solartron Density gm/cc ...................................................................................5-6 Uncompensated Density.............................................................................................5-6 Temperature Compensated Density ...........................................................................5-6 Temperature & Pressure Compensated Density .........................................................5-6 Additional Equation for Velocity of Sound Effects (Solartron Only)...........................5-6 5.1.11. Sarasota Density gm/cc .......................................................................................5-7 5.1.12. UGC Density gm/cc ..............................................................................................5-8 5.1.13. Densitometer Calibration Constants...................................................................5-8 5.1.14. Linearzing Coefficients........................................................................................ 5-8
5.2. Flow Equations and Algorithms for Revision 24 (Metric Units)........................... 5-9
5.2.1. Flowrate At Flowing Conditions: m3/hr ................................................................5-9 5.2.2. Net Flowrate At Base Conditions: Nm3/hr (Except Propylene)............................5-9 5.2.3. Mass Flowrate: ton/hr (Except Propylene) ...........................................................5-9 5.2.4. Equivalencies .........................................................................................................5-9 5.2.5. Calculations For Liquid Flows When Mass Pulses is Selected ........................ 5-10 Table 54A Product Type: Crude Oil .......................................................................... 5-10 Table 54B, Product Type: Fuel Oil............................................................................ 5-10 Table 54B Product Type: Jet Group.......................................................................... 5-10 Table 54B Product Type: Gasolines ......................................................................... 5-10 Table 54B Product Type: Between Jet and Gasoline ................................................ 5-10 For Propylene:.......................................................................................................... 5-11 5.2.6. Density of Ethane/Propane C3+ Mixes................................................................ 5-11 5.2.7. Density and other physical properties of Ethylene (IUPAC).............................. 5-11 Density of Ethylene (NIST) ....................................................................................... 5-11 Density of Ethylene (API) ......................................................................................... 5-11 5.2.8. Prove Gross Flowrate (Uni- and Bi-Directional) ................................................. 5-12 5.2.9. Prove Gross Flowrate (Compact) ......................................................................... 5-12 5.2.10. Prove Meter Factor............................................................................................. 5-12
viii
20/24.71 w 04/98
Volume 3
5.2.17. UGC Density kg/m3 ............................................................................................ 5-17 5.2.18. Densitometer Calibration Constants ................................................................ 5-17
Figures of Volume 3
Fig. 1-1. Typical Configuration Using Helical Turbine, Positive Displacement and Coriolis Flowmeters1-1 Fig. 2-1. Figure Showing Program Inhibit Switch ................................................................................ 2-5 Fig. 3-1. Figure Showing Automatic Four-Meter Flow Zone Thresholds .............................................. 3-6 Fig. 3-2. Figure Showing Four-Meter Run Valve Switching ................................................................. 3-7 Fig. 3-3. Keypad Layout - A through Z Keys ..................................................................................... 3-36
20/24.71 w 04/98
ix
Volume 3
1.1.
Minimum 1 run, Maximum 4 runs - Turbine, Positive Displacement Flow Meters or Mass Flow Meters. 'Level A' dual channel 'Pulse Fidelity' checking can be performed on all 4 meter runs.
1.2.
Product Configuration
Parallel runs measuring the same product or independent runs with different products.
Fig. 1-1.
Typical Configuration Using Helical Turbine, Positive Displacement and Coriolis Flowmeters
20/24.71 w 04/98
1-1
Chapter 1
1.3.
Meter Pulses, meter temperature and pressure, meter density, density temperature and pressure.
1.4.
Prover inlet and outlet temperature and pressure, prover densitometer any type (analog or digital pulse type such as Solartron, Sarasota or UGC ).
1.5.
Temperature
Each temperature sensor can be individually selected to be a 4-20mA, 4-wire DIN curve RTD or 4-wire American curve RTD.
1.6.
Densitometers
Can be configured for any combination or mix of individual or shared densitometers of any type (analog or digital pulse type such as Solartron, Sarasota or UGC ) the maximum number that can be connected is five. Each analog density can be specified as flowing or reference conditions. For mass proving a densitometer can be configured on the prover.
1.7.
Station Capability
Meter runs may be combined or subtracted in any mode to provide station flow rates and totalizers.
1.8.
Auxiliary Inputs
Four auxiliary inputs are provided for miscellaneous sensors (for example: BS&W, Viscosity monitors, etc.) and can be individually selected to be a 420mA, 4-wire DIN curve RTD or 4-wire American curve RTD.
1.9.
Sixteen. - Product name, factors for each meter, gravity/density override, calculation mode to be used when running the product.
1-2
20/24.71 w 04/98
Volume 3
20/24.71 w 04/98
1-3
Chapter 1
1-4
20/24.71 w 04/98
Volume 3
20/24.71 w 04/98
1-5
Volume 3
Configuration data is stored in the computer's battery backed-up RAM memory which will retain its data for at least 1 to 2 months with no power applied. Configuration data can be entered using one of three methods: 1) Configure off-line using the OmniCom PC configuration program and then uploading all data at once. 2) Configure on-line using the OmniCom PC configuration program which uploads each change as it is entered. 3) Enter configuration data via the front panel keypad using the Program Mode. Methods 1) and 2) require an IBM compatible PC running the OmniCom Configuration Software and are described in Volume 5 and in OmniCom Help. Method 3) is described here.
2.2.
2.2.1.
INFO - Key presses are denoted in bold face between brackets; e.g.: the enter key appears in this manual as [Enter].
While in the Display Mode press the [Prog] key. The front panel Program LED above the key will glow green and the following selection menu will be displayed on the first three lines of the LCD display. Press Keys to Select Group Entry, or Press "Prog" to Exit
The 4 line of the display is used to show the user key presses.
th
2.2.2.
Changing Data
Data can be accessed using a sequential list of menu prompts or in a random access manner by going directly to a specific group of entries.
20/24.71 w 04/98
2-1
Chapter 2
2.2.3.
INFO - Characters in [ ] refer to key presses.
TIP - It is best to use the menu selection method when programming an application for the first time as every possible option and variable will be prompted. Once a computer is in operation and you become familiar with the application you can decide to use the faster Random Access Method described on the facing page. While in the Program Mode (program LED on) press [Setup] [Enter]. A menu similar to the following will be displayed.
Use the [ ]/[ ] (up/down arrow) keys to move the cursor to the appropriate entry and press [Enter] to access a particular submenu. The first menu, 'Misc Configuration', should always be completed first as these entries specify the number and type of input and output devices connected to the flow computer; i.e., the menus following the 'Misc Configuration' menu do not ask for configuration data unless a transducer has been defined.
2.2.4.
In addition to the Setup Menu, the data is also presented in related groups such as Temperature, Pressure, Meter, etc. You press the group key of your choice to get to a data area. By specifying a meter run before or after a group you go directly to the data for that group and that group only. Once a group is selected use the 'Up/Down' arrow keys to step to a specific data entry within the group. You can view data and, assuming a valid password has been entered, change its value as required. If an error is made, press [Clear], re-enter the correct data and press [Enter] to enter the new value. The cursor will automatically step to the next data item in that group unless that would cause a total change of screen (i.e., you can always verify your entry). A list of data groups and associated key presses is listed later in this chapter.
Example:
Pressing [Temp] will allow you access to temperature data for all meter runs. Pressing [Meter] [1] [Temp] or [Temp] [Meter] [1] will allow access to only Meter Run #1 temperature data. For example, pressing [Meter] [1] [Temp] will display the following until the [Enter] key is pressed.
The 4 line of the display is used to show the user key presses.
th
'
2-2
20/24.71 04/98
Volume 3
2.2.5.
INFO - Most entry groups occupy multiple screens so be sure to use the []/[] to scroll and see all data.
Passwords
Except when changing transducer high/low alarm limits, a password is usually asked for when changing the configuration data within the computer. The flow computer has independent password protection of the following: t Local Keypad Access / Modbus Port #1 (selectable) (Physical Serial Port #1) t Modbus Port #2 - (Physical Serial Port #2) t Modbus Port #3 - (Physical Serial Port #3) t Modbus Port #4 - (Physical Serial Port #4)
u Level 1
u Level 1A
Correction
Factors
(Pycnometer
u Level 2
20/24.71 04/98
2-3
1) At the keypad press [Prog] [Setup] [Enter]. 2) With the cursor blinking on 'Misc Configuration', press [Enter]. 3) With the cursor blinking on 'Password Main?', press [Enter]. 4) Enter the Privileged Level Password (up to 6 Characters) and press [Enter]. 5) The Level 1, 1A and Level 2 passwords can now be viewed and changed if required.
INFO - See Technical Bulletin TB-960701 in Volume 5 for setting Level B and Level C passwords using OmniCom.
6) Scroll down to access each of the Modbus serial port 'Level A' passwords. These are labeled Serial 1 (if Modbus Protocol is selected), 'Serial 2', Serial 3', and 'Serial 4' corresponding to the physical port numbering for Modbus Ports 1, 2, 3 and 4.
Note: Level B and Level C passwords for each Modbus port cannot be viewed or changed from the keypad.
2.3.
Getting Help
INFO - The Help System is not limited to just the Program Mode. Context sensitive help is available in all modes of operation.
Context sensitive help is available for most data entries. Help is summoned by pressing the [Display/Enter] key twice ([Help] key) with the cursor on the data field in question. Help screens are frequently more than 1 full screen so always use the []/[] keys to scroll in case there is more. Press [Prog] or [Enter] once to exit the help system and return to your original screen.
2.4.
A 'Program Inhibit Switch' mounted behind the front panel prevents unauthorized changing of data when in the 'Inhibit' position. Most data can be viewed while the switch is in the program inhibit position, but any attempt to alter data will be ignored and cause 'PROGRAM LOCKOUT' to be displayed on the bottom line of the LCD display. The inner enclosure of the flow computer can be locked or sealed within the outer enclosure blocking access to the 'Program Inhibit Switch'.
2-4
20/24.71 w 04/98
Volume 3
CAUTION!
These units have an integral latching mechanism which first must be disengaged by lifting the bezel upwards before withdrawing the unit from the case.
Fig. 2-1.
20/24.71 w 04/98
2-5
Chapter 2
2.5.
Tip - It is best to use the Menu Selection Method (see 9.2.3) when programming an application for the first time as every possible option and variable will be prompted. Once a computer is in operation and you become familiar with the application you can decide to use the faster Random Access Method (see 9.2.4).
The Omni Flow Computer can accept many I/O modules and be configured to match just about any combination of measurement transmitters. Configuring the physical I/O means setting up the number of meter runs, what types of transducers are to be used and to which physical I/O points they are connected.
2.5.1.
The physical I/O configuration of the flow computer is changed by entering the Misc. Setup menu while the 'Select Group Entry' screen is displayed (see 9.2.1. Entering the Program Mode). Press Keys to Select Group Entry, or Press "Prog" to Exit Setup Press [Setup] then [Enter] and the following selection menu will be displayed: *** SETUP MENU *** Misc Configuration _ Time/Date Setup Station Setup The cursor automatically appears at the Misc Configuration option. Press [Enter] and the following selection menu will be displayed: *** Misc. Setup *** Password Maint?(Y) Check Modules ?(Y) Config Station?(Y) Config Meter n Config Prove ? (Y) Config PID ? n Config D/A Outn Front Pnl Counters Program Booleans ? Program Variables? User Display ? n Config Digitaln Serial I/O n Peer/Peer Comm(Y)? Custom Packet n Archive File n PLC Group n SCROLL UP FOR MORE
INFO - The first menu, 'Misc Configuration', should always be completed first as these entries specify the number and type of input and output devices connected to the flow computer. You are advise to complete all entries under this menu before proceeding. Only transducers that have been assigned to physical I/O points will be available for further configuration (i.e., the menus following the 'Misc Configuration' menu do not ask for or accept configuration data unless a transducer has been defined). (See 9.5.2.)
2-6
20/24.71 w 04/98
Volume 3
2.5.2.
Configuration parameter groups are only prompted as needed. Meter runs and transducers which are not assigned to a physical I/O point will not be available for configuration. In these cases the following message will be displayed:
If this message is displayed check the I/O point assignment for the variable.
2.5.3.
INFO - Characters in { } refer to password levels. Characters in [ ] refer to key presses. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Some of these entries may not appear on the display or in OmniCom. Depending on the various configuration settings of your specific metering system, only those configuration options which are applicable will be displayed.
Enter [Y] at Password Maint ? of the Misc Setup menu to open the following entries: {PL} Privileged _______________
Enter the privileged password to allow you to view and change all configuration data including other passwords.
{PL} Level 1
_______________
Enter the Level 1 password to allow entry of all configuration data except entries which determine the physical I/O personality of the computer.
{PL} Level 1A
_______________
Enter the Level 1A password to allow entry of Meter factors K Factors and Density Correction Factors only.
{PL} Level 2
_______________
Enter the Level 2 password which is required for operator type entries such as gravity overrides and meter factors.
_______________
Enter the Serial Port password. All data in the Modbus database except passwords can be read via the serial ports. These passwords allow writes to the Modbus database. Password protection can be disabled by entering a blank field as a password.
_______________
{PL} Lockout SW Active? N {PL} Ser3 Passwd {PL} Lockout SW Active? N {PL} Ser4 Passwd {PL} Lockout SW Active? N
20/24.71 w 04/98
2-7
Chapter 2
2.5.4.
INFO - Characters in { } refer to password levels. Characters in [ ] refer to key presses. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Some of these entries may not appear on the display or in OmniCom. Depending on the various configuration settings of your specific metering system, only those configuration options which are applicable will be displayed.
The following entries display only when a Valid Privileged Password is entered: {PL} Model # (0=3000, 1=6000) _______________
This entry is used by the OmniCom configuration software to determine the maximum I/O capability of the computer.
Enter [Y] to re-configure archive records definition. Enter [N] when finished.
Reset All Ram and Reset Totalizers will only display after the privileged password has been entered. will clear to zero all internal totalizers. You can change totalizer decimal place settings after entering [Y]. The three electromechanical totalizers on the front of the computer cannot be zeroed.
_______________
CAUTION!
Resetting all Ram will clear all configuration data, calibration data and totalizers. This means that all configuration data will have to be re-entered.
If you change the number or type of installed I/O modules, you must perform the Check Modules Function to inform the computer that you wish to use the new hardware configuration.
_______________
Entering a [Y] here will set all the analog input calibration constants used to scale zero and span settings to the default value. This will require you to re calibrate all the inputs. You can also do this on a channel by channel basis by entering the input channel number.
_______________
Entering a [Y] here will set all the analog output calibration constants used to scale zero and span settings to the default value. This will require you to re-calibrate all the outputs. You can also do this on a channel by channel basis by entering the output channel number.
2.5.5.
Module Settings
Enter [Y] at Check Modules ? of the Misc Setup menu and a screen similar to the following will display: MODULE S-WARE H-WARE A-1 Y Y B-1 Y Y E/D-1 Y Y E-1 Y Y H-1 Y Y D-2 Y Y S-2 Y Y Update S-Ware ?
_______________
A table is displayed showing all of the physically installed I/O modules verses the I/O modules recognized by the software (see display example above). You must answer the 'Update Software' question entering [Y] whenever you change the number or type of installed modules. The available I/O point numbers are allocated to each module at this time according to the type and number of each module (see Chapter 2 for more information).
2-8
20/24.71 w 04/98
Volume 3
2.5.6.
INFO - The number of process variable I/O points available depends on the number of combo modules installed (see Chapter 2 in Volume 1 for more information). Point numbers range from 01 through 24. Assign [0] to invalidate the assigning of a variable. I/O Type Mismatch - The computer will not let you assign the same I/O point # to incompatible transducer types; i.e., an I/O point cannot be assigned as a temperature input for Meter Run #1 and a pressure input for Meter Run #2. If the I/O Type Mismatch message is displayed, recheck the I/O. Shared Transducers Enter the same I/O point to share transducers between meter runs. Correcting a Mistake Enter an I/O point # of [0] to cancel an incorrectly entered I/O point #, then enter the correct number. Assigning I/O Point #99 This indicates that the associated variable will be available for display and be used in all calculations, but will not be obtained via a live input. The variable value is usually downloaded into the flow computer database via a communication port or via a user variable statement.
Enter [Y] at Config Station ? of the Misc Setup menu to open the following entries: {PL} Station Configured As: _______________
Station Totals and Flows Defined As: Define which meter runs will be included in the station flow rates and totalizers. Meter data can be added or subtracted. Example: Entering [1] [+] [2] [-] [3] [-] [4] defines the station flows and totals as the result of Meter Runs #1 and #2 added together, subtracted by the flows of Meters #3 and #4. Enter [0] for no station totalizers.
_______________
Enter the I/O point number that corresponds to the station density or gravity input used as the product interface detector. Digital densitometers can be corrected for temperature and pressure effects using the station pressure and temperature points. Digital pulse densitometers can only be th assigned I/O point numbers corresponding to the 4 input channel of a B Type Combo Module, or Channels 3 or 4 of an E/D Type Combo Module.
_______________ _______________
Enter the 8-character tag name used to identify this density transducer on the LCD display.
Enter the densitometer type: 1=4-20 API linear, 2=4-20 SG linear, 3=4-20 density linear, 4=Solartron pulse, 5=Sarasota pulse, 6=UGC pulse.
_______________
Enter the I/O point number to which the temperature sensor used to compensate the station densitometer is connected. When a digital densitometer is used as the station transducer, it can be corrected for temperature effects by assigning a temperature I/O point. For the station product interface densitometer, enter a meter run temperature sensor in cases where a separate temperature transmitter is not available. RTD probes should be assigned to the 1 channel on any type of combo module. RTD probes can nd also be assigned to the 2 channel of B Type combo modules.
st
Density T Tag
_______________
Enter the 8-character tag name used to identify this density temperature transducer on the LCD display.
0=DIN,1=AM,2=4-20
_______________
Enter the densitometer temperature transmitter type: 0=DIN RTD, 1=American RTD, Honeywell Smart Transmitter or 2=4-20mA linear output.
_______________
Enter the I/O point number to which the pressure transmitter used to compensate the station digital densitometers is connected. When a digital densitometer is used as the product interface detector, it can be corrected for pressure effects by assigning a station pressure point. If a separate pressure transmitter is not available, enter a meter pressure transmitter I/O point.
Dens P Tag
_______________
Enter the 8-character tag name used to identify this density pressure transducer on the LCD display.
20/24.71 w 04/98
2-9
_______________
Enter the physical I/O point number to which this auxiliary input is connected. Auxiliary Inputs can be used to enter S&W, viscosity and other miscellaneous variables.
_______________ _______________
Enter the 8-character tag name used to identify this transducer on the LCD display.
Enter the Auxiliary Input Type: 0=DIN RTD, 1=American RTD, 2=Honeywell Smart Transmitter or 4-20mA.
{PL} Auxiliary Input #2 I/O Aux #2 Tag 0=DIN,1=AM,2=4-20 {PL} Auxiliary Input #3 I/O Aux #3 Tag _______________ _______________ _______________ _______________
_______________
_______________
INFO - The number of process variable I/O points available depends on the number of combo modules installed (see Chapter 2 in Volume 1 for more information). Point numbers range from 01 through 24. Assign [0] to invalidate the assigning of a variable. I/O Type Mismatch - The computer will not let you assign the same I/O point # to incompatible transducer types; i.e., an I/O point cannot be assigned as a temperature input for Meter Run #1 and a pressure input for Meter Run #2. If the I/O Type Mismatch message is displayed, recheck the I/O. Shared Transducers Enter the same I/O point to share transducers between meter runs. Correcting a Mistake Enter an I/O point # of [0] to cancel an incorrectly entered I/O point #, then enter the correct number.
2.5.7.
Enter [1], [2], [3] or [4] at Config Meter "n" of the Misc Setup menu to open the following entries:
Meter #1 Meter #2 Meter #3 Meter #4
_______
_______
_______
_______
Enter the number of the I/O point used to input the flow signal for each meter run. Flowmeter rd th pulse inputs can only be assigned to the 3 input channel of any combo module and 4 input channel of A Type combo modules. When working with compact provers using pulse interpolation, rd th you must assign each of the flowmeter pulse signals to the 3 or 4 channel of an E Type combo module.
_______ _______
_______ _______
_______ _______
_______ _______
Enter the 8-character tag name used to identify this flowmeter on the LCD display.
Enter [Y] to enable 'Level A' pulse fidelity and security checking for this meter run (API MPMS rd Chapter 5, Section 5). The 'Flow I/O Point' entered above must correspond to the 3 input channel of an E Combo Module. The flowmeter pulses are physically wired to Input Channels 3 and 4 of the E Combo Module.
_______
_______
_______
_______
Enter [Y] if the flowmeter used for this meter run produces mass pulses (i.e., pulses per mass unit). A coriolis mass meter usually provides this type of output signal.
_______
_______
_______
_______
Enter the I/O point number used to input the temperature signal for each meter run. Duplicate I/O assignments are allowed when a sensor is shared by more than one meter run.
2-10
20/24.71 w 04/98
Volume 3
Temp Tag
Config Meter Runs Physical I/O information for up to 4 meter runs can be entered. Transducers that are not assigned an I/O point will not be available for display or further configuration. Assigning I/O Point #99 This indicates that the associated variable will be available for display and be used in all calculations, but will not be obtained via a live input. The variable value is usually downloaded into the flow computer database via a communication port or via a user variable statement.
Enter the 8-character tag name used to identify this temperature transducer on the LCD display.
Enter the Temperature Transmitter Type: 0=DIN RTD, 1=AMER RTD, 2=4-20mA.
Enter the I/O point number used to input the pressure signal for each meter run. Duplicate I/O assignments are allowed when a sensor is shared by more than one meter run.
_______ _______
_______ _______
_______ _______
_______ _______
Enter the 8-character tag name used to identify this pressure transducer on the LCD display.
Enter the I/O point number used to input the density signal for each meter run. Duplicate I/O assignments are allowed when a densitometer is shared by more than one meter run. Digital pulse th densitometers can only be assigned I/O point numbers corresponding to the 4 input channel of a rd th 'B' Type Combo Module or the 3 and 4 input channels of an E/D Combo Module.
_______ _______
_______ _______
_______ _______
_______ _______
Enter the 8-character tag name used to identify this density transducer on the LCD display.
Enter the Densitometer Type: 1=4-20 API linear, 2=4-20 SG linear, 4=Solartron pulse, 5=Sarasota pulse, 6=UGC pulse.
0=Flowing, 1=Ref
_______
_______
_______
_______
This entry is applies only if you selected a 4-20mA type densitometer in the previous entry Specify if the density transducer signal represents density at: 0=flowing temperature and pressure, 1=reference temperature and pressure.
Meter #1
Meter #2
Meter #3
Meter #4
_______
_______
_______
_______
Enter the I/O point number used to input the signal applied to compensate for temperature effects at the densitometer for each meter run. If the densitometer has no temperature sensor fitted, enter the same I/O point assignment as the meter run temperature sensor.
Density T Tag
_______
_______
_______
_______
Enter the 8-character tag name used to identify this density temperature transducer on the LCD display.
_______ _______
_______ _______
_______ _______
_______ _______
Enter the Densitometer Temperature Transmitter Type: 0=DIN RTD, 1=AMER RTD, 2=4-20mA.
Enter the I/O point number used to input the signal applied to compensate for pressure effects at the densitometer for each meter run. If the densitometer has no pressure sensor fitted, enter the same I/O point assignment as the meter run pressure sensor.
Dens P Tag
_______
_______
_______
_______
Enter the 8-character tag name used to identify this density pressure transducer on the LCD display.
20/24.71 w 04/98
2-11
Chapter 2
2.5.8.
INFO - Characters in { } refer to password levels. Characters in [ ] refer to key presses. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Some of these entries may not appear on the display or in OmniCom. Depending on the various configuration settings of your specific metering system, only those configuration options which are applicable will be displayed.
Prover Settings
Enter [Y] at Config Prove ? of the Misc Setup menu to open the following entries:
Inlet Outlet
__________
__________
Enter the I/O point number used to input the prover inlet/outlet temperature signal. Inlet and outlet temperature sensor readings are averaged to determine the actual prover temperature. To use the meter run temperature, enter [0] for both inlet and outlet. If there is only one temperature sensor, enter [0] for outlet or enter the same number for both prover inlet and outlet.
Inlet/Outlet T Tag 0=DIN, 1=AM, 2-4-20 {PL} Prover Pressure I/O Point
Enter the 8-character tag name used to identify this temperature transducer on the LCD display.
Enter the Prover Temperature Transmitter Type: 0=DIN RTD, 1=AMER RTD, 2=4-20mA.
Configuring the Prover When an input and output transducer signal is available, the computer uses the average of both signals. Otherwise, it uses the signal from the available transducer. The pressure or temperature of the meter run being proved will be used to compensate the prover if neither left or right transducer is assigned to an I/O point #.
Enter the I/O point number used to input the prover inlet/outlet pressure signal. Inlet and outlet pressure sensor readings are averaged to determine the actual prover pressure. To use the meter run pressure, enter [0] for both inlet and outlet. If there is only one pressure sensor, enter [0] for outlet or enter the same number for both prover inlet and outlet.
__________
__________
Enter the 8-character tag name used to identify this pressure transducer on the LCD display.
_______________
Applies only when a Brooks compact prover is specified. Enter the I/O point number used to input the compact prover plenum pressure sensor input.
Plenum Tag
_______________
Enter the 8-character tag name used to identify this plenum pressure transducer on the LCD display.
_______________
Enter the I/O point number used to input the density signal for the prover. The prover density I/O point is used to calculate the mass of liquid in the prover during a mass proving run (i.e., coriolis meter proving). Digital pulse densitometers can be corrected for temperature and pressure effects using the station pressure and temperature points. Digital pulse densitometers must be assigned th rd th to the 4 channel of a 'B' type module or the 3 or 4 channel of an E/D module.
_______________ _______________
Enter the 8-character tag name used to identify this density transducer on the LCD display.
Enter the Prover Densitometer Type: 1=4-20 API linear, 2=4-20 SG linear, 3=4-20 density linear, 4=Solartron pulse, 5=Sarasota pulse, 6=UGC pulse.
2-12
20/24.71 w 04/98
Volume 3
{PL} Prover Dens T I/O Point
INFO - The number of process variable I/O points available depends on the number of combo modules installed (see Volume I; Chapter 2 for more information). Point numbers range from 01 through 24. Assign [0] to invalidate the assigning of a variable. I/O Type Mismatch - The computer will not let you assign the same I/O point # to incompatible transducer types; i.e., an I/O point cannot be assigned as a temperature input for Meter Run #1 and a pressure input for Meter Run #2. If the I/O Type Mismatch message is displayed, recheck the I/O. Shared Transducers Enter the same I/O point to share transducers between meter runs. Correcting a Mistake Enter an I/O point # of [0] to cancel an incorrectly entered I/O point #, then enter the correct number. Assigning I/O Point #99 This indicates that the associated variable will be available for display and be used in all calculations, but will not be obtained via a live input. The variable value is usually downloaded into the flow computer database via a communication port or via a user variable statement.
Enter the I/O point number to which the temperature sensor used to compensate the prover densitometer is connected. When a digital densitometer is used as the prover transducer, it can be corrected for temperature effects by assigning a temperature I/O point. For the prover densitometer, enter the same I/O points as the prover inlet/outlet temperature sensor in cases where a separate temperature transmitter is not part of the densitometer. RTD probes should be assigned to the 1 channel on any type of combo module. RTD probes can nd also be assigned to the 2 channel of B Type combo modules.
st
Dens T Tag
_______________
Enter the 8-character tag name used to identify this density temperature transducer on the LCD display.
_______________ _______________
Enter the Prover Temperature Transmitter Type: 0=DIN RTD, 1=AMER RTD, 2=4-20mA.
Enter the I/O point number to which the pressure transmitter used to compensate the prover digital densitometer is connected. Enter the same I/O point as the prover inlet pressure sensor in cases where a separate pressure transmitter is not available.
Dens P Tag
_______________
Enter the 8-character tag name used to identify this density pressure transducer on the LCD display.
20/24.71 w 04/98
2-13
Chapter 2
2.5.9.
Proportional Integral Derivative (PID) -- For practical reasons we refer to PID Control Loops in this manual. However, your flow computer actually performs the Proportional Integral (PI) function and does not apply the derivative term. The addition of the derivative term would greatly complicate tuning of the control loop and besides is not normally applicable to the types of flow and pressure control used in pipelines.
Enter [1], [2], [3] or [4] at Config PID ? "n" of the Misc Setup menu to open the following entries:
Loop #1 Loop #2 Loop #3 Loop #4
_______
_______
_______
_______
Enter the database index number of the primary variable in the PID loop (see the sidebar).
Enter a remark in this 16-character field which identifies and documents the function of each variable assignment.
_______
_______
_______
_______
Enter [F] (forward action) if the value of the primary variable increases as the controller output % increases. Enter [R] (reverse action) if the value of the primary variable decreases as the controller output % increases.
Valid Assignments - Any 32-bit integer or floating point variable within the database can be assigned to be the primary or secondary controlled variable (see Volume 4 for a complete listing of database addresses and index numbers).
_______
_______
_______
_______
Enter the I/O point number that the remote set point analog signal is connected to (01-24). Assign this point to 99 in cases where the set point will be downloaded via a communication port. Enter [0] if you will not be using a remote setpoint.
_______
_______
_______
_______
Enter the database index number of the secondary variable in the PID loop (see the sidebar).
Enter a remark in this 16-character field which identifies and documents the function of each variable assignment.
_______
_______
_______
_______
Enter [F] (forward action) if the value of the primary variable increases as the controller output % increases. Enter [R] (reverse action) if the value of the primary variable decreases as the controller output % increases.
2-14
20/24.71 w 04/98
Volume 3
_______
_______
_______
_______
This entry is used to determine under what circumstances the primary or secondary variable is to be controlled. There are two modes of low/high error select: Mode #1: The controller will attempt to control the primary variable but will switch to controlling the secondary variable, should the controller be trying to drive the secondary variable ABOVE its setpoint. An example of this mode would be controlling flow rate (primary) while not exceeding a MAXIMUM delivery pressure (secondary). The controller will attempt to control primary variable but will switch to controlling the secondary variable, should the controller be trying to drive the secondary variable BELOW its setpoint. An example of this mode would be controlling flow rate (primary) while not dropping below a MINIMUM pressure value (secondary).
Mode #2:
Considering these modes, select your entry according to the following flow diagram.
MODE #1
Are both primary and secondary actions forward?
MODE #2
Are both primary and secondary actions forward?
yes
Enter [L] (Low Error Select)
no
no
Enter [H] (High Error Select)
yes
Enter [H] (High Error Select)
no
no
Enter [L] (Low Error Select)
yes
yes
_______
_______
_______
_______
This entry determines how the computer handles a system reset such as a momentary loss of power. Enter [L] (Last) to cause the PID loop to stay in the operating mode it was last in before the system reset. Enter [M] (Manual) to cause the PID loop to startup with the PID loop in manual control mode and with the valve open % as it was before the system reset.
_______
_______
_______
_______
Enter an 8-character tag name used to identify the PID controller output % signal on the LCD display.
20/24.71 04/98
2-15
Chapter 2
Press [n] [Enter] at Config D/A Out "n" of the Misc Setup menu to open the following entries (n = D/A Output #):
Assign at 4mA at 20mA
__________
__________
__________
Under Assign, enter the database index number of the variable that will be assigned to the digital-to-analog output points. Under at 4mA and at 20mA, enter the required scaling parameters in engineering units at 4mA and 20mA (e.g.: For Meter #1 Net Flow Rate assign 7102. Typical scaling might be 4mA=0.0 bbls/hr and 20mA=1000.0 bbls/hr).
Rmk
_______________
Enter a remark in this 16-character field which identifies and documents the function of each digital-to-analog output.
{L1} Analog Output #2 Rmk {L1} Analog Output #3 Rmk {L1} Analog Output #4 Rmk {L1} Analog Output #5 Rmk {L1} Analog Output #6 Rmk {L1} Analog Output #7 Rmk {L1} Analog Output #8 Rmk {L1} Analog Output #9 Rmk {L1} Analog Output #10 Rmk {L1} Analog Output #11 Rmk {L1} Analog Output #12 Rmk
__________
__________
__________
_______________
2-16
20/24.71 w 04/98
Volume 3
__________
__________
__________
Enter the database index number of the accumulator variable that will be output to this electromechanical counter. The unit of measure is the same as that shown on the LCD for the totalizer (i.e., barrels, klbs, m , etc.) The maximum count rate is limited to 10 counts per second. Count rates higher than 10 pulses per second will cause the computer to remember how many counts did not get output and continue to output after the flow stops until all buffered counts are output.
3
Rmk
Enter a remark in this 16-character field which identifies and documents the function of each front panel counter.
Pulses/Unit
__________
__________
__________
20/24.71 w 04/98
2-17
Chapter 2
Enter [Y] at Program Booleans ? of the Misc Setup menu to open the following entries: Boolean Point 10xx 25: 26: 27: 28: 29: 30: 31: 32: 33: 34: 35: 36: 37: 38: 39: 40: 41: 42: 43: 44: 45: 46: 47: 48: 49: 50: 51: 52: 53: 54: 55:
Equation or Statement Rmk (Comment or Remark)
_______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________
2-18
20/24.71 w 04/98
Volume 3
Boolean Point 10xx
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Program Booleans - These 64 Boolean statements are evaluated every 100 msec starting at Point 1025 continuing through 1088. Each statement can contain up to 3 Boolean variables, optionally preceded by the slash (/) denoting the NOT Function and separated by a valid Boolean operator: Operator Symbol NOT / AND & OR + EXOR * EQUAL = IF ) GOTO G MOVE : COMPARE % INDIRECT E.g.: 1025:1002&/1003 Boolean 1025 is true when point 1002 is true AND point 1003 is NOT true. Note: Points 1002 and 1003 in this example reflect the status of Physical I/O Points 2 and 3. There are no limitations as to what Boolean points can be used in a statement. Statements can contain the results from other statements. E.g.: 1026: /1025+1105 Boolean 1026 is true when Boolean 1025 is NOT true OR Point 1105 is true. Using the = operator, the result of a statement can initiate a command. E.g.: 1027: 1719=1026 Request a Snapshot Report when Boolean 1026 is true.
56: 57: 58: 59: 60: 61: 62: 63: 64: 65: 66: 67: 68: 69: 70: 71: 72: 73: 74: 75: 76: 77: 78: 79: 80: 81: 82: 83: 84: 85: 86: 87: 88:
_______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________
20/24.71 w 04/98
2-19
Chapter 2
2.5.13.
Programmable Variables These 64 variable statements are evaluated every 500 msec starting at the statement that determines the value of Points 7025 through 7088. Each statement can contain up to 3 variables or constants. Variables can be optionally preceded by the $ symbol denoting the ABSOLUTE value of the variable is to be used. Constants are identified by placing a # symbol ahead of the number. These and other operators are: Operator Symbol ABSOLUTE $ CONSTANT # POWER & MULTIPLY * DIVIDE / ADD + SUBTRACT EQUAL = IF ) GOTO G MOVE : COMPARE % INDIRECT The order of precedence is: 1) ABSOLUTE 2) POWER 3) MULTIPLY/DIVIDE 4) ADD/SUBTRACT In cases where operators have the same precedence, statements are evaluated left to right. E.g.: The value of floating point variable 7035 is defined as: 35:7027*7026 The power operator is evaluated first (the value of Point 7035 is set equal to the square root of the number contained in Point 7027) and the result is multiplied by the number stored in variable 7026. Note that statements can contain the results of other statements. (See OmniCom Help for more information by pressing [F1] on your PC keyboard in the Configure Variable Statement menu.)
Enter [Y] at Program Variables ? of the Misc Setup menu to open the following entries: Prog Variable 70xx 25: 26: 27: 28: 29: 30: 31: 32: 33: 34: 35: 36: 37: 38: 39: 40: 41: 42: 43: 44: 45: 46: 47: 48: 49: 50: 51: 52: 53: 54: 55:
Equation or Statement Comment or Remark
_______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________
2-20
20/24.71 w 04/98
Volume 3
Prog Variable 70xx
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you enter in the flow computer.
_______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________ _______________________
Note: See Volume 4 for detailed list of Booleans and Status Commands
Valid Numeric Variables These are any long integer or floating point number within the database (Points 50008999), including Boolean variables. For the purpose of evaluation, Boolean variables have the value of 1.0 if they are True and 0.0 if they are False.
63: 64: 65: 66: 67: 68: 69: 70: 71: 72: 73: 74: 75: 76: 77: 78: 79: 80: 81: 82: 83: 84: 85: 86: 87: 88:
20/24.71 w 04/98
2-21
Chapter 2
Enter 1 through 8 for the selected user display at User Display ? n of the Misc Setup menu to open the following entries:
User Display #1
Key Press _______________
Using the keys marked A through Z , enter the sequence of key presses needed to recall the selected user display (see the side bar for details). A maximum of 4 keys are allowed. User key press sequences take priority over any existing resident key press sequences.
_______________ _______________
Enter an 8-character tag name used to identify the display variable on the LCD display.
Enter the database index number of the variable that you want to appear on the LCD display. Each variable within the flow computer database is assigned an index number or address. Any Boolean integer or floating point variable within the database can be displayed.
Var #1 Dec.
_______________
Enter the number of digits to the right of the decimal point for the variable. Valid entries are 0 though 7. The computer will display each variable using the display resolution that you have selected, except in cases where the number is too large or too small. In either case, the flow computer will adjust the decimal position or default to scientific display mode.
Tag
Index #
Decimal Pos.
User Display #2
Key Press
Tag
_______________
Index # Decimal Pos.
User Display #3
Key Press
Tag
_______________
Index # Decimal Pos.
2-22
20/24.71 w 04/98
Key Press
Tag
_______________
Index # Decimal Pos.
User Display #5
Key Press
Tag
_______________
Index # Decimal Pos.
User Display #6
Key Press
Tag
_______________
Index # Decimal Pos.
User Display #7
Key Press
Tag
_______________
Index # Decimal Pos.
User Display #8
Key Press
Tag
_______________
Index # Decimal Pos.
20/24.71 w 04/98
2-23
Chapter 2
Enter 1 through 24 for the selected digital I/O Point at Config Digital n of the Misc Setup menu to open the following entries:
Assign Pulse Width Pulse/Unit or Delay On Delay Off
________
________ ________
________ ________
Config Digital n - Assign each physical I/O point to a Modbus address of a Boolean variable. There are no limitations as to what Boolean points can be assigned to physical I/O points. Enter [0] (zero) for Modbus control. Assigning as Pulse Outputs - Meter and Station Accumulators may be output in the form of pulses. Pulse Width - Pulse width is measured using 10msec ticks; i.e., 100 = 1 second. Pulse per Unit - Pulse per unit entry can be used to provide unit conversion (e.g.: entering 4.2 pulses per barrel will give 1 pulse every 10 gallons as there are 42 gallons in a barrel). The units of volume, mass and energy flow are the same as is displayed on the LCD. Assigning as Control Output - Any internal alarm or Boolean can be output.
Digital #4 Rmk Digital #5 Rmk Digital #6 Rmk Digital #7 Rmk Digital #8 Rmk Digital #9 Rmk Digital #10 Rmk Digital #11 Rmk Digital #12 Rmk
_______________
2-24
20/24.71 w 04/98
Volume 3
Assign
Delay On/Off - Used to delay or stretch a control output. The delay is measured using 100msec ticks; i.e., 10 = 1 second. Assigning as Status or Command Inputs Switches, etc., can be used to trigger events within the flow computer, such as end a batch or start a prove sequence (see the facing page for more details). 1700 Dummy Boolean Assign all physical I/O points which will be used only in Boolean statements for sequencing or control to 1700. This sets up the points as an input only. Note: See Volume 4 for valid assignments.
Digital #13 Rmk Digital #14 Rmk Digital #15 Rmk Digital #16 Rmk Digital #17 Rmk Digital #18 Rmk Digital #19 Rmk Digital #20 Rmk Digital #21 Rmk Digital #22 Rmk Digital #23 Rmk Digital #24 Rmk
________
________ ________
________ ________
_______________
20/24.71 w 04/98
2-25
Chapter 2
Enter [1], [2], [3] or [4] at Serial I/O n of the Misc Setup menu to open the following entries:
Port #1 Port #2 Port #3 Port #4
{L1} Baud Rate {L1} Number of Data Bit {L1} Number of Stop Bit {L1} Parity Bit (E/O/N) {L1} Xmit Key Delay {L1} Printer = 0, Modbus = 1 {L1} Protocol Type
You must enter [0] for Transmitter Key Delay for any port that will be used with a shared printer.
_______
Baud Rates Available 300, 600, 1200, 2400, 4800, 9600, 19200, 38400. Data Bits - 7 or 8 - 7 for ASCII Modbus, 8 for RTU Modbus. Stop Bits - 0, 1 or 2. Parity Bit - Odd, Even, None. Transmitter Carrier Key Delay - Delays are approximate only. 0=msec, 1=50msec, 2=100msec, 3=150msec. Modbus Type - Select the protocol type which matches the Modbus master device. If the master can support either ASCII or RTU, choose RTU protocol as it is approximately twice as efficient as the ASCII protocol. Modicon Compatible OmniCom will not operate if downloading configuration with this entry set to Y.
This entry corresponds to Serial Port #4 only. Enter the type of protocol to be used on this port: 0=Modbus RTU, 1=Modbus ASCII, 2=Modbus RTU (modem), 3=Allen Bradley Full Duplex, 4=Allen Bradley Half Duplex.
{L1} Modbus ID
_______
_______
_______
_______
Enter the Modbus slave ID number that this serial port will respond to (1 through 247 acceptable). This entry will be disabled for Serial Port #1 if a printer is selected as the port type.
_______
_______
_______
This entry does not apply to Serial Port #4. Enter the Modbus Protocol Type: 0=Modbus RTU binary protocol, 1=Modbus ASCII protocol, 2=Modbus RTU (Modem). Make sure that you have entered the correct number of Data Bits; 8 for RTU or 7 for ASCII.
_______
_______
_______
_______
Enter [Y] to configure these Modbus ports to be compatible with Modicon PLC equipment (e.g.: 984 series fitted with the Enhanced Executive Cartridge) and DCS systems (e.g.: Honeywell TDC3000 systems using the Advanced Process Manager APM-SI). This entry will be disabled for Serial Port #1 if a printer is selected as the port type. In this mode the point number indexes requested and transmitted while using the Modbus RTU modes are actually one less than the index number documented in this manual. ASCII mode transmissions use the address documented in this manual. Data is counted in numbers of 16 bit registers rather than points. i.e., To request two 4 byte IEEE floating point variables, index numbers 7101 and 7102, would require the host to ask for 4 registers starting at index 7100. IEEE Floating Point data bytes are transmitted in swapped format:
ORDER TRANSMITTED
Byte #2 LS Mantissa Byte #3 Biased Exponent Byte #4 MS Mantissa
2-26
20/24.71 w 04/98
Volume 3
{L1} CRC Enabled
Skip CRC/LCR Check - If you have disabled the error checking on incoming messages, you must substitute dummy bytes in the message string. Outgoing messages will always include the error checking bytes.
Many protocols use either a CRC, LCR or BCC error check to ensure that data received is not corrupted. The flow computer can be configured to ignore the eror checking on incomimg messages. This allows software developers an easy means of debugging communications software. Error checking should only be disabled temporarily when debugging the master slave communication link. Enter [Y] to perform error checking on incoming messages. For maximum data integrity always enter [Y] during normal running conditions. Enter [N] to disable error checking on incoming messages. This entry will be disabled for Serial Port #1 if a printer is selected as the port type.
The active redundancy feature allows two flow computers to operate as a pair. Each flow computer receives the same process signals and performs the same calculations; i.e., in redundancy. Enter [Y] to allow both flow computers to manage the peer-to-peer link between them and automatically switch between being the master or slave computer. Important data such as meter factors and PID control settings can be continually exchanged between flow computers ensuring that at any time, should a failure occur to one, the other unit would be able to assume control of the PID and ticketing functions. The redundancy mode requires that four digital I/O ports be cross-connected to sense watchdog failure modes using the following points 2714=Input master status, 2864=Output Master status, 2713 Input watchdog status, 2863 = Output of watchdog status. (See Technical Bulletin TB980402 in Volume 5.)
_______________
Enter the slave number of the next flow computer in sequence in the peer-to-peer communication sequence to pass over control. After the flow computer completes all of it's transactions it will attempt to pass over master control of the Modbus link to this Modbus ID. Enter the Modbus ID of this flow computer if there are no other peers in sequence on the communication link. Enter [0] to disable the peer-to-peer feature and use Serial Port #2 as a standard Modbus slave port.
_______________
Enter the slave number of the last Omni (the highest Modbus ID number) in the peer-to-peer communication sequence. This is required for error recovery. Should this flow computer be unable to hand over control to the 'next master in sequence' (see previous entry), it will attempt to establish communications with a Modbus slave with a higher Modbus ID. It will keep trying until the ID number exceeds this entry. At that point the flow computer will start at Modbus ID #1. Enter the Modbus ID of this flow computer if it is the only master on the link.
_______________
Should any slave device fail to respond to a communication request, the master device will retry to establish communications several times. Enter the number of 50 millisecond ticks that the flow computer should wait for a response from the slave device. To ensure fast recovery from communication failures, set this entry to as low a number as possible. Enter [3] for peer-to-peer links involving only Omni flow computers. Other Modbus devices may require more time to respond.
20/24.71 w 04/98
2-27
Chapter 2
{L1} #1 Slave ID
INFO - Characters in { } refer to password levels. Characters in [ ] refer to key presses.
Each transfer of data is called a transaction. Enter the Modbus ID # of the other slave involved in the transaction. Modbus ID 0 can be used to broadcast write to all Modbus slave devices connected to the peer-to-peer link. Other valid IDs range from 1-247.
Read/Write Source
_______________ _______________
Enter [R] if data will be read from the slave. Enter [W] if data will be written to the slave. INFO - The Omni Flow Computer determines what Modbus function code and what data type is involved by the Modbus index number of the data within the Omnis database. The Source Index determines the data type for a write. The Destination Index determines the data type for a read. Function codes used are:
01=Read Multiple Booleans 15=Write Multiple Booleans 03=Read Multiple Variables 16=Write Multiple Variables
Enter the database index number or address of the Modbus point where the data is to be obtained, corresponding to the first data point of the transaction. This is the slaves database index number when the transaction is a read, and the masters database index number when the transaction is a write. Refer to Volume 4 for a list of available database addresses or index numbers.
Points
_______________
Enter the number of contiguous points to transfer. Each transaction can transfer multiple data points that can be any valid data type recognized by the Omni. The maximum number of points that can be transferred depends on the type of data. IEEE floats (4bytes each)=63 max; 32-bit Integers (4 bytes each)=63 max; 16-bit integers (2 bytes each)=127 max; packed coils or status (8 to a byte)=2040 max. The Omni automatically knows what Modbus function to use and what data types are involved by the Modbus index number of the data within the flow computer database. The destination index number determines the data type when the transactions is a read. The source index number determines the data type when the transaction is a write.
Dest Indx
_______________
Enter the database index number or address of where the data is to be stored (destination index or address). If the transaction is a read, this will be the index number within the master Omnis database. If the transaction is a write, this will be the register number within the remote slaves database.
{L1} #2-Slave ID Read/Write Source Points Dest Indx {L1} #3 Slave ID Read/Write Source Points Dest Indx {L1} #4 Slave ID Read/Write Source Points Dest Indx _______________ _______________ _______________ _______________ _______________ _______________ _______________ _______________ _______________ _______________ _______________ _______________
_______________
_______________
_______________
2-28
20/24.71 w 04/98
Volume 3
{L1} #5 Slave ID
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Some of these entries may not appear on the display or in OmniCom. Depending on the various configuration settings of your specific metering system, only those configuration options which are applicable will be displayed.
Read/Write Source Points Dest Indx {L1} #6 Slave ID Read/Write Source Points Dest Indx {L1} #7 Slave ID Read/Write Source Points Dest Indx {L1} #8 Slave ID Read/Write Source Points Dest Indx {L1} #9 Slave ID Read/Write Source Points Dest Indx {L1} #10- Slave ID Read/Write Source Points Dest Indx
20/24.71 w 04/98
2-29
Chapter 2
{L1} #11 Slave ID
INFO - Characters in { } refer to password levels. Characters in [ ] refer to key presses. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Some of these entries may not appear on the display or in OmniCom. Depending on the various configuration settings of your specific metering system, only those configuration options which are applicable will be displayed.
Read/Write Source Points Dest Indx {L1} #12 Slave ID Read/Write Source Points Dest Indx {L1} #13 Slave ID Read/Write Source Points Dest Indx {L1} #14 Slave ID Read/Write Source Points Dest Indx {L1} #15 Slave ID Read/Write Source Points Dest Indx {L1} #16 Slave ID Read/Write Source Points Dest Indx
INFO - The Omni Flow Computer determines what Modbus function code and what data type is involved by the Modbus index number of the data within the Omnis database. The Source Index determines the data type for a write. The Destination Index determines the data type for a read. Function codes used are:
01=Read Multiple Booleans 15=Write Multiple Booleans 03=Read Multiple Variables 16=Write Multiple Variables
2-30
20/24.71 w 04/98
Volume 3
Custom Modbus Data Packets are provided to reduce the number of polls needed to read multiple variables which may be in different areas of the database. Groups of data points of any type of data can be concatenated into one packet by entering each data group starting index numbers 001, 201 and 401. The number of data bytes in a custom packet in non-Modicon compatible mode cannot exceed 250 (RTU mode) or 500 (ASCII mode). When Modicon compatible is selected, the number of data bytes in a custom packet cannot exceed 400 (RTU mode) or 800 (ASCII mode). Enter [1], [2] or [3] to select a data packet at Custom Packet n of the Misc Setup menu to open the entries below. Under Index #, enter the database address or Modbus index number for each data point of each group. Under Points, emter the number of consecutive data points to include in each data group.
#1_______/_____ #2_______/_____ #3_______/_____ #4_______/_____ #5_______/_____ #6_______/_____ #7_______/_____ #8_______/_____ #9_______/_____ #10_______/_____ #11_______/_____ #12_______/_____ #13_______/_____ #14_______/_____ #15_______/_____ #16_______/_____ #17_______/_____ #18_______/_____ #19_______/_____ #20_______/_____
#1_______/_____ #2_______/_____ #3_______/_____ #4_______/_____ #5_______/_____ #6_______/_____ #7_______/_____ #8_______/_____ #9_______/_____ #10_______/_____ #11_______/_____ #12_______/_____ #13_______/_____ #14_______/_____ #15_______/_____ #16_______/_____ #17_______/_____ #18_______/_____ #19_______/_____ #20_______/_____
20/24.71 w 04/98
2-31
Chapter 2
Note: See Technical Bulletin TB-960702 Communicating with AllenBradley Programmable Logic Controllers in Volume 5 for information on the PLC Group n submenu.
2-32
20/24.71 w 04/98
Volume 3
2.6.
INFO - The first menu, 'Misc Configuration', should always be completed first as these entries specify the number and type of input and output devices connected to the flow computer; i.e., the menus following the 'Misc Configuration' menu do not ask for configuration data unless a transducer has been defined. Flow Computer Configuration via the Menu Selection Method It is best to use this method when programming an application for the first time as every possible option and variable will be prompted. Once a computer is in operation and you become familiar with the application you can decide to use the faster Random Access Method described below. Once you have finished entering data in a setup submenu, press the [Prog] key to return to the Select Group Entry screen. Proceed as described in this manual for each setup option. Time and Date Setup via the Random Access Method - Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press [Time] [Enter] and use [] / [] keys to scroll.
2.6.1.
Applying the Menu Selection Method (see sidebar), in the Select Group Entry screen (Program Mode) press [Setup] [Enter] and a menu similar to the following will be displayed:
2.6.2.
{L1} Time :
Enter Current Time using the correct method 'hh:mm:ss'. To change only the hour, minutes or seconds, move cursor to the respective position and enter the new setting.
{L1} Date :
____/____/____
Enter Current Date using the correct method 'mm/dd/yy' ordd/mm/yy. To change only the month, day or year, move cursor to the respective position and enter the new setting.
_____________
20/24.71 04/98
2-33
Chapter 2
2.7.
Meter Station Setup via the Random Access Method - Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and Select Group Entry screen will appear. Then press [Meter] [Enter] and use [] / [] keys to scroll. Meter Station Run Switching Flow Rate Thresholds - The Omni flow computer has 3 Boolean flags which are set or reset depending on the station flow rate: u Run Switching Flag #1 at Modbus database point 1824. u Run Switching Flag #2 at Modbus database point 1825. u Run Switching Flag #3 at Modbus database point 1826. Each of these flags has a low threshold and high threshold flow rate. Each flag is set when the station flow rate exceeds the corresponding high threshold value. These flags reset when the station flow rate falls below the respective low threshold limit. See Chapter 3 for more information on how to include these flags in Boolean statements to automatically switch meter runs depending on flow rates.
2.7.1.
Applying the Menu Selection Method (see sidebar), in the Select Group Entry screen (Program Mode) press [Setup] [Enter] and a menu similar to the following will be displayed:
2.7.2.
{L1} Station ID
Enter 8 alphanumeric characters maximum. This string variable usually appears in user custom reports (Modbus database point 4815).
Flow Low
_______________
Enter the flow rate below which the Station Low Flow Alarm activates (Modbus database point 1810). Flow rates 5% below this value activate the Low Low Alarm (Modbus database point 1809).
Flow High
_______________
Enter the flow rate above which the Station High Flow Alarm activates (Modbus database point 1811). Flow rates 5% above this value activate the High High Alarm (Modbus database point 1812).
{L1} G FullScal
_______________
Enter the gross flow rate at full-scale for the meter station. Sixteen-bit integer variables representing station gross and net flow rate are included in the database at 3802 and 3804. These variables are scaled using this entry and stored as percentage of full scale with a resolution of 0.1% (i.e., 0 to 999 = 0% to 99.9%)
{L1} M FullScal
_______________
Enter the mass flow rate at full-scale for the meter station. A 16-bit integer variable representing station mass flow rate is included in the database at 3806. This variable is scaled using this entry and stored as percentage of full scale with a resolution of 0.1% (i.e., 0 to 1000 = 0% to 100.0%)
Flag #1
Flag #2
Flag #3
{L1} Thre Lo
Enter the flow rate Low Threshold value which resets each Station Run Switching Flag when the station gross flow rate falls below this limit (see sidebar).
{L1} Thre Hi
Enter the flow rate High Threshold value which sets each Station Run Switching Flag when the station gross flow rate exceeds this limit (see sidebar).
2-34
20/24.71 04/98
Volume 3
{L1} Common Batch Stack
INFO - Characters in { } refer to password levels. Characters in [ ] refer to key presses. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Some of these entries may not appear on the display or in OmniCom. Depending on the various configuration settings of your specific metering system, only those configuration options which are applicable will be displayed.
Enter [Y] to set up the flow computer to use a common product on all four meter runs; i.e., to run the same product at the same time on all 4 meter runs. Enter [N] to run different products at the same time on each meter run.
_______________
Enter the quantity of barrels for the Batch Preset Warning. This entry displays only when Common Batch Stack is selected. The Batch preset counters are activated when a non-zero number is entered for batch size on the batch sequence stack (see previous chapter on Batching Operations). The batch preset reached flag (database point 1819) will be activated whenever the batch preset counter counts down to zero. The batch warning flag (database point 1818) will be activated when the batch preset counter is equal or less than this entry.
_______________
Enter the selected Batch Preset Counter Units: 0=Net (standard) volume units, 1=Gross (actual) volume units, 2=Mass units.
_______________
This entry represents the Specific Gravity Rate of Change and displays only when a Station Density I/O Point has been assigned. It is used to detect product changes in the pipeline (product interface). Enter the Gravity Rate of Change in specific gravity units per barrel or m for this limit. The Gravity Rate of Change Flag (database point 1813) is activated if the flowing gravity measured by the station densitometer exceeds this preset rate of change.
3
INFO - See the previous chapter for a description of batching features of the Omni flow computer.
_______________
This entry represents the Line Pack Delay and displays only when a Station Density I/O Point has been assigned. In many cases, the station densitometer that detects the product interfaces is 3 installed many net barrels (or net m ) in advance of the metering skid to provide prior warning of a product change. Enter the Line Pack Delay as the quantity of net barrels or net m between the product interface detector densitometer or gravitometer and the valve manifold used to end the batch. A Delayed 3 Gravity Rate of Change Flag (database point 1814) is set when this number of barrels or m has been measured after the Product Interface Flag (database point 1813) is activated; i.e., a line pack delay is counted down to zero when a product interface is detected.
3
_______________
This entry represents the Gravity Sample Time and displays only when a Station Density I/O Point has been assigned. It is used with the previous entry to determine the gravity rate of change. Estimate the minimum amount of time (in seconds) it takes for a product change to be complete and set this timer by entering approximately 1/4 to 1/3 of that time. False triggering of the product interface detection flag can be eliminated by ensuring that any density change must exist for at least this many seconds.
20/24.71 w 04/98
2-35
Input #1
Input #2
Input #3
Input#4
Low Limit
_______
_______
_______
_______
Enter thhe auxiliary input signal value below which the Low Alarm activates. The Transducer Failed Low Alarm activates when the auxiliary input signal falls 5% below this limit.
High Limit
_______
_______
_______
_______
Enter the auxiliary input signal value above which the High Alarm activates. The Transducer Failed High Alarm activates when the auxiliary input signal rises 5% above this limit.
{L2} Override
_______
_______
_______
_______
Enter the value (in engineering units) which will be substituted for the transducer value depending, on the override code selected. An * displayed along side of the value indicates that the override value is substituted.
_______
_______
_______
_______
Enter the Override Code which represents the strategy used regarding each auxiliary input override value: 0=Never use override code, 1=Always use override code, 2=Use override code on transmitter failure, 3=On transmitter failures use last hour's average.
Auxiliary Input Setup via the Random Access Method - Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and Select Group Entry screen will appear. Then press [Analysis] [Input] [Enter] or [Analysis] [Input] [n] [Enter] (n = Auxiliary Input # 1, 2, 3 or 4). Use [] / [] keys to scroll.
{L1} at 4mA*
_______
_______
_______
_______
Enter the value (in engineering units) that produces a transmitter output of 4mA or 1vol, or LRV of Honeywell Smart Transmitters t.
{L1} at 20mA*
_______
_______
_______
_______
Enter the value (in engineering units) that produces a transmitter output of 20mA or 5 Volts, or URV of Honeywell Smart Transmitters.
_______
_______
_______
_______
This entry only applies to Honeywell digital transmitters connected to an H Type combo module. The process variable (I.e., temperature/pressure) is filtered by the transmitter before being sent to the flow computer. The time constant used depends on this entry. For Differential Pressure/Pressure Transmitters, enter the selected Damping Code: 0=0 sec, 1=0.16 sec, 2= 0.32 sec, 3=0.48 sec, 4=1.00 sec, 5=2.00 sec, 6=4.00 sec, 7=8.00 sec, 8=16.00 sec, 9=32.00 sec. For Temperature Transmitters, enter the selected Damping Code: 0=0 sec, 1=0.3 sec, 2=0.7 sec, 3=1.5 sec, 4=3.1 sec, 5=6.3 sec, 6=12.7 sec, 7-25.5 sec, 8=51.5 sec, 9=102.5 sec.
Note:
2-36
20/24.71 04/98
Volume 3
2.8.
INFO - The first menu, 'Misc Configuration', should always be completed first as these entries specify the number and type of input and output devices connected to the flow computer; i.e., the menus following the 'Misc Configuration' menu do not ask for configuration data unless a transducer has been defined. Flow Computer Configuration via the Menu Selection Method It is best to use this method when programming an application for the first time as every possible option and variable will be prompted. Once a computer is in operation and you become familiar with the application you can decide to use the faster Random Access Method described below. Once you have finished entering data in a setup submenu, press the [Prog] key to return to the Select Group Entry screen. Proceed as described in this manual for each setup option. Meter Run Setup via the Random Access Method Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press [Meter] [n] [Enter] (n = Meter Run # 1, 2, 3 or 4). Use [] / [] keys to scroll. Alternate Access to Meter Run Settings from Meter Station Setup - After entering the Meter Station Settings, without exiting, press the [] key and you will scroll down through each Meter Run setup entry.
2.8.1.
Applying the Menu Selection Method (see sidebar), in the Select Group Entry screen (Program Mode) press [Setup] [Enter] and a menu similar to the following will be displayed:
2.8.2.
{L1} Meter ID
Enter the ID of the flowmeter (up to 8 alphanumeric characters) for each meter run. This ID usually appears on reports.
Flow Low
Enter the flow rate for each meter run below which the Flow Low Alarm (database point 1n21) activates. The Low Low Alarm (database point 1n20) activates when the flow rate falls 5% below this limit.
Flow High
Enter the flow rate for each meter run above which the Flow High Alarm (database point 1n22) activates. The High High Alarm (database point 1n23) activates when the flow rate rises 5% below this limit.
{L1} G Fullscal
Enter the gross flow rate at full-scale for each meter run. Sixteen-bit integer variables representing meter run gross and net flow rate are included in the database at 3n42 and 3n40 respectively. These variables are scaled using this entry and stored as percentage of full scale with a resolution of 0.1% (i.e., 0 to 1000 = 0% to 100.0%)
{L1} M Fullscal
Enter the mass flow rate at full-scale for each meter run. A 16-bit integer variable representing meter run mass flow rate is included in the database at 3n44. This variable is scaled using this entry and stored as percentage of full scale with a resolution of 0.1% (i.e., 0 to 1000 = 0% to 100.0%)
Enter the Active Frequency Threshold for each meter run. Flow meter pulse frequencies equal or greater than this threshold will cause the Meter Active Flag (1n05) to be set. By using any Boolean statement you can use this flag bit to enable and disable totalizing by controlling the Disable Meter Run Flags (Modbus database points 1736, 1737, 1738 & 1739). Example: 1030:1736=/1105 Turn off Meter #1 flow if not greater than Active Frequency.
20/24.71 04/98
2-37
Chapter 2
INFO - Characters in { } refer to password levels. Characters in [ ] refer to key presses. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Some of these entries may not appear on the display or in OmniCom. Depending on the various configuration settings of your specific metering system, only those configuration options which are applicable will be displayed.
{L1} ErrThreshold
This entry will display only when Dual Pulse is selected under Config Meter Runs (Misc Setup). It applies only when a 'E' combo module is fitted and 'Pulse Fidelity Checking' is enabled. Enter the Pulse Fidelity Error Check Threshold (in Hz) for each meter run. To eliminate bogus alarms and error count accumulations, the dual pulse error checking functions are disabled until the sum of both pulse trains exceeds the pulses per seconds entered for this setting. Example: Entering 50 for this threshold means that the dual pulse error checking will be disabled until both A and B channels of the flowmeter pick-offs are providing 25 pulses per second each.
{L1} ErrCounts
This entry will display only when Dual Pulse is selected under Config Meter Runs (Misc Setup). It applies only when a 'E' combo module is fitted and 'Pulse Fidelity Checking' is enabled. Enter the maximum number of error pulses allowed in one transaction for each meter run. The alarm points are: q q q q 1n48 1n49 1n50 1n51 A/B Comparitor Error Detected A Channel Failed B Channel Failed A and B Channels not equal
The dual pulse A/B Comparitor Error Alarm (1n48) is activated when the accumulated error counts between the flowmeter channels exceeds this count threshold. Accumulated error counts are cleared for every batch. K-Factor Linearization Settings - Turbine and positive displacement flowmeters produce pulses proportional to the flow. The K factor is the quantity of pulses per unit volume 3 (barrels or m ) or mass (lb or kg) that each meter produces. These settings are used to calculate the gross flow rate and volume. TIP - Enter the viscosity linearization setting first and then return to configure the K Factor linearization.
________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________
2-38
20/24.71 w 04/98
Volume 3
Meter Run Setup via the Random Access Method Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press [Meter] [n] [Enter] (n = Meter Run # 1, 2, 3 or 4). Use [] / [] keys to scroll.
Meter #1
Meter #2
Meter #3
Meter #4
{L1A} K-Factor #1
This entry applies for simple flow-based linearization of K Factor; i.e., when none is selected for Flow Rate/Viscosity Linearization (see sidebar and Viscosity Linear entry below). Enter the K Factors for each meter run. In this case, up to 12 K Factors and the associated flowmeter pulse frequencies are entered per meter run to define the K Factor Curve. The flow computer will continuously monitor the flowmeter pulse frequency and calculate gross flow based on and interpolated K Factor derived from the entered data points. Use only K Factor #1 in cases where flowmeter linearizing is not required.
Freq Point 1
Enter the flowmeter pulse frequency associated with the corresponding K Factor. The frequency points must be entered lowest to highest (Hz).
K-Factor #2 Freq Point 2 K-Factor #3 Freq Point 3 K-Factor #4 Freq Point 4 K-Factor #5 Freq Point 5 K-Factor #6 Freq Point 6 K-Factor #7 Freq Point 7 K-Factor #8 Freq Point 8 K-Factor #9 Freq Point 9 K-Factor #10 Freq Point 10 K-Factor #11 Freq Point 11 K-Factor #12 Freq Point 12
________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________
20/24.71 04/98
2-39
Meter #1
Meter #2
Meter #3
Meter #4
Enter [Y] to enable the auto-proving feature. Enter [N] to disable auto-proving. Enabling the autoprove function will cause the flowmeter to be automatically proved on flow rate changes and after a meter has been out of service. The auto-prove enable is cancelled whenever a meter fails an automatic prove on 10 consecutive attempts.
Enter [Y] to apply the meter factor in the net and mass flow equations. Enter [N] to ignore the meter factor in flow calculations; nonetheless, it will still appear on all reports.
This entry applies when Flow Rate/Viscosity Linearization is selected (see Viscosity Linear entry below). Enter [Y] to apply the Linearization Correction Factor (LCF) to gross flow rate and gross totals. Enter [N] if the LCF is not to be applied. The calculation of the gross indicated volume for each option is as follows: q If Yes is selected Gross = (Flowmeter Pulses/ Flowmeter K Factor) x LCF q If No is selected Gross = Flowmeter Pulses/ Flowmeter K Factor
In some cases, the flowmeter may be fitted with a mechanical or electronic temperature compensator. Enter [Y] for the Omni Flow Computer to set the temperature correction (VCF) to 1.0000 in all equations. Enter [N] if the meter provides gross uncompensated pulses.
Select the auxiliary input or other source to be used to input the S&W % for each meter run: 0=None, 1=Use Auxiliary Input #1, 2= Use Auxiliary Input #2, 3= Use Auxiliary Input #3, 4= Use Auxiliary Input #1; 5=Modbus Direct. The flow computer will use this input to determine Net Standard Volume (S&W corrected volume). TIP - Enter the viscosity linearization setting first and then return to configure the K Factor linearization.
Select the source of the viscosity value for the LCF for each meter run: 0=None, 1=Use Auxiliary Input #1, 2= Use Auxiliary Input #2, 3= Use Auxiliary Input #3, 4= Use Auxiliary Input #1; 5=Modbus Direct.
Enter [Y] to select a Helical Turbine Flowmeter. Enter [N] to select a Positive Displacement (PD) Flowmeter. The algorithm used to linearize the flowmeter for flow and viscosity effects is different depending on whether the flowmeter is a helical turbine type or a PD type.
Enter the model number of the flowmeter (up to 8 alphanumeric characters). This entry usually appears on the prove report.
Enter the size of the flowmeter (up to 8 alphanumeric characters). This entry usually appears on the prove report.
Enter the serial number of the flowmeter (up to 8 alphanumeric characters). This entry usually appears on the prove report.
2-40
20/24.71 w 04/98
Volume 3
2.9.
INFO - The first menu, 'Misc Configuration', should always be completed first as these entries specify the number and type of input and output devices connected to the flow computer; i.e., the menus following the 'Misc Configuration' menu do not ask for configuration data unless a transducer has been defined. Flow Computer Configuration via the Menu Selection Method It is best to use this method when programming an application for the first time as every possible option and variable will be prompted. Once a computer is in operation and you become familiar with the application you can decide to use the faster Random Access Method described below. Once you have finished entering data in a setup submenu, press the [Prog] key to return to the Select Group Entry screen. Proceed as described in this manual for each setup option. Meter Temperature Setup via the Random Access Method - Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press [Temp] [Enter], or [Temp] [Meter] [n] [Enter] or [Meter] [n] [Temp] [Enter] (n = Meter Run # 1, 2, 3 or 4). Use [] / [] keys to scroll.
2.9.1.
Applying the Menu Selection Method (see sidebar), in the Select Group Entry screen (Program Mode) press [Setup] [Enter] and a menu similar to the following will be displayed:
2.9.2.
Low Limit
Enter the temperature below which the flowmeter low alarm activates. Transducer values 5% below this entry fail to low.
High Limit
Enter the temperature above which the flowmeter high alarm activates. Transducer values 5% above this entry fail to high.
{L2} Override
Enter the temperature value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
{L1} at 4mA*
Enter the temperature engineering units that the transmitter outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
{L1} at 20mA*
Enter the temperature engineering units that the transmitter outputs at 20mA or 5 Volts, or URV of Honeywell Smart Transmitters.
Note:
20/24.71 04/98
2-41
Chapter 2
2.9.3.
Meter Density Temperature Setup via the Random Access Method To access these settings, in the Program Mode press [Density] [Temp] [Enter]. INFO - The Density Temperature sensor is used to compensate for temperature expansion effects which effect the periodic time of oscillation of the densitometer. It is also used when desired to calculate the density of the liquid to reference temperature using API 2540; Table 23, 23A or 23B.
Low Limit
Enter the temperature below which the densitometer low alarm activates. Transducer values 5% below this entry activate the transducer fail low alarm.
High Limit
Enter the temperature above which the densitometer high alarm activates. Transducer values 5% above this entry activate the transducer fail high alarm.
{L2} Override
Enter the temperature value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
Note:
{L1} at 4mA*
Enter the temperature engineering units that the transducer outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
{L1} at 20mA*
Enter the temperature engineering units that the transducer outputs at 20mA or 5volt, or URV of Honeywell Smart Transmitters.
2.9.4.
Prover Temperature Setup via the Random Access Method - Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press [Prove] [Temp] [Enter] or [Temp] [Prove] [Enter]. Use [] / [] keys to scroll.
Low Limit
___________
___________
Enter the temperature below which the prover low alarm activates. Transducer values 5% below this entry activate the transducer fail low alarm.
High Limit
___________
___________
Enter the temperature above which the prover high alarm activates Transducer values 5% above this entry activate the transducer fail high alarm.
{L2} Override
___________
___________
Enter the temperature value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
___________
___________
Enter the Override Code strategy: 0=Never use override code, 1=Always use override code, 2=Use override code on transmitter failure, 3=On transmitter failures use last hour's average.
2-42
20/24.71 04/98
Volume 3
INFO - Characters in { } refer to password levels. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
{L1} @ 4mA*
___________
___________
Enter the temperature engineering units that the transducer outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
{L1} @ 20mA*
___________
___________
Enter the temperature engineering units that the transducer outputs at 20mA or 5volt, or URV of Honeywell Smart Transmitters.
___________
___________
This entry only applies to Honeywell digital transmitters connected to an H Type combo module. The process variable (I.e., temperature) is filtered by the transmitter before being sent to the flow computer. The time constant used depends on this entry. For Temperature Transmitters, enter the selected Damping Code: 0=0 sec, 1=0.3 sec, 2=0.7 sec, 3=1.5 sec, 4=3.1 sec, 5=6.3 sec, 6=12.7 sec, 7-25.5 sec, 8=51.5 sec, 9=102.5 sec.
2.9.5.
Low Limit
Enter the temperature below which the prover low alarm activates. Transducer values 5% below this entry activate the transducer fail low alarm.
High Limit
___________
___________
Enter the temperature above which the prover high alarm activates. Transducer values 5% above this entry activate the transducer fail high alarm.
{L2} Override
___________
___________
Enter the temperature value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
___________
___________
Enter the Override Code strategy: 0=Never use override code, 1=Always use override code, 2=Use override code on transmitter failure, 3=On transmitter failures use last hour's average.
{L1} at 4mA*
___________
___________
Enter the temperature engineering units that the transducer outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
{L1} at 20mA*
___________
___________
Enter the temperature engineering units that the transducer outputs at 20mA or 5volt, or URV of Honeywell Smart Transmitters.
___________
___________
This entry only applies to Honeywell digital transmitters connected to an H Type combo module. The process variable (I.e., temperature) is filtered by the transmitter before being sent to the flow computer. The time constant used depends on this entry. For Temperature Transmitters, enter the selected Damping Code: 0=0 sec, 1=0.3 sec, 2=0.7 sec, 3=1.5 sec, 4=3.1 sec, 5=6.3 sec, 6=12.7 sec, 7-25.5 sec, 8=51.5 sec, 9=102.5 sec.
20/24.71 w 04/98
2-43
Chapter 2
Low Limit
Enter the pressure below which the flowmeter low alarm activates. Transducer values 5% below this entry fail to low.
High Limit
Enter the pressure above which the flowmeter high alarm activates. Transducer values 5% above this entry fail to high.
{L2} Override
Enter the pressure value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
{L1} at 4mA*
Enter the pressure engineering units that the transmitter outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
{L1} at 20mA*
Enter the pressure engineering units that the transmitter outputs at 20mA or 5 Volts, or URV of Honeywell Smart Transmitters.
2-44
20/24.71 04/98
Volume 3
Station
Meter #1
Meter #2
Meter #3
Meter #4
Low Limit
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
Enter the pressure below which the densitometer low alarm activates. Transducer values 5% below this entry activate the transducer fail low alarm.
High Limit
Enter the pressure above which the densitometer high alarm activates. Transducer values 5% above this entry activate the transducer fail high alarm.
Meter Density Pressure Setup via the Random Access Method - To access these settings, in the Program Mode press [Density] [Press] [Enter]. INFO - The Density Pressure sensor is used to compensate for pressure effects which effect the periodic time of oscillation of the densitometer. It is also used when desired to calculate the density of the liquid at the densitometer to equilibrium pressure using API 2540 MPMS 11.2.1 or 11.2.2.
{L2} Override
Enter the pressure value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
{L1} at 4mA*
Enter the pressure engineering units that the transducer outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
{L1} at 20mA*
Enter the pressure engineering units that the transducer outputs at 20mA or 5volt, or URV of Honeywell Smart Transmitters.
Note:
Inlet
Outlet
Low Limit
___________
___________
Enter the pressure below which the prover low alarm activates. Transducer values 5% below this entry activate the transducer fail low alarm.
High Limit
___________
___________
Enter the pressure above which the prover high alarm activates Transducer values 5% above this entry activate the transducer fail high alarm.
{L2} Override
___________
___________
Enter the pressure value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
___________
___________
Enter the Override Code strategy: 0=Never use override code, 1=Always use override code, 2=Use override code on transmitter failure, 3=On transmitter failures use last hour's average.
20/24.71 w 04/98
2-45
Chapter 2
{L1} at 4mA
Enter the pressure engineering units that the transducer outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
{L1} at 20mA*
Enter the pressure engineering units that the transducer outputs at 20mA or 5volt, or URV of Honeywell Smart Transmitters.
___________
___________
This entry only applies to Honeywell digital transmitters connected to an H Type combo module. The process variable (I.e., pressure) is filtered by the transmitter before being sent to the flow computer. The time constant used depends on this entry. For Differential Pressure/Pressure Transmitters, enter the selected Damping Code: 0=0 sec, 1=0.16 sec, 2= 0.32 sec, 3=0.48 sec, 4=1.00 sec, 5=2.00 sec, 6=4.00 sec, 7=8.00 sec, 8=16.00 sec, 9=32.00 sec.
___________
Engineering units that the transmitter outputs at 4mA or 1volt or LRV of Honeywell Smart Transmitters. The plenum pressure applies only to Brooks compact provers.
___________
Engineering units that the transmitter outputs at 20mA or 5 Volts or URV of Honeywell Smart Transmitters. The plenum pressure applies only to Brooks compact provers.
___________
This entry only applies to Honeywell digital transmitters connected to an H Type combo module. The process variable (I.e., pressure) is filtered by the transmitter before being sent to the flow computer. The time constant used depends on this entry. For Differential Pressure/Pressure Transmitters, enter the selected Damping Code: 0=0 sec, 1=0.16 sec, 2= 0.32 sec, 3=0.48 sec, 4=1.00 sec, 5=2.00 sec, 6=4.00 sec, 7=8.00 sec, 8=16.00 sec, 9=32.00 sec.
2-46
20/24.71 w 04/98
Volume 3
Inlet
Outlet
Low Limit
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
___________
___________
Enter the pressure below which the prover densitometer low alarm activates. Transducer values 5% below this entry activate the transducer fail low alarm.
High Limit
___________
___________
Enter the pressure above which the prover densitometer high alarm activates. Transducer values 5% above this entry activate the transducer fail high alarm.
Prover Density Pressure Setup via the Random Access Method - To access these settings, in the Program Mode press [Prove] [Density] [Press] [Enter]. INFO - The Density Pressure sensor is used to compensate for pressure effects which effect the periodic time of oscillation of the densitometer. It is also used when desired to calculate the density of the liquid at the densitometer to equilibrium pressure using API 2540 MPMS 11.2.1 or 11.2.2.
{L2} Override
___________
___________
Enter the pressure value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
___________
___________
Enter the Override Code strategy: 0=Never use override code, 1=Always use override code, 2=Use override code on transmitter failure, 3=On transmitter failures use last hour's average.
{L1} at 4mA*
___________
___________
Enter the pressure engineering units that the transducer outputs at 4mA or 1volt or LRV of Honeywell Smart Transmitters.
{L1} at 20mA*
___________
___________
Enter the pressure engineering units that the transducer outputs at 20mA or 5volt or URV of Honeywell Smart Transmitters.
___________
___________
This entry only applies to Honeywell digital transmitters connected to an H Type combo module. The process variable (I.e., pressure) is filtered by the transmitter before being sent to the flow computer. The time constant used depends on this entry. For Differential Pressure/Pressure Transmitters, enter the selected Damping Code: 0=0 sec, 1=0.16 sec, 2= 0.32 sec, 3=0.48 sec, 4=1.00 sec, 5=2.00 sec, 6=4.00 sec, 7=8.00 sec, 8=16.00 sec, 9=32.00 sec.
Note:
20/24.71 w 04/98
2-47
Chapter 2
These entries apply if an analog gravitometer or densitometer is specified during the 'Config Meter Run' in 'Misc. Setup'. They are not available when using API or Specific Gravity gravitometers. Enter the Pycnometer Density correction factor (Limit: 0.8 to 1.2). (Usually very close to 1.0000).
Low Limit
Enter the gravity/density below which the prover densitometer low alarm activates. Transducer values 5% below this entry activate the transducer fail low alarm.
High Limit
Enter the gravity/density above which the prover densitometer high alarm activates. Transducer values 5% above this entry activate the transducer fail high alarm.
{L2} Override
Enter the gravity/density value that is substituted for the live transducer value, depending on the override code. An * displayed along side of the value indicates that the override value is substituted.
{L1} at 4 mA
These entries apply if an analog gravitometer or densitometer is specified during the 'Config Meter Run' in 'Misc. Setup'. Engineering units that the transmitter outputs at 4mA or 1volt, or LRV of Honeywell Smart Transmitters.
2-48
20/24.71 04/98
Volume 3
{L1} at 20 mA
Meter Specific Gravity/Density Setup via the Random Access Method - Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then enter the key press sequence that corresponds to the options you want to configure: Specific Gravity/API: To access these settings, press [S.G./API] [Enter] or [S.G./API] [Meter] [n] [Enter] or [Meter] [n] [S.G./API] [Enter]. Density: To access these settings, press [Density] [Enter] or [Density] [Meter] [n] [Enter] or [Meter] [n] [Density] [Enter]. Digital Densitometers: To access these settings, press [Factor] [Density] [Meter] [n] [Enter] or [Density] [Factor] [Meter] [n] [Enter]. (n represents the meter run # 1, 2, 3 or 4). Note: Digital densitometers can only be configured via the Random Access Method. INFO - Densitometer constants are usually on a calibration certificate supplied by the densitometer manufacturer. Usually they are based on SI or metric units. For US customary applications you must ensure that the constants entered are based on gr/cc, F and PSIG. Constants are always displayed using scientific notation; e.g.: K0=-1.490205E+00 (gr/cc) To enter K0, press [Clear] and press [-1.490205] [Alpha Shift] [E] [+00] [Enter].
These entries apply if an analog gravitometer or densitometer is specified during the 'Config Meter Run' in 'Misc. Setup'. Engineering units that the transmitter outputs at 20mA or 5 Volts, or URV of Honeywell Smart Transmitters.
Digital Densitometers
The following entries are required if a digital densitometer is specified during the 'Config Meter Run' in the 'Misc. Setup' menu. There are three selections which refer to digital densitometers: 4 = Solartron, 5 = Sarasota, 6 = UGC. ({L1} Password Level required, except for the Correction Factor.) Solartron
Meter #1 Meter #2 Meter #3 Meter #4 Station
Correction Factor B________ ________ ________ ________ ________ K0 K1 K2 K18 K19 K20A K20B K21A K21B KR KJ Sarasota ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________
Meter #1 Meter #2 Meter #3 Meter #4 Station
Correction Factor B________ ________ ________ ________ ________ D0 T0 T coef T cal Pcoef Pcal ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________
20/24.71 w 04/98
2-49
Chapter 2
UGC
INFO - Characters in { } refer to password levels. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. Digital Densitometer Setup via the Random Access Method - To access these settings, in the Program Mode press [Factor] [Density] [Meter] [n] [Enter] or [Density] [Factor] [Meter] [n] [Enter] (n = Meter Run # 1, 2, 3 or 4).
Correction Factor B________ ________ ________ ________ ________ K0 K1 K2 TC Kt1 Kt2 Kt3 Pc Kp1 Kp2 Kp3 ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________ ________
2-50
20/24.71 w 04/98
Volume 3
Use the [ ]/[ ] (up/down arrow) keys to move the cursor to PID Control Setup and press [Enter] to access the submenu.
Operating Mode
Manual Valve (Y/N) _______ _______ _______ _______
Enter [Y] to adjust the valve open % and adjust using the []/[] keys. Enter [N] to change to AUTO mode.
_______
_______
_______
_______
Enter [Y] to use a local set point and adjust using the []/[] keys. Enter [N] for REMOTE set point mode.
Sec Set.Pt
_______
_______
_______
_______
Enter the value in engineering units for the set point of the secondary variable. The primary variable will be the controlled variable until the secondary variable reaches this set point. The secondary variable will not be allowed to drop below or rise above this set point, depending on the "Error Select" entry in the Config PID menu.
Tuning Adjustments
{L1} Primary Gain {L1} Pri. Rpts/Min _______ _______ _______ _______ _______ _______ _______ _______
Enter a value between 0.01 to 99.99 for the Primary Gain Factor (Gain=1/Proportional Band).
Enter a value between 0.0 and 40.00 for the Primary Integral Factor (Rpts/Min=1/Integral Factor the reciprocal of the reset period).
_______
_______
_______
_______
Enter a value between 0.01 to 99.99 for the Secondary Gain Factor (Gain=1/Proportional Band). The actual controller gain factor used when controlling the secondary variable is the product of this entry and the 'Primary Gain Factor'. Tune the primary control variable first and then use this entry to adjust for stable control of the secondary variable.
20/24.71 04/98
2-51
Chapter 2
INFO - Characters in { } refer to password levels. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
_______
_______
_______
_______
Enter a value between 0.0 and 40.00 for the Secondary Integral Factor (Rpts/Min=1/Integral Factor the reciprocal of the reset period).
{L1} Deadband %
_______
_______
_______
_______
Enter the dead band percent range. PID Control will only compensate for setpoint deviations out of this range. The control output will not change as long as the process input and the setpoint error (deviation) is within this dead band percentage limit range.
_______
_______
_______
_______
Enter the maximum percentage to which the valve movement is limited per 500 msec at start-up. st The control output is clamped at 0% until the 1 PID Permissive (PID #1-#4 database points 1722-1725) is set true. The control output % is then allowed to increase at the start-up ramp rate.
_______
_______
_______
_______
Enter the maximum percentage to which the valve movement is limited per 500 msec at shutdown. st When the 1 PID Permissive is lost, the control output will ramp-down towards 0% at the shutdown ramp rate. During the ramp-down phase, a 2 PID Permissive (PID #1-#4 database points 1752-1755) is nd used to provide a ramp hold function. If this 2 permissive is true, 100 msec before entering the ramp-down phase, the control output % will ramp-down and be held at the minimum ramp-down limit % (see the following entry) until it goes false. The control output will then immediately go to 0% (see sidebar).
nd
_______
_______
_______
_______
Enter the minimum percentage that the control output will be allowed to ramp down to. In many cases, it is important to deliver a precise amount of product. This requires that the control output be ramped to some minimum % and held there until the required delivery is complete. The control output is then immediately set to 0%.
Remote Setpoint
{L1} Low Limit _______ _______ _______ _______
Enter the engineering unit value below which the primary setpoint variable is not allowed to drop while in the remote setpoint mode.
_______
_______
_______
_______
Enter the engineering unit value above which the primary setpoint variable is not allowed to rise while in the remote setpoint mode.
_______
_______
_______
_______
Enter the engineering unit value of the remote setpoint at 4 mA (1 volt) input. You must set this and the following entry even if you do not intend to use a remote setpoint. They are used to determine the scaling of the primary controlled variable.
_______
_______
_______
_______
Enter the engineering unit value of the remote setpoint at 20mA (5 volt) input. You must set this and the previous entry even if you do not intend to use a remote setpoint. They are used to determine the scaling of the primary controlled variable, which is usually 2 times the normal operating setpoint setting.
2-52
20/24.71 w 04/98
_______
_______
_______
_______
If a secondary controlled variable is used, enter the value in engineering units of the variable which will represent zero.
_______
_______
_______
_______
Enter the value in engineering units of the secondary variable at controller full scale, which is usually 2 times the normal operating setpoint setting.
20/24.71 w 04/98
2-53
Chapter 2
Use the [ ]/[ ] (up/down arrow) keys to move the cursor to Prover Setup and press [Enter] to access the submenu.
_______________
Enter the maximum number of runs that will be attempted to achieve a complete prove sequence. This number must be between 2 and 99.
_______________
Enter the type of prover in use: 0=Unidirectional Pipe Prover, 1=Bi-directional Pipe Prover, 2=Unidirectional Compact Prover, 3=Bi-directional Small Volume Prover, 4=Master Meter, 5=2 Series Bi-directional Pipe Prover. Select the Unidirectional Compact [2] if you are using a Brooks Compact Prover. Select the Master Meter Method to compare meter 1, 2 or 3 against the master meter. Meter #4 is always the master meter. For Double Chronometry Proving use type 2 or 3.
{L2} Pv Volume
_______________
This entry does not apply when the prover type selected is a Uni-Compact. Enter the water draw volume of the prover at base temperature and pressure. Certain models of compact provers have different water draws, depending on whether the meters are upstream or downstream. This entry represents the round-trip volume for bidirectional provers and the downstream volume for compact provers. When using the Master Meter Method, enter the minimum volume that must flow through the master meter (Meter #4) for each prove run.
# Passes to Avg
_______________
This entry applies to Unidirectional and Bi-directional compact provers only. Enter the number of single passes that will be averaged to make each run when using the pulse interpolation method. Valid entries are 1 through 25. A pass is round trip when using a bi-directional prover.
2-54
20/24.71 04/98
Volume 3
Exp. Coeff
INFO - Characters in { } refer to password levels. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
This entry applies to unidirectional compact provers only (except Brooks SVP see following setting). Enter the squared coefficient of thermal expansion for any switch rod components which may affect the water draw volume of the compact prover. This Thermal Expansion Coefficient is used to calculate the CTSP factor for the compact prover: q For US Units: Carbon Steel = 0.0000124; Stainless Steel = 0.0000177. q For Metric Units: Carbon Steel = 0.0000223; Stainless Steel = 0.0000319.
Coef Invar
_______________
This entry applies to Brooks Compact Provers only. This prover uses an invar rod to separate the optical detector switches. The rod has a coefficient of 0.0000008 per F (US units) or 0.0000014 per C (metric units).
Plenum Con
_______________
This entry applies to Brooks Compact Provers only. Enter the Nitrogen Spring Plenum Pressure Constant for used to calculate the plenum pressure needed to operate a the Brooks Compact Prover. This pressure is related to the prover line pressure at the time of proving: Plenum Pressure = (Line Pressure / Plenum Constant) + 60 Psig The plenum constant depends on the size of the Brooks Compact Prover. Valid values are: SIZE 8-inch 12-inch Mini 12-inch Standard PLENUM CONSTANT 3.50 3.20 3.20 SIZE 18-inch 24-inch Larger PLENUM CONSTANT 5.00 5.88 Refer to Brooks
Deadband %
_______________
This entry applies to Brooks Compact Provers only. Enter the Plenum Pressure Deadband %. The Brooks Compact Prover requires that the plenum pressure be maintained within certain limits. The flow computer calculates the correct plenum pressure at the beginning of each prove sequence and will charge or vent nitrogen until the measured plenum pressure is within the specified deadband %.
{L1} Up Volume
_______________
This entry applies to compact provers only. Enter the upstream water draw volume at base temperature and pressure, if applicable.
Down Vol
_______________
This entry applies to compact provers only. Enter the downstream water draw volume at base temperature and pressure, if applicable.
OverTravel
_______________
This entry does not apply to Master Meter proving. Enter the estimated amount of flow that the sphere or piston displaces after activating the first detector switch, multiplied by 1.25.
_______________
Enter the time in seconds before the prove is aborted due to prover inactivity. Make sure you allow enough time for the sphere or piston to travel between detector switches at the lowest flow rate expected. When using the Master Meter Method, allow enough time for the amount of flow to pass through the master meter at the lowest expected flow rate.
_______________
This entry is not applicable to Master Meter proving. Enter the internal diameter of the prover tube in inches or mm.
_______________
This entry is not applicable to Master Meter proving. Enter the wall thickness of the prover tube, which is used to calculate the CPSP factor
20/24.71 w 04/98
2-55
Chapter 2
{L1} Elast
Prover Setup via the Random Access Method Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press Prove] [Setup] [Enter] and use [] / [] keys to scroll.
This entry is not applicable to Master Meter proving. Enter the Prover Tube Modulus of Elasticity used to calculate the CPSP factor. u For US Units: Mild Steel = 3.0E7; Stainless Steel = 2.8E7 to 2.9E7. u For Metric Units: 2.07E8 or 1.93E8 to 2.0E8.
_______________
This entry is not applicable to Compact Provers and Master Meter proving. Enter the Prover Tube Cubical Coefficient of Thermal Expansion for full sized pipe provers, used to calculate the CTSP factor. u For US Units: Mild Steel = 0.0000186; Stainless Steel = 0.0000265. u For Metric Units: Mild Steel = 0.0000335; Stainless Steel = 0.00000477.
_______________
This entry is not applicable to Master Meter proving. Enter the atmospheric pressure in Psig or kPag at which the prover was water drawn.
_______________
This entry is not applicable to Master Meter proving. Enter the Base Temperature in F or C at which the prover was water drawn. This entry is used to calculate CTSP.
{L2} Stability Sc
_______________
Enter the Stability Check Sample Time in seconds, used to calculate the rate of change of temperature and flow rate at the prover or master meter. The prove sequence will not start until the temperature and flow rate are stable.
_______________
Enter the temperature change allowed during the stability sample time (see previous entry). The change in temperature per sample period must be less than this value for the temperature to be considered stable enough to start a prove.
_______________
Enter the flow rate change allowed during the stability sample time (see previous two entries). The change in flow rate per sample period must be less than this value before the flow rate is considered to be stable enough to start a prove.
_______________
Enter the prover-to-meter temperature range allowable after the temperature and flow rate have stabilized. The temperature at the meter and the prover must be within this limit or the prove sequence attempt will be aborted.
{L2} MF Repeatability ?
_______________
Enter for the run repeatability calculation based on: 0= run counts, 1= run calculated meter factor. Run counts repeatability is a more stringent test but may be difficult to achieve due to changing temperature and pressure during the prove sequence. Calculating repeatability based upon the calculated meter factor takes into account variations in temperature and pressure, and may be easier to achieve.
_______________
Enter the maximum allowable percentage deviation between run counts or run meter factors (depending on selection of previous entry). The deviation is calculated by comparing the high/low meter counts or meter factors based on their low point, as follows: Deviation = 100 (High - Low) / Low Point This deviation is always calculated using the meter factor when the Master Meter Method of proving is selected.
2-56
20/24.71 04/98
Volume 3
{L2} MF Devia %
INFO - Characters in { } refer to password levels. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
The prove meter factor (just calculated) is compared against the current meter factor and must be within this percentage range to be accepted as a valid meter factor.
_______________
Enter [Y] to automatically implement the new meter factor and store in the appropriate product file. Enter [N] to select not to automatically implement the meter factor determined from the prove.
{L2} Retroactive MF ?
_______________
If you selected to auto-implement the meter factor for the previous entry, enter [Y] to retroactively apply the Meter Factor from the beginning of the batch. The old meter factor will be back calculated out of the current batch and daily totals. The batch and daily totals will be recalculated using the new meter factor. Enter [N] to have the Meter Factor applied from this point on.
Flow Change %
_______________
This entry does not apply to Master Meter proving. Enter the Auto-Prove Flow Rate Change Percent Threshold. The Flow Rate Percent Change Flag will be set if the current flow rate differs from the last meter proving flow rate by more than this percent (i.e., a request for an auto-prove sequence will be flagged if the net/mass flow rate differs from the last proved rate by more than this percent, and remains outside this limit for the flow rate change period). A request for an automatic prove will only be made if both the Percent Change Flag and the Minimum Flow Change Flag are set (see following entry).
Flow Change
_______________
This entry does not apply to Master Meter proving. Enter the Minimum Flow Rate Change Threshold for automatic proving. The Minimum Flow Change Flag will be set if the current flow rate differs from the last meter proving flow rate by more than this amount. A request for an automatic prove will be made if both the Percent Change Flag and the Minimum Flow Change Flag are set (see previous entry). This entry eliminates unnecessary proves that would occur at low flow rates where the percentage change threshold would be a very small flow rate change.
F Stable Min
_______________
This entry does not apply to Master Meter proving. Enter the Flow Rate Stable Period in minutes, for auto-proving. A change in flow rate must be sustained for at least this period of time before an auto-prove sequence will be attempted.
Mtr Down Hr
_______________
This entry does not apply to Master Meter proving. Enter the Meter Shut-in Period in hours, for auto-proving. The need for an auto-prove will be flagged if a flowmeter is shut-in for more than this period of time.
Startup Pv
_______________
This entry does not apply to Master Meter proving. Enter the startup flow for auto-proving. This is the amount of flow which must occur after startup before an auto-prove is attempted, after a meter has been shut-in for more than the Meter Shut-in Period (see previous entry).
Max. Flow
_______________
This entry does not apply to Master Meter proving. Enter the Maximum Flow between Proves. This entry represents the maximum amount of flow that can occur before a meter will be flagged for an auto-prove sequence, if the flow remains stable and the meter is not shut-in
20/24.71 w 04/98
2-57
Chapter 2
Use the [ ]/[ ] (up/down arrow) keys to move the cursor to Product Setup and press [Enter] to access the submenu.
2.14.2.
Product Settings
Product #1
{L1} Name {L1} Table Select _______________ _______________
Enter the name of the product (up to 8 alphanumeric characters), right justified.
Enter the number that corresponds to the API or GPA table to use for the product: 0 = API 2540 Table 24A (US units) / Table 54A (metric units). 1 = API 2540 Table 24B (US units) / Table 54B (metric units). 2 = Table 24C (US units) / Table 54C (metric units). 3 = GPA TP16 (US units) / TP16M (metric units). 4 = Mass Calculation 5 = Propylene API 11.3.3.2 9US units) / 11.3.3.2M (metric units). 6 = E/P Mix. 7 = P/P Mix. 8 = Ethylene IUPAC 9 = Ethylene NIST 1045 10 = Ethylene API 2565/11.3.2. 11 = Carbon Dioxide CO2PAC 12 = Table 24 - 1952 Edition (US units) / Table 54 - 1952 Edition (metric units) 13 = ASTM D1550/1551 14 = ASTM D1555
_______________
This entry applies only to US units (Revision 20). It will appear depending on which table is selected above. Enter the API Gravity at reference conditions. It is used to calculate the Volume Correction Factor (VCF) and the Pressure Correction Factor (Cpl). The flow computer will accept any positive override value and use it as the API in calculations. The override gravity can also be entered as specific gravity (see next entry). To use the live measured density or gravity value (obtained from a densitometer/gravitometer) in the equations, enter any minus number. The flow computer will then correct the signal form the densitometer or gravitometer to 60F, if required (this may be flowing at flowing or reference conditions - see Meter Run I/O Point Configuration). Should the gravitometer fail, the flow computer can be made to use the absolute value of the API Gravity Override. If the override code in Grav/Density Setup is set to 5=On transmitter failure, use absolute value of override SG/API for this product.
2-58
20/24.71 04/98
Volume 3
{L2} Override SG
INFO - Characters in { } refer to password levels. TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer. INFO - The following data, rounded to 4 digits, is from GPA 2145-92 and TP16:
Product Ethane Propane HD5 S.G. .3562 .5070 .5010 .5050 .5100 Propylene .5228* Iso Butane .5629 .5650 n-Butane .5840 .5850 Iso Pentane .6247 n-Pentane .6311 n-Hexane .6638 Natural Gasolines .6650 n-Heptane .6882 n-Octane .7070 n-Nonane .7219 n-Decane .7342 kg/m 355.85 506.90 500.50 504.50 509.50 522.28* 562.34 564.44 583.42 584.42 624.08 630.48 663.14 664.34 687.52 706.30 721.19 733.48
3
This entry applies only to US units (Revision 20). It will appear depending on which table is selected above. You may enter an override gravity as either API or SG units when measuring crude oil or generalized refined products. The Computer will accept any positive override value and use it in the calculations. To use the live measured density or gravity value (obtained from a densitometer/gravitometer) in the equations, enter any minus number. The flow computer will then correct the signal form the densitometer or gravitometer to 60F, if required (this may be flowing at flowing or reference conditions - see Meter Run I/O Point Configuration). Should the gravitometer fail, the flow computer can be made to use the absolute value of the API Gravity Override. If the override code in Grav/Density Setup is set to 5=On transmitter failure, use absolute value of override SG/API for this product.
_______________
This entry applies only to metric units (Revision 24) depending on which table is selected above. 3 This is the density at reference conditions (kg/m at reference temperature). It is used to calculate the volume correction factor VCF and the pressure correction factor Cpl. Using a Live Densitometer Signal - Entering a value with a minus sign ahead of it causes the flow computer to use the live density signal to calculate the density at reference temperature. Using the Product Override if the Densitometer Fails - Selecting 'fail code 5' at the densitometer setup menu will cause the flow computer to stop using the live density signal should it fail, and substitute the absolute value of the density override entry as the reference density. E.g.: Entering -750 causes the computer to ignore the override and use the live densitometer signal as 3 long as the transducer is OK. A reference density of 750 kg/m will be used if the densitometer should fail.
_______________
This entry applies only to metric units (Revision 24 - Table 54C). Enter the base or reference temperature at which net corrected volumes represent equivalent volumes of liquid.
Alpha
Alpha Coefficient. This entry applies depending on which table is selected above. API 2540, Tables 24C/54C equations require you to enter a value for 'alpha'. This alpha value is used to calculate the volume correction factor 'VCF'. Enter the thermal expansion coefficient at reference temperature as 0.000xxxx.
* Propylene figures are derived from API 11.3.3.2. INFO - API 2540; Tables 23A or 23B (US), or 53A or 53B (metric); are also automatically used when applicable. Tables 24A and 53A apply to Generalized Crude Oils (SG range: 1.076-.6110; Dens range: 1075-610.4). Tables 24B and 53B apply to Generalized Products (SG range: 1.076-.6535; Dens range: 1075-652.8). GPA TP16 and TP16M apply to LPG/NGL Products (SG range: .637-.495 on Version 20, and 636.4-494.5 on Version 24 of the Omni. These calculation methods use API Chapter 11.2.1 or 11.2.2, and 11.2.1M or 11.2.2M to calculate the pressure correction factor Cpl.
F Fact
_______________
F Factor Override. This entry applies depending on which table is selected above. Enter 0.0 if you wish the flow computer to use API 11.2.1 or 11.2.2 to calculate the compressibility factor 'F' used in the Cpl equation. Enter the compressibility factor 'F' if you wish to override the API calculated value.
Vapor Pressure
_______________
Vapour Pressure Psia (abs) @ 100F (37.8C). This entry applies only when GPA TP16 is entered for table select. The GPA TP16 standard specifies that the equilibrium pressure of the flowing fluid be calculated according to GPA TP15. Two equations are specified. The first designed for mainly pure products such as propanes, butanes and natural gasolines requires no input data other than the temperature at flowing conditions and the specific gravity at reference conditions. The second improved correlation is suitable for use with more varied NGL mixes where different product mixes could have the same specific gravity but different equilibrium pressures. If you wish to use the improved second method enter the vapor pressure at 100F or 37.8C. Enter a minus number to use the normal TP15 method for propanes, butanes and natural gasolines.
20/24.71 w 04/98
2-59
Chapter 2
Meter Factors
_______
_______
_______
_______
Enter the meter factor to be used by this flowmeter whenever this product is flowing. This factor will be automatically updated whenever a meter factor is changed due to a manual entry or an automatic implementation after a successful prove sequence.
_______________
Density correction factor. Enter [0] to select Density Factor A to correct the densitometer. Enter [1] to select Density Factor B to correct the densitometer.
Product #2
Product Setup via the Random Access Method Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press [Product] [Enter] or [Product] [n] [Enter] (n = Product # 1, 2, 3, 4, 5, 6, 7 or 8). Use [] / [] keys to scroll.
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
Product #3
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
2-60
20/24.71 04/98
Volume 3 Product #4
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
Product #5
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
20/24.71 w 04/98
2-61
Chapter 2 Product #6
Product Setup via the Random Access Method Setup entries require that you be in the Program Mode. In the Display Mode press the [Prog] key. The Program LED will glow green and the Select Group Entry screen will appear. Then press [Product] [Enter] or [Product] [n] [Enter] (n = Product # 1, 2, 3, 4, 5, 6, 7 or 8). Use [] / [] keys to scroll.
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
Product #7
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
2-62
20/24.71 04/98
Volume 3 Product #8
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
Product #9
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
20/24.71 w 04/98
2-63
_______________
M.F. #2 M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
Product #11
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
2-64
20/24.71 w 04/98
_______________
M.F. #1 M.F. #2 M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
Product #13
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
20/24.71 w 04/98
2-65
_______________
M.F. #2 M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
Product #15
Name Table Select Override API (Rev 20) Override SG (Rev 20) Override Ref Dens (Rev 24) Ref Temperature (Rev 24) Alpha F Factor Vapor PSIA (ABS)
M.F. #1 M.F. #2
_______________
M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
2-66
20/24.71 w 04/98
_______________
M.F. #1 M.F. #2 M.F. #3 M.F. #4
_______
_______
_______
_______
_______________
20/24.71 w 04/98
2-67
Chapter 2
!
Use the [ ]/[ ] (up/down arrow) keys to move the cursor to Factor Setup and press [Enter] to access the submenu.
_______________
The flow averaging factor is the number of calculation cycles used to smooth the displayed flow rate. A number 1-99 will be accepted. (A calculation cycle is 500msec).
Alarm Deadband %
_______________
Nuisance alarms can occur when input variables spend any amount of time near the high or low alarm set points. These nuisance alarms can swamp the alarm log with useless alarms leaving no room for real alarms. This entry sets a percentage limit based on the 'high alarm' entry. A variable must return within the high/low alarm limits by more than this amount before the alarm is cleared. E.g.: High limit is 100F, Low limit is 20F, Alarm deadband is set to 2 percent. A transducer input which exceeded 100F will set the 'high alarm'. The transducer signal must drop 2 percent below the high alarm setpoint (98F) before the alarm will clear.
_______________
Atmospheric Pressure in PSIA (ABS). This is used to convert flowing pressure readings in Psig to absolute pressure units Psia for US Units, and for the metric version in absolute units in conformance to pressure (metric) units selected.
_______________
Roll All Totalizers. Totalizers within the computer can be rolled at 8 or 9 significant digits. Default value is 9 (0). This is a read-only entry. This entry can only be changed at the keypad of the flow computer.
2-68
20/24.71 04/98
Volume 3
_______________ _______________
Decimal Places for Correction Factors Appearing on Batch and Prove Reports
The following two entries determine the number of decimal places for the following factors: Ctlm, Ctlp, Cplm, Cplp, Ctsp, Cpsp, CCF. Meter Factor and Density Pycnometer factor remain fixed at 4. For STRICT adherence to API MPMS 12.2 (default) select 4 decimal places. This is the recommend selection. Selecting 5 decimal places causes the flow computer to perform the normal API internal rounding and truncating rules with the exception of the last round which is to 5 places. Selecting 6 decimal places causes the flow computer to perform no internal rounding and truncating and round the final result to 6 decimal places. Dec Factor Batch Report MF Decimal Batch Report Dec Factor Prove Report MF Decimal Prove Report _______________ _______________ _______________ _______________
Enter the number of decimal places required for factors to be displayed on the batch report.
Enter the number of decimal placesrequired for the meter factor appearing on the batch report.
Enter the number of decimal places required for factors to be displayed on the prove report.
Enter the number of decimal places required for the meter factor appearing on the prove report.
20/24.71 w 04/98
2-69
Chapter 2
Print Interval in Minutes. Enter the number of minutes between each interval report. Entering [0] will disable interval reports. The maximum allowed is 1440 minutes which will provide one interval report per 24-hour period.
_______________
Print Interval Start Time. Enter the start time from which the interval report timer is based (e.g.: Entering 01:00 with a Print Interval of 120 minutes will provide an interval report every odd hour only).
_______________
Daily Report Time. Enter the hour at which the daily report will print at the beginning of the contract day (e.g.: 07:00).
_______________
Enter [Y] to disable the Daily Report (default is 'N'). This simply blocks the report from printing. Data will still be sent to the historical buffers (last 8) and archive if archive is setup.
{L1} Daylight Start {L1} Daylight End {L1} Clr Daily at Batch
Daylight Savings Time Start. Enter the Day/Month/Year that daylight savings time begins.
Daylight Savings Time End. Enter the Day/Month/Year that daylight savings time ends.
Clear Daily at Batch. Enter [N] to provide 24 hour totals of all flow through the flowmeter regardless of what product is run. Select [Y] to clear the totalizers at the end of each batch. This would mean that the daily totalizers would not necessarily represent 24 hours of flow but the amount of flow since the last batch end or the daily report
2-70
20/24.71 04/98
Volume 3
{L1} Auto Hourly Batch ?
TIP - Use the blank lines provided next to each configuration option to write down the corresponding settings you entered in the flow computer.
Automatic Hourly Batch Select. Enter [Y] to automatically cause a batch end every hour on the hour. If customized reports are selected a batch end report will be printed. If default reports are selected no batch end report will be printed.
_______________
Automatic Weekly Batch Select. Enter a number 1 through 7 to automatically print a batch end report in addition to a daily report on a specific day of the week (0=No batch end, 1=Monday, 2=Tuesday, etc.).
_______________
Automatic Monthly Batch Select. Enter a number 1 through 31 to automatically print a batch end report in place of a daily report on a specific day of the month (0=No batch end).
_______________
Enter [0] when the computer is connected to a dedicated printer. If several computers are sharing a common printer, one computer must be designated as the master and must be assigned the number 1. The remaining computers must each be assigned a different Print Priority number between 2 and 12.
_______________
For slow printers without an input buffer, a number of null characterss can be sent after each carriage return or line feed. A number between 0-255 will be accepted. Set this to 0 if your printer supports hardware handshaking and you have connected pin 20 of the printer connector to terminal 6 of the flow computer (see Chapter 3).
_______________
Use Default Report Templates? Y/N. Entering [Y] instructs the flow computer to use the default report formats for Daily Batch End, Snapshot and Prover Reports. Enter [N] if you have downloaded your own custom report templates using the OmniCom program. Common Printer Control Codes Epson, IBM & Compatible: Condensed Mode= OF Cancel Condensed= 12 OKI Data Models: Condensed Mode= ID Cancel Condensed= IE HP Laser Jet II & Compatible: Condensed= 1B266B3253 Cancel Cond= 1B266B3053
{L1} Condensed
_______________
Condensed Print Mode Control String. Certain default report templates exceed 80 columns when the computer is configured for 4 meter runs and a station. Enter the hexadecimal character string which will put the printer into the condensed print mode. Data must be in sets of 2 characters (i.e., 05 not 5). Maximum 5 control characters.
{L1} Uncondens
_______________
Cancel Condensed (Normal) Print Mode Control String. Enter the hexadecimal character string which when sent to the printer will cancel the condensed print mode. Data must be in sets of 2 characters (i.e., 05 not 5) Maximum 5 control characters
_______________
Two lines of the display allow entry of the Company Name. On each line enter a maximum of 19 characters and press [Enter]. Both lines are concatenated and appear on all reports.
{L1} Location
_______________
Two lines of the display allow entry of the station location Name. On each line enter a maximum of 19 characters and press [Enter]. Both lines are concatenated and appear on all reports.
20/24.71 w 04/98
2-71
Volume 3
3. User-Programmable Functions
3.1. Introduction
The computer performs many functions, displays and prints large amounts of data, but there are always some application-specific control functions, calculations or displays that cannot be anticipated. The Omni Flow Computer incorporates several programmable features that enable the user to easily customize the computer to fit a specific application. o o o o User Programmable Boolean Flags and Statements User Programmable Variables and Statements User Configurable Display Screens User Customized Report Templates
The first three Items are explained here. The last item requires the use of the OmniCom PC configuration software that comes with the flow computer.
3.2.
3.2.1.
A Boolean point is simply a single bit register within the computer (sometimes called a flag) which has only two states, On or Off (True or False, 1 or 0). These Boolean flags or points are controlled and/or monitored by the flow computer and represent alarms, commands and status points. Each Boolean point is given an identifying number within the data base of the computer allowing the state (On or Off) to be monitored or modified by assigning that Boolean point to a physical digital I/O point or accessing it via a communication port. A maximum of 24 physical digital I/O points are available for monitoring limit switches, status signals or controlling relays or lamps.
20/24.71 w 04/98
3-1
Chapter 3
Boolean points are numbered as follows:
INFO - The 4-digit point numbers referred to in this chapter are Modbus index numbers used to identify each variable (Boolean or other) within the Modbus database.
User-Programmable Functions
1001 through 1024 1025 through 1088 1089 through 1099 1100 through 1199 1200 through 1299 1300 through 1399 1400 through 1499 1500 through 1699 1700 through 1799 1800 through 1899 1900 through 1999* 2100 through 2199 2200 through 2299 2300 through 2399 2400 through 2499 2100 through 2199 2600 through 2623 2700 through 2759 2800 through 2899
Physical Digital I/O Points 1 through 24 Programmable Boolean Points (64 total) Programmable Pulse outputs (11 total) Meter Run #1 Boolean Points (Alarms, Status etc.) Meter Run #2 Boolean Points (Alarms, Status etc.) Meter Run #3 Boolean Points (Alarms, Status etc.) Meter Run #4 Boolean Points (Alarms, Status etc.) Scratchpad Storage for Results of Boolean Statements Command or Status Inputs Station Boolean Flags (Alarms, Status etc.) Prover Boolean Flags (Alarms, Status etc.) Meter Run #1 Totalizer Roll-over Flags Meter Run #2 Totalizer Roll-over Flags Meter Run #3 Totalizer Roll-over Flags Meter Run #4 Totalizer Roll-over Flags Meter Run #1 Totalizer Roll-over Flags Miscellaneous Station Boolean Points (Alarms, Status etc.) Miscellaneous Boolean Command Points Station Totalizer Flags
3-2
20/24.71 w 04/98
Volume 3
3.2.2.
The sign of analog or calculated variables can also be used in a Boolean statements by simply specifying the point number. The Boolean value of the variable is 'true ' if it is positive and 'false' if it has a negative value.
3.2.3.
Each Boolean statement consists of up to 7 variables optionally preceded by the Boolean 'NOT' function and separated by one of the Boolean functions 'AND', 'OR', 'Exclusive OR' or 'EQUAL' . The following symbols are used to represent the functions:
Function NOT AND OR EX OR EQUAL IF GOTO MOVE COMPARE Symbol / & + * = ) 'G' : %
The '=' function allows a statement to be used to change the state of the Boolean point on the left of the equal sign (usually a command point). Evaluation precedence is left to right.
20/24.71 w 04/98
3-3
Chapter 3
User-Programmable Functions
To program the Boolean points proceed as follows: From the Display Mode press [Prog] [Setup] [Enter] and the following menu will be displayed: *** Misc. Setup *** Password Maint?(Y)_ Check Modules ?(Y) Config Station ? (Y) Config Meter "n" Config Prove ? (Y) Config PID ? (Y) Config D/A Out "n" Front Panel Counters Program Booleans ? Program Variables ? User Display ? "n" Scroll down to 'Set Boolean ? (Y)' and enter [Y]. Assuming that no Booleans are as yet programmed, the display shows: Boolean Point #10xx 25: _ 26: 27: Note that the cursor is on the line labeled 25: At this point enter the Boolean equation that will cause Boolean point 1025 to be ON (TRUE).
INFO - Points 1005 and 1006 reflect the current status of physical I/O Points 05 and 06 which could be inputs connected to the outside world or outputs controlling relays, etc.
For example, to turn Boolean 1025 ON whenever Boolean 1005 is OFF, OR whenever 1006 is ON, enter [/1005+1006] (note the use of the '/' to indicate the 'NOT' function). Boolean Point #10XX 25: /1005+1006 26: _ 27 Boolean 1025 could then be used in the statement following which defines Boolean 1026. For example, by including Boolean 1106 which indicates that meter #1 is being proved (see following page), Boolean 1026 will be ON whenever 'Meter 1 is being proved' AND (1005 is NOT ON OR 1006 is ON).
TIP - Leave plenty of empty statements between programmed ones. This will allow you to modify the execution order of your program if you need to later.
Boolean Point #10xx 25: /1005+1006 26: 1106&1025 27: _ Use the 'Up/Down' arrow keys to scroll though all 64 programmable Boolean points.
3-4
20/24.71 w 04/98
Volume 3
Example 1:
INFO - Use the Exclusive OR function * to compare 2 points. The result of an Exclusive OR of 2 points is true only if both points are different states. INFO - Booleans 1025, 1026 and 1027 are only used as an example here. Any unused programmable Booleans can be used for this function.
Object: Using signals from 'flow sensing switches' inserted into the pipeline, provide an alarm output which activates whenever the signals from the flow switches and flow meter signals differ, also provide a snapshot report by setting command point 1719. How the hardware is configured: Physical I/O points 02 and 03 are setup as inputs by assigning them to 1700 (see the Command and Status Booleans on a later page). They are connected to flow sensing switches on meter runs 1 and 2 respectively. The switches activate with flow. Physical I/O point 03 is connected to a 'meter fail alarm bell'. The output is assigned to Programmable Boolean 1027. A 'delay ON' of 5 seconds is selected to eliminate spurious alarms which would occur during startup and shutdown. A 'delay OFF' of 5 seconds is selected to ensures that the alarm bell remains on for at least 5 seconds. The Booleans are programmed as follows:
True if Meter #1 fails. True if Meter #2 fails. Request snapshot if either meter fails.
Boolean Point #10xx 25: 1105*1002 26: 1205*1003 27: 1719=1025+1026 28:
Notes: q Boolean Point 1025 is true (Meter 1 failed) whenever 'Meter 1 Active' (Point 1105) differs from 'Flow Detected' Flow Switch 1 (Point 02). q Boolean Point 1026 is true (Meter 2 failed) whenever 'Meter 2 Active' (Point 1205) differs from 'Flow Detected' Flow Switch 2 (Point 03). q Boolean Point 1027 is true (Meter 1 OR 2 failed) whenever point 1025 OR 0126 are true. The Boolean Command Bit 1719 is set when Boolean Point 1027 is true.
20/24.71 w 04/98
3-5
Chapter 3
User-Programmable Functions Example 2: Automatic Run Switching for 4-Meter Run Application'
Object: To improve metering accuracy by automatically selecting the correct flow meter run to be active in a multi run application. Small turbines need to be protected from over-speeding while for best accuracy larger turbines should be valved off when the flow drops below their minimum rate. In the example shown, except when switching from one flow meter to the other, only one flow meter run is active at one time. This is one example only. The number of runs open for a given application at any flow rate obviously depends on the size of the flow meters used.
Fig. 3-1.
Switching is based on the station flow gross flow rate which is compared to preset switching thresholds entered by the user (See 'Meter Station Settings' in Chapter 2). Threshold Flags 1, 2 and 3 are set and reset according to the actual station flow rate. The first task is identify the 4 zones and assign programmable Boolean points to them. This allows us to include them in further Boolean statements.
Zone 1 = NOT Flag 1 AND NOT Flag 2 AND NOT Flag 3 Zone 2 = Flag 1 AND NOT Flag 2 AND NOT Flag 3 Zone 3 = Flag 1 AND Flag 2 AND NOT Flag3 Zone 4 = Flag 1 AND Flag 2 AND Flag 3
3-6
20/24.71 w 04/98
Volume 3
Boolean Point #10xx 25: /1825&/1826 26: /1824&1025 27: 1824&1025 28: 1824&1825&/1826 29: 1824&1825&1826 In our example each meter run valve (V1, V2, V3 and V4) fails closed, energizes to open. A limit switch mounted on each valve indicates the fully open position (SW1, SW2, SW3 and SW4).
Fig. 3-2.
20/24.71 w 04/98
3-7
Chapter 3
User-Programmable Functions
3.2.4.
We will use Physical I/O Points 11, 12, 13 and 14 to connect to valve limit switches SW1, SW2, SW3 and SW4 respectively. The switches activate when the appropriate valve is fully open. The points are designated as inputs by assigning them to the dummy input Boolean Point 1700 (see the Command and Status Booleans on a later page). Their data base point numbers are simply their I/O point number preceded by 10 (e.g.: I/O Point 11 = 1011). Physical I/O points 15, 16, 17 and 18 are wired so as to open the meter run valves V1, V2, V3 and V4. They will be assigned to the Boolean Flags 32 (Point 1032) through 35 (Point 1035) which represent the required state of V1 through V4 as explained below. The Boolean equations are as follows:
V1 = (NOT SW2 AND NOT SW3 AND NOT SW4) OR Zone 1
Valve #1 is opened when the flow is in Zone 1 and will remain open until at least 1 of the other 3 valves is fully open. Valves V2, V3 and V4 are programmed in a similar fashion.
V2 = (NOT SW1 AND NOT SW3 AND NOT SW4) OR Zone 2 V3 = (NOT SW1 AND NOT SW2 AND NOT SW4) OR Zone 3 V4 = (NOT SW1 AND NOT SW2 AND NOT SW3) OR Zone 4
To simplify we pre-process the common terms. The term 'NOT SW3 AND NOT SW4' is used to determine V1 and V2. The term 'NOT SW1 AND NOT SW2' is used to determine V3 and V4. Assigning the next valid point numbers to our statements and re-write them the way they will be input.
1030 = NOT SW3 AND NOT SW4 1031 = NOT SW1 AND NOT SW2 30: /1013&/1014 31: /1011&/1012
The final Equations to determined the state of V1, V2, V3 and V4 are as follows:
V1= NOT SW2 AND (NOT SW3 AND NOT SW4) OR Zone 1 32: /1012&1030+1026 V2 =NOT SW1 AND (NOT SW3 AND NOT SW4) OR Zone 2 33: /1011&1030+1027 V3= (NOT SW1 AND NOT SW2) AND NOT SW4 OR Zone 3 34: 1031&/1014+1028 V4 =(NOT SW1 AND NOT SW2) AND NOT SW3 OR Zone 4 35: 1031&/1013+1029
The computer evaluates each expression from left to right, so the order of the variables in the above statements is critical. The logic requires that the OR variable comes last.
3-8
20/24.71 w 04/98
Volume 3
V1 V2 V3 V4
Boolean Point #10xx 25: /1825&/1826 26: /1824&1025 27: 1824&1025 28: 1824&1825&/1826 29: 1824&1825&1826 30: /1013&/1014 31: /1011&/1012 32: /1012&1030+1026 33: /1011&1030+1027 34: 1031&/1014+1028 35: 1031&/1013+1029
The only thing left to do now is assign Booleans 1032, 1033, 1034 and 1035 to the appropriate digital I/O points which control V1, V2, V3 and V4. Here is a summary of all of the digital I/O as assigned:
ASSIGNED TO BOOLEAN
1700 1700 1700 1700 1032 1033 1034 1035
WIRED T O
Valve 1 Fully Open Switch Valve 2 Fully Open Switch Valve 3 Fully Open Switch Valve 4 Fully Open Switch Valve 1 Actuator Valve 2 Actuator Valve 3 Actuator Valve 4 Actuator
SYMBOL
SW1 SW2 SW3 SW4 V1 V2 V3 V4
20/24.71 w 04/98
3-9
Chapter 3
User-Programmable Functions
3.2.5.
Notes: q For meter run Boolean points, n=meter run #1, #2, #3, #4. q Meter Active (Point 1n05) is set whenever the pulses from the flow meter equal or exceed the 'Active Frequency' threshold. q Meter Being Proved (Point 1n06) is set whenever the meter has been selected as the meter to be proved, and remains set for the duration of the prove. q Batch End Ack (1n08) toggles state at the end of each batch. q Batch Preset Warning Flag (1n09) is set whenever the batch preset counter counts down to less than the warning barrel count. q Calculation Out of Limits Flag (1n13) is set whenever the operating temperature, pressure or density are outside of the chosen calculation algorithm limits of operation.
Each meter run has an identical set of Boolean points. The only numbering difference is the second digit which indicates the number of the meter run; i.e., 11XX indicates a Meter Run # 1 Boolean, 12XX indicates a Meter Run # 2 Boolean.
Note: * Used to assign an accumulator to the front panel counters or digital I/O points)
Calculation Alarm
Usually temperature, pressure or density is outside of the range of the algorithm selected.
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Override In Use - Temperature Override In Use - Pressure Override In Use - Gravity/Density Transducer Override In Use - Density Temperature Flowrate - Low Low Alarm
For points 1n20-1n23, flow rate units are gross volume or mass units for all products.
INFO - Transducer and flow rate alarms remain set while the alarm condition exists.
Flowrate - Low Alarm Flowrate - High Alarm Flowrate - High High Alarm
3-10
20/24.71 w 04/98
Volume 3
1n24 1n25 1n26 1n27 1n28 1n29 1n30 1n31 1n32 1n33 1n34 1n35 1n36 1n37 1n38 1n39 1n40 to 1n43 1n44 1n45 1n46 1n47 1n48 1n49 1n50 1n51 Spare
Density Pressure - Transducer Failed Low Density Pressure - Low Alarm Density Pressure - High Alarm Density Pressure - Transducer Failed High Turbine - Meter Comparitor Alarm
Only when dual pulse fidelity check enabled.
1n59
Spare
20/24.71 w 04/98
3-11
Volume 3
Micro Motion - Data obtained via RS-485 link with Micro Motion device.
The following Micro Motion Alarm points can be accessed from the RFT via Modbus and placed in the Micro Motion Alarm Word as the destination address 3n18 in the flow computer, to log the alarm points. The alarms will be logged into the computer alarm log and will be displayed on the LCD when they occur.
1n60 1n61 1n62 1n63 1n64 1n65 1n66 1n67 1n68 1n69 1n70 1n71 1n72 1n73 1n74 1n75 Micro Motion - EPROM Checksum Failure Micro Motion - Transmitter Configuration Change Made Micro Motion - Sensor Failure Micro Motion - Temperature Sensor Failure Micro Motion - Input Over-ranged Micro Motion - Frequency Output Over-ranged Micro Motion - Transmitter Not Configured Micro Motion - Real Time Interrupt Failure Micro Motion - mA Output Saturated Micro Motion - mA Output Fixed Micro Motion - Density Out of Limits Micro Motion - Zeroing Operation Failure Micro Motion - Transmitter Electronics Failure Micro Motion - Slug Flow Detected Micro Motion - Self-calibration In Progress Micro Motion - Power Reset Occurred
INFO - The second digit of the index number defines the number of the meter run.
1n79 to 1n99
Spare Spare
20/24.71 w 04/98
3-13
Chapter 3
User-Programmable Functions
3.2.6.
INFO - Unless indicated as being Level Sensitive, most commands are 'edge triggered'. To activate a command simply write a '1' or 'True' to that point. It is not necessary to write a '0' or 'False' after the command is given. The status of a command may also be read or used as input in a Boolean or variable statement.
Hardware Interaction Unreliable operation will result if a command which has been assigned to a digital I/O point directly also needs to be activated via a Modbus write. This is because the On/Off state of the digital I/O point overwrites the command point every 100 msec and most command point actions are only triggered every 500 msec.
Boolean points numbered 17XX are used as command or status points within the computer. These Boolean points can be altered by manipulating them via the Modbus ports or by assigning them to a physical digital I/O point. The various Boolean command and status flags are monitored for change of state by the appropriate software tasks running within the computer. For example, Point 1701 (Prover Ready) would be checked by the computer during a prove run to ensure that the 4-way valve did not move. Each physical I/O point configured as an input is scanned by the computer every 50 msec and the Boolean assigned to each point would be set On or Off depending on the state of the physical I/O point. Edge changes are also stored to ensure that a momentary signal would not be missed. Physical digital I/O points that will be used only in Boolean statements should be assigned to Point 1700 (dummy Boolean). Unless indicated as being Level Sensitive, most commands are 'edge triggered'. To activate a command simply write a '1' (1 = True) to that point. It is not necessary to write a '0' (0 = False) after the command. The status of a command may also be read or used as input in a Boolean or variable statement.
1700 Dummy
Used only to reserve a digital I/O point to be used as an input. Point 1700 can be assigned to as many I/O points as needed.
Prover Seal is OK
Must be true when sphere is between detectors.
End Batch - Meter #2 End Batch - Meter #3 End Batch - Meter #4 Station - Change Product Strobe
Rising edge triggers batch end and change to product selected by 1743-1745. Used with Station Product ID Bit 0-3 (1820-1823).
1708 1709 1710 1711 1712 1713 1714 1715 1716 1717
Prove - Meter #2 Request Prove - Meter #3 Request Prove - Meter #4 Request Station Alarm Acknowledge
Acknowledges all alarms.
Trial Prove - Meter #2 Request Trial Prove - Meter #3 Request Trial Prove - Meter #4 Request
3-14
20/24.71 w 04/98
Volume 3
1718
Notes: q Inputs are scanned every 50 msec so signals must be present for at least 50 msec in order to be recognized. Points marked with * are positive edge triggered commands. q Prover Start Permissive if configured (Point 1726) must be true before a prove sequence will start. q Prover Seal OK if configured (Point 1701) must be true while the prover sphere is between the detector switches or the prove in progress will be shorted. q Compact Prover Piston Downstream if configured (Point 1731) must be false before the Compact Prover Run signal (Point 1927) will be set active low. q Product Select Inputs (Points 1743-1746) must be set up with next product to run before any of the Product Change Strobes (Points 1707 and 1747-1750) are activated. q PID Start Permissive if configured (Points 17221725) must be true before the control outputs will be allowed to ramp open. They will ramp closed when it is negated.
# # # #
1st PID Permissive - Loop #2 1st PID Permissive - Loop #3 1st PID Permissive - Loop #4 Prover Start Permissive
Checked after temperature and flow are stable. Indicates that the meter divert valves are lined up. Enables prover sequencing when set.
1727
1728 1729 1730 1731 1732 1733 1734 1735 * * * * 1736 1737 1738 1739 1740 1741 1742 1743
Start Ramp-up PID - Loop #2 Start Ramp-up PID - Loop #3 Start Ramp-up PID - Loop #4 Compact Prover Piston Downstream
Applies only to Brooks SVP, must be false before the piston can be re-launched.
Alarm Acknowledge - Meter Run #2 Alarm Acknowledge - Meter Run #3 Alarm Acknowledge - Meter Run #4 Disable Flow Totalizing - Meter Run #1 Disable Flow Totalizing - Meter Run #2 Disable Flow Totalizing - Meter Run #3 Disable Flow Totalizing - Meter Run #4 Spare Remote Up Arrow Key
Duplicates the keypad function. Level sensitive.
Notes:
These points are defaulted to active and need not be manipulated unless the application requires it. These points also affect station totalizing (see also point 1761). Level sensitive.
20/24.71 w 04/98
3-15
Chapter 3
1747
INFO- Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
User-Programmable Functions
Change Product Strobe - Meter #1
For points 1747-1750, rising edge triggers a batch end and a change to the product specified by points 1743-1746.
Change Product Strobe - Meter #2 Change Product Strobe - Meter #3 Change Product Strobe - Meter #4 Freeze Analog Inputs
Used when calibrating analog inputs. Freezes ALL analogs. Level sensitive.
2nd PID Permissive - Meter #2 2nd PID Permissive - Meter #3 2nd PID Permissive - Meter #4 Spare Spare Leak Detection Freeze Command
Stores totalizers, temperatures, pressures and density variables to temporary storage (see 5n66 and 7634). This command is usually broadcast to all RTUs simultaneously.
1761
Remote Print - Previous Batch Report #8 Remote Print - Previous Daily Report #1
At local printer.
Remote Print - Previous Daily Report #8 Remote Print - Previous Prove Report #1
At local printer.
1787
3-16
20/24.71 w 04/98
Volume 3
1788
Note: More Command Boolean Points are located at address 2701.
Shutdown PID - Loop #2 Shutdown PID - Loop #3 Shutdown PID - Loop #4 Stop Flow PID - Loop #1
Points 1792-1795 deactivate the 1 and 2 PID permissive, causing the valve to ramp to the top off setting, and then immediately closes the valve. If the valve is already at the top off setting, the valve immediately closes.
st nd
INFO - Unless indicated as being Level Sensitive, most commands are 'edge triggered'. To activate a command simply write a '1' or 'True' to that point. It is not necessary to write a '0' or 'False' after the command is given. The status of a command may also be read or used as input in a Boolean or variable statement.
Stop Flow PID - Loop #2 Stop Flow PID - Loop #3 Stop Flow PID - Loop #4 Raw Data Archive Run
Level sensitive.
1796 1797
1798
CAUTION
Reconfigure Archive
Level sensitive.
Stored archive data may be lost! See chapter on Raw Data Archive before manipulating these data points. These functions are duplicated using integers at 13920 and 13921.
20/24.71 w 04/98
3-17
Chapter 3
User-Programmable Functions
3.2.7.
Notes: q The station is defined as a set of meter runs whose flows are added or subtracted. q Batch End Acknowledge (Point 1817) is toggled at the end of each batch; i.e., True for every other batch. q Run Switching Flags (Points 1824-1826) are controlled by the station gross flow rate and the 'Meter Station Threshold Limits'. q Power Failed Flag (Point 1829) is set automatically when power or reset is applied. It is cleared by momentarily activating the 1713 command point.
The station also has a set of Boolean points. Data points not specifically connected to a particular meter run are grouped here. These include flow computer general system alarms and metering group alarms and status points.
* * * * * * * * 1801 1802 1803 1804 1805 1806 1807 1808 1809 1810 1811 1812 1813 1814 1815 1816 1817 1818 Positive - Gross Volume Pulses (IV) Positive - Net Volume Pulses (GSV) Positive - Mass Pulses Positive - S&W Corrected Net Volume Pulses (NSV) Negative - Gross Volume Pulses (IV)
Points 1805-1808 refer to flow which occurs in the reverse direction.
Negative - Net Volume Pulses (GSV) Negative - Mass Pulses Negative - S&W Corrected Net Volume Pulses (NSV) Flowrate - Low Low Alarm
For points 1809-1812, flow rate units are gross volume or mass units for all products.
Flowrate - Low Alarm Flowrate - High Alarm Flowrate - High High Alarm Gravity Rate of Change Flag
Set when rate of change of flowing SG exceeds the setting in 7889.
Note:
* Used to assign
accumulators to the front panel electromechanical counters and digital I/O points.
1819 1820
Station - Current Product ID Bit 1 Station - Current Product ID Bit 2 Station - Current Product ID Bit 3 Run Switching - Threshold Flag 1
Flags 1824-1826 activate/deactivate depending on the run switching threshold settings and are based on current station flow rates.
Run Switching - Threshold Flag 2 Run Switching - Threshold Flag 3 Leak Detection Freeze Command was received
See point 1760.
3-18
20/24.71 w 04/98
Volume 3
#
Note:
# # # # # #
Snapshot Printed
Indicates snapshot report printed.
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Zero Value
Always false.
1842
to 1857
Notes:
# # # #
Station Density - Transducer Failed Low Station Density - Low Alarm Station Density - High Alarm Station Density - Transducer Failed High
20/24.71 w 04/98
3-19
Chapter 3
1866 to 1869 1870 to 1873 * * 1874 1875 1876
User-Programmable Functions
Density Temperature - Transducer Failed Low Density Temperature - Transducer Failed High Density Pressure - Transducer Failed Low Density Pressure - Transducer Failed High Viscosity Appearing on Report Flag Net Standard Volumes (NSV) Appearing on Report Flag Batch Recalculation Acknowledge Flag
Pulses for 500 msec when the 1798 command is received.
1877 * * *
Note:
*> 1881 *> 1882 1883 1884 1885 1886 1887 to 1890 1891 to 1894 1895 to 1898
>
Auxiliary Input #1 - Transducer Failed Low Auxiliary Input #1 - Low Alarm Auxiliary Input #1 - High Alarm Auxiliary Input #1 - Transducer Failed High Auxiliary Input #2 - Transducer Failed Low Auxiliary Input #2 - Transducer Failed High Auxiliary Input #3 - Transducer Failed Low Auxiliary Input #3 - Transducer Failed High Auxiliary Input #4 - Transducer Failed Low Auxiliary Input #4 - Transducer Failed High Net Volume @ 2
nd
Note: See 2600 area and 2800 area for more station alarms and status points.
1899
3-20
20/24.71 w 04/98
Volume 3
3.2.8.
Notes: q Point numbers marked with '*' are updated at the end of a prove and are not reset until the beginning of the next prove. q Point numbers marked 'm' are momentary lasting 2 seconds. q Run Compact Prove (Point 1927) is normally high and goes low to activate a run.
Boolean points numbered 19XX are dedicated to the prover alarms and status. point numbers. The second digit 9 defines a prover. See the 1700 area for command points associated with the prover.
1901 1902 1903 1904 1905 1906 1907 1908 Inlet (Left) Pressure - Transducer Low Alarm Inlet (Left) Pressure - Transducer High Alarm Outlet (Right) Pressure - Transducer Low Alarm Outlet (Right) Pressure - Transducer High Alarm Inlet (Left) Temperature - Transducer Low Alarm Inlet (Left) Temperature - Transducer High Alarm Outlet (Right) Temperature - Transducer Low Alarm Outlet (Right) Temperature - Transducer High Alarm Prove Aborted - Temperature Unstable Prove Aborted - Meter-to-Prover Temperature Deviation Exceeded Prove Sequence - Successfully Completed Prove Sequence Aborted - Did Not Complete 1st Detector Sensed - Sphere in Flight Forward Direction 3rd Detector Sensed - Sphere in Flight Reverse Direction 2nd Detector Sensed - In Over-travel Forward Direction 4th Detector Sensed - In Over-travel Reverse Direction Launch Sphere - Forward Direction
Two second pulse.
Note:
# # # #
1909 1910 1911 1912 1913 1914 1915 1916 1917 1918
# # # # # #
Prove Aborted - Run Repeatability Deviation Limit Exceeded Prove Aborted - Prover Seal Not OK - Sphere Between Detectors
See 1701.
Prove Aborted - Flowrate was Unstable Prove Aborted - No Prover Permissive Received
See 1726.
Meter Factor Obtained was Not Implemented Prove Aborted - Meter Selected was not Flowing
See 1n05.
1926 1927
Plenum - Vent Required Brooks Small Volume Prover - Run Command Output
Active low output to launch piston.
20/24.71 w 04/98
3-21
Volume 3
1928 1929 1930 1931 1932 * * * * * *
Note:
Using Fixed Override - Prover Inlet (Left) Temperature Using Fixed Override - Prover Outlet (Right) temperature Using Fixed Override - Prover Inlet (Left) Pressure Using Fixed Override - Prover Outlet (Right) Pressure Mass Prove Flag Net Prove Flag Mass Prove Report Flag Net Prove Report Flag Mass Calculation in Use Flag Meter Factor Repeatability in Use Flag
Set when run deviation is based on meter factor.
1933 1934 1935 1936 1937 1938 1939 1940 1941 1942 1943 1944 to 1947 1948 to 1951 1952 to 1954
Prover Density - Transducer Failed Low Alarm Prover Density - Low Alarm Prover Density - High Alarm Prover Density - Transducer Failed High Alarm Prover Density Temperature - Transducer Failed Low Alarm Prover Density Temperature - Transducer Failed High Alarm Prover Density Pressure - Transducer Failed Low Alarm Prover Density Pressure - Transducer Failed High Alarm Spare Spare Viscosity Linearization - Proving Mode Selected Viscosity Linearization - Mode NOT Selected Spare Spare Prove Report - Print 4 Decimal Places for Correction Factors Prove Report - Print 5 Decimal Places for Correction Factors Prove Report - Print 6 Decimal Places for Correction Factors Prove Report - Print 4 Decimal Places for Meter Factors Prove Report - Print 5 Decimal Places for Meter Factors Prove Report - Print 6 Decimal Places for Meter Factors Prove Report - Print 5 Decimal Places for Intermediate Meter Factors Prove Report - Print 6 Decimal Places for Intermediate Meter Factors Prove Report - Print 7 Decimal Places for Intermediate Meter Factors Spare Spare
* *
* * * * * * * * *
1959 1960 1961 1962 1963 1964 1965 1966 1967 1968 to 1999
20/24.71 w 04/98
3-23
Chapter 3
User-Programmable Functions
3.2.9.
The following Boolean points are flags indicating that a totalizer has rolled-over (i.e., reached maximum count and restarted from zero). These flags are used to conditionally print characters (usually **) in front of the totalizer which has rolled on the appropriate report. Examination of an Omni Custom Report Template will show how this is accomplished. The second digit of the index number defines the number of the meter run. See also points at 2801 for station versions of these flags.
Note: The In Progress flags are those which the flow computer uses when printing the reports on the connected printer. Use the Previous flags if the report is being printed by another device such as a SCADA or MMI. This is necessary because the flow computer clears the In Progress data immediately after it prints the local report.
2n01 2n02 2n03 2n04 2n05 2n06 2n07 2n08 2n09 2n10 2n11 2n12 2n13 2n14 2n15 2n16 2n17 2n18 2n19 2n20 2n21
Batch In Progress - Gross Totalizer Rollover Flag Batch In Progress - Net (GSV) Totalizer Rollover Flag Batch In Progress - Mass Totalizer Rollover Flag Batch In Progress - NSV Totalizer Rollover Flag Batch In Progress - Cumulative - Gross Totalizer Rollover Flag Batch In Progress - Cumulative - Net (GSV) Totalizer Rollover Flag Batch In Progress - Cumulative - Mass Totalizer Rollover Flag Batch In Progress - Cumulative - NSV Totalizer Rollover Flag Daily In Progress - Gross Totalizer Rollover Flag Daily In Progress - Net (GSV) Totalizer Rollover Flag Daily In Progress - Mass Totalizer Rollover Flag Daily In Progress - NSV Totalizer Rollover Flag Daily In Progress - Cumulative - Gross Totalizer Rollover Flag Daily In Progress - Cumulative - Net (GSV) Totalizer Rollover Flag Daily In Progress - Cumulative - Mass Totalizer Rollover Flag Daily In Progress - Cumulative - NSV Totalizer Rollover Flag Previous Batch n - Gross Totalizer Rollover Flag Previous Batch n - Net GSV) Totalizer Rollover Flag Previous Batch n - Mass Totalizer Rollover Flag Previous Batch n - NSV Totalizer Rollover Flag Previous Batch n - Cumulative - Gross Totalizer Rollover Flag Previous Batch n - Cumulative - Net (GSV) Totalizer Rollover Flag Previous Batch n - Cumulative - Mass Totalizer Rollover Flag Previous Batch n - Cumulative - NSV Totalizer Rollover Flag Previous Daily - Gross Totalizer Rollover Flag Previous Daily - Net (GSV) Totalizer Rollover Flag Previous Daily - Mass Totalizer Rollover Flag Previous Daily - NSV Totalizer Rollover Flag Previous Daily - Cumulative - Gross Totalizer Rollover Flag Previous Daily - Cumulative - Net (GSV) Totalizer Rollover Flag Previous Daily - Cumulative - Mass Totalizer Rollover Flag Previous Daily - Cumulative - NSV Totalizer Rollover Flag Batch In Progress - 2nd Net Totalizer Rollover Flag Daily In Progress - 2nd Net Totalizer Rollover Flag Previous Batch n - 2 Previous Daily - 2
nd nd
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
2n22 2n23 2n24 2n25 2n26 2n27 2n28 2n29 2n30 2n31 2n32 2n33 2n34
Note: See 1800 area and 2800 area for more station alarms and status points.
2n35 2n36
3-24
20/24.71 w 04/98
Volume 3
2n37 2n37 2n37 2n37
2601 to 2604 2605 2606 2607 2608 2620 2621 2622 2623
Auxiliary Input #1 - Override in Use Auxiliary Input #1 - Override in Use Inlet Temperature - Override in Use Outlet Temperature - Override in Use Inlet Pressure - Override in Use Outlet Pressure - Override in Use Calibration Data Checksum Error
Correctable as secondary copy was OK.
3.2.11. Commands Which Cause Custom Data Packets to be Transmitted Without a Poll
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Activating any of the edge triggered command points below causes the appropriate Custom Data Packet to be transmitted out of the selected serial port without the serial port being polled for data. This function can be useful when communicating via VSAT satellite systems where operating cost is directly proportional to RF bandwidth used.
2701
Note: Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
Data Packet #1 to Serial Port #1 Data Packet #2 to Serial Port #1 Data Packet #3 to Serial Port #1 Data Packet #1 to Serial Port #2 Data Packet #2 to Serial Port #2 Data Packet #3 to Serial Port #2 Data Packet #1 to Serial Port #3 Data Packet #2 to Serial Port #3 Data Packet #3 to Serial Port #3 Data Packet #1 to Serial Port #4 Data Packet #2 to Serial Port #4 Data Packet #3 to Serial Port #4
2702 2703 2704 2705 2706 2707 2708 2709 2710 2711 2712
20/24.71 w 04/98
3-25
Chapter 3
User-Programmable Functions
2756
Recalculate and Print Selected Batch - Meter #2 Recalculate and Print Selected Batch - Meter #3 Recalculate and Print Selected Batch - Meter #4
In Progress Flags - The In Progress flags are the flags which the flow computer uses when printing the reports on the connected printer. Use the Previous flags if the report is being printed by another device such as an SCADA or MMI. This is necessary because the flow computer clears the In Progress data immediately after it prints the local report.
The following Boolean points are flags indicating that a totalizer has rolled-over (i.e., reached maximum count and restarted from zero). These flags are used to conditionally print characters (usually ** ) in front of the totalizer which has rolled on the appropriate report. Examination of an Omni Custom Report Template will show how this is accomplished. See also points at 2n01 for meter run versions of flags.
2801 2802 2803 2804 2805 2806 2807 2808 2809 2810 2811 2812 Batch In Progress - Gross Totalizer Rollover Flag Batch In Progress - Net (GSV)) Totalizer Rollover Flag Batch In Progress - Mass Totalizer Rollover Flag Batch In Progress - NSV Totalizer Rollover Flag Batch In Progress - Cumulative - Gross Totalizer Rollover Flag Batch In Progress - Cumulative - Net (GSV) Totalizer Rollover Flag Batch In Progress - Cumulative - Mass Totalizer Rollover Flag Batch In Progress - Cumulative - NSV Totalizer Rollover Flag Daily In Progress - Gross Totalizer Rollover Flag Daily In Progress - Net (GSV) Totalizer Rollover Flag Daily In Progress - Mass Totalizer Rollover Flag Daily In Progress - NSV Totalizer Rollover Flag
3-26
20/24.71 w 04/98
Volume 3
2813
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
2814 2815 2816 2817 2818 2819 2820 2821 2822 2823 2824 2825 2826 2827 2828 2829 2830 2831 2832 2833 2834 2835 2836 2837 to 2851
All totalizers within the flow computer are long integer types. This data type uses an implied decimal position. The computer uses these flags internally to determine how to format all totalizers of the same type for printing purposes.
2852 2853 2854 Batch Report - Print 4 Decimal Places for Correction Factors Batch Report - Print 5 Decimal Places for Correction Factors Batch Report - Print 6 Decimal Places for Correction Factors Batch Report - Print 4 Decimal Places for Meter Factors Batch Report - Print 5 Decimal Places for Meter Factors Batch Report - Print 6 Decimal Places for Meter Factors Print 0 Decimal Place for Gross & Net Totalizer Print 1 Decimal Place for Gross & Net Totalizer Print 2 Decimal Places for Gross & Net Totalizer Print 3 Decimal Places for Gross & Net Totalizer Spare
Note: It is unlikely that the user would have any use for these variables.
20/24.71 w 04/98
3-27
Volume 3
2864
Master Status
Indicates mastership. Monitored by other flow computer in a redundant system (see 2714).
Print 0 Decimal Place for Mass Totalizer Print 1 Decimal Place for Mass Totalizer Print 2 Decimal Places for Mass Totalizer Print 3 Decimal Places for Mass Totalizer Spare Spare
20/24.71 w 04/98
3-29
Chapter 3
User-Programmable Functions
3.3.
There are 64 user-programmable floating point variables within the flow computer numbered 7025 through 7088. The value stored in each of these variables depends on an associated equation or statement. These statements are evaluated every 500 msec and the resultant variable values can be displayed on the LCD display, printed on a report, output to a D-A output, or accessed via one of the communication ports. Typical uses for the variables and statements include providing measurement units conversions, special averaging functions, limit checking and comparisons.
3.3.1.
Each statement can contain up to 3 variables or constants. The following symbols are used to represent the functions:
Operator
TIP - The order of precedence is: ABSOLUTE, POWER, MULTIPLY & DIVIDE, ADD & SUBTRACT. Where operators have the same precedence the order is left to right.
Symbol + * / # & $ = ) G : %
Description Add the two variables or constants Subtract the RH variable or constant from LH Multiply the two variables or constants Divide the two variables or constants The number following is interpreted as a Raise the LH variable to the power of the RH Use the abs. unsigned value of variable following Make the variable on left equal to the expression Compares the variable to another (What if?) Go to a different variable Move statement or result to another variable. Compare a value with or equal to Variable contains point address of target
ADD SUBTRACT MULTIPLY DIVIDE CONSTANT constant POWER ABSOLUTE EQUAL IF STATEMENT GOTO STATEMENT MOVE COMPARE INDIRECT variable
To program the user variables proceed as follows: From the Display Mode press [Prog] [Setup] [Enter] [Enter] and the following menu will be displayed: *** Misc. Setup *** Password Maint?(Y)_ Check Modules ?(Y) Config Station ? (Y) Config Meter "n" Config Prove ? (Y) Config PID ? "n" Config D/A Out "n" Front Panel Counters Program Booleans ? Program Variables ?
3-30
20/24.71 w 04/98
Volume 3
Example 1:
To provide a variable (7025) which represents Meter Run #1 gross flow rate in barrels per day' in place of the usual barrels per hour, multiply the 'barrels/hour' variable (7101) by the constant 24. PROG. VARIABLE #70xx 25: 7101*#24 26: _ 27:
bbls/hr x 24 = bbls/day
Example 2:
To provide a variable that represents 'gallons per minute' (7026) we can convert the 'barrels per hour'variable (7101) to gallons by multiplying by 0.7 (0.7 = 42/60 which is the number of gallons in a barrel / divided by the number of minutes in an hour).
bbls/hr x 24 = bbls/day bbls/hr x0.7 = gal/min
Example 3:
To provide a variable (7028) that represents meter run #1 temperature in 'degrees Celsius' we subtract 32 from the 'degrees Fahrenheit' variable (7105) and divide the result (7027) by 1.8.
bbls/hr x 24 = bbls/day bbls/hr x 0.7 = gal/min F - 32.0 (F - 32.0) / 1.8 = C
PROG. VARIABLE #70xx 25: 7101*#24 26: 7101*#.7_ 27: 7105-#32 28: 7027/#1.8
20/24.71 w 04/98
3-31
Chapter 3 Example 4:
User-Programmable Functions
Gross barrels within the flow computer are simply flow meter counts divided by the flow meter 'K-Factor' (pulses per barrel); i.e., gross barrels are not meter factored. To provide a variable (7029) which represents Meter Run #1 gross meter factored barrels, multiply the batch gross barrel totalizer (5101) by the batch flow weighted average meter factor (5114).
bbls/hr x 24 = bbls/day bbls/hr x 0.7 = gal/min F - 32.0 (F - 32.0) / 1.8 = C Gross bbls x Meter Factor
PROG. VARIABLE #70xx 25: 7101*#24 26: 7101*#.7_ 27: 7105-#32 28: 7027/#1.8 29: 5101*5114
3.3.2.
Boolean points used in a programmable variable statement are assigned the value 1.0 when the Boolean value is TRUE and 0.0 when the Boolean value is FALSE. By multiplying by a Boolean the user can set a variable to 0.0 when the Boolean point has a value FALSE.
Example:
Provide a variable (7025) which functions as a 'Report Number'. The report number which will appear on each 'batch end report' must increment automatically after each batch and reset to zero at the contract day start hour on January 1 of each year.
Add 1.0 at Batch End Clear batch report number on Jan 1 Contract Hour
PROG. VARIABLE #70xx 25: 7025+1835 26: 1834)7025=#0 Boolean 1835 is true one calculation cycle at the end of a batch. Boolean point 1834 is equal to 1.0 for one calculation cycle on the contract day start hour on January 1. If statement 1834 is true we reset counter 7025.
3-32
20/24.71 w 04/98
Volume 3
3.3.3.
In some cases it may be necessary to enter data directly into a user variable (not the expression, just the variable). For example, to preset the 'Report Number' Variable 7025 in the example above we proceed as follows. While in the Display Mode press [Prog] [Input] [Enter], the following will display:
Current value - you can change this. Expression for this variable you cannot change from this entry.
3.3.4.
Entering plain text into the expression associated with the variable causes the computer no problems. It ignores the text and leaves the variable unchanged. For example: USER VARIABLE 7025 Value ? .00018 Enter Lbs to SCF ?
3.3.5.
The first four variables, 7025, 7026, 7027 and 7028 require Level 2 password. the remaining variables require Level 1.
20/24.71 w 04/98
3-33
Chapter 3
User-Programmable Functions
3.3.6.
In some cases it is also necessary to trigger some type of an event based on the value of a calculated variable. Boolean variables used in the Boolean expressions and described in the previous text can have only one of two values, ON or OFF (TRUE or FALSE). How can the floating point numbers described in this chapter be used in a Boolean expression? Simply using the fact that a variable can be either positive (TRUE) or negative (FALSE). Any variable or floating point can be used in a Boolean expression.
Example:
Provide an alarm and snapshot report which will occur when the absolute difference in net flow rate between Meter Runs #1 and #2 exceeds 10 bbls/hr, but only when Meter Run #1 flow rate is greater than 1000 bbls/hr.
Result can be positive or negative. Absolute flow difference minus 10. Positive if flow rate is >1000
PROG. VARIABLE #70xx 30: 7102- 7202 31: $7030-#10 32: 7102-#1000 Variable 7031 will be positive (TRUE) if Meter Runs #1 and #2 flow rates differ by more than 10 bbls/hr. Variable 7032 will be positive (TRUE) when Meter Run #1 flow rate exceeds 1000 bbls/hr. User variables 7031 and 7032 shown above must both be positive for the alarm to be set. In addition, we will require that the condition must exist for 5 minutes to minimize spurious alarms. The alarm will be activated by Physical I/O Point #02 and we will use Boolean statements 1025 and 1026. Enter the following Boolean statements (1025 and 1026 used as example only):
True when both are positive. Snapshot report when alarm active.
BOOLEAN POINT #70xx 25: 7031&7032 26: 1719 = 1002 To complete the example we assign Digital I/O Point #02 (Point # 1002) to 1025 and select a 'delay on' of 3000 to provide a 5 minute delay on activate (3000 ticks = 3000 x 100 msec = 300 seconds). Set the delay off to 0.
Note: See the beginning of this chapter on how to program a Boolean expression if necessary:
3-34
20/24.71 w 04/98
Volume 3
3.4.
The user can specify up to eight display screen setups. Each display screen can be programmed to show four variables, each with a descriptive tag. Any variable within the data base can be selected for display. Steps needed to configure a display screen are:
INFO - The computer checks for the user display key presses first so you may override an existing display screen by selecting the same key press sequence.
1) Specify a sequence of up to four key presses that will be used to recall the display. Key presses are identified by the A through Z character on each key. For each variable (four maximum): 2) Specify the eight character string to be used to identify the variable. Any valid characters on the keypad can be used. 3) Specify the database index or point number. 4) Specify the display resolution of the variable (i.e., how many digits to the right of the decimal point). Should the number exceed the display capacity, the decimal will be automatically shifted right to counter the overflow. The computer will shift to scientific display mode if the integer part of the number exceeds +/- 9,999,999. To configure the user display screens proceed as follows: From the Display Mode press [Prog] [Setup] [Enter] [Enter] and the following menu will be displayed: *** Misc. Setup *** Password Maint?(Y)_ Check Modules ?(Y) Config Station ? (Y) Config Meter "n" Config Prove ? (Y) Config PID ? "n" Config D/A Out "n" Front Panel Counters Program Booleans ? Program Variables ? User Display ? "n" Config Digital "n" Serial I/O "n" Custom Packet ? (Y) Scroll down to 'User Display ? "n" and enter 1 through 8 to specify which screen you wish to configure.
20/24.71 w 04/98
3-35
Chapter 3
The screen for Display #1 shows:
User-Programmable Functions
USER DISPLAY #1 Key Press _ Var #1 Tag Var #1 Index Var #1 Dec. Var #2 Tag Var #2 Index Var #2 Dec. Var #3 Tag Var #3 Index Var #3 Dec. Var #4 Tag Var #4 Index Var #4 Dec. Use the 'UP/DOWN' arrows to scroll through the screen. For 'Key Press' enter the key press sequence (up to 4 keys) that will be used to recall this display. The keys are identified by the letters A through Z.
Fig. 3-3.
3-36
20/24.71 w 04/98
Volume 3 Example:
You wish to recall 'User Display #1' by pressing [Gross] [Meter] [1], select the key sequence [A] [L] [O] as shown below. USER DISPLAY #1 Key Press A L O Var #1 Tag Var #1 Index Var #1 Dec. Continue configuring User Display #1 by entering the description tag, index number and decimal position required for each variable.
Press [Gross] [Meter] [1] Description Tag Index # for Meter #1 Flow Rate Display XXXX.XX Description Tag Index # for Meter #1 Batch Barrels Display XXXXXXXXX Description Tag Index # for Meter #1 Preset Count Display XXXXXXXXX Description Tag Index # for Meter #1 Batch F.W.A.M/F Display X.XXXX Description Tag
USER DISPLAY #1 Key Press A L O Var #1 Tag M1 MSCF Var #1 Index 7101 Var #1 Dec. 2 Var #2 Tag M1 MMSCF Var #2 Index 5101 Var #2 Dec. 0 Var #3 Tag M1 PRSET Var #3 Index 5116 Var #3 Dec. 0 Var #4 Tag M1 MFACT Var #4 Index 5114 Var #4 Dec. 4 Var #4 Tag _
20/24.71 w 04/98
3-37
Chapter 3
User-Programmable Functions
In the preceding example, User Display #1 is used to display Meter Run #1:
Variable #1 Variable #2 Variable #3 Variable #4 Flow rate in MSCF per Hour Accumulated Batch MSCF Batch Preset MSCF To Deliver Meter Factor for the Batch
The screen is recalled by pressing [Gross] [Meter] [1] [Enter] and displays: USER DISPLAY # 1 M1 MSCF 1234.56 M1 MMSCF 123456789 M1 PRSET 1234567 M1 MFACT 1.0000
3-38
20/24.71 w 04/98
Volume 3
Omni Flow Computers implement a superset of the Gould Modbus Protocol on Serial Ports #1 (selectable), #2, #3 and #4 (selectable), thus allowing simultaneous communications with two totally independent Modbus systems. Maximum transmission baud rate is 38.4 kbps with an average answer response time of 70 msec plus any modem warm-up time. The Modbus Protocol specifies one master and up to 247 slaves on a common communication line. Each slave is assigned a fixed unique device address in the range of 1 to 247. The Master always initiates the transaction. Transactions are either a query/response type (only one slave is accessed at a time) or a broadcast / no response type (all slaves are accessed at the same time). A transaction comprises a single query and single response frame or a single broadcast frame.
4.2.
Modes of Transmission
Two basic modes of transmission are available: ASCII or Remote Terminal Unit (RTU). The mode selected depends on the equipment being used.
RTU
8-bit binary
20/24.71 w 04/98
4-1
Chapter 4
4.2.1.
Framing in ASCII Transmission Mode is accomplished by the use of the colon (:) character indicating the beginning of a frame and a carriage return (CR) line feed (LF) to delineate end of frame. The line feed character also serves as a synchronizing character which indicates that the transmitting station is ready to receive an immediate reply.
FRAME :
Assuming 7 bits per transmitted character.
END
OF
FRAME CR 7 Bits
7 Bits
4.2.2.
Frame synchronization can be maintained in RTU Transmission Mode only by simulating a synchronous message. The 'OMNI' monitors the elapsed time between receipt of characters. If 3.5 character times elapse without a new character or completion of the frame, then the frame is reset and the next bytes will be processed looking for a valid address. RTU MESSAGE FORMAT
ADDRESS 8 Bits FUNCTION 8 Bits DATA N x 8 Bits ERROR CHECK 16 Bits
4.3.
4.3.1.
Message Fields
Address Field
The address field immediately follows the beginning of the frame and consists of 2 characters (ASCII) or 8 bits (RTU). These bits indicate the user assigned address of the slave device that is to receive the message sent by the master. Each slave must be assigned a unique address and only the addressed slave will respond to a query that contains its address. When the slave sends a response, the slave address informs the master which slave is communicating. In broadcast mode, an address of zero (0) is used. All slaves interpret this as an instruction to read and take action, but do not issue a response message.
4-2
20/24.71 w 04/98
Volume 3
4.3.2.
Note: See 4.5 for
descriptions and examples of these function codes. See 4.4 for a description of exception responses.
The function code field tells the addressed slave what function to perform. The high order bit of the function code field is set by the slave device to indicate that other than a normal response is being transmitted to the Master device. This bit remains 0 if the message is a query or a normal response message.
FUNCTION CODE 01 03 05 06 15 16 65 66 ACTION READ MULTIPLE BOOLEAN POINTS READ STRINGS OR MULTIPLE 16 OR 32 BIT VARIABLES WRITE SINGLE BOOLEAN POINT WRITE SINGLE 16 BIT INTEGER WRITE MULTIPLE BOOLEAN POINTS WRITE STRINGS OR MULTIPLE 16 VARIABLES READ ASCII TEXT BUFFER WRITE ASCII TEXT BUFFER OR 32 BIT
4.3.3.
Data Field
The data field contains the information needed by the slave to perform the specific function or it contains data collected by the slave in response to a query. This information may be text strings, values, exception code or text buffers.
4.3.4.
This field allows the master and slave devices to check a message for errors in transmission. A transmitted message may be altered slightly due to electrical noise or other interference while it is on its way from one unit to another. The error checking assures that the master and the slave do not react to messages that have been changed during transmission. The error check field uses a longitudinal redundancy check (LRC) in the ASCII Mode and a CRC-16 check in the RTU Mode. The bytes checked include the slave address and all bytes up to the error checking bytes. Checking is done with the data in the binary mode or RTU mode.
20/24.71 w 04/98
4-3
The message is considered as one continuous binary number whose most significant bit (MSB) is transmitted first. The message is pre-multiplied by x 16 (shifted left 16-bits), then divided by (x16+x15+x2+1) expressed as the binary number (11000000000000101).The integer quotient digits are ignored and the 16-bit remainder (initialized to all ones at the start to avoid the case of all zeros being an accepted message) is appended to the message (MSB first) as the two CRC check bytes. The resulting message including CRC, when divided by the same polynomial (x16 + x15 + x2 + 1) at the receiver will give a zero remainder if no errors have occurred (see pages1-4 through 1-6 of the Gould Modbus Reference Guide for more details).
4.4.
Exception Response
Programming or operation errors are those involving illegal data in a message, no response or difficulty in communicating with a slave. These errors result in an exception response from the slave, depending on the type of error. When such a message is received from the master the slave sends a response to the master echoing the slave address, function code (with high bit set), exception code and error check fields. To indicate that the response is a notification of an error, the high order bit of the function code is set to 1.
EXCEPTION CODE 01 02 03 04 05 DESCRIPTION ILLEGAL FUNCTION ILLEGAL DATA ADDRESS ILLEGAL DATA VALUE DATA CANNOT BE WRITTEN PASSWORD NEEDED
4-4
20/24.71 w 04/98
Volume 3
4.5.
4.5.1.
Function Codes
Function Code 01 (Read Boolean Status)
This function allows the user to obtain the ON/OFF status of Booleans used to control discrete outputs from the addressed slaves only. Broadcast mode is not supported with this function code. In addition to the slave address and function field, the message requires that the information field contain the initial point number to be read (Starting point) and the number of points that will be read to obtain the Boolean data. Boolean points are numbered as from 1001; (Boolean number 1= 1001). The data is packed one bit for each Boolean flag variable. The response includes the slave address, function code, quantity of data characters, the data characters and error checking. Data will be packed with one bit for each Boolean flag (1 = ON, 0 = OFF). The low order bit of the first character contains the addressed flag, and the remainder follow. For Boolean quantities that are not even multiples of eight, the last characters will be filled in with zeros at high order end. Example: Read Booleans 1120 to 1131 from Slave Device #01. POLL MASTER-TO-SLAVE : ASCII TRANSMISSION MODE
ADDRESS : 3031 FUNCTION CODE 3031 DATA STARTING POINT # HI 3034 LO 3630 NUMBER OF POINTS HI 3030 LO 3043 LCR CHECK 8-BIT 3845 CR LF
The status of Booleans 1120 through 1127 is shown as 08 (hex) = 0000 1000 (binary). Reading right to left, this shows that status 1123 is on. The other data flags are decoded similarly. Due to the quantity of Boolean status requested, the last data field, which is shown as 00 (hex) = 0000 0000 (binary), contains the
20/24.71 w 04/98
4-5
Chapter 4
4-6
20/24.71 w 04/98
Volume 3
4.5.2.
Function Code 03 allows the master to obtain the binary contents of holding registers in the addressed slave. The protocol allows for a maximum of 125 sixteen-bit registers to be obtained at each request. Broadcast mode is not allowed for function 03. These 16-bit registers are also grouped in sets of registers and accessed as one variable. The numeric range of the point number defines the variable type and indicates how many 16-bit registers make up that variable.
The addressed slave responds with its address and the function code, followed by the information field. The information field contains a single byte indicating the number of data bytes returned followed by the actual data bytes. The data is returned in multiples of two bytes, with the binary content right justified. The data is sent MS Byte first. Example: Read Short Integer Message 3012 through 3013 from Slave #2.
The slave responds with its address and the function code, byte count of the data field followed by the actual data field. In the above example the data field contains 4 bytes representing the value of the requested data.
20/24.71 w 04/98
4-7
Chapter 4
4.5.3.
This message forces a single Boolean variable either ON or OFF. Boolean variables are points numbered 1XXX or 2XXX. Writing the 16-bit value 65,280 (FF00 HEX) will set the Boolean ON, writing the value zero will turn it OFF; all other values are illegal and will not effect the Boolean. Using a slave address 00 (Broadcast Mode) will force all slaves to modify the desired Boolean. Example: Turn Single Boolean Point 1711 ON Slave #2.
The normal response to the command request is to retransmit the message as received after the Boolean state has been altered.
4-8
20/24.71 w 04/98
Volume 3
4.5.4.
Any numeric variable that has been defined on the 16-bit integer index table can have its contents changed by this message. The 16-bit integer points are numbered from 3XXX or 13XXX. When used with slave address zero (Broadcast Mode) all slaves will load the specified points with the contents specified. The following example sets one 16bit integer at address 3106 (0C22 HEX) of Slave #2 (i.e., Load address 3106 with data 0003). Example: Set Single 16-Bit Integer Slave #2.
The normal response to a Function 06 query is to retransmit the message as received after the 16-bit integer has been altered.
20/24.71 w 04/98
4-9
Chapter 4
4.5.5.
Function code 0FHEX writes to each Boolean variable in a consecutive block of Boolean variables to a desired ON or OFF state. Each Boolean is packed in the data field, one bit for each Boolean flag (1 = ON 0 = OFF). The data field consists of increments of 2 bytes and can be up to 250 bytes (2000 points). Boolean points are packed right-to-left, 8 to a byte with unused bits set to '0'. The use of slave address 00 (Broadcast Mode)will force all slaves to modify the desired Boolean bits. The following example writes to 14 Boolean variables starting at address 1703. The data field value 05 1703 through 1710, and data field value 20 represents the status of points 1711 through 1716. These data values are transmitted as 0000 0101 and 0010 0000, indicating that Booleans points 1703, 1705, 1716 are to be forced ON and 1704 and 1706 through 1715 are to be forced OFF (the 2 most significant positions of the second byte are unused and set to 0). Example: Turn on Boolean points 1703, 1705, 1716 ON Slave #3.
00
0E
The normal response to a Function 15 query is to echo the slave address, function code, starting address and quantity of points written.
4-10
20/24.71 w 04/98
Volume 3
4.5.6.
Function code 10HEX allows the master to change the binary contents of holding registers in the addressed slave. The protocol allows for a maximum of 125 16bit registers to be changed at each download. Using a slave address of zero (00) allows the master to change registers in all slaves simultaneously (Broadcast mode). These 16-bit registers are also grouped as sets of registers and accessed as one variable. The numeric range of the point number defines the variable type and indicates how many 16-bit registers make up that variable.
The addressed slave responds with its address and the function code, followed by the information field. The information field contains a single byte indicating the number of data bytes returned and the actual data bytes. The data is sent as multiples of two bytes, with the binary content right justified. The data is sent MS Byte first. Example: Write Short Integers 3012 through 3013 to Slave #2.
Byte Count: The Byte Count will be increments of 2, 4, 8 or 16 bytes depending on the address range of the points downloaded.
BYTE COUNT 04
DATA HI 1F LO 40
DATA HI 1F LO 3E
CRC CHECK nn nn
00
02
00
02
The slave responds with its address and the function code, starting point number and quantity of points.
20/24.71 w 04/98
4-11
Chapter 4
BYTE COUNT 04
DATA HI 00 LO 4F
DATA HI 20 LO 4E
CRC CHECK nn nn
00
01
CRC CHECK nn nn
00
01
The slave responds with its address and the function code, starting point number and quantity of points.
4.5.7.
Function Code 41HEX allows the master to read the contents of an ASCII text buffer within an addressed slave. Data is always sent and received in packets containing 128 characters. Packets are numbered from 0 to 255. The size of the text buffer is always an exact multiple of 128 bytes. The last buffer will contain an ASCII ^2 (end of file character). Example: Read 2nd packet of an ASCII Text Buffer Point 9001 from Slave # 5. POLL MASTER-TO-SLAVE : RTU TRANSMISSION MODE
ADDRESS 05 FUNCTION CODE 41 POINT # HI 23 LO 29 PACKET # HI LO 00 01 CRC CHECK nn nn
4-12
20/24.71 w 04/98
Volume 3
4.5.8.
Function code 42HEX is used by the master to download an ASCII text buffer to an addressed slave. Data is always sent and received in packets containing 128 characters. Packets are numbered from 0 to 255. The size of the text buffer is always an exact multiple of 128 bytes. The last buffer will contain an ASCII ^2 (end of file character). Example: Write 1st packet of an ASCII Text Buffer Point 9002 to Slave # 2. POLL MASTER-TO-SLAVE : RTU TRANSMISSION MODE
ADDR 02 FUNC CODE 42 POINT # HI 23 LO 2A PACKET # HI 00 Lo 00 DATA BYTE 0 39 DATA BYTE 128 2F CRC CHECK nn nn
20/24.71 w 04/98
4-13
Chapter 4
4.6.
Many point numbers were left unused when numbering the variables within the database. This allows for future growth and different application data. Without custom data packets many polls would be required to retrieve data distributed throughout the database. The custom data packets allows you to concatenate or join different groups or sets of data in any order and of any data type into 1 message response. These custom packets are a type 03 read and are located at points 1, 201 and 401 in the database. Example: Read Custom Data Packet #1 at Point 0001 from Slave #2.
4-14
20/24.71 w 04/98
Volume 3
4.7.
Serial Port #2 (Modbus Port #1) can be configured to allow peer-to-peer communications. In this mode any Omni flow computer can act as a Modbus master and communicate with any other Modbus device on the communication link (see technical Bulletin TB-980401 Peer-to-Peer Basics).
4.8.
The physical wiring of a Modbus link is usually full duplex, although the Modbus communication protocol is a half duplex protocol (i.e., both devices never transmit at the same time). For peer-to-peer communications the physical link must be wired for half duplex operation with all transmit and receive terminals wired in parallel (see Chapter 3). This allows all devices to hear all transmissions; even their own.
4.9.
Active Master
Control of the communication link is passed from the current master to the next master in the sequence by broadcasting the ID number of the next master in sequence. When that flow computer has completed its transaction list (see Chapter 5 'Peer-To-Peer') it will in turn hand over control to the next master in the sequence.
20/24.71 w 04/98
4-15
Volume 3
5.1.1.
5.1.2.
5.1.3.
Mass Flowrate = Gross Flowrate (IV) x Flowing Density x MF / 1000 If no Live Density is applied: Mass Flowrate = Net Flowrate (GSV) x Density @ 60OF / 1000
20/24.71 w 04/98
5-1
Chapter 5
5.1.4.
Where:
Equivalencies
MF = Meter Factor is entered from keypad, downloaded from SCADA or other remote device, or automatically changed by a sequence of proves Flowing Density = [Flowing gr/cc / .999012] x Wt. of water at 60OF & 14.696 Psia. Density at 60OF = SG 60 x Wt. of water at 60OF & 14.696 Psia. CSW = [1- (% S&W/100)] VCF = Volume Correction Factor (ASTM D1250) = Exp (-Alpha T x Delta T x (1+.8 x Alpha T x Delta T)) Delta T = T Actual - T Reference Rhot = Product density at reference temperature = 141.5 x Density of Water / (API + 131.5) Where API = API gravity at reference temperature Alpha T = Correction of expansion at reference temperature = [K0 + (K1 x Rhot)] / Rhot
2 2
When the product is between the jet group and the gasoline group: Alpha T = A + B / Rhot Where: K0 and K1 are physical constants derived from mathematical data published by the American Petroleum Institute in the API Manual of Petroleum Measurement Standards and are as follows:
5-2
20/24.71 w 04/98
Configuration and Advanced Operation Product Type: Between Jet and Gasoline
B = 1489.0670
F = Compressibility factor for hydrocarbon using API Chapter 11.2.1 for liquids 0 - 90 API using API Chapter 11.2.2 for Hydrocarbons 0.350 to 0.637 relative density and -50OF to 140OF CPL = Correction for pressure on liquid = 1 / 1 - (P - Pe) x F P = Flowing pressure in PSIG Pe = Equilibrium vapor pressure which is calculated from the correlations developed by Dr. R. W. Hankinson et al of Phillips Petroleum Company for member companies of the GPA and published as GPA Technical Publication No. 15. Temperature Range : -50OF to 140OF. Relative Density Range : .49 to .676
For Propylene
Net Flowrate = Gross Flowrate x CCF x MF Mass Flowrate = Gross Flowrate x MF x Flowing SG x Wt of H2O @60OF & 14.696 Psia where: CCF = Ratio of Calculated Flowing Density to Density at 60OF and Saturation Pressure. Calculated Flowing Density = Density at Flowing Temperature and Pressure Calculated using API Chapter 11.3.3.2 Flowing SG = (Calculated Flowing Density in Lbs/Ft x 0.0161846) / 0.999012
3
20/24.71 w 04/98
5-3
Ethylene density is calculated using the API 11.3.2.1 (formerly API 2565). This is the unmodified original standard.
5.1.5.
5.1.6.
5.1.7.
5.1.8.
Where:
Equivalencies
PV = Base prover volume at 60OF and 0 PSIG CTSP = Correction for temperature on steel
5-4
20/24.71 w 04/98
Volume 3
5.1.9.
PID Control
Primary Variable error % ep ep = Primary Setpoint % Span - Primary Variable % Span Forward Action ep = Primary Variable % Span - Primary Setpoint % Span Reverse Action Secondary Variable error % es es = Sec Gain * (Sec Setpoint % Span - Sec Variable % Span) Forward Action es = Sec Gain * (Sec Variable % Span - Sec Setpoint % Span) Reverse Action Control Output % C0 (Before Startup Limit Function) C0 = Primary Gain * (ep + e) Controlling on Primary Variable C0 = Primary Gain * (es + e) Controlling on Secondary Variable Integral Error e e = (Rpts/minp * Sample period * ep) + e n-1 Controlling on Primary Variable e = (Rpts/mins * Sample period * es) + e n-1 Controlling on Secondary Variable
20/24.71 w 04/98
5-5
Chapter 5
Uncompensated Density
D = K0 + (K1 x t) + (K2 * t ) Where: t = Densitometer oscillation time period in microseconds. K0, K1, K2 = Calibration constants supplied by Solartron.
2
Users wishing to implement the above term are advised to contact Solartron to obtain a reworked calibration sheet containing the coefficients 'Kr' and 'Kj'. (Typically, Kr = 1.1 and Kj = 0.5) User not wishing to implement the above term should enter 0.0 for Kr.
5-6
20/24.71 w 04/98
Volume 3
20/24.71 w 04/98
5-7
Chapter 5
5-8
20/24.71 w 04/98
Volume 3
5.2.
5.2.1.
5.2.2.
5.2.3.
Mass Flowrate = Gross Flowrate x Flowing Density x MF / 1000 If no Live Density is applied: Mass Flowrate = Net Flowrate x Density @15OC and equilibrium pressure / 1000
5.2.4.
Where:
Equivalencies
MF = Meter Factor is entered from keypad, downloaded from SCADA or other remote device, or automatically changed by a sequence of proves VCF = Volume Correction Factor (ASTM D1250) = Exp (-Alpha T x Delta T x (1+.8 x Alpha T x Delta T)) Delta T = T Actual - T Reference Alpha T = Correction of expansion at reference temperature = [K0 + (K1 x Rhot)] / Rhot
2 2
When the product is between the jet group and the gasoline group: Alpha T = A + B / Rhot Where: K0 and K1 are physical constants derived from mathematical data published by the American Petroleum Institute in the API Manual of Petroleum Measurement Standards and are as follows:
20/24.71 w 04/98
5-9
Chapter 5
5.2.5.
Gross Flowrate (m 3 / hr) = Mass Flowrate (m 3 / hr) = Net Flowrate (m 3 / hr) = where: K Factor = Pulses/kg
Table 54A
Table 54B,
K0 = 186.9696 K1 = 0.4862
Table 54B
Table 54B
K0 = 346.4228 K1 = .4388
Table 54B
B = 2680.3206
F = Compressibility factor for hydrocarbon using API Chapter 11.2.1M for 3 Crude Oil (638 to 1075 kg/m density, -30OC to 90OC), using API Chapter 3 11.2.2M for Hydrocarbon Products (350-637 kg/m density, -46OC to O 60 C).
5-10
20/24.71 w 04/98
Volume 3
For Propylene:
Net Flowrate = Gross Flowrate x CCF x MF Mass Flowrate = Gross Flowrate x MF x Flowing Density (kg/m3) where: CCF = Ratio of Calculated Flowing Density to Density at 15 deg.C and Saturation Pressure. Calculated Flowing Density = Density at Flowing Temperature and Pressure Calculated using API Chapter 11.3.3.2*
* Calculated using US unit algorithm with input and output variables converted using appropriate conversion factors.
5.2.6.
Density at Flowing Temperature and Pressure is calculated based on a computer algorithm developed by Phillips Petroleum Aug. 1992. The algorithm was based on data points published in GPA TP1, TP2 and TP15 publications.
5.2.7.
The physical properties of Ethylene calculated are: density, viscosity and isentropic exponent at flowing temperature and pressure. These are calculated using equations based on the International Union of Pure and Applied Chemistry Ethylene Tables (IUPAC).
20/24.71 w 04/98
5-11
Chapter 5
5.2.8.
5.2.9.
5.2.11. Equivalencies
Where: PV = Base prover volume at 15OC and 0 kpa CTSP = Correction for temperature on steel
5-12
20/24.71 w 04/98
Volume 3
Forward Reverse
5-13
Chapter 5
Secondary Variable error % es
es = Sec Gain * (Sec Setpoint % Span - Sec Variable % Span) Forward Action es = Sec Gain * (Sec Variable % Span - Sec Setpoint % Span) Reverse Action Control Output % C0 (Before Startup Limit Function) C0 = Primary Gain * (ep + e) Controlling on Primary Variable C0 = Primary Gain * (es + e) Controlling on Secondary Variable Integral Error e e = (Rpts/minp * Sample period * ep) + e n-1 Controlling on Primary Variable e = (Rpts/mins * Sample period * es) + e n-1 Controlling on Secondary Variable
5-14
20/24.71 w 04/98
Volume 3
Uncompensated Density
D = K0 + (K1 x t) + (K2 * t ) Where: t = Densitometer oscillation time period in microseconds. K0, K1, K2 = Calibration constants supplied by Solartron.
2
Users wishing to implement the above term are advised to contact Solartron to obtain a reworked calibration sheet containing the coefficients ' Kr' and ' Kj'. (Typically, Kr = 1.1 and Kj = 500.) Users not wishing to implement the above term should enter 0.0 for Kr.
20/24.71 w 04/98
5-15
Chapter 5
5-16
20/24.71 w 04/98
Volume 3
t = Densitometer oscillation time period in microseconds Pf = Flowing Pressure in kpa.g Kt1,2,3 = Temperature constants Kp1,2,3 = Pressure constants Tf = Flowing temperature in Deg.C T =Calibration temperature in Deg.C Pc = Calibration pressure kpa.g
20/24.71 w 04/98
5-17
Firmware Revisions 20.71/24.71
Volume 4
Contents of Volume 4
1. User-Defined, Status and Command Data (0001 - 2999)........................................ 1-1
1.1. Custom Data Packets or Modicon G51 Compatible Register Arrays...............1-1 1.2. Archive Control Flags.............................................................................................1-1 1.3. Status / Command Data..........................................................................................1-2
1.3.1. Reading and Writing the Physical Digital I/O....................................................... 1-2 1.3.2. Programmable Booleans....................................................................................... 1-2 1.3.3. Programmable Accumulator Points ..................................................................... 1-2 1.3.4. Meter Run Status and Alarm Points ..................................................................... 1-3 1.3.5. Micro Motion Alarm Status Points ..................................................................... 1-5 1.3.6. More Meter Run Status and Alarm Points ............................................................ 1-6 1.3.7. User Scratch Pad Boolean Points ........................................................................ 1-6 1.3.8. User Scratch Pad One-Shot Boolean Points........................................................ 1-6 1.3.9. Command Boolean Points/Variables.................................................................... 1-7 1.3.10. Meter Station Alarm and Status Points ............................................................ 1-10 1.3.11. Prover Alarm and Status Points ....................................................................... 1-14 1.3.12. Meter Totalizer Roll-over Flags......................................................................... 1-16 1.3.13. Miscellaneous Meter Station Alarm and Status Points ................................... 1-17 1.3.14. Commands Which Cause Custom Data Packets to be Transmitted Without a Poll...................................................................................................................... 1-18 1.3.15. Commands Needed To Accomplish a Redundant Flow Computer System ... 1-18 1.3.16. Commands to Recalculate and Print Selected Batch ...................................... 1-19 1.3.17. Station Totalizer Roll-over Flags ...................................................................... 1-19
20/24.71+ w 04/98
Contents of Volume 4
1.3.18. Station Totalizer Decimal Resolution Flags ..................................................... 1-20 1.3.19. Status Booleans Relating to Redundant Flow Computer Systems................. 1-21 1.3.20. More Station Totalizer Decimal Resolution Flags ............................................ 1-21
2.2. Miscellaneous 16-Bit Integer Data......................................................................... 2-2 2.3. Meter Run 16-Bit Integer Data ............................................................................... 2-2 2.4. Scratchpad 16-Bit Integer Data ............................................................................. 2-4 2.5. User Display Definition Variables.......................................................................... 2-4
2.5.1. User Display Number 1 ..........................................................................................2-4 2.5.2. User Display Number 2 ..........................................................................................2-4 2.5.3. User Display Number 3 ..........................................................................................2-4 2.5.4. User Display Number 4 ..........................................................................................2-5 2.5.5. User Display Number 5 ..........................................................................................2-5 2.5.6. User Display Number 6 ..........................................................................................2-5 2.5.7. User Display Number 7 ..........................................................................................2-5 2.5.8. User Display Number 8 ..........................................................................................2-5
2.6. Data Used to Access the Raw Data Archive Records.......................................... 2-6 2.7. More Miscellaneous 16-Bit Integer Data ............................................................... 2-8 2.8. Meter Station 16-Bit Integer Data .......................................................................... 2-8 2.9. Batch Stack Storage of Product Numbers to Run ............................................. 2-10
2.9.1. Meter #1 Batch Sequence .................................................................................... 2-10 2.9.2. Meter #2 Batch Sequence .................................................................................... 2-10 2.9.3. Meter #3 Batch Sequence .................................................................................... 2-11 2.9.4. Meter #4 Batch Sequence .................................................................................... 2-11
2.10. Flow Computer Time and Date Variables ......................................................... 2-11 2.11. More Miscellaneous 16-Bit Integer Data ........................................................... 2-12 2.12. Prover 16-Bit Integer Data ................................................................................. 2-12
Volume 4
iii
Contents of Volume 4
5.11. Miscellaneous Meter Run 32-Bit IEEE Floating Point Data.............................. 5-24
5.11.1. Previous Batch Average .................................................................................... 5-24 5.11.2. Previous Hours Average ................................................................................... 5-25 5.11.3. Previous Days Average..................................................................................... 5-25 5.11.4. Statistical Moving Window Averages of Transducer Inputs............................ 5-26 5.11.5. Miscellaneous In Progress Averages................................................................ 5-26 5.11.6. Previous Batch and Daily Average Data ........................................................... 5-26 5.11.7. More Miscellaneous In Progress Averages ...................................................... 5-27 5.11.8. Previous Batch Quantities................................................................................. 5-27 5.11.9. Miscellaneous Live or Calculated Data............................................................. 5-28 5.11.10. Station - Previous Batch Average Data........................................................... 5-28
7.2. Flow Computer Configuration 16-Character ASCII String Data ........................ 7-17 7.3. Flow Computer Configuration 32-Bit Long Integer Data ................................... 7-19 7.4. Flow Computer Configuration 32-Bit IEEE Floating Point Data ........................ 7-27
iv
20/24.71+ w 04/98
Volume 4
These three addresses specify reserved areas used to access user defined groups of data variables. Data can be accessed as read only blocks of data or the data is arranged as an array of adjacent 16-bit registers which can be read or written independently, if the Modicon Compatible mode is selected when setting up the serial port.
0001 Custom Data Packet / Array #1
Maximum 250 bytes using Modbus RTU mode (for Packet/Array definition see Index 3001-3040).
0201
0401
1.2.
Data to be added into the Text Archive RAM is flagged by embedding Boolean Point 1000 or 2000 within the appropriate custom report immediately preceding the data to be archived. You may enable or disable the archiving of data by resetting or setting this variable.
1000 2000 Archive Control Flag
Report data following flag will be archived not printed.
20/24.71+ w 04/98
1-1
Chapter 1
1.3.
1.3.1.
IMPORTANT
Never set a physical I/O point which has been assigned as an input as this could cause a DC voltage to appear on the input terminals of that point which may conflict with any voltage already present on those terminals.
The current status of physical Digital I/O Points 01 through 12 (Omni 3000) or 01 though 24 (Omni 6000) can be accessed by reading Modbus Indexes 1001 through 1024. All points which are to be written to exclusively via the Modbus must first have the point assigned to Modbus control by entering zero (0) for 'Digital Point Assign' (see Chapter 9). Assigning to '0' prevents the Omni application software from overwriting the Modbus write.
1001 to 1024 Digital I/O Point #24 Digital I/O Point #1
1.3.2.
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Programmable Booleans
Points 1025 through 1088 are updated every 100 msec with the current value of the programmable Boolean statements (see Chapter 10). You may read from or write to these variables, but anything that you write may be overwritten by the flow computer depending upon the logic functions programmed into the logic statement.
1025 to 1088 Boolean Point #88 Boolean Point #25
1.3.3.
Points 1089 through 1099 are paired with Floating Point Variables 7089 through 7099. For example, numeric data placed in 7089 can be output as pulses by assigning a Digital I/O Point to 1089.
1089 to 1099 Programmable Accumulator #11
Used to pulse out data placed into 7099.
Programmable Accumulator #1
Used to pulse out data placed into 7089.
1-2
20/24.71+ w 04/98
Volume 4
1.3.4.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
The second digit of the index number defines the number of the meter run. For example: Point 1105 is the Meter Active Flag for Meter Run #1. Point 1405 would be the Meter Active Flag for Meter Run #4.
* * * * 1n01 1n02 1n03 1n04 Pulses - Gross Indicated Volume Pulses - Net Volume (GSV) Pulses - Mass Pulses - Net Standard Volume
S&W corrected GSV.
Note: * Used to assign accumulator to the front panel counters or digital I/O points)
1n08
1n09
1n13
Calculation Alarm
Usually temperature, pressure or density is outside of the range of the algorithm selected.
1n14
1n15
Override In Use - Temperature Override In Use - Pressure Override In Use - Gravity/Density Transducer Override In Use - Density Temperature
20/24.71+ w 04/98
1-3
Chapter 1
1n20
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Flowrate - Low Alarm Flowrate - High Alarm Flowrate - High High Alarm Meter Temperature - Transducer Failed Low Alarm Meter Temperature - Low Alarm Meter Temperature - High Alarm Meter Temperature - Transducer Failed High Alarm Meter Pressure - Transducer Failed Low Alarm Meter Pressure - Low Alarm Meter Pressure - High Alarm Meter Pressure - Transducer Failed High Alarm Gravity/Density - Transducer Failed Low Alarm Gravity/Density - Low alarm Gravity/Density - High Alarm Gravity/Density - Transducer Failed High Alarm Density Temperature - Transducer Failed Low Alarm Density Temperature - Low Alarm Density Temperature - High Alarm Density Temperature - Transducer Failed High Alarm Spare Spare Density Pressure - Transducer Failed Low Density Pressure - Low Alarm Density Pressure - High Alarm Density Pressure - Transducer Failed High Turbine - Meter Comparitor Alarm
Only when dual pulse fidelity check enabled.
INFO - Transducer and flow rate alarms remain set while the alarm condition exists.
1n25 1n26 1n27 1n28 1n29 1n30 1n31 1n32 1n33 1n34 1n35 1n36 1n37 1n38 1n39 1n40 to 1n43 1n44 1n45 1n46 1n47 1n48 1n49 1n50 1n51
1-4
20/24.71+ w 04/98
Volume 4
1n52
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
INFO - The second digit of the index number defines the number of the meter run.
1n58
1n59
Spare
1.3.5.
Micro Motion - Data obtained via RS-485 link with Micro Motion device.
The following Micro Motion Alarm points can be accessed from the RFT via Modbus and placed in the Micro Motion Alarm Word as the destination address 3n18 in the flow computer, to log the alarm points. The alarms will be logged into the computer alarm log and will be displayed on the LCD when they occur.
1n60 1n61 1n62 1n63 1n64 1n65 1n66 1n67 1n68 1n69 1n70 1n71 1n72 1n73 1n74 1n75 Micro Motion - EPROM Checksum Failure Micro Motion - Transmitter Configuration Change Made Micro Motion - Sensor Failure Micro Motion - Temperature Sensor Failure Micro Motion - Input Over-ranged Micro Motion - Frequency Output Over-ranged Micro Motion - Transmitter Not Configured Micro Motion - Real Time Interrupt Failure Micro Motion - mA Output Saturated Micro Motion - mA Output Fixed Micro Motion - Density Out of Limits Micro Motion - Zeroing Operation Failure Micro Motion - Transmitter Electronics Failure Micro Motion - Slug Flow Detected Micro Motion - Self-calibration In Progress Micro Motion - Power Reset Occurred
20/24.71+ w 04/98
1-5
Chapter 1
1.3.6.
Note: See 2n00 area for even more meter run alarms and status points.
Spare Spare
1.3.7.
There are two groups of user scratchpad flags which can be used to store the results of Boolean statements or to group data to be transmitted or received over a Modbus data link.
1501 to 1599 1600 Scratchpad - Point 99 Reserved
DO NOT USE!
Scratchpad - Point 01
1601 to 1649
1.3.8.
Many times it is necessary to send a command which momentarily turns on a Boolean point. The following one-shot Boolean points simplify this action. They remain activated for exactly 2 seconds after they have been written to.
1650 to 1699 Scratchpad One-Shot - Point 50 Scratchpad One-Shot - Point 01
1-6
20/24.71+ w 04/98
Volume 4
1.3.9.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Unless indicated as being Level Sensitive, most commands are 'edge triggered'. To activate a command simply write a '1' (1 = True) to that point. It is not necessary to write a '0' (0 = False) after the command. The status of a command may also be read or used as input in a Boolean or variable statement.
1700 Dummy
Used only to reserve a digital I/O point to be used as an input. Point 1700 can be assigned to as many I/O points as needed.
INFO - Unless indicated as being Level Sensitive, most commands are 'edge triggered'.
1701
Prover Seal is OK
Must be true when sphere is between detectors.
Hardware Interaction Unreliable operation will result if a command which has been assigned to a digital I/O point directly also needs to be activated via a Modbus write. This is because the On/Off state of the digital I/O point overwrites the command point every 100 msec and most command point actions are only triggered every 500 msec.
End Batch - Meter #2 End Batch - Meter #3 End Batch - Meter #4 Station - Change Product Strobe
Rising edge triggers batch end and change to product selected by 1743-1746. Used with Station Product ID Bit 0-3 (1820-1823).
1708 1709
Prove - Meter #2 Request Prove - Meter #3 Request Prove - Meter #4 Request Station Alarm Acknowledge
Acknowledges all alarms.
INFO- Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
Trial Prove - Meter #2 Request Trial Prove - Meter #3 Request Trial Prove - Meter #4 Request Abort the Prove in Progress Request Local Snapshot Report
Printed on local printer connected to flow computer.
20/24.71+ w 04/98
1-7
Chapter 1
#
INFO - Unless indicated as being Level Sensitive, most commands are 'edge triggered'. To activate a command simply write a '1' or 'True' to that point. It is not necessary to write a '0' or 'False' after the command is given. The status of a command may also be read or used as input in a Boolean or variable statement.
# # # #
1st PID Permissive - Loop #2 1st PID Permissive - Loop #3 1st PID Permissive - Loop #4 Prover Start Permissive
Checked after temperature and flow are stable. Indicates that the meter divert valves are lined up. Enables prover sequencing when set.
1727
Note:
These points are defaulted to active and need not be manipulated unless the application requires it.
Start Ramp-up PID - Loop #2 Start Ramp-up PID - Loop #3 Start Ramp-up PID - Loop #4 Compact Prover Piston Downstream
Applies only to Brooks SVP, must be false before the piston can be re-launched.
Alarm Acknowledge - Meter Run #2 Alarm Acknowledge - Meter Run #3 Alarm Acknowledge - Meter Run #4 Disable Flow Totalizing - Meter Run #1 Disable Flow Totalizing - Meter Run #2 Disable Flow Totalizing - Meter Run #3 Disable Flow Totalizing - Meter Run #4 Spare Remote Up Arrow Key
Duplicates the keypad function. Level sensitive.
* * * *
These points also affect station totalizing (see also point 1761). Level sensitive.
1743
1-8
20/24.71+ w 04/98
Volume 4
1747
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Change Product Strobe - Meter #2 Change Product Strobe - Meter #3 Change Product Strobe - Meter #4 Freeze Analog Inputs
Used when calibrating analog inputs. Freezes ALL analogs. Level sensitive.
1752
2nd PID Permissive - Meter #2 2nd PID Permissive - Meter #3 2nd PID Permissive - Meter #4
1756 to 1759
Spare Spare
1760
1761
1762 to 1769
INFO- Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
1770 to 1777
1778 to 1785
1786
20/24.71+ w 04/98
1-9
Chapter 1
1787
Note: More Command Boolean Points are located at address 2701.
1788
INFO - Unless indicated as being Level Sensitive, most commands are 'edge triggered'. To activate a command simply write a '1' or 'True' to that point. It is not necessary to write a '0' or 'False' after the command is given. The status of a command may also be read or used as input in a Boolean or variable statement.
Shutdown PID - Loop #2 Shutdown PID - Loop #3 Shutdown PID - Loop #4 Stop Flow PID - Loop #1
Points 1792-1795 deactivate the 1 and 2 PID permissive, causing the valve to ramp to the top off setting, and then immediately closes the valve. If the valve is already at the top off setting, the valve immediately closes.
st nd
Stop Flow PID - Loop #2 Stop Flow PID - Loop #3 Stop Flow PID - Loop #4 Raw Data Archive Run
Level sensitive.
CAUTION
1796 1797
1798
Stored archive data may be lost! See chapter on Raw Data Archive before manipulating these data points. These functions are duplicated using integers at 13920 and 13921.
Reconfigure Archive
Level sensitive.
Data points not specifically connected to a particular meter run are grouped here. These include flow computer general system alarms and metering group alarms and status points.
* * * * 1801 1802 1803 1804 1805 1806 1807 1808 1809 Positive - Gross Volume Pulses (IV) Positive - Net Volume Pulses (GSV) Positive - Mass Pulses Positive - S&W Corrected Net Volume Pulses (NSV) Negative - Gross Volume Pulses (IV)
Points 1805-1808 refer to flow which occurs in the reverse direction.
Note:
* * * *
* Used to assign
accumulators to the front panel electromechanical counters and digital I/O points.
Negative - Net Volume Pulses (GSV) Negative - Mass Pulses Negative - S&W Corrected Net Volume Pulses (NSV) Flowrate - Low Low Alarm
For points 1809-1812, flow rate units are gross volume or mass units (depending on which unit is selected) for all products.
Flowrate - Low Alarm Flowrate - High Alarm Flowrate - High High Alarm
1-10
20/24.71+ w 04/98
Volume 4
1813
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
1814
1815 1816
1817 1818
1819
1820
Station - Current Product ID Bit 1 Station - Current Product ID Bit 2 Station - Current Product ID Bit 3 Run Switching - Threshold Flag 1
Flags 1824-1826 activate/deactivate depending on the run switching threshold settings and are based on current station flow rates.
Run Switching - Threshold Flag 2 Run Switching - Threshold Flag 3 Leak Detection Freeze Command was received
See point 1760.
Note:
# # # # # #
Snapshot Printed
Indicates snapshot report printed.
20/24.71+ w 04/98
1-11
Chapter 1
1837
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Zero Value
Always false.
1842
to 1857
Notes:
# # # #
1862 1863 1864 1865 1866 to 1869 1870 to 1873 * * 1874 1875 1876
Station Density - Transducer Failed Low Station Density - Low Alarm Station Density - High Alarm Station Density - Transducer Failed High Density Temperature - Transducer Failed Low Density Temperature - Transducer Failed High Density Pressure - Transducer Failed Low Density Pressure - Transducer Failed High Viscosity Appearing on Report Flag Net Standard Volumes (NSV) Appearing on Report Flag Batch Recalculation Acknowledge Flag
Pulses for 500 msec when the 1798 command is received.
1877
Spare
1-12
20/24.71+ w 04/98
Volume 4
*
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
* *
Note:
Auxiliary Input #1 - Transducer Failed Low Auxiliary Input #1 - Low Alarm Auxiliary Input #1 - High Alarm Auxiliary Input #1 - Transducer Failed High
>
1887 to 1890
Auxiliary Input #2 - Transducer Failed Low Auxiliary Input #2 - Transducer Failed High
1891 to 1894
Auxiliary Input #3 - Transducer Failed Low Auxiliary Input #3 - Transducer Failed High
1895 to 1898
Note: See 2600 area and 2800 area for more station alarms and status points.
Auxiliary Input #4 - Transducer Failed Low Auxiliary Input #4 - Transducer Failed High
1899
20/24.71+ w 04/98
1-13
Chapter 1
Alarm and Status points connected with the meter proving system are grouped here. The second digit 9 defines a prover. See the 1700 area for command points associated with the prover.
Inlet (Left) Pressure - Transducer Low Alarm Inlet (Left) Pressure - Transducer High Alarm Outlet (Right) Pressure - Transducer Low Alarm Outlet (Right) Pressure - Transducer High Alarm Inlet (Left) Temperature - Transducer Low Alarm Inlet (Left) Temperature - Transducer High Alarm Outlet (Right) Temperature - Transducer Low Alarm Outlet (Right) Temperature - Transducer High Alarm Prove Aborted - Temperature Unstable Prove Aborted - Meter-to-Prover Temperature Deviation Exceeded Prove Sequence - Successfully Completed Prove Sequence Aborted - Did Not Complete 1st Detector Sensed - Sphere in Flight Forward Direction 3rd Detector Sensed - Sphere in Flight Reverse Direction 2nd Detector Sensed - In Over-travel Forward Direction 4th Detector Sensed - In Over-travel Reverse Direction Launch Sphere - Forward Direction
Two second pulse.
Note:
# # # #
1909 1910 1911 1912 1913 1914 1915 1916 1917 1918
# # # # # #
Prove Aborted - Run Repeatability Deviation Limit Exceeded Prove Aborted - Prover Seal Not OK - Sphere Between Detectors
See 1701.
Prove Aborted - Flowrate was Unstable Prove Aborted - No Prover Permissive Received
See 1726.
Meter Factor Obtained was Not Implemented Prove Aborted - Meter Selected was not Flowing
See 1n05.
1925
1926 1927
Plenum - Vent Required Brooks Small Volume Prover - Run Command Output
Active low output to launch piston.
1928
1-14
20/24.71+ w 04/98
Volume 4
1929
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
1930 1931 1932 * * * * * * * 1933 1934 1935 1936 1937 1938 1939
Note:
Prover Density - Transducer Failed Low Alarm Prover Density - Low Alarm Prover Density - High Alarm Prover Density - Transducer Failed High Alarm
1944 to 1947
Prover Density Temperature - Transducer Failed Low Alarm Prover Density Temperature - Transducer Failed High Alarm
1948 to 1951
Prover Density Pressure - Transducer Failed Low Alarm Prover Density Pressure - Transducer Failed High Alarm
1952 to 1954
Spare Spare
* *
1955 1956
Viscosity Linearization - Proving Mode Selected Viscosity Linearization - Mode NOT Selected
1957 1958
Spare Spare
20/24.71+ w 04/98
1-15
Chapter 1
*
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
* * * * * * * *
Note:
2n01 2n02 2n03 2n04 2n05 2n06 2n07 2n08 2n09 2n10 2n11 2n12 2n13 2n14 2n15 2n16 2n17 2n18 2n19 2n20
Batch In Progress - Gross Totalizer Rollover Flag Batch In Progress - Net (GSV) Totalizer Rollover Flag Batch In Progress - Mass Totalizer Rollover Flag Batch In Progress - NSV Totalizer Rollover Flag Batch In Progress - Cumulative - Gross Totalizer Rollover Flag Batch In Progress - Cumulative - Net (GSV) Totalizer Rollover Flag Batch In Progress - Cumulative - Mass Totalizer Rollover Flag Batch In Progress - Cumulative - NSV Totalizer Rollover Flag Daily In Progress - Gross Totalizer Rollover Flag Daily In Progress - Net (GSV) Totalizer Rollover Flag Daily In Progress - Mass Totalizer Rollover Flag Daily In Progress - NSV Totalizer Rollover Flag Daily In Progress - Cumulative - Gross Totalizer Rollover Flag Daily In Progress - Cumulative - Net (GSV) Totalizer Rollover Flag Daily In Progress - Cumulative - Mass Totalizer Rollover Flag Daily In Progress - Cumulative - NSV Totalizer Rollover Flag Previous Batch n - Gross Totalizer Rollover Flag Previous Batch n - Net GSV) Totalizer Rollover Flag Previous Batch n - Mass Totalizer Rollover Flag Previous Batch n - NSV Totalizer Rollover Flag
1-16
20/24.71+ w 04/98
Volume 4
2n21
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
2n22 2n23 2n24 2n25 2n26 2n27 2n28 2n29 2n30 2n31 2n32 2n33 2n34
Note: See 1800 area and 2800 area for more station alarms and status points.
2601 to 2604 2605 2606 2607 2608 2620 2621 2622 2623
Auxiliary Input #1 - Override in Use Auxiliary Input #1 - Override in Use Inlet Temperature - Override in Use Outlet Temperature - Override in Use Inlet Pressure - Override in Use Outlet Pressure - Override in Use Calibration Data Checksum Error
Correctable as secondary copy was OK.
20/24.71+ w 04/98
1-17
Chapter 1
1.3.14. Commands Which Cause Custom Data Packets to be Transmitted Without a Poll
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Activating any of the edge triggered command points below causes the appropriate Custom Data Packet to be transmitted out of the selected serial port without the serial port being polled for data. This function can be useful when communicating via VSAT satellite systems where operating cost is directly proportional to RF bandwidth used.
2701
Note: Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
Data Packet #1 to Serial Port #1 Data Packet #2 to Serial Port #1 Data Packet #3 to Serial Port #1 Data Packet #1 to Serial Port #2 Data Packet #2 to Serial Port #2 Data Packet #3 to Serial Port #2 Data Packet #1 to Serial Port #3 Data Packet #2 to Serial Port #3 Data Packet #3 to Serial Port #3 Data Packet #1 to Serial Port #4 Data Packet #2 to Serial Port #4 Data Packet #3 to Serial Port #4
2702 2703 2704 2705 2706 2707 2708 2709 2710 2711 2712
1-18
20/24.71+ w 04/98
Volume 4
2756
Recalculate and Print Selected Batch - Meter #2 Recalculate and Print Selected Batch - Meter #3 Recalculate and Print Selected Batch - Meter #4
INFO - Remember that the station is defined as a group of individual meter runs.
In Progress Flags - The In Progress flags are the flags which the flow computer uses when printing the reports on the connected printer. Use the Previous flags if the report is being printed by another device such as an SCADA or MMI. This is necessary because the flow computer clears the In Progress data immediately after it prints the local report.
20/24.71+ w 04/98
1-19
Chapter 1
2821
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
2822 2823 2824 2825 2826 2827 2828 2829 2830 2831 2832 2833 2834 2835 2836
2837 to 2851
Spare Spare
All totalizers within the flow computer are long integer types. This data type uses an implied decimal position. The computer uses these flags internally to determine how to format all totalizers of the same type for printing purposes.
2852 2853 2854 Batch Report - Print 4 Decimal Places for Correction Factors Batch Report - Print 5 Decimal Places for Correction Factors Batch Report - Print 6 Decimal Places for Correction Factors Batch Report - Print 4 Decimal Places for Meter Factors Batch Report - Print 5 Decimal Places for Meter Factors Batch Report - Print 6 Decimal Places for Meter Factors Print 0 Decimal Place for Gross & Net Totalizer Print 1 Decimal Place for Gross & Net Totalizer Print 2 Decimal Places for Gross & Net Totalizer Print 3 Decimal Places for Gross & Net Totalizer Spare
Note: It is unlikely that the user would have any use for these variables.
1-20
20/24.71+ w 04/98
Volume 4
2864
Master Status
Indicates mastership. Monitored by other flow computer in a redundant system (see 2714).
Print 0 Decimal Place for Mass Totalizer Print 1 Decimal Place for Mass Totalizer Print 2 Decimal Places for Mass Totalizer Print 3 Decimal Places for Mass Totalizer
2869 to 2999
Spare Spare
20/24.71+ w 04/98
1-21
Volume 4
2.1.1.
The 16-bit integers needed to define the 20 groups of data that make up Custom Data Packet #1 which is accessed at database Index 0001 are listed below.
3001 3002 to 3039 3040 Group 20 - Starting Index Point Number Group 20 - Number of Index Points Group 1 - Starting Index Point Number Group 1 - Number of Index Points
2.1.2.
The 16-bit integers needed to define the 8 groups of data that make up Custom Data Packet #2 which is accessed at database Index 0201 are listed below.
3041 3042 to 3055 3056 Group 8 - Starting Index Point Number Group 8 - Number of Index Points Group 1 - Starting Index Point Number Group 1 - Number of Index Points
2.1.3.
The 16-bit integers needed to define the 20 groups of data that make up Custom Data Packet #3 which is accessed at database Index 0401 are listed below.
3057 3058 to 3095 3096 Group 20 - Starting Index Point Number Group 20 - Number of Index Points Group 1 - Starting Index Point Number Group 1 - Number of Index Points
20/24.71+ w 04/98
2-1
Chapter 2
2.2.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Note:
>
2.3.
The second digit of the index number defines the number of the meter run. For example: 3106 is the 'Meter Active Frequency' for Meter Run # 1. The same point for Meter Run # 4 would be 3406.
3n01 Override Code - Temperature
For points 3n01-3n05: 0=Never use; 1=Always use; 2=Use if transmitter fails; 3=If transmitter fails use last hours average.
Override Code - Pressure Override Code - Gravity/Density Override Code - Density Temperature Override Code - Density Pressure Active Threshold Hz
Point 1n05 is set when flow pulses exceed this frequency.
3n09 3n10
3n11 3n12
Spare Spare
BS&W Source
0=None; 1=Auxiliary #1; 2=Auxiliary #2; 3=Auxiliary #3; 4=Auxiliary #4; 5=Modbus.
2-2
20/24.71+ w 04/98
Volume 4
3n17 3n18 3n19
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
3n20 3n21
Setpoint Mode
Read only. DO NOT WRITE! 1=Local; 0=Remote.
3n22 3n23 3n24 3n25 3n26 3n27 3n28 3n29 3n30 3n31 3n32 3n33 3n34
Frequency Point - K Factor #2 Frequency Point - K Factor #3 Frequency Point - K Factor #4 Frequency Point - K Factor #5 Frequency Point - K Factor #6 Frequency Point - K Factor #7 Frequency Point - K Factor #8 Frequency Point - K Factor #9 Frequency Point - K Factor #10 Frequency Point - K Factor #11 Frequency Point - K Factor #12 Comparitor Error Threshold
When dual pulse error checking enabled only.
Notes:
Spare Spare Current Net (GSV) Flowrate Net (GSV) Totalizer Current Gross Flowrate Gross Total Current Mass Flowrate Mass Total Current Meter Run Pressure Current Meter Run Temperature Current Transducer Density/Gravity Current S&W Corrected Net (NSV) Flowrate S&W Corrected Net (NSV) Total Move Previous Batch Number to Print Area Number of Calculation Times of Batch Report
# 2s complement numbers
based on span entries 17176 through 17189. Values expressed as percentages of span in tenth percent increments;. i.e., 1000 represents 100.0%
* Unsigned integer
totalizers cumulative based. They roll at 65536.
~ 2s complement numbers
based on the 4-20 mA spans. Values are expressed as percentages of span in tenth percent increments; i.e., 1000 equals 100.0 %.
20/24.71+ w 04/98
2-3
Chapter 2
2.4.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Ninety-nine integer registers are provided for user scratch pad. These registers are typically used to store and group data that will be moved via peer-to-peer operations or similar operations.
3501 to 3599 Scratchpad - Short Integer #99 Scratchpad - Short Integer #1
2.5.
The 16-bit integers needed to define the variables that appear in the eight User Displays are listed below. Look in the 4601 area for string associated with setting up User Displays.
2.5.1.
3601 3602 3603 3604 3605 3606 3607 3608
2.5.2.
3609 to 3616
2.5.3.
3617 to 3624
2-4
20/24.71+ w 04/98
Volume 4
2.5.4.
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
3625 to 3632
2.5.5.
3633 to 3640
2.5.6.
3641 to 3648
2.5.7.
3649 to 3656
2.5.8.
3657 to 3664
20/24.71+ w 04/98
2-5
Chapter 2
2.6.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
See the chapter describing how to use the raw data archiving features of the flow computer including how to manipulate the pointers below.
3701 3702 3703 Archive 701 - Maximum Records
Number of data records in archive file.
2-6
20/24.71+ w 04/98
Volume 4
3719
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
3720 3721
20/24.71+ w 04/98
2-7
Chapter 2
2.7.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
3737
Time Tag
MM/DD or DD/MM format.
Time Tag
YY/HH format
Time Tag
MM/SS format.
New Archive
Bit 0-Bit 9 for files 701-710
3742 to 3768
Spare Spare
3769
3770 to 3799
Spare Spare
2.8.
~ 3800
3801 # * # * # * # # # 3802 3803 3804 3805 3806 3807 3808 3809 3810 3811 3812
Current Net (GSV) Flowrate Net (GSV) Totalizer Current Gross (IV)Flowrate Gross (IV) Totalizer Current Mass Flowrate Mass Totalizer Current Pressure Current Temperature Current Gravity/Density Allen Bradley - CRC Error Counter Allen Bradley - Message Type Error Counter
# 2s complement numbers
based on span entries 17176 through 17189. Values expressed as percentages of span in tenth percent increments. i.e. 1000 represents 100.0% . No over range or under range checking is done.
2-8
20/24.71+ 04/98
Volume 4
3813
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
3814 3815 3816 3817 3818 3819 3820 3821 3822 3823 3824 3825 3826 3827 3828 3829 3830 3831 3832
Algorithm Select - Product #2 Algorithm Select - Product #3 Algorithm Select - Product #4 Algorithm Select - Product #5 Algorithm Select - Product #6 Algorithm Select - Product #7 Algorithm Select - Product #8 Algorithm Select - Product #9 Algorithm Select - Product #10 Algorithm Select - Product #11 Algorithm Select - Product #12 Algorithm Select - Product #13 Algorithm Select - Product #14 Algorithm Select - Product #15 Algorithm Select - Product #16 Flow Average Factor
Number of 500 msec calculation cycles to average.
Print Priority
0=Not sharing a printer; 1=Master; n=slaves 2-12.
20/24.71+ w 04/98
2-9
Chapter 2
2.9.
Application Revision 20/24.71 - This database corresponds to Application Revision 20/24.71 for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
The following 24 registers are treated as either one 24-position shift stack or, 4 separate 6-position shift stacks depending upon register 3837. Data in the stack(s) is shifted automatically at the beginning of a new batch. A new batch starts after a either a station batch end (1702) or meter batch end (1703 to 1706) command is received and meter pulses occur. Data on the top of a stack is the current running product for the batch in progress. This entry is discarded (popped off) and replaced with the entry below on receipt of a batch end. A batch stack may be stopped from shifting by leaving the second entry 0. Note that these entries are only part of the batch stack. Matching entries for other data types such as long integers and strings can be found at 5819 and 4852. All three data type stacks act as a single unit, they all synchronize and shift together.
2.9.1.
3843 3844 3845 3846 3847 3848
2.9.2.
3849 3850 3851 3852 3853 3854
2-10
20/24.71+ w 04/98
Volume 4
2.9.3.
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
2.9.4.
3861 3862 3863 3864 3865 3866
Current - Minute
0-59.
Current - Second
0-59.
Current - Month
1-12.
Current - Year
0-99; Year 2000=00.
20/24.71+ w 04/98
2-11
Chapter 2
Spare Override Code - Density Override Code - Density Temperature Override Code - Density Pressure Move Previous n Batch to Print Area
3880 to 3895
Density Factor - Select A/B - Product #1 Density Factor - Select A/B - Product #16
3896 to 3899
Spare Spare
Prove Counts Override Code - Prover Density/Gravity Override Code - Prover Density Temperature Override Code - Prover Density Pressure Enable Trial Prove Report
0=No; 1=Yes.
2-12
20/24.71+ w 04/98
Volume 4
3912
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
3913 3914 3915 3916 3917 3918 3919 3920 3921 3922 3923 3924 3925 3926 3927 3928
Temperature Stability Sample Time Override Code - Inlet (Left) Temperature Override Code - Outlet (Right) Temperature Override Code - Inlet (Left) Pressure Override Code - Outlet (Right) Pressure Uni- or Bi-directional Prover
0=Uni, 1=Bi; 2=Uni-Compact; 3=Bi-SVP; 4=Master Meter Prove; 5=2 Series Bi.
3929 3930 3931 3932 3933 3934 3935 3936 3937 3938 3939 3940 3941 3942 3943 3944
Spare Proved Meter Temperature Compensated Run # - 4th Last Run # - 3rd Last Run # - 2nd Last Run # - Last Run # - 1 Run Run # - 2
nd st
Run
Run # - 3rd Run Run # - 4 Run Run # -5 Run Run # - 6th Run Run # - 7th Run Run # - 8th Run Run # - 9 Run Run # - 10 Run
th th th th
20/24.71+ w 04/98
2-13
Chapter 2
3945 Current Prove Passes
3946 to 3999
Spare Spare
2-14
20/24.71+ w 04/98
Volume 4
The second digit of the index number defines the number of the meter run. For example: 4114 is the 'Meter ID' for Meter Run #1. The same point for Meter Run #4 would be 4414. Each ASCII string is 8 characters occupying the equivalent of 4 short integer registers (see the side bar comments).
4n01 4n02 # # 4n03 4n04 4n05 4n06 4n07 Running Batch - Start Date Running Batch - Start Time Batch End - Date Batch End - Time Running Product Name Current - Calculation Mode
Algorithm set used, in string format.
Note: The index number of each string refers to the complete string which occupies the space of 4 registers. It must be accessed as a complete unit. You cannot read or write a partial string. Each point counts as one point in the normal Omni Modbus mode.
Current - Batch ID
Characters 1-8.
Modicon Compatible Mode - For the purpose of point count only, each string counts as 4 registers. The starting address of the string still applies.
Current - Batch ID
Characters 9-16.
Note:
4n11 4n12 4n13 4n14 4n15 4n16 4n17 4n18 4n19 4n20 4n21 4n22
Meter - Serial Number Meter - Size Meter - Model Meter - ID Flow Meter Tag Spare Transmitter Tag - Temperature Transmitter Tag - Pressure Transmitter Tag - Densitometer Transmitter Tag - Density Temperature Transmitter Tag - Density Pressure Output Tag - PID Control
20/24.71+ w 04/98
3-1
Chapter 3
4n23
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
to 4n30 4n31 4n32 4n33 4n34 4n35 4n36 4n37 4n38 4n39
3.2.
Storage for ninety-nine ASCII strings is provided for user scratch pad. These registers are typically used to store and group data that will be moved via peerto-peer operations or similar operations.
4501 to 4599 Scratchpad - ASCII String #99 Scratchpad - ASCII String #1
3.3.
The string variables which define the descriptor tags that appear in the eight User Displays and the key press combinations which recall the displays are listed below.
INFO - See 3601 area for more data points needed to setup the user displays.
User Display #1 - Descriptor Tag - Line #1 User Display #1 - Descriptor Tag - Line #2 User Display #1 - Descriptor Tag - Line #3 User Display #1 - Descriptor Tag - Line #4
4605 to 4632
User Display #2 - Descriptor Tag - Line #1 User Display #8 - Descriptor Tag - Line #4
4633 to 4640
User Display #1 - Key Press Sequence User Display #8 - Key Press Sequence
3-2
20/24.71+ w 04/98
Volume 4
3.4.
INFO - These ASCII string variables are accessed using Modbus function codes 03 for all reads and 16 for all writes.
4707 to 4710
Note: The index number of each string refers to the complete string which occupies the space of 4 registers. It must be accessed as a complete unit. You cannot read or write a partial string. Each point counts as one point in the normal Omni Modbus mode.
3.5.
4801 4802 4803 4804 4805 4806 4807 4808 4809 4810 4811
Modicon Compatible Mode - For the purpose of point count only, each string counts as 4 registers. The starting address of the string still applies.
4812 4813
Density/Gravity Tag Station - ID Station - Density Temperature Tag Station - Density Pressure Tag Print Interval Timer Start Time
Time format field (**:**:**).
4820 to 4835
20/24.71+ w 04/98
3-3
Chapter 3
4836
Application Revision 20/24.71 - This database corresponds to Application Revision 20/24.71 for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
4837 4838 4839 4840 4841 4842 4843 4844 4845 4846
Company Name
Characters 9-16.
Company Name
Characters 17-24.
Company Name
Characters 25-32.
Company Name
Characters 33-38. (Note: Last two characters are spares.)
Station Location
Characters 1-8.
Station Location
Characters 9-16.
Station Location
Characters 17-24.
Station Location
Characters 25-32.
Station Location
Characters 33-38. (Note: Last two characters are spares.)
Note:
* *
Current Date
Point 3842 selects date format (see also 3870-3872).
Current Time
See also 3867-3869.
4851
Spare
3-4
20/24.71+ w 04/98
Volume 4
3.5.1.
INFO - These ASCII string variables are accessed using Modbus function codes 03 for all reads and 16 for all writes.
Meter #1 Batch ID
Sequence #1 - Individual Batch Stack or Common Batch Stack Sequence #1 Batch ID Sequence #2 - Individual Batch Stack or Common Batch Stack Sequence #2 Batch ID Sequence #3 - Individual Batch Stack or Common Batch Stack Sequence #3 Batch ID Sequence #4 - Individual Batch Stack or Common Batch Stack Sequence #4 Batch ID Sequence #5 - Individual Batch Stack or Common Batch Stack Sequence #5 Batch ID Sequence #6 - Individual Batch Stack or Common Batch Stack Sequence #6 Batch ID
Note: The index number of each string refers to the complete string which occupies the space of 4 registers. It must be accessed as a complete unit. You cannot read or write a partial string. Each point counts as one point in the normal Omni Modbus mode.
Modicon Compatible Mode - For the purpose of point count only, each string counts as 4 registers. The starting address of the string still applies.
3.5.2.
4864 4865 to 4874 4875
Meter #2 Batch ID
Sequence #1 - Individual Batch Stack or Common Batch Stack Sequence #7 Batch ID Sequence #6 - Individual Batch Stack or Common Batch Stack Sequence #12 Batch ID
3.5.3.
4876 4877 to 4886 4887
Meter #3 Batch ID
Sequence #1 - Individual Batch Stack or Common Batch Stack Sequence #13 Batch ID Sequence #6 - Individual Batch Stack or Common Batch Stack Sequence #18 Batch ID
20/24.71+ w 04/98
3-5
Chapter 3
3.5.4.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Meter #4 Batch ID
Sequence #1 - Individual Batch Stack or Common Batch Stack Sequence #19 Batch ID Sequence #6 - Individual Batch Stack or Common Batch Stack Sequence #24 Batch ID
3.6.
4901 4902 4903 4904 4905 4906 4907 4908 4909
4910
Spare
Prover - Inlet (Left) Temperature Tag Prover - Outlet (Right) Temperature Tag Prover - Inlet (Left) Pressure Tag Prover - Outlet (Right) Pressure Tag Plenum Pressure Tag Prover - Density/Gravity Tag Prover - Density Temperature Tag Prover - Density Pressure Tag
4919 4920
Spare Reserved
3-6
20/24.71+ w 04/98
Volume 4
4921 4922 4923 4924 4925 4926 4927 4928 4929 4930 4931 4932 4933 4934
Master Meter - ID Master Meter - Serial Number Master Meter - Size Master Meter - Model
20/24.71+ w 04/98
3-7
Volume 4
The second digit of the index number defines the number of the meter run. For example: 5105 is the 'Cumulative Gross Totalizer' for Meter Run # 1. The same point for Meter Run # 4 would be 5405.
5n01 Batch in Progress - Gross Totalizer
Points 5n01-5n04 represent the total batch quantities measured so far for the batch in progress. Results are moved to 5n50 area at the end of the batch.
* * * * *
Batch in Progress - Net Totalizer Batch in Progress - Mass Totalizer Batch in Progress - NSV Totalizer Cumulative In Progress - Gross Totalizer
Points 5n05-5n08 are non-resetable totalizers which are snapshot for opening readings.
Cumulative In Progress - Net Totalizer Cumulative In Progress - Mass Totalizer Cumulative In Progress - NSV Totalizer Todays In Progress - Gross Totalizer
Points 5n09-5n12 are total daily quantities measured since the day start hour today. These are moved to the 5n54 area at the start of a new day.
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
* * *
* *
Notes:
5n10 5n11 5n12 5n13 5n14 5n15 5n16 5n17 5n18 5n19 5n20
Todays In Progress - Net Totalizer Todays In Progress - Mass Totalizer Todays In Progress - NSV Totalizer Meter Factor in Use Now Average Meter Factor - Batch in Progress Average Meter Factor - Todays In Progress Batch Preset Remaining Running Product Number Dual Pulse (Comparitor) Error Counts for Batch
When pulse fidelity check enabled only.
* # # #
20/24.71+ w 04/98
4-1
Chapter 4
#
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
# # # # # # # # # # # # # # # # #
5n39 5n40
Spare Spare
Micro Motion - Frequency Micro Motion - Mass Total In Progress - Raw Input Counts for Hour
Raw turbine counts for the hour so far.
In Progress - Net Total for Hour In Progress - Mass Total for Hour In Progress - NSV Total for Hour In Progress - Raw Input Counts for Batch
Raw turbine counts; this batch.
Previous Batch n - Net Totalizer Previous Batch n - Mass Totalizer Previous Batch n - NSV Totalizer
4-2
20/24.71+ w 04/98
Volume 4
5n54
INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode.
Previous Days - Net Totalizer Previous Days - Mass Totalizer Previous Days - NSV Totalizer Current Batch - Opening Gross Totalizer
Points 5n58-5n61 are cumulative totalizers snapshot at the start of the batch in progress. These variables are also the closing totalizers for the previous batch.
Current Batch - Opening Net Totalizer Current Batch - Opening Mass Totalizer Current Batch - Opening NSV Totalizer Todays - Opening Gross Totalizer
Points 5n62-5n65 are cumulative totalizers snapshot at day start hour for today. These variables are also the closing totalizers for the previous day.
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
Todays - Opening Net Totalizer Todays - Opening Mass Totalizer Todays - Opening NSV Totalizer Cumulative - Gross Total @ Leak Detection Freeze Command
Points 5n66-5n69 are cumulative totalizers snapshot when the Leak Detection Freeze Command (1760) is received (see also points 7634, 7644, 7654 & 7664).
Cumulative - Net Total @ Leak Detection Freeze Command Cumulative - Mass Total @ Leak Detection Freeze Command Cumulative - NSV Total @ Leak Detection Freeze Command Increment - Gross Totalizer
Points 5n70-5n73 contains the incremental integer counts that were added to the totalizers for this current cycle (500msec).
Increment - Net Totalizer Increment - Mass Totalizer Increment - NSV Totalizer Previous Hourly - Gross Total
Points 5n74-5n77 represent the total quantities measured for the last hour. These are moved here from 5n44 area at the end of hour.
Previous Hourly - Net Total Previous Hourly - Mass Total Previous Hourly - NSV Total Previous Batch n - Opening Gross
Data from 5n58 area gets moved to 5n78-5n81 at the end of each batch.
Previous Batch n - Opening Net Previous Batch n - Opening Mass Previous Batch n - Opening NSV
20/24.71+ w 04/98
4-3
Chapter 4
5n82
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
5n83 5n84 5n85 5n86 5n87 5n88 5n89 5n90 5n91 5n92 to 5n95 5n96 5n97 5n98 5n99
Previous Days - Opening Net Previous Days - Opening Mass Previous Days - Opening NSV Previous Batch n - Closing Gross Total Previous Batch n - Closing Net Total Previous Batch n - Closing Mass Total Previous Batch n - NSV Total Previous Batch n - Batch Report Number
Use this value on Batch Report.
Previous Batch n - Batch Product Number Spare Spare Batch Net @ 2nd Reference Temperature Daily Net @ 2nd Reference Temperature Previous Batch n Net @ 2nd Reference Temperature Previous Daily Net @ 2nd Reference temperature
4.2.
Ninety-nine 32-bit integer registers are provided for user scratch pad. These registers are typically used to store the results of variable statement calculations, to group data that will be moved via peer-to-peer operations or similar types of operations.
5501 to 5599 Scratchpad - 32-Bit Integer #99 Scratchpad - 32-Bit Integer #1
4-4
20/24.71+ w 04/98
Volume 4
4.3.
INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode.
5801
* * * * * * * *
Batch in Progress - Net Totalizer Batch in Progress - Mass Totalizer Batch in Progress - NSV Totalizer Cumulative in Progress - Gross Totalizer
Points 5805-5808 are non-resetable totalizers which are snapshot for opening readings.
Cumulative in Progress - Net Totalizer Cumulative in Progress - Mass Totalizer Cumulative in Progress - NSV Totalizer Todays in Progress - Gross Totalizer
Points 5809-5812 are total daily quantities measured since the day start hour today. These are moved to the 5854 area at the start of a new day.
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
* * *
Todays in Progress - Net Totalizer Todays in Progress - Mass Totalizer Todays in Progress - NSV Totalizer Spare Line Pack Remaining Batch Preset Warning Batch Preset Remaining Running Product ID Batch Number
Note:
20/24.71+ w 04/98
4-5
Chapter 4
4.4.
4.4.1.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
4.4.2.
5825 to 5830
4.4.3.
5831 to 5836
4.4.4.
5837 to 5842
5843
Spare
4-6
20/24.71+ w 04/98
Volume 4
5844
INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode.
Station - In Progress - Net Total for Hour Station - In Progress - Mass Total for Hour Station - In Progress - NSV Total for Hour
5848 5849
5850
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
Previous Batch n - Net Totalizer Previous Batch n - Mass Totalizer Previous Batch n - NSV Totalizer Previous Days - Gross Totalizer
Points 5854-5857 are total quantities for the previous day; day start hour to day start hour. These are moved here from 5809 area at the end of the day.
Previous Days - Net Totalizer Previous Days - Mass Totalizer Previous Days - NSV Totalizer Current Batch - Opening Gross Totalizer
Points 5858-5861 are cumulative totalizers snapshot at the start of the batch in progress. These variables are also the closing totalizers for the previous batch.
Current Batch - Opening Net Totalizer Current Batch - Opening Mass Totalizer Current Batch - Opening NSV Totalizer Todays - Opening Gross Totalizer
Points 5862-5865 are cumulative totalizers snapshot at day start hour for today. These variables are also the closing totalizers for the previous day.
Todays - Opening Net Totalizer Todays - Opening Mass Totalizer Todays - Opening NSV Totalizer Cumulative - Gross Total @ Freeze
Points 5866-5869 are cumulative totalizers snapshot when the Leak Detection Freeze Command (1760) is received (see also points 7634, 7644, 7654 & 7664).
Cumulative - Net Total @ Freeze Cumulative - Mass Total @ Freeze Cumulative - NSV Total @ Freeze
20/24.71+ w 04/98
4-7
Chapter 4
*
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
* * *
Increment - Net Totalizer Increment - Mass Totalizer Increment - NSV Totalizer Previous Hourly - Gross
Points 5874-5877 represent the total quantities measured for the last hour. These are moved here from 5844 area at the end of hour.
Note:
5875 5876 5877 5878 5879 5880 5881 5882 5883 5884 5885
Previous Hourly - Net Previous Hourly - Mass Previous Hourly - NSV Previous Batch n - Opening Gross
Data from 5858 area gets moved to points 5878-5881 at the end of each batch.
Previous Batch n - Opening Net Previous Batch n - Opening Mass Previous Batch n - Opening NSV Previous Days - Opening Gross
Data from 5862 area gets moved to points 5882-5885 at the end/beginning of each day.
Previous Days - Opening Net Previous Days - Opening Mass Previous Days - Opening NSV
Previous Batch n - Closing Gross Total Previous Batch n - Closing Net Total Previous Batch n - Closing Mass Total Previous Batch n - Closing NSV Total Previous Batch n - Batch Number Previous Batch n - Product Number
5892 to 5895
Spare Spare
Reference Temperature
nd
Reference Temperature
Reference Temperature
4-8
20/24.71+ w 04/98
Volume 4
4.5.
INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode.
5904 to 5919 5920 to 5929 5930 5931 5932 5933 5934 5935 5936 5937 5938 5939 5940 5941 5942 5943 to 5960 5961 5962 5963 5964 to 5973
Spare Spare Pulses - Total Linear Correction Factor - 1st Run Pulses - Total Linear Correction Factor - 10th Run Net Total since Last Prove Prove Report Number Previous Prove Totalizer Totalizer Reading This Prove Pulses - Forward - 4th Last Pulses - Total - 4th Last Pulses - Forward - 3rd Last Pulses - Total - 3rd Last Pulses - Forward - 2nd Last Pulses - Total - 2nd Last Pulses - Forward - Last Pulses - Total - Last Pulses - Forward - 1st Run Pulses - Total - 1st Run Pulses - Forward - 10 Run Pulses - Total - 10th Run Previous Meter Factor - from Last Prove Actual Meter Factor - Current Run Flowmeter Frequency - 1st Run Flowmeter Frequency - 10 Run
th th
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
20/24.71+ w 04/98
4-9
Chapter 4
4.5.1.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
5997 to 5999
Spare Spare
4-10
20/24.71+ w 04/98
Volume 4
6001 to 6999
Reserved Reserved
5.1.
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
Any analog output point which physically exists can be read via these point numbers. Data returned is expressed as a percentage of the output value. Only those points which physically exist and have been assigned to Modbus control by assigning zero (0) at 'D/A Out Assign' (see Volume 3) should be written to Outputs which are not assigned to Modbus control will be overwritten every 500 msec by the flow computer. Data written should be within the range of -5.00 to 11000.
7001 to 7012 Analog Output #12 Analog Output #1
7013
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Spare Spare
to 7024
20/24.71+ w 04/98
5-1
Chapter 5
5.2.
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
Database points 7025 through 7088 have been assigned as user variables (see Volume 3). The value contained in the variable depends on the associated program statement which is evaluated every 500 msec. You may read these variables at any time. You may also write to these variables but anything you write may be overwritten by the flow computer depending on the evaluation of the statement. Leave the statement blank or simply put a comment or prompt into it to avoid having the flow computer overwrite it.
7025 to 7088
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
5.3.
Points 7089 through 7099 are paired with Boolean Point Variables 1089 through 1099. Numeric data placed in 7089, for example, can be output as pulses by assigning a digital I/O point to 1089.
7089 to 7099
Programmable Accumulator #1
Data placed into 7089 is pulse out using 1089.
5-2
20/24.71+ w 04/98
Volume 4
5.4.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
The second digit of the index number defines the meter run number. For example: 7105 is the 'Temperature' variable for Meter Run #1. The same point for Meter Run #4 would be 7405.
< 7n01 < 7n02 < 7n03 Flowrate - Gross
Bbl or m /hr.
3
Flowrate - Net
Bbl or m /hr.
3
Flowrate - Mass
Klb or ton/hr.
INFO - The second digit of the index number defines the number of the meter run number.
< 7n04
Flowrate - NSV
Bbl or m /hr.
3
*
INFO - Calculated averages can be either flow weighted or time weighted depending upon point number.
* *
Notes:
* *
7n08 7n09
* *
7n10 7n11
* * * * * *
API Flowing API @ 60 F / API @ Reference Temperature Specific Gravity Flowing Specific Gravity @ 60 F / Density @ 15 C VCF
Volume Correction Factor.
CPL
Correction Factor for Pressure on Liquids.
20/24.71+ w 04/98
5-3
Chapter 5
7n18
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
7n19 7n20 7n21 7n22 7n23 7n24 7n25 7n26 7n27 7n28 7n29
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
7n30 7n31 7n32 7n33 7n34 7n35 7n36 7n37 * ~ 7n38 * ~ 7n39 * ~ 7n40 7n41 7n42 7n43 7n44 7n45 7n46
Notes:
5-4
20/24.71+ w 04/98
Volume 4
7n47
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Coefficient a LCF
Linear Correction Factor.
Coefficient c Coefficient d Coefficient e Coefficient f Coefficient g Spare Spare Meter Run Gross/Mass Flowrate - Low Limit Meter Run Gross/Mass Flowrate - High Limit Meter Temperature - Low Limit Meter Temperature - High Limit Meter Temperature - Override Meter Temperature - @ 4mA Meter Temperature - @ 20mA
INFO - The second digit of the index number defines the number of the meter run number.
7n55 to 7n60
Note:
# #
Indicates meter run gross or mass flow rate depending on which unit is selected
7n68 to 7n72
7n73 to 7n77
7n78 to 7n82
Density Transducer Pressure - Low Limit Density Transducer Pressure - @ 20mA Density Transducer - Correction Factor
Used to correct densitometer.
20/24.71+ w 04/98
5-5
Chapter 5
*
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
* * * * * * * *
Densitometer - Constant #2
K1/T0.
Densitometer - Constant #3
K2/Tcoef.
Densitometer - Constant #4
K18/Tcal/Tc.
Densitometer - Constant #5
K19/Pcoef/Kt1.
Densitometer - Constant #6
K20A/Pcal/Kt2.
Densitometer - Constant #7
K20B/Kt3.
Densitometer - Constant #8
K21A/Pc.
Densitometer - Constant #9
K21B/Kp1.
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
* *
Note:
5.5.
Ninety-nine IEEE 32-bit floating point registers are provided for user scratch pad. These registers are typically used to store and group data that will be moved via peer-to-peer operations or similar uses.
7501 to 7599
5-6
20/24.71+ w 04/98
Volume 4
5.6.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
# *
7601 7602
Notes:
20/24.71+ w 04/98
5-7
Chapter 5
5.7.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
Vapor Pressure @ 100 F - Meter Run #2 Vapor Pressure @ 100 F - Meter Run #3 Vapor Pressure @ 100 F - Meter Run #4 Vapor Pressure @ 100 F - Prover Meter Run #1 - Temperature @ Leak Detect Freeze Command
See 1760 command.
Meter Run #1 - Pressure @ Leak Detection Freeze Command Meter Run #1 - Density / Gravity @ Leak Detect Freeze Command
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Spare Spare Meter Run #1 - Gross Volume Increment Meter Run #1 - Net Increment Volume Meter Run #1 - Mass Increment Meter Run #1 - NSV Increment Meter Run #2 - Temperature @ Freeze Command Meter Run #2 - Pressure @ Freeze Command Meter Run #2 - Density / Gravity @ Freeze Command
INFO - See 7n01 through 7n99 for more meter run related data.
7647 to 7649
Spare Spare
5-8
20/24.71+ w 04/98
Volume 4
*
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
* * * # # #
7657 to 7659
Spare Spare
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
* * * * # # #
Meter Run #3 - Gross Volume Increment Meter Run #3 - Net Volume Increment Meter Run #3 - Mass Increment Meter Run #3 - NSV Increment Meter Run #4 - Temperature @ Freeze Command Meter Run #4 - Pressure @ Freeze Command Meter Run #4 - Density / Gravity @ Freeze Command
INFO - See 7n01 through 7n99 for more meter run related data.
Notes:
7667 to 7669
Spare Spare
* * * * # # #
Meter Run #4 - Gross Volume Increment Meter Run #4 - Net Volume Increment Meter Run #4 - Mass Increment Meter Run #4 - NSV Increment Station - Temperature @ Freeze Command Station - Pressure @ Freeze Command Station - Density / Gravity @ Freeze Command
7677 to 7679
Spare Spare
20/24.71+ w 04/98
5-9
Chapter 5
*
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
* * *
7684 to 7698
Spare Spare
Notes:
7699
5.8.
The percentage of span for each of the 24 process input channels is available as a floating point variable point.
INFO - The data is only meaningful when the input channel is used as an analog input or a Honeywell digital transducer input. For pulse type input channels see data points located at 15131 through 15154.
7701 to 7724
7725 to 7782
Spare Spare
7783 7784 7785 7786 7787 7788 7789 7790 7791 7792 7793 7794 7795
Sequence #2 Batch Size - Meter #1 Sequence #2 Batch Size - Meter #2 Sequence #2 Batch Size - Meter #3 Sequence #2 Batch Size - Meter #4 Sequence #1 Batch Size - Meter #1 Sequence #1 Batch Size - Meter #2 Sequence #1 Batch Size - Meter #3 Sequence #1 Batch Size - Meter #4 Batch Preset Warning - Meter #1 Batch Preset Warning - Meter #2 Batch Preset Warning - Meter #3 Batch Preset Warning - Meter #4 Batch Preset Warning - Station
20/24.71+ w 04/98
5-10
Volume 4
7796
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
5.9.
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
7804
7808
Spare
7809
Auxiliary Input #1
Points 7809-7812 represent miscellaneous live input signals provided for user-defined functions.
Date - yymmdd
Read only (e.g.: the number 970527 represents May 27/ 97; the date format used here does not follow the US/European format selection).
7815 to 7820
Spare Spare
20/24.71+ w 04/98
5-11
Chapter 5
7821
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
7822 7823 7824 7825 7826 7827 7828 7829 7830 7831 7832 7833 7834 7835 7836 7837 7838 7839 7840 7841 7842 7843 7844 7845 7846 7847 7848 7849 7850
5-12
20/24.71+ w 04/98
Volume 4
7851 7852
7853
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
7854
7855 7856 7857 7858 7859 7860 7861 7862 7863 7864 7865 7866
Flow Threshold - Run Switch Flag #1 - Increasing Flow Flow Threshold - Run Switch Flag #2 - Decreasing Flow
See 1825.
Flow Threshold - Run Switch Flag #2 - Increasing Flow Flow Threshold - Run Switch Flag #3 - Decreasing Flow
See 1826.
Flow Threshold - Run Switch Flag #3 - Increasing Flow Station - Pressure - Low Limit
Points 7861-7865 are configuration settings used when the pressure is a live 4-20 mA.
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Station - Pressure - High Limit Station - Pressure - Override Station - Pressure - @ 4mA Station - Pressure - @ 20mA Station - Gravity/Density - Low Limit
Points 7866-7870 are configuration settings used when the gravity/density is a live 4-20 mA.
Station - Gravity/Density - High Limit Station - Gravity/Density - Override Station - Gravity/Density - @ 4mA Station - Gravity/Density - @ 20mA Station - Density Temperature - Low Limit
Points 7871-7875 are configuration settings used when the gravity/density is a live 4-20 mA.
Station - Density Temperature - High Limit Station - Density Temperature - Override Station - Density Temperature - @ 4mA Station - Density Temperature - @ 20mA
20/24.71+ w 04/98
5-13
Chapter 5
7876
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
* * * * * *
7877 7878 7879 7880 7881 7882 7883 7884 7885 7886 7887
Notes:
* * * * *
# Miscellaneous conversion
factors and constants.
# # # # # # #
7888 7889 7890 7891 7892 7893 7894 7895 7896 7897 7898 7899
Weight of Water
Lbm/Bbl or Kg/m .
3
Local Atmospheric Pressure Contract Base Temperature Kg/m3 to lb/ft3 Contract Base Pressure Spare Auto Prove Mode - Startup Flow Auto Prove Mode - Maximum Flow between Proves Auto Prove Mode - Minimum Flow Rate Change Auto Prove Mode - Delta Flow Rate
Flow rate unstable check.
5-14
20/24.71+ w 04/98
Volume 4
7901 7902 7903 7904 7905 7906 7907 7908 7909 7910 7911
Prover - Inlet (Left) Temperature Prover - Outlet (Right) Temperature Prover - Temperature in Use Prover - Inlet (Left) Pressure Prover - Outlet (Right) Pressure Prover - Pressure in Use Prover - Plenum Pressure
Compact Prover.
Prover - Run Time Volume - Master Prove Volume - Test Meter Calculated Plenum Pressure Prover - Density/Gravity Prover - Density Temperature Prover - Density Pressure Prover - Uncorrected Density Prover - Density Invar Rod Temperature
Small Volume Prover.
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Overtravel
Bbls/m .
3
Prover - Diameter
Inches/mm.
Prover - Modulus of Elasticity Prover - Coefficient of Cubic Expansion Prover - Base Pressure Prover - Temperature Stability Limits Prove & Meter - Temperature Deviation Prover - Count Deviation %
[(Maximum Deviation - Minimum Deviation) / Minimum Deviation] x 100%.
20/24.71+ w 04/98
5-15
Chapter 5
7929
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
7934 to 7938
Prover - Temperature Outlet (Right) - Low Limit Prover - Temperature Outlet (Right) - @ 20mA
7939 to 7943
Prover - Pressure Inlet (Left) - Low Limit Prover - Pressure Inlet (Left) - @ 20mA
7944 to 7948
Prover - Pressure Outlet (Right) - Low Limit Prover - Pressure Outlet (Right) - @ 20mA
7949 7950 7951 7952 7953 7954 7955 7956 7957 7958
Flow Rate % Change Threshold Linear Thermal Coefficient Plenum Pressure - Constant Plenum - Deadband % Plenum Pressure - @ 4mA Plenum Pressure - @ 20mA Prover - Volume Upstream Prover - Specific Gravity @ 60 F / Density @ Meter Factor Prover - Temperature @ Meter Factor Prover - Pressure @ Meter Factor
5-16
20/24.71+ w 04/98
Volume 4
Prover - Modulus of Elasticity Prover - Coefficient of Cubic Expansion Prover - K Factor Prover - Master Meter K Factor Prover - Previous Meter Factor @ Flowrate
The following refers to the data rejected during Prove Run #3. The same data is available for the Last, 1st and 2nd Prove Runs at the following addresses:
7967 7968 7969 7970 7971 7972 3rd Run - Meter Temperature 3rd Run - Meter Pressure 3rd Run - Prover Temperature 3rd Run - Prover Pressure 3rd Run - Reference Gravity 3rd Run - Flowrate
7973 to 7978
7979 to 7984
st
7985 to 7990
20/24.71+ w 04/98
5-17
Chapter 5
The following data refers to Prove Run #1. The same data is available for all 10 prove runs at the following addresses:
7991 7992 7993 7994 7995 7996 1st Run - Meter Temperature 1st Run - Meter Pressure 1st Run - Prover Temperature 1st Run - Prover Pressure 1st Run - Specific Gravity @ 60 F / Density @ Reference Temperature 1st Run - Flowrate
7997 to 8002
8003 to 8008
8009 to 8014
8015 to 8020
8021 to 8026
8027 to 8032
8033 to 8038
th
5-18
20/24.71+ w 04/98
Volume 4
8039
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
to 8044
8045 to 8050
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Prove - CPSP
Prover Correction Factor for the Effect of Pressure on Steel.
Prove - CTLP
Prover Correction Factor for the Effect of Temperature on a Liquid.
Prove - CPLP
Prover Correction Factor for the Effect of Pressure on a Liquid.
Prove - CCFP
Prover Combined Correction Factor.
Prove - CPLM
Meter Correction Factor for the Effect of Pressure on a Liquid.
Prove - CCFM
Meter Combined Correction Factor.
Prove - Average Counts multiplied by Linear Correction Factor Prove - Meter Factor Deviation % from Previous Meter Factor Prove - Actual K Factor Prove - Average Flowmeter Hertz Prove - Prover Compressibility F Factor
20/24.71+ w 04/98
5-19
Chapter 5
8075 8076
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
8092 to 8103
8104 to 8115
8116 to 8127
th
8128 to 8139
5-20
20/24.71+ w 04/98
Volume 4
8140
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
to 8151
8152 to 8163
8164 to 8175
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
8176 to 8187
8188 to 8199
> 8200 > 8201 > 8202 > 8203 > 8204 > 8205 > 8206 > 8207 > 8208 > 8209 > 8210 > 8211 > 8212 > 8213 > 8214 > 8215
Series #1 - Average Counts Series #1 - Average Meter Temperature Series #1 - Average Meter Pressure Series #1 - Average Prover Temperature Series #1 - Average Prover pressure Series #1 - Average Gravity @ 60 F or Reference Temperature Series #1 - Average Flowrate Series #1 - CTSP Series #1 - CPSP Series #1 - CTLP Series #1 - CPLP Series #1 - Average Net Prover Volume Series #1 - CTLM Series #1 - CPLM Series #1 - Average Gross Meter Volume Series #1 - Net Meter Volume
>
20/24.71+ w 04/98
5-21
Chapter 5
> 8216
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
> 8217 > 8218 > 8219 >* 8220 >* 8221 >* 8222 >* 8223
Notes:
>
Applies only to Revision 20 for US customary units. * Points 8220-8223 are only for Exxons Prover Report.
1 Run - CTLM
Meter Correction Factor for the Effect of Temperature on a Liquid.
st
1 Run - CPLM
Meter Correction Factor for the Effect of Pressure on a Liquid.
st
1 Run - CPSP
Correction factor for the Effect of Pressure on Steel.
st
5-22
20/24.71+ w 04/98
Volume 4
8244
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
to 8298 8299 to 8315 8316 to 8332 8333 to 8349 8350 to 8366 8367 to 8383 8384 to 8400
20/24.71+ w 04/98
5-23
Chapter 5
8403 Spare
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
to 8500 Spare
Previous Batch n - Average Temperature Previous Batch n - Average Pressure Previous Batch n - Average Density Previous Batch n - Average VCF Previous Batch n - Average CPL Previous Batch n - Average Meter factor Previous Batch n - Average Specific Gravity Previous Batch n - Average SG @ 60 F / Density @ Reference Temperature Previous Batch n - Average Density Temperature Previous Batch n - Average Density Pressure Previous Batch n - Average Density Correction Factor Previous Batch n - Average Unfactored Density Previous Batch n - Average K Factor Previous Batch n - Average Viscosity Previous Batch n - Average Linear Correction Factor Previous Batch n - Average Gross Flowrate Previous Batch n - Average %S&W Previous Batch n - Average Equilibrium Pressure Previous Batch n - Average API @ 60 F
8502 8503 8504 8505 8506 8507 8508 8509 8510 8511 8512 8513 8514 8515 8516 8517 8518 8519
5-24
20/24.71+ w 04/98
Volume 4
Previous Hours - Average Temperature Previous Hours - Average Pressure Previous Hours - Average Density Previous Hours - Average Specific Gravity @ 60F / Density @ Reference Temperature Previous Hours - Average K Factor Previous Hours - Average Meter Factor Previous Hours - Average %S&W
8527 to 8530
Spare Spare
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Previous Hours Average Refers to data stored at the end of the last hour. It is valid for one hour and is then overwritten. This is the data that should be used by SCADA or MMIs which need hourly averages.
8532 8533 8534 8535 8536 8537 8538 8539 8540 8541 8542 8543 8544 8545 8546 8547 8548
Previous Days Average Refers to data stored at the end of the contract day. It is valid for 24 hours and overwritten at the day start hour. This is the data that should be used by SCADA or MMIs to build daily reports.
20/24.71+ w 04/98
5-25
Chapter 5
8549
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Previous Days - Net @ 2nd Reference Temperature in Float Format Spare Spare
INFO - The indicated data (8501-8599) refers to Meter Run #1. The same data is available for all meter runs at the following addresses: Meter Run #1: 8501 through 8599 Meter Run #2: 8601 through 8699 Meter Run #3: 8701 through 8799 Meter Run #4: 8801 through 8899
8565 8566
Spare Spare
>
5-26
20/24.71+ w 04/98
Volume 4
8570 8571 8572 8573 8574 8575 8576 8577 8578 8579 8580 8581 8582 8583 8584
In Progress - Hourly Average - Temperature In Progress - Hourly Average - Pressure In Progress - Hourly Average - Density In Progress - Hourly Average - Specific Gravity @ 60F / Density @ Reference Temperature In Progress - Hourly Average - K Factor In Progress - Hourly Average - Meter Factor In Progress - Hourly Average - %S&W In Progress - Batch Average - Viscosity In Progress - Batch Average - Linear Correction Factor In Progress - Batch Average - Gross Flowrate In Progress - Daily Average - Viscosity In Progress - Daily Average - Linear Correction Factor In Progress - Daily Average - Gross Flowrate In Progress - Daily Average - %S&W In Progress - Daily Average - %S&W
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
8585
Spare
Previous Batch - Gross in Float Format Previous Batch - Net in Float Format Previous Batch - Mass in Float Format Previous Batch - NSV in Float Format Previous Batch - Net @ 2
nd
Reference Temperature
20/24.71+ w 04/98
5-27
Chapter 5
> 8591
Calculated Specific Gravity @ 60F using Table 23B when Table 24C is selected.
Spare Spare Meter Density Spare Spare Meter Current - %S&W Meter Current - CSW Meter Current - VCF @ 2nd Reference Temperature
INFO - The indicated data (8501-8599) refers to Meter Run #1. The same data is available for all meter runs at the following addresses: Meter Run #1: 8501 through 8599 Meter Run #2: 8601 through 8699 Meter Run #3: 8701 through 8799 Meter Run #4: 8801 through 8899
Notes:
>
5-28
20/24.71+ w 04/98
Volume 4
8931
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
8932 8933 8934 8935 8936 8937 8938 8939 8940 8941 8942 8943 8944 8945 8946 8947 8948 8949 8950 8951 8952 8953 8954 8955
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
8956 to 8960
Spare Spare
20/24.71+ w 04/98
5-29
Chapter 5
8961
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
8962 8963 8964 8965 8966 8967 8968 8969 8970 8971 8972 8973 8974 8975 8976 8977 8978 8979 8980
8981 to 8985
Spare Spare
Station - Previous Batch - Gross in Float Format Station - Previous Batch - Net in Float Format Station - Previous Batch - Mass in Float Format Station - Previous Batch - NSV in Float Format Station - Previous Batch - Net @ 2nd Reference Temperature
8991 to 8999
Spare Spare
5-30
20/24.71+ w 04/98
Volume 4
These are ASCII text files which serve as a format template for certain printed reports.
9001 9002 9003 9004 9005 to 9100 Spare Report Template - Snapshot / Interval Report Template - Batch Report Template - Daily Report Template - Prove Spare
INFO - These ASCII text buffers are accessed using Modbus function codes 65 for reads and 66 for writes. The index number for each 9000 type variable refers to the complete text buffer which may be as big as 8192 bytes. Data is transmitted or received as multiple transmissions of 128 byte packets (see Chapter 6)
6.2.
20/24.71+ w 04/98
6-1
Chapter 6
6.3.
INFO - These ASCII text buffers are accessed using Modbus function codes 65 for reads and 66 for writes. The index number for each 9000 type variable refers to the complete text buffer which may be as big as 8192 bytes. Data is transmitted or received as multiple transmissions of 128 byte packets (see Chapter 6)
6.4.
6.5.
9401
6-2
20/24.71+ w 04/98
Volume 4
6.6.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
The following buffer is used to retrieve miscellaneous reports. Report data is loaded into this buffer depending on which bit is written to integer point 15129. Reports which are retrieved using this buffer are: o o o o o Current Snapshot Report Alarm Report Audit Trail Report Status Report Product File Report
Text Archive Data defined by integers 15127 and 15128 is also retrieved using this buffer.
9402 Miscellaneous Report Buffer
9403 to 13000
Spare Spare
20/24.71+ w 04/98
6-3
Volume 4
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
The following data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni before manipulating configuration data directly via a serial port or programmable variable statements.
7.1.
7.1.1.
13001 13002 13003 13004
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
Meter Run #1 - Pressure I/O Point Meter Run #1 - Density I/O Point Meter Run #1 - Density Type
1=API; 2=SG; 3=gr/cc; 4=Solartron; 5=Sarasota; 6=UGC.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Meter Run #1 - Density Temperature I/O Point Meter Run #1 - Density Temperature Type
0=DIN RTD; 1=Amer RTD; 2=4-20mA/Honeywell.
Meter Run #1 - Density Press I/O Point Meter Run #1 - Density @ Reference Conditions
0=Flowing; 1=Reference.
20/24.71+ w 04/98
7-1
Chapter 7
13014
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
Meter Run #3 - Flow I/O Point Meter Run #3 - Density @ Reference Conditions Spare Spare Meter Run #3 - Flowmeter Dual Pulse Fidelity
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
Meter Run #4 - Flow I/O Point Meter Run #4 - Density @ Reference Conditions Spare Spare Meter Run #4 - Flowmeter Dual Pulse Fidelity
7-2
20/24.71+ w 04/98
Volume 4
7.1.2.
13053 13054 13055 13056 13057 13058 13059 13060 13061 13062 13063 13064 13065 13066 13067 13068 13069 13070
Prover - Temperature Outlet (Right) - I/O Point Prover - Temperature Outlet (Right) - Type
0=DIN RTD; 1=Amer RTD; 2=4-20mA/Honeywell.
Prover - Pressure Inlet (Left) - I/O Point Prover - Pressure Outlet (Right) - I/O Point Prover - Plenum Pressure - I/O Point Prover - Density Temperature - I/O Point Prover - Density Temperature - Type
0=DIN RTD; 1=Amer RTD; 2=4-20mA/Honeywell.
Station - Pressure - I/O Point Station - Density - I/O Point Station - Density - Type
1=API; 2=SG; 3=gr/cc; 4=Solartron; 5=Sarasota; 6=UGC.
Notes:
< 13071
<
13072 13073
Spare Spare
20/24.71+ w 04/98
7-3
Chapter 7
7.1.3.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
13074 13075 13076 13077 13078 13079 13080 13081 13082 13083 13084
Number of A Combo Modules Installed Number of B Combo Modules Installed Number of C Combo Modules Installed Number of Digital Modules Installed Number of Serial Modules Installed Number of E Combo Modules Installed Number of H Combo Modules Installed Number of ED Combo Modules Installed Spare Spare
7.1.4.
13085 13086 13087 13088 13089 13090 13091 13092 13093 13094 13095
Serial Port #1 - ID
Read only point which reports back the number of the port you are connected to.
7-4
20/24.71+ w 04/98
Volume 4
13096
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
13105 to 13107 13108 13109 13110 13111 13112 13113 13114 13115 13116
Spare Spare Serial Port #3 - Baud Rate Serial Port #3 - Data Bits Serial Port #3 - Stop Bits Serial Port #3 - Parity Serial Port #3 - Transmit Delay Serial Port #3 - Modbus or Node ID Serial Port #3 - Protocol Type
0=Modbus RTU; 1=Modbus ASCII; 2=Modbus RTU Modem (Relaxed Timing).
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
13117 to 13119 13120 13121 13122 13123 13124 13125 13126 13127
Spare Spare Serial Port #4 - Baud Rate Serial Port #4 - Data Bits Serial Port #4 - Stop Bits Serial Port #4 - Parity Serial Port #4 - Transmit Delay Serial Port #4 - Enable CRC Checking Serial Port #4 - Modbus or Node ID Serial Port #4 - Protocol Type
0=Modbus RTU; 1=Modbus ASCII; 2=Modbus RTU Modem (Relaxed Timing); 3=AllenBradley Full Duplex DF1; 4=Allen-Bradley Half Duplex.
13128
20/24.71+ w 04/98
7-5
Chapter 7
7.1.5.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
13136 to 13142
PID Loop #2 - I/O Point Assignment - Remote Setpoint PID Loop #2 - Startup Mode
13143 to 13149
PID Loop #3 - I/O Point Assignment - Remote Setpoint PID Loop #3 - Startup Mode
13150 to 13156
PID Loop #4 - I/O Point Assignment - Remote Setpoint PID Loop #4 - Startup Mode
I/O Point Assignment - Auxiliary Input #1 I/O Point Assignment - Auxiliary Input #2 I/O Point Assignment - Auxiliary Input #3 I/O Point Assignment - Auxiliary Input #4
7-6
20/24.71+ w 04/98
Volume 4
7.1.6.
CAUTION!
13161 13162 13163 13164 13165 13166 13167 13168 13169 13170 13171 13172 13173 13174 13175 13176 13177 13178 13179 13180 13181 13182 13183 13184 13185 13186 13187 13188 13189 13190 13191 13192 13193 PLC Group #1 - Index 1 PLC Group #1 - Number of Points 1 PLC Group #1 - Index 2 PLC Group #1 - Number of Points 2 PLC Group #1 - Index 3 PLC Group #1 - Number of Points 3 PLC Group #1 - Index 4 PLC Group #1 - Number of Points 4 PLC Group #1 - Index 5 PLC Group #1 - Number of Points 5 PLC Group #1 - Index 6 PLC Group #1 - Number of Points 6 PLC Group #1 - Index 7 PLC Group #1 - Number of Points 7 PLC Group #1 - Index 8 PLC Group #1 - Number of Points 8 PLC Group #1 - Index 9 PLC Group #1 - Number of Points 9 PLC Group #1 - Index 10 PLC Group #1 - Number of Points 10 PLC Group #1 - Index 11 PLC Group #1 - Number of Points 11 PLC Group #1 - Index 12 PLC Group #1 - Number of Points 12 PLC Group #1 - Index 13 PLC Group #1 - Number of Points 13 PLC Group #1 - Index 14 PLC Group #1 - Number of Points 14 PLC Group #1 - Index 15 PLC Group #1 - Number of Points 15 PLC Group #1 - Index 16 PLC Group #1 - Number of Points 16
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
PLC Group #2 - Starting Address PLC Group #2 - Index 1 PLC Group #2 - Index 16 PLC Group #2 - Number of Points 16
20/24.71+ w 04/98
7-7
Chapter 7
13227
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
PLC Group #4 - Starting Address PLC Group #4 - Index 1 PLC Group #4 - Index 6 PLC Group #4 - Number of Points 6
PLC Group #5 - Starting Address PLC Group #5 - Index 1 PLC Group #5 - Index 6 PLC Group #5 - Number of Points 6
13286 to 13288
Spare Spare
Input Type - Auxiliary Input #2 Input Type - Auxiliary Input #3 Input Type - Auxiliary Input #4
13297 to 13299
Spare Spare
7-8
20/24.71+ w 04/98
Volume 4
7.1.7.
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
Transaction #1 - Slave ID Transaction #1 - Read / Write Transaction #1 - Source Index Transaction #1 - Number of Points Transaction #1 - Destination Index
13307
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
to 13311
13312 to 13316
13317 to 13321
13322 to 13326
13327 to 13331
13332 to 13336
20/24.71+ w 04/98
7-9
Chapter 7
13337
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
to 13341
13342 to 13346
13347 to 13351
13352 to 13356
13357 to 13361
13362 to 13366
13367 to 13371
13372 to 13376
13377 to 13381
7-10
20/24.71+ w 04/98
Volume 4
13382
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
Number of Decimal Places for Gross & Net Totalizer Spare Number of Decimal Places for Mass Totalizer Spare Number of Decimal Places for Factors on Batch Report Number of Decimal Places for Meter Factor on Batch Report Number of Decimal Places for Factors on Prove Report Number of Decimal Places for Meter Factor on Prove Report Spare Spare Override Code - Auxiliary Input #1 Override Code - Auxiliary Input #2 Override Code - Auxiliary Input #3 Override Code - Auxiliary Input #4 Spare Spare Meter Run #1 - Temperature Damping Factor Meter Run #1 - Pressure Damping Factor Meter Run #1 - Density Temp Damping Factor Meter Run #1 - Density Press Damping Factor
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
13390 13391 13392 13393 13394 13395 13396 13397 13398 13399 13400 13401 13402 13403 13404 13405
13406 13407
Spare Spare
13408 to 13411
Meter Run #2 - Temperature Damping Factor Meter Run #2 - Density Press Damping Factor
20/24.71+ w 04/98
7-11
Chapter 7
13412
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
13413
13414 to 13417
Meter Run #3 - Temperature Damping Factor Meter Run #3 - Density Press Damping Factor
13418 13419
Spare Spare
13420 to 13423
Meter Run #4 - Temperature Damping Factor Meter Run #4 - Density Press Damping Factor
13424 13425 13426 13427 13428 13429 13430 13431 13432 13433 13434 13435 13436
Damping Factor - Station - Density Temperature Damping Factor - Station - Density Pressure Damping Factor - Prover - Inlet (Left) Temperature Damping Factor - Prover - Outlet (Right) Temperature Damping Factor - Prover - Inlet (Left) Pressure Damping Factor - Prover - Outlet (Right) Pressure Damping Factor - Plenum Pressure Damping Factor - Prover - Density Temperature Damping Factor - Prover - Density Pressure Damping Factor - Auxiliary Input #1 Damping Factor - Auxiliary Input #2 Damping Factor - Auxiliary Input #3 Damping Factor - Auxiliary Input #4
13437 to 13449
Spare Spare
7-12
20/24.71+ w 04/98
Volume 4
13450
CAUTION!
13451 13452 13453 13454 13455 13456 13457 13458 13459 13460 13461
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
13462
13463 13464 13465 13466 13467 13468 13469 13470 13471 13472 13473 13474 13475 13476 13477 13478 to 13499
Redundancy - Master PID #1 - Setpoint Mode Redundancy - Master PID #2 - Valve Mode Redundancy - Master PID #2 - Setpoint Mode Redundancy - Master PID #3 - Valve Mode Redundancy - Master PID #3 - Setpoint Mode Redundancy - Master PID #4 - Valve Mode Redundancy - Master PID #4 - Setpoint Mode Redundancy - Slave PID #1 - Valve Mode Redundancy - Slave PID #1 - Setpoint Mode Redundancy - Slave PID #2 - Valve Mode Redundancy - Slave PID #2 - Setpoint Mode Redundancy - Slave PID #3 - Valve Mode Redundancy - Slave PID #3 - Setpoint Mode Redundancy - Slave PID #4 - Valve Mode Redundancy - Slave PID #4 - Setpoint Mode Spare Spare
20/24.71+ w 04/98
7-13
Chapter 7
7.1.8.
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
The following entries are used to define the record structure of each Raw Data Archive file:
Archive 701 #1 - Starting Index Archive 701 #1 - Number of Points Archive 701 #16 - Starting Index Archive 701 #16 - Number of points
Archive 702 #1 - Starting Index Archive 702 #1 - Number of Points Archive 702 #16 - Starting Index Archive 702 #16 - Number of Points
Archive 703 #1 - Starting Index Archive 703 #1 - Number of Points Archive 703 #16 - Starting Index Archive 703 #16 - Number of Points
Archive 704 #1 - Starting Index Archive 704 #1 - Number of Points Archive 704 #16 - Starting Index Archive 704 #16 - Number of Points
13652 to 13659
Spare Spare
Archive 705 #1 - Starting Index Archive 705 #1 - Number of Points Archive 705 #16 - Starting Index Archive 705 #16 - Number of Points
7-14
20/24.71+ w 04/98
Volume 4
13700
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
Archive 707 #1 - Starting Index Archive 707 #1 - Number of Points Archive 707 #16 - Starting Index Archive 707 #16 - Number of Points
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
Archive 708 #1 - Starting Index Archive 708 #1 - Number of Points Archive 708 #16 - Starting Index Archive 708 #16 - Number of Points
Archive 709 #1 - Starting Index Archive 709 #1 - Number of Points Archive 709 #16 - Starting Index Archive 709 #16 - Number of Points
Archive 710 #1 - Starting Index Archive 710 #1 - Number of Points Archive 710 #16 - Starting Index Archive 710 #16 - Number of Points
13892 to 13899
Spare Spare
20/24.71+ w 04/98
7-15
Chapter 7
13900
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
13901 13902 13903 13904 13905 13906 13907 13908 13909 13910 to 13919
Trigger Boolean - Archive 702 Trigger Boolean - Archive 703 Trigger Boolean - Archive 704 Trigger Boolean - Archive 705 Trigger Boolean - Archive 706 Trigger Boolean - Archive 707 Trigger Boolean - Archive 708 Trigger Boolean - Archive 709 Trigger Boolean - Archive 710 Spare Spare
CAUTION!
*13920 *13921
13930
Archive Run ?
0=Stops archiving; 1=Starts archiving.
POTENTIAL FOR DATA LOSS! Read Archive documentation before manipulating points 13920 and 13921.
Reconfigure Archive?
0=No configuration allowed; 1=Configuration changes allowed.
Archive 711 #1 Number of Points Archive 711 #16 Starting Index Archive 711 #16 Number of Points
13962
Archive 712 #1 Number of Points Archive 712 #16 Starting Index Archive 712 #16 Number of Points
13994 to 14000
Spare Spare
7-16
20/24.71+ w 04/98
Volume 4
7.2.
INFO - These ASCII string variables are accessed using Modbus function codes 03 for reads, and 16 for writes. Note that the index number for each string refers to the complete string which occupies the space of eight 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial string. Each string counts as one point in the normal Omni Modbus mode.
14001 to 14048 14049 14050 14051 to 14098 14099 14100 14101 to 14148
Modicon Compatible Mode - For the purposes of point count only, each string counts as 8 registers. The starting address of the string still applies.
14149
14150
14151 to 14198
Comment String - Variable Statement #7025 Comment String - Variable Statement #7072
14199 to 14200
Spare Spare
14201 to 14216
20/24.71+ w 04/98
7-17
Chapter 7
14217 Spare Spare
CAUTION!
to 14220
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
14221 to 14236
14237 to 14240
Spare Spare
INFO - These ASCII string variables are accessed using Modbus function codes 03 for reads, and 16 for writes. Note that the index number for each string refers to the complete string which occupies the space of eight 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial string. Each string counts as one point in the normal Omni Modbus mode.
14241 to 14256
Comment String - Boolean Statement #1073 Comment String - Boolean Statement #1088
14257 to 14260
Spare Spare
Modicon Compatible Mode - For the purposes of point count only, each string counts as 8 registers. The starting address of the string still applies.
14261 to 14276
Comment String - Variable Statement #7073 Comment String - Variable Statement #7088
14277 to 14300
Spare Spare
14301 to 14312
Comment String - Assign - Digital to Analog Output #1 Comment String - Assign - Digital to Analog Output #12
14321 to 14344
Comment String - Assign - Digital I/O Point #1 Comment String - Assign - Digital I/O Point #24
7-18
20/24.71+ w 04/98
Volume 4
14360
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
14361 14362 14363 14364 14365 14366 14367 14380 14381 14382 14383 to 15000
7.3.
INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode.
15001 to 15012
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
15017 to 15020
15021 to
20/24.71+ w 04/98
7-19
Chapter 7
15024
15025
CAUTION!
to 15028
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
15029 to 15032
15033 to 15036
INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode.
15037 to 15040
15041 to 15044
15045 to 15048
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
15049 to 15052
Digital Point #10 - Assignment Digital Point #10 - Timer - Pulse Width
15053 to 15056
Digital Point #11 - Assignment Digital Point #11 - Timer - Pulse Width
7-20
20/24.71+ w 04/98
Volume 4
15057 to 15060
15061
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Digital Point #13 - Assignment Digital Point #13 - Timer - Pulse Width
to 15064
15065 to 15068
Digital Point #14 - Assignment Digital Point #14 - Timer - Pulse Width
15069 to 15072
Digital Point #15 - Assignment Digital Point #15 - Timer - Pulse Width
15073 to 15076
Digital Point #16 - Assignment Digital Point #16 - Timer - Pulse Width
15077 to 15080
Digital Point #17 - Assignment Digital Point #17 - Timer - Pulse Width
15081 to 15084
Digital Point #18 - Assignment Digital Point #18 - Timer - Pulse Width
15085 to 15088
Digital Point #19 - Assignment Digital Point #19 - Timer - Pulse Width
15089 to 15092
Digital Point #20 - Assignment Digital Point #20 - Timer - Pulse Width
20/24.71+ w 04/98
7-21
Chapter 7
15093 to 15096
15097
Digital Point #22 - Assignment Digital Point #22 - Timer - Pulse Width
(10msec Ticks)
CAUTION!
to 15100
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
15101 to 15104
Digital Point #23 - Assignment Digital Point #23 - Timer - Pulse Width
15105 to 15108
Digital Point #24 - Assignment Digital Point #24 - Timer - Pulse Width
INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode.
Assign - Front Panel Counter A Assign - Front Panel Counter B Assign - Front Panel Counter C Max Comparitor - Error Counts per Batch - Meter #1
Points 15112-15115 represent dual pulse error checks.
Max Comparitor - Error Counts per Batch - Meter #2 Max Comparitor - Error Counts per Batch - Meter #3 Max Comparitor - Error Counts per Batch - Meter #4
15116 to 15119
Spare Spare
Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
15120
15121
Spare
15122
7-22
20/24.71+ w 04/98
Volume 4
15123 15124 15125
20/24.71+ w 04/98
7-23
Chapter 7
15126
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
B16 B17 B18 B19 B20 B21 B22 B23 B24 B25 B26 B27 B28 B29 B30 B31 MSB
Flow Rate Unstable No Prove Permissive Prover Seal Not OK Meter Not Active Piston Downstream Checking Plenum Master Meter Proving Check Stability Master Meter Spare Spare Power Fail Flag End Batch #4 End Batch #3 End Batch #2 End Batch #1 End Batch Station
15127 15128
15129
7-24
20/24.71+ w 04/98
Volume 4
15129
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements. INFO - These 32-bit long integer variables are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple writes. Note that the index number for each variable refers to one complete long integer which occupies the space of two 16-bit registers. It must be accessed as a complete unit. You cannot read or write a partial 32-bit integer. Each 32-bit long integer counts as one point in the normal Omni Modbus mode. Modicon Compatible Mode - For the purpose of point count only, each 32-bit integer counts as two registers. The starting address of the 32-bit integer still applies.
15130
Spare
15131 to 15154
15155 to 15199
Spare Spare
20/24.71+ w 04/98
7-25
Chapter 7
Flow Computer Configuration Data (13001- 18999) Archive Data File Size
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
Note:
* Archive Data File Size These variables contain the number of bytes each archive file uses within memory. They are updated when the archiving process is started and memory is allocated. The maximum memory that can be allocated to this group of variables is a total of 229359 bytes.
15211 15212
Spare Spare
15213
15214
15215 to 17000
Spare Spare
7-26
20/24.71+ w 04/98
Volume 4
7.4.
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
17025 to 17048
Pulses per Unit - Digital I/O #1 Pulses per Unit - Digital I/O #24
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
Pulses per Unit - Counter A Pulses per Unit - Counter B Pulses per Unit - Counter C PID #1 - Remote Setpoint - Low Limit
Setpoint download will be limited to this setting.
17056 17057
PID #1 - Primary Gain PID #1 - Primary Repeats/Minute PID #1 - Secondary Value - @ Zero PID #1 - Secondary Value - @ Full Scale PID #1 - Secondary Gain PID #1 - Secondary Repeats/Minute PID #1 - Maximum Ramp Up Rate % - p/500 msec
Limits rate of valve movement at startup only.
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
# #
Note:
# Input expected is
engineering units.
PID #1 - Deadband %
No change in output if the % error is less than this
20/24.71+ w 04/98
7-27
Chapter 7
17067
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
to 17081
17082 to 17096
17097 to 17111
17112 to 17123
17124 to 17135
Spare Spare
PID #1 - Primary Controlled Variable Value PID #1 - Secondary Controlled Variable Value PID #1 - Control Output % PID #1 - Primary Setpoint Value PID #1 - Secondary Setpoint Value
17141 to 17145
Spare Spare
17146 to 17150
7-28
20/24.71+ w 04/98
Volume 4
17151 to 17155 Spare Spare
17156
CAUTION!
to 17160
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
17161 to 17165
Spare Spare
17166 to 17170
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
17171 to 17175
Spare Spare
17176 17177
17178 17179
Spare Spare
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Meter #2 - Full Scale - Gross Flowrate Meter #2 - Full Scale - Mass Flowrate Spare Spare
Meter #3 - Full Scale - Gross Flowrate Meter #3 - Full Scale - Mass Flowrate Spare Spare
20/24.71+ w 04/98
7-29
Chapter 7
17188
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
17192 17193
17194 to 17197
17198
Alarm Deadband %
0-5%. Global dead-band applied to all analog alarms. Variable must return this % out of alarm for alarm to cancel.
17199 to 17202
Spare Spare
17203 to 17218
Notes:
<
17235 to 17259
Spare Spare
7-30
20/24.71+ w 04/98
Volume 4
17260
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
17265 to 17269
17270 to 17274
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
17275 * * * * * * * * * 17276 17277 17278 17279 17280 17281 17282 17283 17284 17285 17286
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Note:
* *
17287
17288 to 17379
Reserved Reserved
20/24.71+ w 04/98
7-31
Chapter 7
17380
Application Revision 20/24.71+ - This database corresponds to Application Revision 20/24.71+ for Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems, with K Factor Linearization. Both US and metric unit versions are considered.
17385 to 17389
17390 to 17394
17395 to 17399
17400 to 17500
Spare Spare
17501 17502 17503 17504 17505 17506 17507 17508 17509 17510 17511 17512
Meter #1 - K Factor #1
See 3122 for matching flow frequency entry.
Meter #1 - K Factor #2 Meter #1 - K Factor #3 Meter #1 - K Factor #4 Meter #1 - K Factor #5 Meter #1 - K Factor #6 Meter #1 - K Factor #7 Meter #1 - K Factor #8 Meter #1 - K Factor #9 Meter #1 - K Factor #10 Meter #1 - K Factor #11 Meter #1 - K Factor #12
17513 to 17600
Spare Spare
7-32
20/24.71+ w 04/98
Volume 4
17601
CAUTION!
Flow computer configuration data is especially critical to the correct operation of the flow computer. Any modifications to this data while operating the flow computer could cause unpredictable results which could cause measurement or control errors. Users are encouraged to consult with Omni Flow Computers, Inc. before manipulating configuration data directly via a serial port or programmable variable statements.
17613 to 17700
Spare Spare
17701 to 17712
Meter #3 - K Factor #1
See 3322 for matching flow frequency entry.
INFO - These 32 Bit IEEE Floating Point variables are accessed using Modbus function code 03 for all reads, 06 for single writes or 16 for single or multiple writes. Note that the index number for each variable refers to the complete floating point variable which occupies the space of two 16- bit registers. It must be accessed as a complete unit. You cannot read or write a partial variable. Each floating point variable counts as one point in the normal Omni Modbus mode.
17713 to 17800
Spare Spare
17801 to 17812
Meter #4 - K Factor #1
See 3422 for matching flow frequency entry.
17813
Modicon Compatible Mode - For the purpose of point count only, each IEEE float point counts as 2 registers. The starting address of the variable still applies.
Spare Spare
to 17899
17900 to 18174
Reserved Reserved
Note:
18175 to 20000
Reserved Reserved
20001 to 49999
Reserved Reserved
20/24.71+ w 04/98
7-33
Volume 4d
1815
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
1816
1817
1821 to 1826
Spare Spare
1827
Note:
# # # # # #
Snapshot Printed
Indicates snapshot report printed.
1838
1839
Spare
23/27.71+ 05/98
1-11
Chapter 1
~
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
1842
to 1857
Notes:
# # # #
1862 1863 1864 1865 1866 to 1869 1870 to 1873 1874 to 1877
Reference Specific Gravity - Transducer Failed Low Reference Specific Gravity - Low Alarm Reference Specific Gravity - High Alarm Reference Specific Gravity - Transducer Failed High Mol% Nitrogen - Transducer Failed Low Mol% Nitrogen - Transducer Failed High Mol% Carbon Dioxide - Transducer Failed Low Mol% Carbon Dioxide - Transducer Failed High Heating Value - Transducer Failed Low Heating Value - Transducer Failed High
* * *
1881 1882
Spare Spare
1-12
23/27.71+ 05/98
Volume 4d
1883
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
1887 to 1890
Auxiliary Input #2 - Transducer Failed Low Auxiliary Input #2 - Transducer Failed High
Note:
1891 to 1894
Auxiliary Input #3 - Transducer Failed Low Auxiliary Input #3 - Transducer Failed High
1895 to 1898
Note: See 2600 area and 2800 area for more station alarms and status points.
Auxiliary Input #4 - Transducer Failed Low Auxiliary Input #4 - Transducer Failed High
1899 to 2000
Spare Spare
23/27.71+ 05/98
1-13
Chapter 1
1.3.9.
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
The following Boolean points are flags indicating that a totalizer has rolled-over (i.e., reached maximum count and restarted from zero). These flags are used to conditionally print characters (usually **) in front of the totalizer which has rolled on the appropriate report. Examination of an Omni Custom Report Template will show how this is accomplished. The second digit of the index number defines the number of the meter run. See also points at 2801 for station versions of these flags.
2n01 2n02 2n03 2n04 2n05 2n06 2n07 2n08 2n09 2n10 2n11 2n12 2n13 2n14 2n15 2n16 2n17 2n18 2n19 2n20 2n21 2n22 2n23 2n24 2n25 2n26 2n27 2n28 Batch In Progress - Gross Totalizer Rollover Flag Batch In Progress - Net Totalizer Rollover Flag Batch In Progress - Mass Totalizer Rollover Flag Batch In Progress - Energy Totalizer Rollover Flag Batch In Progress - Cumulative - Gross Totalizer Rollover Flag Batch In Progress - Cumulative - Net Totalizer Rollover Flag Batch In Progress - Cumulative - Mass Totalizer Rollover Flag Batch In Progress - Cumulative - Energy Totalizer Rollover Flag Daily In Progress - Gross Totalizer Rollover Flag Daily In Progress - Net Totalizer Rollover Flag Daily In Progress - Mass Totalizer Rollover Flag Daily In Progress - Energy Totalizer Rollover Flag Daily In Progress - Cumulative - Gross Totalizer Rollover Flag Daily In Progress - Cumulative - Net Totalizer Rollover Flag Daily In Progress - Cumulative - Mass Totalizer Rollover Flag Daily In Progress - Cumulative - Energy Totalizer Rollover Flag Previous Batch - Gross Totalizer Rollover Flag Previous Batch - Net Totalizer Rollover Flag Previous Batch - Mass Totalizer Rollover Flag Previous Batch - Energy Totalizer Rollover Flag Previous Batch - Cumulative - Gross Totalizer Rollover Flag Previous Batch - Cumulative - Net Totalizer Rollover Flag Previous Batch - Cumulative - Mass Totalizer Rollover Flag Previous Batch - Cumulative - Energy Totalizer Rollover Flag Previous Daily - Gross Totalizer Rollover Flag Previous Daily - Net Totalizer Rollover Flag Previous Daily - Mass Totalizer Rollover Flag Previous Daily - Energy Totalizer Rollover Flag
Note: The In Progress flags are those which the flow computer uses when printing the reports on the connected printer. Use the Previous flags if the report is being printed by another device such as a SCADA or MMI. This is necessary because the flow computer clears the In Progress data immediately after it prints the local report.
1-14
23/27.71+ 05/98
Volume 4d
2n29
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
2n33 to 2n40
Spare Spare
Note: Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
2n41
Note: See 1800 area and 2800 area for more station alarms and status points.
2n42 to 2n99
Spare Spare
2500 to 2600
Spare Spare
23/27.71+ 05/98
1-15
Chapter 1
2601 2602 2603 2604 2605 2606 2607 2608 2620 2621
Override in Use - Auxiliary Input #1 Override in Use - Auxiliary Input #2 Override in Use - Auxiliary Input #3 Override in Use - Auxiliary Input #4 Override in Use - Reference Specific Gravity Override in Use - % Nitrogen Transducer Override in Use - % Carbon Dioxide Transducer Override in Use - Heating Value Transducer Calibration Data Checksum Error
Correctable as secondary copy was OK.
INFO - To differentiate between normal message responses and unsolicited transmissions, Modbus function code 67 appears in the transmitted message rather than function code 03.
2622
2623
2624 to 2700
Spare Spare
1-16
23/27.71+ 05/98
Volume 4d
1.3.11. Commands Which Cause Custom Data Packets to be Transmitted Without a Poll
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
Activating any of the edge triggered command points below causes the appropriate Custom Data Packet to be transmitted out of the selected serial port without the serial port being polled for data. This function can be useful when communicating via VSAT satellite systems where operating cost is directly proportional to RF bandwidth used.
2701
Note: Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
Data Packet #1 to Serial Port #1 Data Packet #2 to Serial Port #1 Data Packet #3 to Serial Port #1 Data Packet #1 to Serial Port #2 Data Packet #2 to Serial Port #2 Data Packet #3 to Serial Port #2 Data Packet #1 to Serial Port #3 Data Packet #2 to Serial Port #3 Data Packet #3 to Serial Port #3 Data Packet #1 to Serial Port #4 Data Packet #2 to Serial Port #4 Data Packet #3 to Serial Port #4
2702 2703 2704 2705 2706 2707 2708 2709 2710 2711 2712
2713 2714
2715 2716
23/27.71+ 05/98
1-17
Chapter 1
Status inputs and outputs are required to achieve the automatic meter tube switching function. The command input points below are used to interface to motor-operated valve (MOV) limit switch signals and allow the user to take an MOV out of service. See 2877 to 2896 for points needed to send MOV open and close commands.
INFO - To differentiate between normal message responses and unsolicited transmissions, Modbus function code 67 appears in the transmitted message rather than function code 03.
Meter #2 - MOV - Open Status Meter #2 - MOV - Closed Status Meter #2 - MOV - In Service Status
How the MOV Limit Switches are Interpreted 2717=On 2717=Off 2717=Off 2717=On 2718=Off Open 2718=On Closed 2718=Off Travel 2718=On Illegal
Meter #3 - MOV - Open Status Meter #3 - MOV - Closed Status Meter #3 - MOV - In Service Status Meter #4 - MOV - Open Status Meter #4 - MOV - Closed Status Meter #4 - MOV - In Service Status Spare Spare
Archive Trigger Command - Meter #2 Archive Trigger Command - Meter #3 Archive Trigger Command - Meter #4 Spare
1-18
23/27.71+ 05/98
Volume 4d
The following Boolean points are flags indicating that a totalizer has rolled-over (i.e., reached maximum count and restarted from zero). These flags are used to conditionally print characters (usually ** ) in front of the totalizer which has rolled on the appropriate report. Examination of an Omni Custom Report Template will show how this is accomplished. See also points at 2n01 for meter run versions of flags.
2801 2802 2803 2804 2805 2806 2807 2808 2809 2810 2811 2812 2813 2814 2815 2816 2817 2818 2819 2820 2821 2822 2823 2824 2825 2826 2827 2828 Batch In Progress - Gross Totalizer Rollover Flag Batch In Progress - Net Totalizer Rollover Flag Batch In Progress - Mass Totalizer Rollover Flag Batch In Progress - Energy Totalizer Rollover Flag Batch In Progress - Cumulative - Gross Totalizer Rollover Flag Batch In Progress - Cumulative - Net Totalizer Rollover Flag Batch In Progress - Cumulative - Mass Totalizer Rollover Flag Batch In Progress - Cumulative - Energy Totalizer Rollover Flag Daily In Progress - Gross Totalizer Rollover Flag Daily In Progress - Net Totalizer Rollover Flag Daily In Progress - Mass Totalizer Rollover Flag Daily In Progress - Energy Totalizer Rollover Flag Daily In Progress - Cumulative - Gross Totalizer Rollover Flag Daily In Progress - Cumulative - Net Totalizer Rollover Flag Daily In Progress - Cumulative - Mass Totalizer Rollover Flag Daily In Progress - Cumulative - Energy Totalizer Rollover Flag Previous Batch - Gross Totalizer Rollover Flag Previous Batch - Net Totalizer Rollover Flag Previous Batch - Mass Totalizer Rollover Flag Previous Batch - Energy Totalizer Rollover Flag Previous - Cumulative - Gross Totalizer Rollover Flag Previous - Cumulative - Net Totalizer Rollover Flag Previous - Cumulative - Mass Totalizer Rollover Flag Previous - Cumulative - Energy Totalizer Rollover Flag Previous Daily - Gross Totalizer Rollover Flag Previous Daily - Net Totalizer Rollover Flag Previous Daily - Mass Totalizer Rollover Flag Previous Daily - Energy Totalizer Rollover Flag
Note: Notice that all write commands have indexes / point addresses with a 7 in rd the 3 digit from the right.
INFO - Remember that the station is defined as a group of individual meter runs.
In Progress Flags - The In Progress flags are the flags which the flow computer uses when printing the reports on the connected printer. Use the Previous flags if the report is being printed by another device such as an SCADA or MMI. This is necessary because the flow computer clears the In Progress data immediately after it prints the local report.
23/27.71+ 05/98
1-19
Chapter 1
2829
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
All totalizers within the flow computer are long integer types. This data type uses an implied decimal position. The computer uses these flags internally to determine how to format all totalizers of the same type for printing purposes.
2858 2859 2860 2861 2862 Print 0 Decimal Place for Gross Totalizer Print 1 Decimal Place for Gross Totalizer Print 2 Decimal Places for Gross Totalizer Print 3 Decimal Places for Gross Totalizer Spare
2864
Master Status
Indicates mastership. Monitored by other flow computer in a redundant system (see 2714).
1-20
23/27.71+ 05/98
Volume 4d
2873
INFO - Boolean data is accessed using Modbus function codes 01 for reads, 05 for single point writes and 15 for multiple bit writes. Boolean data is packed 8 points to a byte when reading.
1.3.19. Boolean Command Outputs and Status Points Used For Meter Tube Switching
Status inputs and outputs are required to achieve the automatic meter tube switching function. The command output points below are used to open and close the motor-operated valve (MOV). Alarm points are also provided which indicate MOV problems. See 2717 for points needed to interface to the MOV limit switches.
MOV Alarms: Any MOV alarm will cause the flow computer to take the MOV out of service (see 2719) and send a close MOV command.
2882 to 2886
Meter #2 - Open MOV - Command Out Meter #2 - Time-out Alarm - Closing MOV
2887 to 2891
Meter #3 - Open MOV - Command Out Meter #3 - Time-out Alarm - Closing MOV
2892 to 2896
Meter #4 - Open MOV - Command Out Meter #4 - Time-out Alarm - Closing MOV
2897 to 3000
Spare Spare
23/27.71+ 05/98
1-21
Volume 4d
2.1.1.
The 16-bit integers needed to define the 20 groups of data that make up Custom Data Packet #1 which is accessed at database Index 0001 are listed below.
3001 3002 to 3039 3040 Group 20 - Starting Index Point Number Group 20 - Number of Index Points Group 1 - Starting Index Point Number Group 1 - Number of Index Points
2.1.2.
The 16-bit integers needed to define the 8 groups of data that make up Custom Data Packet #2 which is accessed at database Index 0201 are listed below.
3041 3042 to 3055 3056 Group 8 - Starting Index Point Number Group 8 - Number of Index Points Group 1 - Starting Index Point Number Group 1 - Number of Index Points
2.1.3.
The 16-bit integers needed to define the 20 groups of data that make up Custom Data Packet #3 which is accessed at database Index 0401 are listed below.
3057 3058 to 3095 3096 Group 20 - Starting Index Point Number Group 20 - Number of Index Points Group 1 - Starting Index Point Number Group 1 - Number of Index Points
23/27.71+ 05/98
2-1
Chapter 2
2.2.
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
3097 3098
3099 3100
Spare Spare
2.3.
The second digit of the index number defines the number of the meter run. For example: 3106 is the 'Meter Active Frequency' for Meter Run # 1. The same point for Meter Run # 4 would be 3406.
3n01 Override Code - Temperature
For points 3n01-3n05: 0=Never use; 1=Always use; 2=Use if transmitter fails; 3=If transmitter fails use last hours average.
3n02 3n03 3n04 3n05 3n06 3n07 3n08 3n09 3n10 3n11 3n12
Note:
Override Code - Pressure Override Code - Gravity/Density Override Code - Density Temperature Override Code - Density Pressure Active Threshold Hz
Point 1n05 is set when flow pulses exceed this frequency.
Orifice Taps
0=Flange; 1=Pipe; 2=Corner taps; 3=D&D/2; 4=Nozzle; 5 & 6= Venturi
# Downstream
temperature can be corrected to upstream conditions assuming an isentropic expansion after the orifice. Default is Disable because AGA 3 / API 14.3 DO NOT mandate this correction.
3n16
Spare
2-2
23/27.71+ 05/98
Volume 4d
3n17
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
Setpoint Mode
Read only. DO NOT WRITE! 1=Local; 0=Remote.
3n22 3n23 3n24 3n25 3n26 3n27 3n28 3n29 3n30 3n31 3n32 3n33 3n34
Frequency Point - K Factor #2 Frequency Point - K Factor #3 Frequency Point - K Factor #4 Frequency Point - K Factor #5 Frequency Point - K Factor #6 Frequency Point - K Factor #7 Frequency Point - K Factor #8 Frequency Point - K Factor #9 Frequency Point - K Factor #10 Frequency Point - K Factor #11 Frequency Point - K Factor #12 Comparitor Error Threshold
When dual pulse error checking enabled only.
Notes:
# 2s complement numbers
based on span entries 17176 through 17189. Values expressed as percentages of span in tenth percent increments;. i.e., 1000 represents 100.0%
3n35
Spare
3n36 3n37 3n38 3n39 # * # * # * ~ ~ ~ # * 3n40 3n41 3n42 3n43 3n44 3n45 3n46 3n47 3n48 3n49 3n50
Meter Run - Flow Time - Hours Since Day Start Meter Run - Flow Time - Minutes Since Day Start Meter Run - Flow Time - Hours Previous Day Meter Run - Flow Time - Minutes Previous Day Current Net Flowrate Net Totalizer Current Gross Flowrate Gross Total Current Mass Flowrate Mass Total Current Meter Run Pressure Current Meter Run Temperature Current Transducer Density/Gravity Energy Flowrate Energy Total
* Unsigned integer
totalizers cumulative based. They roll at 65536.
~ 2s complement numbers
based on the 4-20 mA spans. Values are expressed as percentages of span in tenth percent increments; i.e., 1000 equals 100.0 %.
23/27.71+ 05/98
2-3
Chapter 2
3n51
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
3n52
2.4.
Ninety-nine integer registers are provided for user scratch pad. These registers are typically used to store and group data that will be moved via peer-to-peer operations or similar operations.
3501 to 3599 Scratchpad - Short Integer #99 Scratchpad - Short Integer #1
3600
Spare
2-4
23/27.71+ 05/98
Volume 4d
2.5.
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
The 16-bit integers needed to define the variables that appear in the eight User Displays are listed below. Look in the 4601 area for string associated with setting up User Displays.
2.5.1.
3601 3602 3603 3604 3605 3606 3607 3608
2.5.2.
3609 3610 3611 3612 3613 3614 3615 3616
2.5.3.
3617 3618 3619 3620 3621 3622 3623 3624
23/27.71+ 05/98
2-5
Chapter 2
2.5.4.
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
2.5.5.
3633 3634 3635 3636 3637 3638 3639 3640
2.5.6.
3641 3642 3643 3644 3645 3646 3647 3648
2-6
23/27.71+ 05/98
Volume 4d
2.5.7.
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
2.5.8.
3657 3658 3659 3660 3661 3662 3663 3664
23/27.71+ 05/98
2-7
Chapter 2
2.6.
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
See the chapter describing how to use the raw data archiving features of the flow computer including how to manipulate the pointers below.
3701 3702 3703 Archive 701 - Maximum Records
Number of data records in archive file.
2-8
23/27.71+ 05/98
Volume 4d
3719
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
3720 3721
23/27.71+ 05/98
2-9
Chapter 2
2.7.
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
3737
3738 to 3750
Spare Spare
3751 3752
3753 to 3768
Spare Spare
3769
2-10
23/27.71+ 05/98
Volume 4d
2.8.
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
The data points below are used to map the component order of the GC analysis to the component order needed by AGA8.
3770 Component # n for % Methane 3771 Component # n for % Nitrogen 3772 Component # n for % Carbon Dioxide 3773 Component # n for % Ethane 3774 Component # n for % Propane 3775 Component # n for % Water 3776 Component # n for % Hydrogen Sulfide 3777 Component # n for % Hydrogen 3778 Component # n for % Carbon Monoxide 3779 Component # n for % Oxygen 3780 Component # n for % i-Butane 3781 Component # n for % n-Butane 3782 Component # n for % i-Pentane 3783 Component # n for % n-Pentane 3784 Component # n for % n-Hexane 3785 Component # n for % n-Heptane 3786 Component # n for % n-Octane 3787 Component # n for % n-Nonane 3788 Component # n for % n-Decane 3789 Component # n for % Helium 3790 Component # n for % Argon 3791 Component # n for Heating Value 3792 Component # n for Reference Specific Gravity
3793 to 3799
Spare Spare
23/27.71+ 05/98
2-11
Chapter 2
2.9.
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
3800
Spare Current Net Flowrate Net Totalizer Current Gross Flowrate Gross Totalizer Current Mass Flowrate Mass Totalizer
3808 to 3810
Spare Spare
# #
3811 3812 3813 3814 3815 3816 3817 3818 3819 3820 3821 3822 3823 3824
Current Energy Flowrate Energy Totalizer Fluid Type Select - Product #1 Fluid Type Select - Product #2 Fluid Type Select - Product #3 Fluid Type Select - Product #4 AGA 8 Method Select - Product #1 AGA 8 Method Select - Product #2 AGA 8 Method Select - Product #3 AGA 8 Method Select - Product #4 Heating Value Method Select - Product #1
0=AGA 5; 1=GPA 2172-96
# 2s complement numbers
based on span entries 17176 through 17189. Values expressed as percentages of span in tenth percent increments. i.e. 1000 represents 100.0% . No over range or under range checking is done.
Heating Value Method Select - Product #2 Heating Value Method Select - Product #3 Heating Value Method Select - Product #4
3825 to 3828
Spare Spare
2-12
23/27.71+ 05/98
Volume 4d
3829
INFO - These short integers are accessed using Modbus function code 03 for reads, 06 for single writes and 16 for multiple register writes.
Print Priority
0=Not sharing a printer; 1=Master; n=slaves 2-12.
Analyzer Number
ID Used in communications
3842
23/27.71+ 05/98
2-13
Chapter 2
3843
3844 3845 3846 3847 3848 3849 3850 3851 3852 3853 3854 3855 3856 3857 3858 3859
Danalyzer - Alarm Word - 3048 Danalyzer - Alarm Word - 3049 Danalyzer - Alarm Word - 3050 Danalyzer - Alarm Word - 3051 Danalyzer - Alarm Word - 3052 Danalyzer - Alarm Word - 3053 Danalyzer - Alarm Word - 3054 Danalyzer - Alarm Word - 3055 Danalyzer - Alarm Word - 3056 Danalyzer - Alarm Word - 3057 Danalyzer - Cycle Start - Month
Points 3855-3859 represent the time and date when the last analysis was started.
INFO - The addresses on the right (3047-3057) are the corresponding addresses in the Danalyzer.
Danalyzer - Cycle Start - Day Danalyzer - Cycle Start - Year Danalyzer - Cycle Start - Hour Danalyzer - Cycle Start - Minute
3860 to 3866
Spare Spare
2-14
23/27.71+ 05/98
Volume 4d
Time and date can be read and written here. See also 4847 and 4848.
3867 3868 3869 3870 3871 3872 3873 3874 Current - Hour
0-23.
Current - Minute
0-59.
Current - Second
0-59.
Current - Month
1-12.
Current - Year
0-99; Year 2000=00.
23/27.71+ 05/98
2-15
Chapter 2
3875 to 3879
Spare Spare
Override Code - Reference Specific Gravity Override Code - Nitrogen Override Code - Carbon Dioxide Override Code - Heating Value Override Code - Gas Chromatograph
3885 to 4000
Spare Spare
2-16
23/27.71+ 05/98
Volume 4d
The second digit of the index number defines the number of the meter run. For example: 4114 is the 'Meter ID' for Meter Run #1. The same point for Meter Run #4 would be 4414. Each ASCII string is 8 characters occupying the equivalent of 4 short integer registers (see the side bar comments).
4n01 4n02 # # 4n03 4n04 4n05 4n06 Running Batch - Start Date Running Batch - Start Time Batch End - Date Batch End - Time Running Product Name Current - Calculation Mode
Algorithm set used, in string format.
Note: The index number of each string refers to the complete string which occupies the space of 4 registers. It must be accessed as a complete unit. You cannot read or write a partial string. Each point counts as one point in the normal Omni Modbus mode.
4n07
Modicon Compatible Mode - For the purpose of point count only, each string counts as 4 registers. The starting address of the string still applies.
4n08 4n09
4n10
Note:
Spare Meter - Serial Number Meter - Size Meter - Model Meter - ID Flow Meter Tag / Low Range Tag - Differential Pressure Differential Pressure - High Range Tag Transmitter Tag - Temperature Transmitter Tag - Pressure Transmitter Tag - Densitometer Transmitter Tag - Density Temperature Transmitter Tag - Density Pressure Output Tag - PID Control
4n11 4n12 4n13 4n14 4n15 4n16 4n17 4n18 4n19 4n20 4n21 4n22
23/27.71+ 05/98
3-1
Chapter 3
4n23
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
to 4n99 4500
3.2.
Storage for ninety-nine ASCII strings is provided for user scratch pad. These registers are typically used to store and group data that will be moved via peerto-peer operations or similar operations.
4501 to 4599 Scratchpad - ASCII String #99 Scratchpad - ASCII String #1
3.3.
The string variables which define the descriptor tags that appear in the eight User Displays and the key press combinations which recall the displays are listed below.
INFO - See 3601 area for more data points needed to setup the user displays.
User Display #1 - Descriptor Tag - Line #1 User Display #1 - Descriptor Tag - Line #2 User Display #1 - Descriptor Tag - Line #3 User Display #1 - Descriptor Tag - Line #4
4605 to 4632
User Display #2 - Descriptor Tag - Line #1 User Display #8 - Descriptor Tag - Line #4
4633 to 4640
User Display #1 - Key Press Sequence User Display #8 - Key Press Sequence
4641 to 4706
Spare Spare
3-2
23/27.71+ 05/98
Volume 4d
3.4.
INFO - These ASCII string variables are accessed using Modbus function codes 03 for all reads and 16 for all writes.
4707 to 4710
Note: The index number of each string refers to the complete string which occupies the space of 4 registers. It must be accessed as a complete unit. You cannot read or write a partial string. Each point counts as one point in the normal Omni Modbus mode.
4711 to 4806
Spare Spare
3.5.
Modicon Compatible Mode - For the purpose of point count only, each string counts as 4 registers. The starting address of the string still applies.
4812 4813
23/27.71+ 05/98
3-3
Chapter 3
4820
Application Revisions 23.71+ & 27.71+ - This database corresponds to Application Revisions 23.71/27.71 for Orifice/Turbine Gas Flow Metering Systems. Both US and metric unit versions are considered.
4824 to 4831
Spare Spare
4832 4833 4834 4835 4836 4837 4838 4839 4840 4841 4842 4843 4844 4845 4846
Note:
Reference Specific Gravity Tag Nitrogen Tag Carbon Dioxide Tag Heating Value Tag Flow Computer ID Company Name
Characters 1-8.
Company Name
Characters 9-16.
Company Name
Characters 17-24.
Company Name
Characters 25-32.
Company Name
Characters 33-38. (Note: Last two characters are spares.)
Station Location
Characters 1-8.
Station Location
Characters 9-16.
Station Location
Characters 17-24.
Station Location
Characters 25-32.
Station Location
Characters 33-38. (Note: Last two characters are spares.)
* *
Current Date
Point 3842 selects date format (see also 3870-3872).
Current Time
See also 3867-3869.
4851 to 5000
Spare Spare
3-4
23/27.71+ 05/98
,lk TB: 960701
Overview of OmniCom Configuration PC Software
Communicating with Allen-Bradley Programmable Logic Controllers
TB: 960702
TB: 960703
Storing Archive Data within the Flow Computer Communicating with Honeywell ST3000 Smart Transmitters
TB: 960704
TB: 970701
Stability Requirements: Final Calibration of Flow Computer Secondary Totalizers Provide Net Volume at Temp. Other than 15C or 60F
TB: 970702
TB: 970801
Using Boolean Statements to Provide Custom Alarms in the Flow Computer Omni Flow Computer Modbus Database: Overview
TB: 970802
TB: 970803
TB: 970804
Calculation of Natural Gas Net Volume and Energy: Using Gas Chromatograph, Product Overrides or Live 4-20mA Analyzer Inputs of SG and HV Dual Pulse Flowmeter Pulse Fidelity Checking Communicating with Honeywell TDC3000 Systems
TB: 970901
TB: 980201
TB: 980202
TB: 980301
TB: 980401
Peer-to-Peer Basics
TB: 980402
TB: 980501
TB: 980503
Date: 07
23
96
TB # 960701
Scope....................................................................................................................2 Abstract ................................................................................................................2 Configuring the Flow Computer ........................................................................2 Report Configurator ............................................................................................3 Operations Utilities and Help .............................................................................3 Dial-up Access.....................................................................................................3 Passwords Using OmniCom ..............................................................................3
Local Keypad Access .................................................................................................... 4 Changing Passwords at the Keypad ............................................................................. 4 Setting Up the Initial 'Level B' and 'Level C' Passwords for each Modbus Port............. 5 Maintaining the Modbus Port Password Using OmniCom ........................................... 5 Disabling Modbus Port Passwords................................................................................ 6
Technical Bulletin
Scope
OmniCom Software is compatible with all firmware revisions of Omni 6000/Omni 3000 Flow Computers. It is installed in a personal computer from which you can configure your flow computer.
Abstract
OmniCom is a simple-to-use yet sophisticated PC-based configuration program that can be used to setup, copy or modify, and save to disk entire configurations for Omni flow computers. You can also select custom report options and modify report templates and Omni display screens that are resident within the program, or create new ones. These can then be uploaded to the flow computer. Default reports provide standard data and formats for most requirements. Major application programming has already been developed by Omni and is resident in EPROM. This is of particular importance in custody transfer measurement contracts. They require that the relevant API, AGA, GPA or ISO standards are fully implemented and not exposed to tampering. The OmniCom program allows you to develop your own system requirements by a simple process of menu selection and table completion. This replicates the data entry tables which can be accessed through the front panel keypad of your Omni Flow Computer.
Configuring the flow computer involves specifying what transducers are going to be used, their calibrated ranges and the physical I/O points being assigned. Other data needed by the flow computer relates to the flowing product to be measured, the type of calculations to be used, and communication and control features. You will usually configure the flow computer in the Off-line Mode and then upload your data. You do not have to be connected to the flow computer at this time. You will usually go to the Online Menu only when you need to communicate directly with the flow computer. Any changes made are immediately reflected in the flow computer.
TB-960701
Report Configurator
One of OmniCom's indispensable features is the ability to reformat default reports by using OmniCom's report templates. This is the ONLY feature not available through the front panel keypad. Any variable defined in the Modbus database, or programmed as a variable can be inserted into a report with accompanying text. Reports can be created in languages other than English to suit local needs.
Operational tools such as remotely proving meters, and reading hardware diagnostics are provided. Diagrams are also provided for communications cable hook-up. Application Programs and PC Setup for OmniCom can also be selected. As you work through the entries, you will find entry-sensitive Help that explains the meaning of the particular entry. Whether at the flow computer keypad or at a PC there is always assistance.
For Further Help - If you require further help, call Omnis technical support at: +1-281-240-6161
Dial-up Access
Omni Flow Computers encourages the installation of a telephone dial-up modem as a ready means of providing installation and maintenance support for customer and vendor alike. Serial communication passwords provide enhanced security. Three levels of password pre-exist within Omni flow computers to provide privileged or restricted access to critical configuration and calibration data. The OmniCom program allows you to upload/download data to and from the flow computer in an on-line mode at a range of baud rates by direct-wire or by telephone dial-up modem access. This is particularly useful when the flow computer is in use. Occasionally, you will want to modify configuration or calibration data, or just monitor activity. You can do all this without interfering with pipeline or process operations or with communication links to host SCADA or DCS systems.
1) 2) 3) 4) 5)
Local Keypad access Modbus Port #1 (Physical serial Port #1) Modbus Port #2 (Physical serial Port #2) Modbus Port #3 (Physical serial Port #3) Modbus Port #4 (Physical serial Port #4)
Technical Bulletin
6) Scroll down to access each of the Modbus serial port 'Level A' passwords. These are labeled 'Ser1Passwd', Ser2 Passwd', 'Ser3 Passwd' and Ser4 Passwd corresponding to the physical port numbering for Modbus Ports 1, 2, 3 and 4 respectively.
TB-960701
Setting Up the Initial 'Level B' and 'Level C' Passwords for each Modbus Port
7) Enter an initial 'Level A' Password for the appropriate physical serial port at the keypad of the Omni Flow Computer as described above. 8) Connect a PC running OmniCom Software to the selected serial port of the Omni Flow Computer. Open a file and 'Receive Omni Configuration Data'. 9) A red pop-up screen will appear which notes that a password is required to proceed. If any other screen appears at this point, check wiring and communication settings, Modbus ID, baud rate, etc. 10) Do not enter the 'Level A' password at this point. Keep pressed [Alt] as you press [E] to edit the passwords. A second red pop-up screen will appear asking for the 'current valid password'. A good practice would be to use uppercase letters (activate [CapsLock] on the keyboard) because when setting passwords from the flow computers keypad, they are always entered in uppercase. 11) Enter the 'Level A' password that was selected for this serial port. 12) You are asked if you would like to change the 'Level A', 'Level B' and 'Level C' passwords. Select to change 'Level B' at this point. You will be asked to enter a password. As you enter the password, asterisks will show in place of the characters you typed. You will be asked to re-enter the password to ensure that what you typed was correct. 13) To setup a Level C password, repeat Steps 2 and 6 substituting Level C for Level B at Step 6.
Technical Bulletin
Level B and Level C passwords should be disabled via OmniCom (see sidebar) before disabling the privileged Level A password at the keypad. 1) To disable each password proceed as though you are going to change or set-up the password. 2) Press the [Delete] key six (6) times where the initial password was entered followed by the [Enter] key (no asterisks will show). 3) When asked to re-enter the password, re-enter six [Delete] key presses followed by the [Enter] key. 4) Repeat this procedure for both Level B and Level C passwords. 5) From the Omni flow computer keypad, delete the 'Level A' password for the appropriate Modbus serial port (see Volume 3). To do this, move the cursor to the serial Level A password to disable and press the [Clear] key and then the [Enter] key.
Getting Started
CAUTION!
Terminate and Stay Resident (TSR) programs such as SideKick and Keyboard Macro processors can affect the operation of high speed communication programs such as OmniCom. They do this by 'stealing' processor cycles or turning off the hardware interrupt system of the personal computer. These programs may have to be disabled when you are in the 'On-line' Mode, if you encounter difficulties communicating with the Omni flow computer.
Installation Requirements
To properly run OmniCom, and have sufficient memory for report templates and copies of the database, you will require the following: IBM PC (or compatible) MS DOS, V3.3 or later (excepting 4.01) 640Kb RAM 20Mb Free Hard Disk Space with a minimum of one floppy disk drive, 3" 1.44 Mb Monochrome or color monitor with EGA or VGA graphics capability One RS-232 serial port One LPT port (optional) One RS-232 modem (optional at various supported baud rates)
Installing OmniCom Revisions Previous to 70 Before you install earlier revisions of OmniCom software, you must save your existing phone directory entries and setup. For instructions and any other assistance you may need, please contact our technical support staff at the following phone number: +1-281-240-6161
Installation Procedure
OmniCom is delivered on 1.44 Mb, 3" diskettes in an archived format. To install, do the following: 1) Insert the diskette into your PC's corresponding floppy disk drive. 2) Type the respective drive letter followed by a colon (e.g.: A: or B). 3) Type Install and press [Enter]. The OmniCom installation program will guide you through the rest of the installation.
TB-960701
Opening a File
Accessing Help in OmniCom - At the 'Using Help' feature, press [Enter] and [F1] for editing keystrokes.
First open an existing Omni-supplied file. Each application and derived files come with their own set of templates. You can then 'SAVE AS' to create a new file to commence your configuration. Each file that you create will occupy approximately 60 Kbytes of disk space. This includes 36 Kbytes for the configuration file and 6 Kbytes for each of the four custom report templates. All menu selections are supported by entry-sensitive Help. No matter where you are, by pressing [F1] you can obtain an explanation of the requirements for your entry selection.
For Further Help - If you require further help, call Omnis technical support at: +1-281-240-6161
View
Files can be viewed separately or in parallel with a file that is currently being edited. This allows you to compare various numeric entries in similar files. This can be helpful if you are maintaining historical files that track changes you have made. You may not be able to use the View feature with certain variations of flow computer configuration files because newer firmware include additional entry fields not available in earlier revisions.
Off-line
You will usually begin in the Off-line Mode to configure your flow computer. It naturally leads in to the 'Omni Configuration' Menu selections. Only when you complete this section will you be able to activate the various 'Setup' options and proceed to establish your calibration ranges and other related data. Before you begin the configuration of I/O, be sure you know what number and type of physical I/O has been installed in the flow computer. A mismatch between your off-line configuration and physical hardware will not make a data upload to the flow computer meaningful in key areas of your configuration data.
On-line
When you have completed building your configuration database, you are then ready to upload data to your Omni flow computer. The OmniCom program uses the Modbus RTU binary protocol which mandates the use of 8 data bits. Be sure that the serial I/O parameters in both devices have been properly setup before attempting to communicate. Baud rate and parity settings are less critical but must also be the same. With a direct-connect to a PC, OmniCom will perform an auto baud rate search and display an error if baud rates are incompatible (see 2.5.16. Serial Input/Output Settings in Volume 3). Baud rates from 1.2 kbps to 38.4 kbps are supported. When using a modem, the auto baud rate search is not performed. In this case, the baud rate is that at which the modem is setup. Some personal computers may not have the processing power to support the higher baud rates. Note also that modems are capable of using a higher baud rate at the RS-232 connector than they are communicating on the telephone line. If the modems connect but the flow computer does not respond, try adjusting the flow computers baud rate.
Technical Bulletin
Reports
The 'Report' Menu allows you to retrieve snapshot and historical reports from the flow computer or from your hard disk. These are pre-formatted default reports that are included in the Omni application software. You can also customize your own reports from standard templates. By using the on-screen report editor, you can add or delete text and data character strings which identify the variable in the computer's Modbus database. [F1] for help describes the control functions to enable you to format the report easily. Bring up a report template and move the cursor onto the 'XXXX.XX' fields. Press [Enter] and a pop-up menu defines the variable being used. Type or edit text anywhere, move the cursor and keeping pressed [Shift] as you press [$] enables you to enter or delete any database address from the report.
Utilities
The Utilities Menu has several useful tools for setting up and maintaining OmniCom. The utilities available are: u u u u I/O Point Assignment List OmniCom Setup OmniCom Application Archive Maintenance u Prover/Batch End Commands u Diagnostics u Omni Panel
OmniCom Setup
This utility allows you to: u Select the type of video monitor. u Turn the sound effects on/off. u Setup the modem command strings.
TB-960701
Turbine / Positive Displacement 22 Liquid Flow Metering Systems (with Meter Factor Linearization) 23 Orifice / Turbine Gas Flow Metering Systems
Turbine / Positive Displacement 26 Liquid Flow Metering Systems (with Meter Factor Linearization) 27 Orifice / Turbine Gas Flow Metering Systems
WARNING!
Warning: The flow computer will not accept changes made to the archive setup at the time of a 'Transmit Omni Configuration' upload unless the archiving feature has been turned off.
When this menu is entered, OmniCom tries to establish communications with the flow computer using the comm parameter settings currently selected in the 'Start Comm' submenu of the 'Online' menu. It does this to establish the status of the 'Archive' flag and 'Archive Config Enable' flag. Check comm settings if all items on the menu are inactive; i.e., OmniCom is unable to communicate with the target computer. Any changes made to the flow computers configuration which involves the format of the data record, number of records in an archive file, or the total number of archive files within the flow computer, will cause the memory used to store the archive data to be reinitialized. This would cause all data stored in archive to be lost. Therefore, no changes to the target flow computers archive configuration will be allowed unless automatic data archiving has been disabled and the 'Archive Config Enable' flag is on.
Accessing Help in OmniCom - At the 'Using Help' feature, press [Enter] and [F1] for editing keystrokes.
For Further Help - If you require further help, call Omnis technical support at: +1-281-240-6161
Technical Bulletin
Proving features displayed here can only be viewed when communicating directly with an Omni Flow Computer. You may monitor or control the operation of a meter prover which is controlled by a remote Omni flow computer. You must have already established communications with the flow computer before making this selection. If you have not established communications with a flow computer you will receive one of the following error messages:
Byte count does not match expected - OmniCom is confused and thinks your modem is connected to a flow computer. Try dialing out first. No response from Omni - You are either not connected to anything or the slave ID number of the flow computer you are trying to talk to does not match OmniCom's setting.
Use the 'Shift' key with the appropriate 'Function' key to select the flowmeter you wish to remote prove. The 'Status Window' shows the event history and the 'Omni Display' echoes data shown locally at the Omni flow computer.
Diagnostics
You must be connected and online with a flow computer for this selection to work. The screen displays diagnostic information about the flow computer such as number and type of I/O modules fitted, status of digital I/O, current output percent of analog outputs and raw input signals coming into the flow computer.
Help
Accessing Help in OmniCom - At the 'Using Help' feature, press [Enter] and [F1] for editing keystrokes.
You can further customize your Help screens by making use of an on-screen editor. Via this feature you can modify Help text by additions or deletions to suit your own needs and operations. Windows can be resized and repositioned to suit your own personal preference. This can be particularly useful as an additional memory aid, if the Operations Manual is not available to you, or if additional information is required for other users of this program.
10
TB-960701
Remember to mail in the registration of your distribution diskette to Omni flow computers. OmniCom is provided with each Omni flow computer on a singleuser license basis. Any additional installations of this program will require reregistration by the user. This will ensure that you will have the opportunity to receive free telephone support, and notice of program revisions and new add-on programs for your installation.
11
Date: 07
23
96
TB # 960702
Scope....................................................................................................................1 Abstract ................................................................................................................2 Protocol and Error Checking .............................................................................2 PLC Supported ....................................................................................................2 Flow Computer Database ...................................................................................2
4th and 5th Digit from the Right Identifies Type of Variable .......................................... 2 rd 3 Digit from Right Identifies which Area within the Application.................................... 3
How the Allen-Bradley Accesses the Omni Flow Computer Database .......3
PLC-2 ............................................................................................................................ 3 PLC-3 ............................................................................................................................ 3 PLC-5 ............................................................................................................................ 3 Valid Starting Addresses of PLC-5 Files ....................................................................... 4
16-Bit Integers ......................................................................................................................... 4 8-Character Strings.................................................................................................................. 4 32-Bit Integers ......................................................................................................................... 4 32-Bit IEEE Floating Points ..................................................................................................... 4 Bit Integers .............................................................................................................................. 4 16-Character Strings................................................................................................................ 4 32-Bit Integers ......................................................................................................................... 4 32-Bit IEEE Floating Points ..................................................................................................... 4
Allen-Bradley Communications - This feature allows communicating with AllenBradley PLCs. However, Omni Flow Computers is not responsible for the operation, connectivity or compatibility of AllenBradley products, and furthermore, we do not warrant these products.
Scope
All firmware revisions of Omni 6000/Omni 3000 Flow Computers allow communications with Allen-Bradley Programmable Logic Controllers (PLCs). This technical bulletin refers to communication aspects specific to the Omni Flow Computer and serves as information only. Please refer to the manufacturer for any support or information on Allen-Bradley products.
Technical Bulletin
Abstract
The Omni 6000 flow computer provides serial communications between the flow computer and an Allen-Bradley Programmable Logic Controller (PLC), usually via a KE or KF Communication Module connected to the Data Highway. Data is transmitted serially at a maximum rate of 38.4 kbps using 8 data bits, 1 stop bit and no parity bit. Average speed of response to a message request is approximately 75 msec.
PLC Supported
The Omni computer supports the following Allen-Bradley PLC types and messages. Note that bit level operations are not supported. PLC-2 PLC-3 PLC-5 SLC-502/3 Unprotected Block Reads and Writes Word Range Reads and Writes Typed Reads and Writes Unprotected Typed Reads and Writes
4th and 5th Digit from the Right Identifies Type of Variable
1??? 3??? 4??? 5??? 7??? 8??? 13??? 14??? Variable is a digital status or command bit Variable is a 16 bit signed integer Variable is a 8 character ASCII string Variable is a 32 bit signed integer Variable is a 32 bit IEEE floating point Variable is a 32 bit IEEE floating point Variable is a 16 bit signed integer Variable is a 16 character ASCII string
15??? Variable is a 32 bit signed integer 17??? Variable is a 32 bit IEEE floating point
TB-960702
3rd Digit from Right Identifies which Area within the Application
?1?? ?2?? ?3?? ?4?? ?5?? ?6?? ?7?? ?8?? ?9?? Variable relates to Meter Run #1 Variable relates to Meter Run #2 Variable relates to Meter Run #3 Variable relates to Meter Run #4 Variable is scratchpad Variable is PID related or scratchpad Variable is a command write. Variable is related to station functions Variable is related to prover functions
t Translation Tables #1 through #3 are used to set up block reads which can contain status points packed 16 to a word, 16-bit or 32-bit integers and IEEE floating points. t Translation Table #4 is used for block writes of status and command bits only. Data is packed 16 to a word. t Translation Table #5 provides for block writes to any selected data.
PLC-3
This family can use the methods described above as well as 'word range reads and writes' of any variable within the database (see PLC-5 list for starting addresses).
PLC-5
This family utilizes 'typed reads and writes' of the complete Database. To accommodate the PLC-5 'file system method of addressing, the Modbus index numbers serve as the basis of the internal file system of the computers as it appears to a PLC-5 device. Table below shows typical examples:
Technical Bulletin
PLC-5 ADDRESS
N11:01 N12:17 N17:01 N32:01 N32:10 N39:01 B41:01 B41:02 N51:01 N51:02 N51:03 F74:01 F74:05
ELEMENT SIZE
1 Word (16 Flags) 1 Word (16 Flags) 1 Word (16 Flags) 1 Word (Integer) 1 Word (Integer) 1 Word (integer) 1 Byte (ASCII) 1 Byte (ASCII) 1 Word (Long Integer) 1 Word (Long Integer) 1 Word (Long Integer) 2 Words (IEEE Float) 2 Words (IEEE Float)
COMMENT
Meter #1 Status Flags Meter #2 Status Flags Command Flags Meter #1 Data Offsets track Prover Data 4 Words per Variable 1 Byte per element 2 Words per variable 2 Words per variable Same again 2 Words per variable Offsets track
8-Character Strings
B41:01 B42:01 B43:01 B44:01 B45:01 B46:01 B47:01 B48:01 B49:01
32-Bit Integers
N51:01 N52:01 N53:01 N54:01 N55:01 N58:01 N59:01
Bit Integers
N130:01 N134:01
16-Character Strings
B140:01
32-Bit Integers
N150:01
Date: 07
23
96
TB # 960703
Data Archiving - The archiving feature allows you to store raw data, ASCII text data and historical reports.
How The Available Memory Is Allocated ....................................................................... 7 Checking The Archive File Memory Status Screens ..................................................... 8 Summary 0f Raw Data Archiving Features.................................................................... 9
Raw Data Archive Definition: Alarm/Event Log and Audit Event Log .........10
Alarm/Event Log Record Structure: Archive File Address 711.................................... 10 Audit Event Log Record Structure: Archive File Address 712. .................................... 10
Using The Custom Reports to Access the Text Archive Feature.................11 Custom Report Templates ...............................................................................12
Scope
All firmware revisions of Omni 6000/Omni 3000 Flow Computers have the archiving feature. This feature allows you to archive raw data, ASCII data and historical reports
Technical Bulletin
Abstract
Definitions & Terminology Archive Address - A unique Modbus address used to read a data record from an archive file. These addresses are in the 700 series; i.e., 701, 702, 703, etc. Archive Record - A structure containing a fixed set of data variables which cannot exceed 250 bytes in length. Data within the record can be of any valid data type in any order. Archive Trigger Boolean The actual event which causes the flow computer to capture and store a record within the archive file. The trigger can be any Boolean variable within the database including the result of a Boolean statement. Block Read - Modbus protocol block read requires that Function Code 03 (read multiple registers) be used to retrieve data. Circular Archive File - A file of n records arranged as a circular buffer which always contains the most recent n records; i.e., the oldest data record is overwritten by each new record as it is added. Current Record Pointer A 16-bit read-only integer register containing a number between 0 and n, representing the position of the most recently added record within the archive file. The pointer is adjusted after each complete record is added. A value of 0 indicates that no data records have been added since the last initialization of the archive memory.
The flow computer provides three distinct methods of storing data. These are as follows: 1) Raw Data Archive Data records are defined and stored in raw binary format in circular files of 'n' records per file. Ten user configurable files are provided as well as an alarm file and audit trail file. This data can be retrieved using standard Modbus Function Codes 3 and 6. ASCII data which is captured and saved whenever a Snapshot, Daily, Batch End or Prove report is printed. Data is stored chronologically. To retrieve this data you must use OmniCom, OmniView or a custom Modbus driver which understands the proprietary Omni Modbus Function Codes 64 and 65. These are exact copies of data that was sent to the local printer in ASCII format. The flow computer stores the last eight copies of each of the following reports: Daily, Batch End and Prove.
3) Historical Reports
Method 3 is limited to storing the last eight reports and is therefore not considered archive data. Therefore this chapter will be limited to describing how Methods 1 and 2 are used to store archive data within the flow computer.
(Continues)
TB3-960703
Retrieving Data
Definitions & Terminology
(Continued)
Maximum Records Register - A 16-bit readonly integer adjacent to the Current Record Pointer which contains the number n, indicating the maximum number of records within the archive file. Requested Record Pointer - A 16-bit read/write integer used to select a specific record within an archive file. Time and Date Stamp - Six bytes of binary data representing the date and time that the archive record was stored. The byte order is as follows: u Byte 1 = Month (1-12) or Day (1-31) u Byte 2 = Day (1-31) or Month (1-12) u Byte 3 = Year (0-99) u Byte 4 = Hour of Day (023) u Byte 5 = Minute (0-59) u Byte 6 = Seconds (0-59) u European Format Selected (dd/mm/yy) Valid Data Types u 32-bit IEEE floating point data u 32-bit long integer data u 16-bit integer data u 8-byte ASCII string data; byte packed Boolean status data
Data records are retrieved one record at a time by writing the number of the record required, to the requested record pointer register. The data can then be accessed immediately by a block read of the archive address. Data must be read as one complete block. Also, because the flow computer always responds with a complete record, the 'number of registers' field of the Modbus poll request is ignored by the flow computer. The following record retrieval method is simple and efficient; it works well assuming that there is only one host device retrieving data. The method assumes that the number of the last record retrieved is left in the requested record pointer within the flow computer. This will not be the case when more than one host device will be retrieving data; in this case each host device must know the number of the last record it retrieved. 1) Read the maximum records register, current record pointer and requested record pointer. These registers are adjacent to each other in the flow computers database. 2) A current record pointer value of 0 indicates that the archive file has been initialized (i.e. cleared to binary zeroes/ASCII Nulls) and no trigger event has occurred since initialization). 3) Compare the contents (just read) of the current record pointer with the requested record pointer. 4) If the records numbers are equal no additional records have been added since the last read and no further action is needed. 5) If the record numbers are not equal, increment the value of requested record pointer. 6) If the resultant value is greater than the value obtained from the maximum record pointer, roll-over has occurred and record number one should be retrieved by writing '1' to the requested record pointer register. Otherwise write the incremented value to the requested record pointer register. 7) After writing to the requested record pointer register in the flow computer, the selected archive record can be read immediately using Modbus function '3' (read multiple registers). Archive file addresses are in the 700 area of the flow computers database (i.e., archive file 1 = 701, archive file 2 = 702 etc.). 8) Repeat steps 3 through 7 until all records are read. During the normal course of events, the host attempts to read the next record in sequence based on the number of the last record it retrieved. An archive record containing binary 0s indicates that the archive has been initialized since the last read and that the host should restart by reading record number one (assuming that the current record pointer is not 0)
Technical Bulletin
Archive #2
Archive #3
Archive #4
Archive #5
Archive #6
Archive #7
Archive #8
Archive #9
TB3-960703
Archive #10
Record Access Address Access Record Date/Time Only Maximum # of Records Last Record Updated Pointer Record Req To Read Pointer4 Record Access Address Access Record Date/Time Only Maximum # of Records Last Record Updated Pointer Record Req To Read Pointer Record Access Address Access Record Date/Time Only Maximum # of Records Last Record Updated Pointer Record Req To Read Pointer
Read Only Read Only Read Only Read Only Read/Write Read Only Read Only Read Only Read Only Read/Write Read Only Read Only Read Only Read Only Read/Write
0710 0760 3728 3729 3730 0711 0761 3731 3732 3733 0712 0762 3734 3735 3736
Alarm Archive
Audit Archive
Select 'Password Maint' and press [Enter]. Enter the privileged password when prompted and scroll down the screen until the following is displayed:
Technical Bulletin
TB3-960703
A maximum of 16 groups of variables may be included in an archive record. Data can be of any valid type. The record is limited to a total of 250 data bytes remembering that the time and date stamp included in each record occupies 6 bytes. Scrolling down the screen displays the following:
Enter the maximum number of archive records to be contained within this circular archive file. At the 'Trig Boolean' entry, enter the database address of the Boolean trigger which will cause the flow computer to store the archive data record. For example, entering 1831 (the 'hour start flag) would cause the flow computer to store data at hourly intervals. Once you have entered all the necessary data for all of the archive records return to the following screen which is in the 'Password Maintenance' menu.
)
&#
* ! &#
* ) ! "
INFO - Redefining the archive Boolean trigger does not cause the archive RAM to be cleared.
Set 'Reconfig Archive' to 'N' and 'Archive Run' to 'Y'. At this point the flow computer will reinitialize archive RAM memory and attempt to allocate memory as configured.
Technical Bulletin
TB3-960703
Technical Bulletin
Raw Data Archive Definition: Alarm/Event Log and Audit Event Log
Alarm/Event Log Record Structure: Archive File Address 711
Note: Alarm types are: 0 = Log event, sound beeper and display in LCD any edge change in bit identified by field #3. 1 = Log event, sound beeper and display in LCD rising edge changes in bit identified by field #3 2 = Event log any edge change in bit identified by field #3. No beeper or LCD display action. 3 = Event log rising edge changes in bit identified by field #3. No beeper or LCD display action. Rising edge change means 0 to1 transition.
3-Byte Date 3-Byte Time 16-Bit Integer 1 Byte 1 Byte IEEE Float 32-Bit Integer 32-Bit Integer
(MM, DD, YY or DD, MM, YY) (HH, MM, SS) (Modbus Index # of alarm or event) (Alarm Type - see sidebar) (Boolean Value, 1 or 0 representing Alarm or OK) (Value of transducer variable at the time of alarm or event) (Volume totalizer at time of event or alarm) (Mass totalizer at the time of the event or alarm)
Note: Fields 5 and 6 are set to 0.0 when the variable type changed is String. Fields 7 and 8 contain null characters when the variable type changed is NOT a string. When fields 7 and 8 contain 8 character strings the remaining 8 characters are padded with nulls.
16-Char ASCII (String variable value before change - old value) 16-Char ASCII (String variable value after change - new value) 32-Bit Integer (Volume totalizer at time of change) (Mass totalizer at the time of the change)
10
TB3-960703
The user has embedded a Boolean point address 2000 to indicate that the following data enclosed by the {} characters is to be printed and archived. When embedding the point, set the width=1 and number of decimal places=0.
Company Name Time : XX:XX:XX Computer ID : XXXXXXXX XXXXXXXX XXXXXXXX XX/XX/XX XX:XX:XX XX/XX/XX XX:XX:XX XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXXXXXX XXXXX.X XXXXX.X XXXXX.X XXXXX.X XXXXX.X X.XXXX X.XXXX X.XXXX XXXXXXX XXXXXXXX
The User has embedded a Boolean point address 1000 to indicate that the following data enclosed by the {} characters is to be archived only and not printed. When embedding the point, set the width=1 and number of decimal places=0.
Meter ID XXXXXXXX Product ID XXXXXXXX API Table Selected XXXXXXXX Batch Start Date XX/XX/XX Batch Start Time XX:XX:XX Batch End Date XX/XX/XX Batch End Time XX:XX:XX Batch Gross (IV) BBL XXXXXXXXX Batch Net (GSV) BBL XXXXXXXXX Batch Mass LB XXXXXXXXX X{ Opening Gross (IV) BBL XXXXXXXXX Opening Net (GSV) BBL XXXXXXXXX Opening Mass LB XXXXXXXXX Closing Gross (IV) BBL XXXXXXXXX Closing Net (GSV) BBL XXXXXXXXX Closing Mass LB XXXXXXXXX Batch Flow Weighted Averages: Gross Flow (IV) BBL/HR XXXXXX.X Temperature Deg.F XXXXXX.X Pressure PSIG XXXXXX.X Flowing Density GM/CC XXXXXX.X API @ 60 Deg.F XXXXXX.X VCF X.XXXX CPL X.XXXX Meter Factor X.XXXX }
INFO - Data is archived only when the report is processed for the first time. Reprinting a stored report does not cause any data to be stored in the archive.
The template files shown below can be used to archive text data whenever the report is processed. 1) 2) 3) 4) 'FILENAME.TP1' 'FILENAME.TP2' 'FILENAME.TP3' 'FILENAME.TP4' Snapshot Report Batch Report Daily Report Prover Report
11
Technical Bulletin
Prove Report
Templates can only be accessed if they exist; i.e., if you are currently working on 'FILENAME.OMI' opening the custom templates will just create an empty file. You must first create a set of templates by copying the appropriate sample templates as follows: 1) At the OmniCom File menu select 'Shell to DOS'. 2) Type the following to create a set of custom templates for a common product system using a full sized pipe prover (assumes Rev. 20.?? application): COPY OMNI20\REV20D.TP? OMNI20\filename.TP? 3) Type EXIT to return to OmniCom. In the above example OMNI20 is the sub directory which contains all files related to Application Revision 20. Likewise OMNI24 refers to Revision 24 applications.
12
Date: 07
23
96
TB # 960704
Scope....................................................................................................................1 Abstract ................................................................................................................1 Digitally Enhanced (DE) Protocol Overview .....................................................2 Transmitter Database..........................................................................................2 Using the Honeywell Handheld Communicator ............................................3 Combo Module LED Status Indicators..............................................................3 Switching Between Analog and Digital Mode. .................................................4
Auto Mode ..................................................................................................................... 4 Manual Operation .......................................................................................................... 4
Communication with Honeywell ST3000/STT3000 Smart Transmitters - This feature allows you to communicate with Honeywell Smart Temperature and Pressure Transmitters, via Omnis H type Process I/O Combo Module and using Honeywells DE Protocol.
Viewing the Status of the Honeywell Transmitter from the Omni Front Panel .....................................................................................................................4
Scope
All firmware revisions of Omni 6000/Omni 3000 Flow Computers have the feature of communicating with Honeywell ST3000 Smart Transmitters. This feature uses Honeywells Digitally Enhanced (DE) Protocol and requires that an H Combo I/O Module be installed in your flow computer.
Abstract
Using 'H' Combo I/O Modules, the Omni Flow Computer can communicate with Honeywell Smart Temperature and Pressure Transmitters using Honeywells DE Protocol. Up to 4 transmitters can be connected to each 'H' Type Combo Module, with loop power being provided by the combo module.
Technical Bulletin
Transmitter Database
By using the data contained in Bytes #5 and #6, the flow computer builds and maintains an exact copy of the smart transmitters configuration database. A transmitter database varies in size from about 90 bytes for a pressure transmitter to 120 bytes for a temperature transmitter. It takes between 30 and 45 seconds to completely build a copy of the transmitter database within the flow computer. The transmitter database is continuously compared against the flow computer configuration settings for that transmitter. The flow computer automatically corrects any differences between the databases by writing the correct configuration data to the transmitter.
TB-960704
Any changes made to 1, 2 and 3 using the handheld communicator will be overwritten by the flow computer. In the digital mode it is not necessary to calibrate the transmitter output using the handheld communicator. The digital signal can be calibrated using the normal Omni analog input method described in Chapter 8 of Volume 1.
Technical Bulletin
Manual Operation
For manual operation, do the following: 1. Disable communications between the Honeywell transmitter and the flow computer by deleting all I/O point assignments within the flow computer to that I/O point. 2. Using the Honeywell SFC, SCT or any Honeywell handheld communicator, press [Shift] [A/D] and wait till the handheld displays 'Change to Analog?' 3. Answer (Yes) by pressing [Enter]. SFC Working will be displayed. The 'H' Combo modules green LED on that channel will stop pulsing. 4. Re-enter the I/O point to cause the Omni to send the communication request command to the Honeywell and after three command sends the green LED on the Honeywell module will pulse at a steady 3Hz rate.
Viewing the Status of the Honeywell Transmitter from the Omni Front Panel
To verify the data being received from the smart transmitter, press [Input] [Status] and [Enter] from the front panel. The following displays:
! "!
# $
% &
! ' ( ))))))))
# * + , -*
TB-960704
H1-2 Transmitter
: Indicates the Honeywell Combo Module (H1) and the channel number on that module (Channel 2 in this case). : Process variable value in percentage of the transmitters span. A -25.00 displayed on the Omni could mean that the transmitter is not communicating (see Status definition below). : There are five status states. 1) OK : Communications between the flow computer and smart Honeywell transmitter are OK. The database within the transmitter matches the flow computer. : This flow computer I/O point has been assigned to a Honeywell transmitter but is not receiving data from the transmitter. Possible cause is a wiring problem such as reversal of wiring. If you observe the status LEDs you will note that the flow computer attempts to establish communications by sending a wake-up command every 10 seconds or so.
PV%
Status
2) Idle
3) Bad PV : Communications between the flow computer and smart Honeywell transmitter are OK but the transmitter has determined that a critical error has occurred within the transmitter meaning the value of the process variable cannot be trusted. The flow computer will set the transducer failure alarm and follow the fail code strategy selected by the user for this transducer. 4) DB Error : Communications between the flow computer and smart Honeywell transmitter are OK but the flow Computer has determined that the database within the flow computer does not agree with the database within the transmitter. If you observe the status LEDs you will note that the flow computer attempts to correct the transmitters database by writing the correct data to the transmitter once every 30-45 seconds or so.
Technical Bulletin
5) 4 Byte
: The transmitter is operating in the 4-Byte Broadcast Mode. Because the flow computer will not tolerate this mode of operation, this status display should only be displayed momentarily as the flow computer will automatically switch the transmitter into the 6-Byte Broadcast Mode.
LRV
: Lower Range Value of the transmitter in engineering units. Engineering units are degrees Celsius for temperature transmitters, inches of water for differential pressure transmitters, and pounds per square inch for pressure transmitters. : The Span of the transmitter in engineering units (the Span is the difference between the lower and upper ranges of the transmitter). Engineering units are degrees Celsius for temperature transmitters, inches of water for differential pressure transmitters, and pounds per square inch for pressure transmitters. The flow computer will display DB Error if the user tries to enter a span of 0% or a span which would exceed the transmitters upper range limit' (URL). : Damping Time of the transmitter output in seconds. : Meaningful only with differential pressure transmitters. Conformity Bit 0 = linear output; Conformity Bit 1 = square root output. This bit should always be 0 for smart temperature transmitters.
Span
Software Revision : Current Software installed within the smart device. Serial # : Serial Number of the smart transmitter.
Transmitter Type : Valid transmitter types are: TT = Temperature Transmitter DP = Differential Pressure Transmitter GP = Gauge Pressure Transmitter
TB-960704
URL
: Upper Range Limit of the transmitter in engineering units. The transmitter will not accept configuration entries which exceed this value. : ASCII string used to identify the transmitter. : Secondary Process Variable Value expressed in C. This represents sensor temperature for pressure transmitters, and junction temperature for temperature transmitters. The flow computer may or may not have a value in this field, depending upon whether the SV is included in the part of the transmitters database which is sent to the Omni.
ID/TAG SV
Date: 07
02
97
TB # 970701
Scope
All Omni 6000/3000 Flow Computers have calibration stability requirements.
Abstract
Because of the temperature sensitivity and bit resolutions of the A/D and D/A converters, and the high accuracy requirements, it is important that the following procedures are followed when calibrating flow computer I/O circuits.
Instructions
(1) Adjust the power supply to give 5.05-5.10 volts at backplane test points. (2) All final calibrations must be performed using the matching set of combo modules and power supply module (i.e. changing the power supply or adjusting the voltage during the final calibration requires that a sample calibration made up to that point be checked. If there is a noticeable change, all calibrated points should be rechecked). (3) Before calibrating, eliminate temperature gradient errors by closing the box and allowing at least 20 minutes for temperature stabilization to occur. Ensure that unit is not in a high air draft area (i.e. in the path of a fan or AC duct) Make adjustments such as jumper repositioning quickly. Wherever possible keep the unit closed to retain internal heat. Board replacements will require that sufficient time be allowed to achieve temperature stability. (4) Observe temperature stability requirements of any equipment used in the calibration process (i.e., current and voltage generators, digital voltmeters etc.)
TB-970701 ALL.70+
Date: 07
04
97
TB # 970702
Secondary Totalizers Provide Net Volume at Temperatures Other than 15C or 60F
Contents
User Manual Reference This technical bulletin complements the information contained in Volumes 2, 3 and 4, applicable to firmware revisions 20/24.71+ and 21/25.71+. This bulletin was previously published with a different page layout.
Scope....................................................................................................................1 Abstract ................................................................................................................1 Database Location of Second Set of Net Totalizer Data Points .....................2 Keypad Entries Needed to Display the Extra Totalizers..................................2
Scope
All firmware Versions 20/24 and 21/25, Revisions.70+ of Omni 6000/Omni 3000 Flow Computers have secondary net totalizers for when more than one reference temperature is required.
Abstract
Some times it is necessary to provide net totalizers at more than one reference temperature. Following are the Modbus data points that are used to provide secondary net totalizers in the Omni. Secondary totalizers are calculated real time just like the normal totalizers. The secondary totalizers are activated by setting up floating point data point 7699 with the secondary reference temperature required. This data point is initialized to 0 at a cold start up which effectively disables the extra totalizers and their appearance on the Omni default reports (obviously, 0 cannot be used as a second reference temperature). You may set up 7699 with a simple variable statement. For example: 7699=#68 will provide a second set of net totalizers corrected to 68 degrees. You may also initialize point 7699 via a one time Modbus write. If you choose to use the statement method you may remove the statement immediately after you enter it, but you should probably leave it to serve as a document trail. Note that the Omni initializes point 7699 to 0.0 on a cold boot. A cold boot occurs after a Clear All Ram command is executed.
TB-970702 ALL.70+
Technical Bulletin
TB-970702 ALL.70+
Date: 08
04
97
TB # 970801
Scope
User Manual Reference This technical bulletin complements the information contained in the User Manual, and is applicable to all firmware revisions Version .70+. This bulletin was previously published with a different page layout.
All firmware revisions Version .70+ of Omni 6000/Omni 3000 Flow Computers have the feature of customizing alarms with Boolean statements.
Abstract
The flow computer automatically records and logs many important alarm events and status changes. These events include transducer Low Alarm and High Alarm states and failure of any transducer connected to the flow computer which is measurement related. There are instances however where the flow computer user would like to monitor other internal or external status events that may have nothing to do with the measurement functions. These alarms may be the result of a digital I/O point changing state, or the result of a Boolean logic statement or a variable statement comparison. Because of this requirement, the last 16 Boolean statements of the flow computer serve the dual function of evaluating normal logic expressions, and also providing user configurable alarm messages. The alarm message text to be logged and displayed can be entered into the expression fields in any of these last 16 Boolean statements. These statement numbers are, 1057 through 1072 for flow computers with 48 Boolean statements, and 1073 through 1088 for computers with 64 statements. Each Boolean statement has an associated status point which is accessed using the same address as the statement number (Modbus Point 1072 for instance). The logic state of this status bit normally reflects the logical result of the statement (1 or 0, true or false). When the statement is used to provide a custom alarm message it functions in a different manner. To cause an alarm message to be logged, simply turn on the status point associated with the message.
TB-970801 ALL.70+
Technical Bulletin
Example:
In this example, the user wishes to monitor a tank level switch that is connected to Digital I/O Point #1. When the tank level is high, the level switch applies 24 volts to the digital I/O point. Digital I/O Point #1 is first assigned to the Dummy Boolean 1700, this reserves the Point as a digital Input . Modbus Point 1001 will simply follow the digital level applied to the terminals of digital point #1. Had it been Digital Point #22, Modbus Point 1022 would be affected. 1025: 1072: 1072=1001
Statement 1025 (above) is used to transfer the logic state of Digital I/O Point #1 to Point 1072, activating the user alarm whenever 24 volts is applied to the input terminals by the tank high level switch contacts.
TB-970801 ALL.70+
Date: 08
08
97
TB # 970802
Scope....................................................................................................................1 Abstract ................................................................................................................2 Omni Flow Computer Modbus Database Extents .........................................4 I/O Driver Concerns When Interfacing to Omni Equipment..........................12
For Example: ..........................................................................................................................12
Write Single Variable - Modbus Function 06 ............................................................... 12 Address Ranges - Future Expansion........................................................................... 12
Modbus Database Modbus function codes are shown in hexadecimal th notation. The 4 digit (from the right) of the data point address defines the data type.
Scope
All firmware revisions Versions 70+ of Omni 6000/Omni 3000 Flow Computers are characterized by a Modbus database structured as described in this technical bulletin.
TB-970802 ALL.70+
Technical Bulletin
Abstract
The following are the data types within the database: Digital Flag Bits : Also known as Boolean bits, status bits and command bits. All data points of this type can be read via Modbus function code 01 and written to using function codes 05 and 0F . Function codes 01 and 0F transfer byte packed data that is sent in the byte order they are prepared (not word order). Points are packed eight to a byte, packing from least significant to most significant Unused bit positions within a byte are cleared on transmission from the Omni and ignored by the Omni when receiving. Writing to status points is allowed but normally is pointless as the status point will be refreshed by the Omni every 500 ms. Valid addresses for this type of data are: 1XXX i.e. 1101, 1705, 1921 etc. 16-bit Integer Registers : All data points of this type can be read via Modbus function code 03 and written to using function codes 06 and 10. Byte order transmitted is: MS byte then LS byte. Valid addresses for this type of data are: X3XXX i.e. 3121, 13133 etc. 8-character ASCII Strings : All data points of this type can be read via Modbus function code 03 and written to using function code 10 (note that function code 06 is not available on this data type). Byte order transmitted is as you would type it. Valid addresses for this type of data are: 4XXX i.e. 4101, 4502 etc. 32-bit Integer Registers : Formatted as twos complement. All data points of this type can be read via Modbus function 03 and written to using function codes 06 and 10. Byte order transmitted is: MS byte of MS word, LS byte of MS word, MS byte of LS word then LS byte of LS word. Valid addresses for this data type are: X5XXX i.e. 5101, 15205 etc.
TB-970802 ALL.70+
TB-970802
32-bit IEEE Floating Point : All data points of this type can be read via Modbus function 03 and written to using function codes 06 and 10. Byte order transmitted is: Mantissa Sign bit/Exponent byte, LS Exponent bit/MS mantissa byte, middle significant mantissa byte then LS mantissa byte. Valid addresses for this data type are: X7XXX i.e. 7210, 17006 etc. 16-character ASCII Strings : All data points of this type can be read via Modbus function code 03 and written to using function code 10 (note that function code 06 is not available for this data type). Byte order transmitted is as you would type it. Valid addresses for this type of data are: 14XXX i.e. 14001, 14022 etc.
TB-970802 ALL.71+
Technical Bulletin
DATA TYPE
COMMENTS
03 00001 Mixed 03 (06) (10) 03 00201 Mixed 03 (06) (10) 03 00401 Mixed 03 (06) (10) 03 03 03 03 03 03 03 03 03 03
User-defined read only packet - Omni native mode. User-defined array - Modicon compatible. User-defined read only packet - Omni native mode. User defined array - Modicon compatible. User-defined read only packet - Omni native mode. User defined array - Modicon compatible. #1 User defined data archive record Firmware Revisions .70+. #2 User defined data archive record Firmware Revisions .70+. #3 User defined data archive record Firmware Revisions .70+. #4 User defined data archive record Firmware Revisions .70+. #5 User defined data archive record Firmware Revisions .70+. #6 User defined data archive record Firmware Revisions .70+. #7 User defined data archive record Firmware Revisions .70+. #8 User defined data archive record Firmware Revisions .70+. #9 User defined data archive record Firmware Revisions .70+. #10 User defined data archive record - Firmware Revisions .70+.
0701 0702 0703 0704 0705 0706 0707 0708 0709 0710
Mixed Mixed Mixed Mixed Mixed Mixed Mixed Mixed Mixed Mixed
TB-970802 ALL.70+
TB-970802
DATA TYPE
COMMENTS
0711 0712 1001 to 1099 1101 to 1199 1201 to 1299 1301 to 1399 1401 to 1499 1501 to 1699 1701 to 1799 1801 to 1899 1901 to 1999 1301 to 1399 2001 to 2100 2101 to 2199 2201 to 2299 2301 to 2399
Alarm/Event Log archive record Firmware Revisions .70+. Audit Log archive record - Firmware Revision Versions .70+.
01
Status
01
Status
01
01 Point 1600 is a dummy point included to concatenate tables 15XX and 16XX.
01
Status
01
Status
01 Reserved for Future Expansion currently will return error exception 02 (illegal data address).
Status
01
Status
01
Status
01
Status
01
TB-970802 ALL.71+
Technical Bulletin
DATA TYPE
COMMENTS
2401 to 2499 2501 to 2699 2701 to 2799 2801 to 2899 2901 to 2999 3001 to 3099 3101 to 3199 3201 to 3299 3301 to 3399 3401 to 3499 3501 to 3599 3601 to 3699 3701 to 3799 3801 to 3899 3901 to 3999
Status
01 Reserved for Future Expansion currently will return error exception 02 (illegal data address).
01
01 Reserved for Future Expansion currently will return error exception 02 (illegal data address).
Status 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register 16-bit Integer Register
01
TB-970802 ALL.70+
TB-970802
DATA TYPE
COMMENTS
4001 to 4099 4101 to 4199 4201 to 4299 4301 to 4399 4401 to 4499 4501 to 4599 4601 to 4699 4701 to 4799 4801 to 4899 4901 to 4999 5001 to 5099 5101 to 5199 5201 to 5299 5301 to 5399 5401 to 5499
8-character ASCII String 8-character ASCII String 8-character ASCII String 8-character ASCII String 8-character ASCII String 8-character ASCII String 8-character ASCII String 8-character ASCII String 8-character ASCII String 8-character ASCII String 32-bit Integer 2s Complement 32-bit Integer 2s Complement 32-bit Integer 2s Complement 32-bit Integer 2s Complement 32-bit Integer 2s Complement
03, (10)
Reserved for Future Expansion currently will return error exception 02 (illegal data address).
03, (10)
03, (10)
03, (10)
03, (10)
03, (10)
03, (10)
03, (10)
03, (10)
03, (10) Reserved for Future Expansion currently will return error exception 02 (illegal data address).
TB-970802 ALL.71+
Technical Bulletin
DATA TYPE
COMMENTS
5501 to 5599 5601 to 5699 5701 to 5799 5801 to 5899 5901 to 5999 6001 to 6099 6101 to 6199 6201 to 6299 6301 to 6399 6401 to 6499 6501 to 6799 6801 to 6899 6901 to 6999 7001 to 7099 7101 to 7199
32-bit Integer 2s Complement 32-bit Integer 2s Complement 32-bit Integer 2s Complement 32-bit Integer 2s Complement 32-bit Integer 2s Complement 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point
03, (06), (10) Reserved for Future Expansion currently will return error exception 02 (illegal data address). Reserved for Future Expansion currently will return error exception 02 (illegal data address).
03, (06), (10) Applicable to Firmware Revisions 22/26.71+ only. 32-bit, 2s Complement (Firmware Revision 23.70+ only). 32-bit, 2s Complement (Firmware Revision 23.70+ only). 32-bit, 2s Complement (Firmware Revision 23.70+ only). 32-bit, 2s Complement (Firmware Revisions 23.70+ and 22/26.71+ only). Applicable to Firmware Revisions 22/26.71+ only. 32-bit, 2s Complement (Firmware Revision 23.70+ only). Reserved for Future Expansion currently will return error exception 02 (illegal data address).
TB-970802 ALL.70+
TB-970802
DATA TYPE
COMMENTS
7201 to 7299 7301 to 7399 7401 to 7499 7501 to 7599 7601 to 7699 7701 to 7799 7801 to 7899 7901 to 8499 8501 to 8599 8601 to 8699 8701 to 8799 8801 to 8899 8901 to 8999 9001 to 9499 9500 to 13000
32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point ASCII Text Buffers
03, (06), (10) Applicable to Firmware Revisions 20/24.71+ and 22/26.71+ only.
03, (06), (10) Applicable to Firmware Revisions 20.71+ and 22/26.71+ only. Maximum of sixty-four 128-byte buffers per data point .
41, (42)
Reserved for Future Expansion - currently will return error exception 02 (illegal data address).
TB-970802 ALL.71+
Technical Bulletin
DATA TYPE
COMMENTS
13001 to 13299 13301 to 13399 13401 to 13499 13501 to 13599 13601 to 13699 13701 to 13799 13801 to 13899 13901 to 13999 14001 to 14099 14101 to 14199 14201 to 14299 14301 to 14399 14400 to 15000 15001 to 15299 15300 to 17000
16-bit Integer Registers 16-bit Integer Registers 16-bit Integer Registers 16-bit Integer Registers 16-bit Integer Registers 16-bit Integer Registers 16-bit Integer Registers 16-bit Integer Registers 16-character ASCII String 16-character ASCII String 16-character ASCII String 16-character ASCII String
03, (10)
03, (10)
03, (10)
03, (10)
Reserved for Future Expansion - currently will return error exception 02 (illegal data address). 32-bit IEEE Floating Point 03, (06), (10)
Reserved for Future Expansion - currently will return error exception 02 (illegal data address).
10
TB-970802 ALL.70+
TB-970802
DATA TYPE
COMMENTS
17001 to 17399 17401 to 17499 17501 to 17899 17901 to 18099 18101 to 18199 18200 to 49999
32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point 32-bit IEEE Floating Point
03, (06), (10) Not applicable to Firmware Revisions 22 & 26. Not applicable to Firmware Revisions 21/25 & 22/26. Reserved for Future Expansion currently will return error exception 02 (illegal data address). Applicable to Firmware Revisions 23/27.71+ only.
Reserved for Future Expansion - currently will return error exception 02 (illegal data address).
TB-970802 ALL.71+
11
Technical Bulletin
For Example:
An application requires data from points 7188, 7201 and 7210 to be read and displayed on screen. An intelligent I/O driver may determine that it is more efficient to read 23 data points starting with point 7188 and discard the unused data. In this particular example the Omni will transmit the data for points 7188 through 7199 and blank data will be returned for data points 7200 through 7210 because the data requested is in two different blocks within the Omni. To obtain the data correctly the I/O driver should determine that point 7188 and point 7201 are in different data blocks (because the third digit from the right changed from a 1 to a 2) and send out two data requests; one request for point 7188 and another for points 7201 through 7210.
12
TB-970802 ALL.70+
Date: 08
12
97
TB # 970803
Scope
Firmware Revisions 22.70+ and 26.70+ of Omni 6000/Omni 3000 Flow Computers have the feature of Meter Factor Linearization. This feature applies to Turbine/Positive Displacement Liquid Flow Metering Systems (with Meter Factor Linearization).
TB-970803 22/26.70+
Technical Bulletin
Abstract
Meter Factor Linearization Function
Flowmeter performance varies depending upon flow rate and fluid viscosity. The flow computer can compensate for this variation in performance by applying a meter factor which is determined by interpolation of a base meter factor curve. The user develops this base meter factor curve by proving the flowmeter at various flow rates and determining the meter factors for those flow rates. A base meter factor curve must be developed for each product or fluid viscosity. The curve can consist of from one to twelve meter factor / flow rate points.
The MF is continuously adjusted for flowrate during a delivery. The MF is flow weight averaged for the batch.
Meter Factor The flow computer lifts or lowers the MF curve based on the MF obtained at the latest official flowmeter proving. Flowrate MFs are normalized to the Prove Base Flowrate for validation / comparison and historical archival purposes.
Fig. 1.
TB-970803 22/26.70+
TB-970803
Test 2 - Maximum Deviation Allowed From The Average of The Last n Meter Factors Historical Average of Last n Meter Factors
Base MF Curve
Fig. 2.
TB-970803 22/26.71+
Date: 08
28
97
TB # 970804
Calculation of Natural Gas Net Volume and Energy: Using Gas Chromatograph, Product Overrides or Live 4-20mA Analyzer Inputs of Specific Gravity and Heating Value
Contents
User Manual Reference This technical bulletin complements the information contained in Volume 3, applicable to Revision 23.71/27.71. This bulletin was previously published with a different page format.
Scope....................................................................................................................1 Abstract ................................................................................................................2 Basic Calculations ..............................................................................................2 Critical Configuration Entries Which Affect the Calculation of Net Volume and Energy ...........................................................................................................2
Density of Air at Base Conditions .................................................................................. 2 Gas Relative Density (SG) ............................................................................................ 3 Gas Heating Value (HV) ................................................................................................ 3 Key Analyzer Setup Menu Entries Needed ................................................................... 3
No Gas Chromatograph Used - Manual Overrides Required ................................................... 3 Component Analysis Data Obtained From a Gas Chromatograph ........................................... 4 Using Manual Overrides for Component Analysis Data............................................................ 4 Component Analysis Data via a Serial Data Link ..................................................................... 4 Using Live Inputs for Heating Value, Specific Gravity, Nitrogen or Carbon Dioxide.................. 4
Natural Gas Net Volume and Energy Calculation Natural gas net volume and energy calculations apply to all gas flow computers, (firmware Revisions 23/27.71) shipped after July 1997. These calculations are considered using a gas chromatograph, product overrides, or live 4-20 mA analyzer inputs of specific gravity (SG) and heating value (HV).
Scope
Firmware Revisions 23.71+ and 27.71+ of Omni 6000/Omni 3000 Flow Computers have the feature of Natural Gas Net Volume and Energy Calculation. This feature applies to Orifice/Turbine Gas Flow Metering Systems. This bulletin covers natural gas net volume and energy calculations using a gas chromatograph, product overrides, or live 4-20 mA analyzer inputs of specific gravity (SG) and heating value (HV).
TB-970804 23/27.71+
Technical Bulletin
Abstract
Gas compositional data needed by the flow computer to calculate flowing density, mass flow and energy flow of natural gas can be obtained from various sources. The following describes how the flow computer should be configured for each possible scenario.
Basic Calculations
The basic calculations are: u Net Volume = Mass Flow / Density @ Base Conditions u Energy = Net Volume x Heating Value (1) (2)
Density at Base Conditions can be obtained by one of the following methods: u u u u (GC Relative Density) x (Density of Air @ Base Conditions) (Override Relative Density) x (Density of Air @ Base Conditions) (Live 4-20mA Relative Density) x (Density of Air @ Base Conditions) Calculated using Detailed Method of AGA 8 (3) (4) (5) (6)
u u u u
GC Analysis HV Manual Override HV Live 4-20mA HV Calculated using AGA 5, GPA 2172 or ISO 6976 (component analysis required)
Component Analysis Data is obtained from one of the following sources: u u u u Online Danalyzer or Applied Automation Gas Chromatograph Manual Overrides in the Fluid Data Analysis menu Serial Communication Link Live 4-20mA SG, HV, N2 and CO2 (AGA 8 gross calculation methods only) (11) (12) (13) (14)
Critical Configuration Entries Which Affect the Calculation of Net Volume and Energy
Density of Air at Base Conditions
This entry is in the Factor Setup menu. Setting this entry to 0 ensures that gas density at base conditions is calculated using AGA 8. (method (6) previous page). Entering the density of air at base conditions assuming a valid gas relative density (SG) is available (see next paragraph) will override the AGA 8 calculation of gas density at base conditions. In this case gas density at base conditions is calculated using either method (3), (4) or (5) (previous page).
TB-970804 23/27.71+
TB-970804
TB-970804 23/27.71+
Technical Bulletin
Using the GC Heating Value and Relative Density. To ensure that the heating value and relative density calculated by GC are used in the calculations, make sure that component numbers are assigned for the Heating Value and Specific Gravity entries in the Analyzer Setup menu. The number entered is not critical, simply use the next consecutive numbers after all the other components are numbered. Ignoring the GC Heating Value and Relative Density. Entering 0 for the component number for Heating Value and Specific Gravity entries in the Analyzer Setup menu causes the flow computer to ignore the heating value and relative density sent by the GC and to use the override values entered in the Fluid Data & Analysis Data menu.
Using Live Inputs for Heating Value, Specific Gravity, Nitrogen or Carbon Dioxide
Activate the Fluid Data & Analysis entries by selecting Always Use Fluid Data Overrides for GC Fail Code in the Analyzer Setup menu. No other entries are needed in the Analyzer Setup menu. In the Station Configure menu, assign valid I/O points where 4-20mA and/or Solartron 3096 gravitometer signals will be connected. Input valid scaling factors in the Station N2 / SG Setup menu. Note that override data fields in Product #1 entries of the Fluid Data & Analysis Data menu are overwritten by live data values when 4-20mA inputs are used for HV, SG, N2 or CO2.
TB-970804 23/27.71+
Date: 09
01
97
TB # 970901
Scope....................................................................................................................1 Abstract ................................................................................................................2 Installation Practices ..........................................................................................2 How the Flow Computer Performs Fidelity Checking .....................................3 Correcting Errors ................................................................................................3
Common Mode Electrical Noise and Transients ........................................................... 3 Noise Pulse Coincident with an Actual Flow Pulse ....................................................... 3 Total Failure of a Pulse Channel ................................................................................... 4
Pulse Fidelity Checking The dual pulse fidelity checking feature allows you to reduce flowmeter measurement uncertainty caused by added or missing pulses due to electrical transients or equipment failure.
Scope
Firmware Revisions 20/24, 22/26 and 23/27 Versions.70+ of Omni 6000/Omni 3000 Flow Computers have the feature of Dual Pulse Fidelity Checking. This feature applies to Turbine/Positive Displacement Liquid and Gas Flow Metering Systems.
TB-970901 20/24//22/26//23/27.70+
Technical Bulletin
Abstract
The object of dual pulse fidelity checking is to reduce flowmeter measurement uncertainty caused by added or missing pulses due to electrical transients or equipment failure. Correct totalizing of flow must be maintained whenever possible. This is achieved by correct installation practices and by using turbine or positive displacement flowmeters which provide two pulse train outputs. In addition, an E Combo I/O Module must be installed and the correct configuration settings entered in the Omni Flow Computer. The two pulse trains are called the A pulse and the B pulse. In normal operation, both signals are equal in frequency and count but are always separated in phase or time. The API Manual of Petroleum Measurement Standards (Chapter 5, Section 5) describes several levels of pulse fidelity checking ranging from Level E to Level A. Level A is the most stringent method, requiring automatic totalizer corrections whenever the pulse trains are different for any reason. For all practical purposes, Level A as described in the API document is probably unachievable. The Omni Flow Computer implements a significantly enhanced Level B pulse security method by not only continuous monitoring and alarming of error conditions but also correcting for obvious error situations, such as a total failure of a pulse train or by rejecting simultaneous transient pulses. No attempt is made to correct for ambiguous errors, such as missing or added pulses. These errors are detected, alarmed and quantified only.
Installation Practices
When using pulse fidelity checking, it is assumed that the user begins with and maintains a perfect noise free installation. The user must ensure that each pulse train input to the flow computer is a clean, low impedance signal which will not be subject to extraneous noise or electromagnetic transients. Any regular occurrence of these types of events must cause the equipment and/or wiring to be suspect and investigated. Pulse fidelity check circuitry is not intended to facilitate continued operation with a poor wiring installation which is prone to noise or transient pickup.
TB-970901 20/24//22/26//23/27.70+
TB-970901
Correcting Errors
Missing or added pulses to either pulse train are considered ambiguous errors and cannot be corrected. However, they are detected with a 100% certainty and will be counted, eventually causing an alarm. Totalizing will continue using the A Pulse Train.
Common mode electrical noise and transients occur at the same instant in time (during the same clock period) on each pulse channel. They are detected with a certainty of 85%*. The certainty can never be 100% because of the slight differences in time (approximately 2 microseconds) that it takes each pulse to travel through its associated input circuitry. These simultaneous pulses are not used to totalize flow but are counted and will cause an alarm.
TB-970901 20/24//22/26//23/27.70+
Technical Bulletin
TB-970901 20/24//22/26//23/27.70+
Date: 02
06
98
TB # 980201
Communication Options with Honeywell TDC3000 Systems - The Omni flow computer can communicate with Honeywell TDC3000 Systems via SIO modules in combination with APM or HPM modules. PLCG or CLM modules communicate directly with the Omni.
Configuring The Omni Flow Computer .......................................................................... 4 Data Grouping Option (a) Custom Data Packet Setup.................................................. 4 Modbus Function Codes Used to Access Custom Packet Data Within The Omni........ 4 Data Grouping Option (b) Variable Statement Moves to Scratchpad Variables ............ 6
Scope
MVIP Testing - The Omni flow computer has been tested by Honeywell Phoenix as part of their MVIP certification program. Contact Honeywell at:
All firmware revisions Version .71+ of Omni 6000/Omni 3000 flow computers have the capability of communicating with Honeywell TDC3000 Systems. This is a new feature that requires specified communication modules.
(602) 313-5830
TB-980201 ALL.71+
Technical Bulletin
Abstract
This technical bulletin addresses the various serial communication options that can be used to transfer data between Omni flow computers and Honeywell TDC3000 systems. The hardware equipment used and the limitations of each method are also discussed. Three types of serial communication modules are available:
TB-980201 ALL.71+
TB-980201
With a maximum of 16 array points available per FTA it can be seen that data consolidation and grouping becomes very important. Typical TDC3000-Omni systems will require a mixture of data types to be exchanged, this further complicates the configuration process. The user must take care not to waste valuable memory space by partially filling array points. Try to minimize the types of variable (e.g.: if you only need to read a few short integers consider converting them to long integers within the flow computer using variable statements). The limited number of array points also impacts how many Omni flow computers can be connected (multi dropped) to each FTA for example: Most applications require long integer totalizers, IEEE floating point values and also alarm statuses. This means that at least 3 array points will be needed per Omni and that assumes that 16 IEEE floats, 16 totalizers and 512 alarms will be sufficient to transfer all the data needed by the TDC3000 system (extremely unlikely, as there could be up to 4 meter runs configured).
Meter #1 - Current MF in Use Meter #2 - Current MF in Use Meter #3 - Current MF in Use Meter #4 - Current MF in Use Station Running Batch Size Station Next Batch Size
TB-980201 ALL.71+
Technical Bulletin
Long Integer
IEEE Float
Meter #1 - Next Batch Size Meter #2 - Running Batch Size Meter #2 - Next Batch Size Meter #3 - Running Batch Size Meter #3 - Next Batch Size Meter #4 - Running Batch Size Meter #4 - Next Batch Size
Modbus Function Codes Used to Access Custom Packet Data Within The Omni
The Omni supports the following Modbus function codes to access custom packet data: Read Multiple Registers Write Multiple Registers Write Single Register 03 16 06
TB-980201 ALL.71+
TB-980201
From the above it can be seen that Boolean variables must be handled differently when grouped within a custom array. They cannot be accessed using the normal Modbus function codes 01, 05 and 15. They can be read and written but as byte packed bits within Registers not as Coils and Status bits. For this reason it is recommended that writes to Boolean coils be accomplished by using the normal Modbus function code 05 and writing directly to the database Boolean point address.
CAUTION!
Here is an example showing a typical setup using the custom packet located at address 0001:
Packet #01 Point # # of Points Packet #02 Point # # of Points Packet #03 Point # # of Points Packet #04 Point # # of Points Packet #05 Point # # of Points Packet #06 Point # # of Points Packet #07 Point # # of Points Packet #08 Point # # of Points Packet #09 Point # # of Points Packet #10 Point # # of Points Packet #11 Point # # of Points Packet #12 Point # # of Points Packet #13 Point # # of Points Packet #14 Point # # of Points Packet #15 Point # # of Points Packet #16 Point # # of Points Packet #17 Point # # of Points Packet #18 Point # # of Points Packet #19 Point # # of Points Packet #20 Point # # of Points 7101 8 7201 8 7301 8 7401 8 5101 4 5201 4 5301 4 5401 4 3101 4 3201 4 3301 4 3401 4 1105 48 1205 48 1305 48 1405 48 0 0 0 0 0 0 0 0 ADDRESS 0001 - 0016 0017 - 0032 0033 - 0048 0049 - 0064 0065 - 0072 0073 - 0080 0081 - 0088 0089 - 0096 0097 - 0100 0101 - 0104 0105 - 0108 0109 - 0112 0113 - 0115 0116 - 0118 0119 - 0121 0122 - 0124 FTA ARRAY # USED 1 Total 16 Floats 1 2 Total 16 Floats 2 3 3 Total 16 Long Int. 3 3 4 4 Total 16 Short Int. 4 4 5 5 5 5 Total 24 Packed Bytes
Because Boolean data is byte packed the user must ensure that the number of Booleans included in the custom packet are grouped in such a way as to ensure that the packet always contains an even number of bytes (i.e. the function codes we are using expect to be dealing with registers and you cant have half a register).
These packets are available but are not used in this example.
The above shows a total of 32 floating points,16 long integers, 16 short integers and 192 Boolean status bits packed in 24 bytes being mapped in 1 custom data packet and 5 FTA arrays.
TB-980201 ALL.71+
Technical Bulletin
User Boolean statements are used to group Boolean bits as follows: Example:
1025: 1026: 1501=1105:1169 1565=1205:1269 Move 64 bits to 1501 through 1564 Move 64 bits to 1565 through 1628
User variable statements are used to move all of the remaining data types as follows: Example:
7025: 7026: 7501=7101:7103 7504=7201:7203 Move 3 floats to 7501 through 7503 Move 3 floats to 7504 through 7506
TB-980201 ALL.71+
TB-980201
Counter inputs ranging from 0-65535 are treated more generically requiring no scaling and are usually used for display purposes or are passed to an Application Module (AM) for processing. There are two options to monitor totalizing within the Omni flow computer:
The advantage of option (1) above is that any of the internal totalizers of the flow computer can be read in this manner and the results displayed by the TDC3000 system will match the flow computer displayed values. Option (2) is limited to one set of non-resetable totals which are not normally displayed at the flow computer and are of limited use. Using Variable Statements within the Omni flow computer makes it easy to convert just about any variable within the flow computers data base into a 16-bit register that can be read by the PLCG as either a counter or an analog (assuming the data will fit), the only problem being the availability of enough variable statements (64 are provided). Example 1: Variable read as counter for display only
7025: 3501=7105*#10 3501 contains M #1 temperature in tenths of degrees
Note that in Example 2 above, no attempt was made to limit the impact of over or under range values passed to the PLCG. It is the authors understanding that inputs outside of the expected range cause bad process value alarms in the PLCG.
TB-980201 ALL.71+
Technical Bulletin
TB-980201 ALL.71+
Date: 02
23
98
TB # 980202
Scope....................................................................................................................1 Abstract ................................................................................................................2 Calculations Performed ......................................................................................2 Using the Flow Computer Keypad to Recalculate a Previous Batch Ticket ....................................................................................................................3
Step 1 ............................................................................................................................ 3 Step 2 ............................................................................................................................ 3 Step 3 ............................................................................................................................ 3 Step 4 ............................................................................................................................ 4 Step 5 ............................................................................................................................ 4
Batch Recalculation - The batch recalculation feature allows you to adjust quantities of the previous 4 batches at measurement locations where SG60/API60 and S&W values only become available after the batch has been delivered.
Conclusion...........................................................................................................7
Scope
Firmware Revisions 20.71+ and 24.71+ of Omni 6000/Omni 3000 Flow Computers have the feature of Batch Recalculation. This feature applies to Turbine/Positive Displacement/Coriolis Liquid Flow Metering Systems (with K Factor Linearization.
TB-980202 20/24.71+
Technical Bulletin
Abstract
The purpose of recalculating a previous batch is to make batch quantity corrections based on SG60/API60 and Sediment and Water data becoming available via sample analysis performed after a batch delivery is complete. At measurement locations where SG60/API60 and S&W values are not available online, sampler devices continuously extract a representative sample of fluid during a batch. At the end of the batch the sample container is sent for lab analysis. The data obtained from the analysis report can then be used to recalculate the batch correction factors and therefore batch quantities. Historical data from these analysis reports is also used to determine what values of SG60/API60 should be used for real time calculation of future batches that are known to have similar characteristic. These batches ultimately can also be recalculated when their actual analysis is determined.
Calculations Performed
u The liquid correction factors Ctl and Cpl are first recalculated using the sample analysis SG60/API60 and the batch flow weighted average temperature and pressure calculated during the batch. u Gross Standard Volume (GSV) is recalculated using the newly calculated Ctl and Cpl. u The Sediment and Water correction factor Csw is calculated using the sample analysis S&W%. u Net Standard Volume (NSV) is recalculated using the recalculated GSV and Csw factor.
TB-980202 20/24.71+
TB-980202
To ensure that previous batch data is correctly recalculated do not recalculate a batch close to ending a current batch in progress.
Step 1
Press [Prog] [Batch] [Meter] [n] [Enter] (n = meter run number). The Omni LCD screen will display:
TIP - Note that only 4 lines can be displayed at one time. Use the scroll up or down arrows keys to display additional text.
! "
Step 2
Select which previous batch you wish to recalculate. The Omni stores the last 4 completed batches numbered as: 1 = last batch completed to 4 = oldest batch completed. Press [] to scroll down to Select Prev # Batch and enter a number between 1 and 4, depending upon which batch is to be recalculated. The flow computer moves the selected previous batch data to the previous batch data points within the database (see explanation later in this document)
Step 3
Enter Password when requested.
TB-980202 20/24.71+
Technical Bulletin
Step 4
Scroll to either Enter API60 or Enter SG60. Type in a valid value and press [Enter].
Step 5
Scroll to Recalculate & Print?. Press [Y] and then [Enter]. At this time the flow computer will recalculate the batch data and send the report to the printer and the Historical Batch Report Buffer in RAM memory. Batch report data can also be captured in Raw Data Archive RAM using the trigger Boolean 1n76. The default batch report shows the batch number as XXXXXXXX where the number ahead of the - is the batch number (5n90) and the number after the - is the number of times that the batch has been recalculated (3n52). Variable (3n52) is reset to 0 at the end of a batch and increments each time the batch is recalculated.
TB-980202 20/24.71+
TB-980202
u Modbus address of Current Batch in Progress Gross Totalizer is 5n01 u Modbus address of Previous Batch Gross Totalizer is 5n50 u Modbus address of Pointer register to select which previous batch is mapped is 3n51 As the batch progresses, the gross totalizer (5n01) accumulates flow. At the end of the batch the flow computer performs the following actions:
1) #3 previous batch data replaces #4 previous batch data 2) #2 previous batch data replaces #3 previous batch data 3) #1 previous batch data replaces #2 previous batch data 4) Current batch data replaces #1 previous batch data 5) Pointer register 3n51 is set to the value 1 so that the Modbus database
addresses for previous batch will access data for the batch just ended. This ensures that the batch report which prints immediately at the end of a batch and gets its data from the Modbus database, includes the correct information. The following table (using the batch gross totalizer as an example) shows typical data that would be read by accessing Modbus points 5n01 and 5n50. The data read depends upon the value of pointer register 3n51.
TB-980202 20/24.71+
Technical Bulletin
STEP
DESCRIPTION
Value contained in Pointer register 3n51.
ST
ND
RD
TH
12340
First batch ended. Second batch ended. Third batch ended. Fourth batch ended. Fifth batch ended with sixth batch running.
23450
12340
34560
23450
12340
45670
34560
23450
12340
56780
45670
34560
23450
12340
6123
56780
45670
34560
23450
METER #1
SG 60 or Reference Density (Rev. 24.71) API 60 Gravity Sediment and Water Percentage (BS&W) Command Boolean which triggers the recalculation
TB-980202 20/24.71+
TB-980202
Conclusion
Note: Setting these registers via Variable Statements is not allowed and will not produce the expected results
The flow computer retains data for the last four completed batches. Only one set of this data can be accessed at a time. Pointer registers, 3151 Meter Run #1, 3251 Meter Run #2, 3351 Meter Run #3, 3451 Meter Run #4n and 3879 for Meter Station are used to determine what set of batch data will be accessed. API60/SG60 and S&W data can be adjusted and the batch recalculated by writing a 1 to points, 2756 for Meter Run #1, 2757 for Meter Run #2, 2758 for Meter Run #3, 2759 for Meter Run #4 and 1798 for Meter Station.
TB-980202 20/24.71+
Date: 03
10
98
TB # 980301
Contents
Scope....................................................................................................................1 Abstract ................................................................................................................1 Instructions..........................................................................................................2
DANGER!
Scope
Electrical Shock Hazard! Dangerous AC voltages are present on the power supply module and ribbon cable when the unit is AC powered. To avoid electrical shock which could be fatal, It is imperative that you remove all power before opening and disassembling the flow computer and take any other necessary precautions. Only qualified technicians should work on any internal circuitry. Omni Flow Computers, Inc. is not responsible for personal injuries or accidents that may occur when working on flow computer circuitry.
The observations and instructions for replacing Erasable Programmable Readonly Memory (EPROM) chips contained in this technical bulletin are applicable to all firmware revisions of Omni 6000/Omni 3000 Flow Computers. It is strongly recommended that EPROMs be replaced only by qualified personnel.
Abstract
You will need to replace EPROMs usually to upgrade your flow computer firmware. Certain critical steps must be performed when replacing EPROMs. It is strongly recommended that EPROMs be replaced only by qualified personnel. Before removing any circuit boards from the flow computer, the following must be observed: u Personal Safety : Although most of the internal circuits are powered by relatively low voltages, dangerous AC voltages are present on the power supply module and ribbon cable when the unit is AC powered. For this reason it is important to remove all power before disassembling the computer. u Static Electricity : Static electricity can be generated simply by moving around on certain surfaces or wearing certain types of clothing. The flow computers printed circuits can be damaged by this static electricity. Take approved static device handling precautions when working on the flow computer. After replacement, the old EPROMs must be returned to the manufacturing department of Omni Flow Computers, Inc. in Stafford, Texas. A Business Reply Label is available for this purpose.
CAUTION!
Static electricity can damage flow computer circuitry. Take approved static device handling precautions when working on the flow computer.
Technical Bulletin
Instructions
To replace EPROM chips, follow these instructions: (1) Stop flow then end the batch. Record all data by retrieving all reports and saving and printing the flow computer configuration using OmniCom Software. Verify that the file in OmniCom is the correct version. (2) Enter the Password Maintenance Mode and enter the privileged password for your computer. Scroll down to Reset All Ram ? and enter [Y]. For Omni flow computers manufactured after 1995, resetting all RAM will not affect totalizer and calibration data. (3) Remove all power from the computer and completely disconnect all AC/DC power. (4) If you have an Omni 3000 Flow Computer, remove the Digital I/O Module from Slot #2. This will allow better access to the CPU Module in Slot #1.
CAUTION!
When removing the CPU Module, take extreme care not to bend or fold the membrane keypad ribbon cable too sharply, or the metallic traces could be damaged.
(5) The CPU is connected to the front panel via a short ribbon cable that is folded in a specific manner. Carefully remove the CPU Module just far enough to unplug this ribbon cable. When removing the CPU Module, allow the connector edge of the module to tilt towards the back of the flow computer. This will enable the Ni-Cad battery on the CPU Module to slide past the program inhibit switch on the front panel assembly. Take special care not to bend or fold the membrane keypad ribbon cable too sharply, or the metallic traces could be damaged. (6) Using an EPROM extractor or small flat-bladed screwdriver, carefully pry up one end of the EPROM and repeat the prying at its other end. This will allow the EPROM to be removed without bending any pins. (7) Lay the module on a non-metallic surface to prevent shorting out the NiCad Battery. Install the new EPROMs making sure that the orientation notches are correctly positioned and that no pins are bent under the chip. To install, line up one edge of the EPROM pins making sure that the opposite edge is lined up with the socket holes, and firmly press the EPROM into the socket. (8) Reinstall the CPU Module in the reverse order and apply power. (9) Initialize the computer using OMNI as the password. Repeat Step (2) to reset all RAM, and reintialize the flow computer once again using OMNI as the password. (10) Manually create a new file based on the oil file printout and upload the newly created configuration file to the OMNI. Remember to use the Business Reply Label supplied with your new EPROMs. Please return the old EPROMs to Omni Flow Computers, Inc.
Location of EPROM Chips- The location of the EPROM chips on the CPU Module is shown in Fig. 1. The EPROMs are the two large 32-pin Integrated Circuits (ICs or chips) with labels marked U3 and U4. Note the position of the orientation notches at one end of each EPROM.
TB-980301
IMPORTANT!
TROUBLESHOOTING TIP: Omni Display Does Not Come On After Resetting All RAM - If the Omni Display does not come on after resetting all RAM, proceed as follows: (1) Disconnect all power to the Omni. (2) Remove CPU Module and also remove the System Watchdog Jumper J3 (See Fig. 1) on the CPU. (3) Reinstall CPU Module with Jumper J3 removed. (4) Power up the Omni and reset all RAM again. Display should be on. (5) Power down again the flow computer and remove CPU Board. (6) Replace Jumper J3 and then reinstall the CPU Module. (7) Once again, apply power to the flow computer. Display should be normal. If you encounter any other difficulties, please contact our technical staff. Phone: (281) 240-6161 Fax: (281) 240-6162 E-mail:
techsupport@omniflow.com
Math Processor
Central Processor
Program EPROM
Program RAM
Archive RAM
Backup Batttery
J1
J2
J3
Fig. 1.
Layout of Central Processor Module Showing Location of EPROM ICs and Jumper J3.
Date: 04
06
98
TB # 980401
Peer-to-Peer Basics
Contents
User Manual Reference This technical bulletin complements the information contained in User Manual, and is applicable to all firmware revisions Version .70+. This is an updated edition that replaces previously published bulletins under the same title. See also the following: u TB-980402 - Using the Peer-to-Peer Function in a Redundant Flow Computer Application u Volume 1 - 1.6.3. Serial Communication Modules
Scope....................................................................................................................1 Abstract ................................................................................................................2 Determining Which Computer Will Be Master..................................................2 Communication Settings for the Peer-to-Peer Link.........................................3 Foreign Modbus Devices and Single Master Systems ....................................3 Wiring Options.....................................................................................................4
RS-232-C Wiring Requirements.................................................................................... 4 RS-232 to RS-485 Converter Wiring Requirements...................................................... 5 RS-485 Wiring Requirements........................................................................................ 6
Setting up Transactions .....................................................................................8 What Modbus Function Codes Are Used..........................................................8 Special Considerations when Modicon Compatible is Selected for Port #2 ..................................................................................................................8 Using Peer-to-Peer with Micro Motion Coriolis Mass Meters ......................9
The Micro Motion Meter is a Modicon Compatible Device........................................... 11 Setting Up the Peer-to-Peer Transactions................................................................... 11
Peer-to-Peer Communications - The peer-to-peer communication feature allows you to multidrop up to 32 flow computers and other devices in RS-485 serial communications mode, and up to 12 using RS-232-C communications.
Scope
All firmware revisions Version .70+ of Omni 6000/Omni 3000 Flow Computers have the Peer-to-Peer Communication feature.
Peer-to-Peer Redundancy Schemes - Redundancy schemes allows for uninterrupted measurement and control functionality by interconnecting two identically equipped and configured flow computers.
TB-980401 ALL.70+
Technical Bulletin
Abstract
Communications between Omni flow computers is accomplished using the peerto-peer function. This function is available only on Serial Port #2 with data being transmitted and received using Modbus RTU protocol. A data transaction list within each flow computer defines each Read or Write operation to be transacted for that computer. A maximum of 16 transactions per flow computer are available. The transaction list must be contiguous (i.e., an empty transaction will be treated as the end of list). Two optional serial communication I/O modules are available with your flow computer: the RS-232-C (compatible) Model #68-6005, and the RS-232-C/RS485 Model #68-6205. The older Model #68-6005 is only capable of RS-232 compatible serial communications. The newer Model #68-6205 is capable of either RS-232 or RS-485 communications via a selection jumper. When jumpered for RS-232, the characteristics and functionality of this module is identical to that of the older RS-232-C module.
TB-980401 ALL.70+
TB-980401
Peer-to-Peer Basics
While slower baud rates can be used, 38.4 kbps or 19.2 kbps will provide maximum performance.
The peer-to-peer function is not limited to multiple Omni flow computers. Some applications simply require a single flow computer master to communicate with a variety of Modbus slave devices which may be flow computers, PLCs etc. In these cases, the entries 1 and 2 above would be set to 1 in the master flow computer only, signifying only one master is in the system. Entry 3 above would normally be set to 3 but may need to be increased depending upon the message response time of any foreign Modbus devices in the system.
TB-980401 ALL.70+
Technical Bulletin
Wiring Options
RS-232-C Wiring Requirements
The following diagram shows the wiring requirements using the RS-232-C termination option. When multiple flow computers are used as peer-to-peer masters, they are connected in two-wire, multi-drop mode.
INFO - The Omni Flow Computer uses a proprietary tristatable RS-232-Compatible serial port, which unlike a normal RS-232 port, can be multidropped, interconnecting up to 12 flow computers or other serial devices.
Om ni #1
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12
Om ni #2
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12
Om ni #3
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12
Om ni #4
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12
Fig. 1.
Omni 6000 (3000) Peer-to-Peer Wiring Requirements using the RS-232-C Termination Option
TB-980401 ALL.70+
TB-980401
Peer-to-Peer Basics
Omni #1
TB3 (TB2) 1 2 3 4 5 6 7 8 9 10 11 12
Omni #2
TB3 (TB2) 1 2 3 4 5 6 7 8 9 10 11 12 RS-232 to 485 Converter (Disable Echo) R S 2 3 2 TX-A TX-B RX-A RX-B A
PLC
R S B 4 8 5
Fig. 2.
Omni 6000 (3000) Peer-to-Peer Wiring Requirements with PLC using a Standard RS-232 to RS-485 Converter Module
TB-980401 ALL.70+
Technical Bulletin
The diagram below shows a typical peer-to-peer installation using RS-485 communications, where four flow computers are interconnected in a two-wire, multi-drop mode.
Omni #1
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12 RS-485 Two-wire Terminated (A) (B)
Omni #2
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12 RS-485 Two-wire Non-terminated (A) (B)
Omni #3
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12 RS-485 Two-wire Non-terminated (A) (B)
Omni #4
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12 RS-485 Two-wire Terminated (A) (B)
Fig. 3.
Omni 6000 (3000) Peer-to-Peer Wiring Requirements using the RS-485 Two-wire Multi-drop
TB-980401 ALL.70+
TB-980401
Peer-to-Peer Basics
The peer-to-peer communication link may also be used to transfer data to and from any other Modbus slave device such as a PLC. The following diagram shows a typical installation using RS-485 where two flow computers are connected to a PLC in a two-wire, multi-drop mode.
Omni #1
TB3 (TB2) 1 2 3 4 5 6
Omni #2
TB3 (TB2) 1 2 3 4 5 6
PLC
R S A 4 8 5 B
(B) 7 8 9 10 (A) 11 12
RS-485 Two-wire Terminated
(B) 7 8 9 10 (A) 11 12
RS-485 Two-wire Non-terminated
Fig. 4.
Omni 6000 (3000) Peer-to-Peer Wiring Requirements with PLC using the RS-485 Two-wire Multi-drop
TB-980401 ALL.70+
Technical Bulletin
Setting up Transactions
To process a transaction the flow computer requires the following data for each transaction:
Modbus Broadcast Address 0 - This address only applies to write transactions.
: The Modbus address of the target device. This can be any valid Modbus address including the broadcast address 0. Read or Write : Select the appropriate operation. Source Point Number : Specifies the data base address of the variable in the source device. For a read operation the slave is the source. For a write operation the source is the Omni flow computer master. Number of Points : The number of consecutive data variables to transfer between devices, starting at the source point number or address. Destination Point Number : Specifies the data base address of the variable in the destination device. For a write operation the slave is the destination. For a read operation the destination is the Omni flow computer master. Slave ID
TB-980401 ALL.70+
TB-980401
Peer-to-Peer Basics
Omni #1
TB3 (TB2) 1 2 3 4 5 6 7 8 9 10 11 12
Omni #2
TB3 (TB2) 1 2 3 4 5 6 7 8 9 10 11 12 RS-232 to 485 Converter (Disable Echo) R S 2 3 2 TX-A TX-B RX-A RX-B
Micro Motion RFT #2 R S 27 (Z22) 4 26 (D22) 8 5 R 27 (Z22) S 26 (D22) 4 8 5 Micro Motion RFT #1
Note: Termination Points 26 & 27 correspond to the explosion-proof field-mount RFT9739; and (D22) & (Z22) to the rack-mount version of the model.
Fig. 5.
Omni 6000 (3000) Peer-to-Peer Wiring Requirements with Micro Motion RFT Transmitters using a RS-232 to RS-485 Converter
TB-980401 ALL.70+
Technical Bulletin
The following diagram shows a typical peer-to-peer installation using RS-485, where two flow computers are connected to two Micro Motion RFT9739 transmitters via a proprietary RS-232/485 Serial I/O Module #68-6205.
Micro Motion Elite Model RFT9739 Transmitter Connectivity Both field-mount (explosionproof) and rack-mount models of the RFT9739 transmitter have the A and B channels reversed to the industry standard applied to Omni flow computers; i.e., the flow computers A channel connects to Micro Motions B channel. Omni has tested this connectivity with the Micro Motion RFT9739 Field-Mount Transmitter, but connecting to the rack-mount version has not yet been tested. Information on this connectivity has been provided by Micro Motion, Inc. Please contact Micro Motion for further information.
Omni #1
TB3 (TB2) 1 2 3 4 5 6 7 (B) 8 9 10 (A) 11 12
RS-485 Two-wire Terminated
Omni #2
TB3 (TB2) 1 2 3 4 5 6 7 (B) 8 9 10 (A) 11 12
RS-485 Two-wire Non-terminated
(A) 27 (Z22)
120
(A) 27 (Z22)
Note: Termination Points 26 & 27 correspond to the explosion-proof field-mount RFT9739; and (D22) & (Z22) to the rack-mount version of the model.
Fig. 6.
Omni 6000 (3000) Peer-to-Peer Wiring Requirements with Micro Motion RFT9739 Transmitters using the RS-485 Two-wire Multidrop.
10
TB-980401 ALL.70+
TB-980401
Peer-to-Peer Basics
The following peer-to-peer transaction reads the flowing density of the fluid from the Micro Motion device (Modbus ID #2) and stores it in data base point 7108 (unfactored density, meter run #1). Transaction #1 Target Slave ID Read/Write ? Source Point # # of Points Destination Pnt # ........ ........ ........ ........ ........ 2 R 248 2 7108
The next transaction reads a 16-bit integer register from the MM meter which contains packed alarm status bits. These are stored in a special register within the flow computer which causes them to be time and date tagged, printed and logged just as though they were flow computer alarms. Transaction #2 Target Slave ID Read/Write ? Source Point # # of Points Destination Pnt # ........ ........ ........ ........ ........ 2 R 0 1 3118
The examples above refer to Meter #1 transactions that the flow computer is requesting. More transactions may be needed depending upon what data is required and how many meter runs are being used.
TB-980401 ALL.70+
11
Date: 04
07
98
TB # 980402
Scope....................................................................................................................1 Abstract ................................................................................................................2 RS-232-C Wiring Requirements .........................................................................2 RS-485 Wiring Requirements .............................................................................3 Setting Up the Peer-to-Peer for Redundant Flow Computer Applications....3 Sensing Failures and Switching between Redundant Computers.................5 Changing the Master / Slave Status via a Modbus Serial Port .......................6 Redirecting the Control Signals.........................................................................6 Sharing Input Signals Between Primary and Secondary Flow Computers ...7 Re-Calibration of Analog Inputs ........................................................................7 Sharing Digital I/O Signals Between Primary and Secondary Flow Computers ...........................................................................................................7
Peer-to-Peer Redundancy Schemes - Redundancy schemes allows for uninterrupted measurement and control functionality by interconnecting two identically equipped and configured flow computers.
Scope
All firmware revisions Versions .70+ of Omni 6000/Omni 3000 Flow Computers have the Peer-to-Peer Communications feature, which is available only on Serial Port #2. This features includes the capability of setting-up redundant flow computer schemes.
TB-980402 ALL.70+
Technical Bulletin
Abstract
Redundancy involves using two identically equipped flow computers and connecting them in such a way to ensure uninterrupted measurement and control functionality in the event of failure of one of the units. This requires that all input and output signals are connected to both computers. During normal operation, one computer is designated the primary and the other computer the secondary or backup. To ensure synchronization between both devices, important variables such as PID controller settings, control valve positions and proving meter factors must be transmitted from the primary flow computer via the peer-to-peer link to the secondary flow computer. Should a failure of the primary flow computer occur, the secondary flow computer is automatically promoted to primary and assumes all control and measurement functions. In this case the data flow on the peer-to-peer link reverses automatically and the new master begins to transmit critical data to the slave, assuming that it is functioning. Peer-to-peer communication errors can occur during the switch over and are normal. They are cleared by pressing the [Ack] key on the flow computer keypad or writing to point 1712 (acknowledge station alarms). If the other flow computer is non-operational, the peer-to-peer communication errors cannot be cleared.
Omni #1
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12
Omni #2
TB3 (TB2)
1 2 3 4 5 6 7 8 9 10 11 12
Fig. 1.
TB-980402 ALL.70+
TB-980402
Omni #1
TB3 (TB2) 1 2 3 4 5 6
Omni #2
TB3 (TB2) 1 2 3 4 5 6
(B) 7 8 9 10 (A) 11 12
RS-485 Two-wire Terminated
(B) 7 8 9 10 (A) 11 12
RS-485 Two-wire Terminated
Fig. 2.
Omni 6000 (3000) Peer-to-Peer Wiring Requirements using the RS-485 Two-wire Termination Mode in a Redundant Flow Computer Scheme
TB-980402 ALL.70+
Technical Bulletin
Transaction #1
Target Slave ID Read/Write ? Source Point # # of Points Destination Pnt # Target Slave ID Read/Write ? Source Point # # of Points Destination Pnt #
........ 2 ........ W ........ 13462 ........ 8 ........ 13470 ........ ........ ........ ........ ........ 2 W 7601 20 7601
Transaction #2
More peer-to-peer transactions are needed if additional data needs to be transferred, meter factors for example. Flow computers containing firmware Revisions 22 or 26 handle meter factor implementation differently than Revisions 20 or 24. These applications maintain historical meter factor entries which are triggered and stored when the meter factor is accepted and implemented at the end of a meter proving. As only the primary flow computer will be doing the actual proving, three special variables with associated firmware code have been added to the data base of revisions 22 and 26. By writing to and reading from these variables via the peer-to-peer link, the secondary flow computer can implement the meter factor result obtained when the primary computer completes and accepts a prove result.
Transactions #3 & #4 (Applicable to Firmware Versions 22 & 26 Only) Both primary and secondary flow computers must have these entries. u Transaction #3 is used to send the prove meter factor (5904) and the number of the meter last proved (5905) to the secondary flow computer. u Transaction #4 confirms that the meter factor has been implemented in the secondary flow computer by reading back a copy of the number of the meter run just proved (5906).
The following two transactions are required: Transaction #3 Target Slave ID Read/Write ? Source Point # # of Points Destination Pnt # Target Slave ID Read/Write ? Source Point # # of Points Destination Pnt # ........ ........ ........ ........ ........ ........ ........ ........ ........ ........ 2 W 5904 2 5904 2 R 5906 1 5906
Transaction #4
TB-980402 ALL.70+
TB-980402
2864
2713 2714
O m ni #1
TB 1
1 2 3 4
O m ni #2
TB 1
1 2 3 4 5 6 7 8 O th e r M a s te r S ta tu s (2 7 1 4 ) O th e rs M a s te r S ta tu s (2 7 1 4 ) 9 M a s te r S ta tu s (2 8 6 4 ) O th e rs W a tc hd o g (2 7 1 3 ) W a tc h d o g O u t (2 8 6 3 ) M a s te r S ta tu s (2 8 6 4 ) O th e rs W a tc hd o g (2 7 1 3 ) W a tc h d o g O u t (2 8 6 3 ) 10 11 12
Redundancy Failover Wiring - Any 4 digital I/O points may be used to provide a failover switching mechanism. Fig. III.8-3 is an example that shows digital I/O 9 through 12 being used
5 6 7 8 9 10 11 12
TB 11
+
TB 11
+
Fig. 3.
TB-980402 ALL.70+
Technical Bulletin
Note: The 2716 command will not work if the other flow computers watchdog status is not active (i.e., the other computer must be functioning correctly before this flow computer can give up mastership).
2716
Both the above commands are edge triggered needing only to be turned on, they do not need to be turned off.
TB-980402 ALL.70+
TB-980402
Sharing Digital I/O Signals Between Primary and Secondary Flow Computers
Digital I/O channels configured as status inputs should be simply wired in parallel (ORed) with the other flow computer. Digital I/O channels configured as outputs may possibly require relay isolation similar to that needed for analog outputs described previously. Typical output signals that need to be relay isolated are sampler pulse outputs. Prover control signals do not usually need to be relay isolated as the secondary computer will never be attempting to control the prover while it is the slave or secondary computer. The user will need to determine which outputs need to be isolated based on whether it is possible or likely that the slave computer would activate the output when not in control.
TB-980402 ALL.70+
Date: 05
03
98
TB # 980501
Scope....................................................................................................................2 Abstract ................................................................................................................2 Important Omni Flow Computer Compatibility Issues When Using SV Combo Modules ..................................................................................................3
Serial Communication Module Compatibility ................................................................. 3 Other Know System Incompatibilities ............................................................................ 3 Equipment Ordering Limitations .................................................................................... 3
Connectivity Issues When Connecting to the 3095FB Multivariable Transmitters: Multi-drop versus Point-to-Point ...............................................4
Advantages of Multi-drop Configurations ...................................................................... 4 Disadvantages of Multi-drop Configurations.................................................................. 4
Initial Setup of the Rosemount 3095FB Multi Variable Transmitter ............8 Connecting the 3095FB to the Omni Flow Computer......................................9
3095FB Transmitter RS-485 Connections................................................................... 10 3095FB Transmitter Power Connections and Requirements ...................................... 10 Isolation and Transient Protection Issues ................................................................... 11 Wiring Considerations When Replacing a Multi-dropped 3095FB Transmitter ........... 11
Configuring the Omni Flow Computer to use the 3095FB Multi Variable Transmitter.........................................................................................................12
Configuring the Meter Run I/O..................................................................................... 12
Selecting the Device Type ......................................................................................................12 Selecting the SV Combo Module Port.....................................................................................12 Select Modbus Address for 3095FB .......................................................................................12 What I/O Points are Used and Why ........................................................................................12
Data Transferred between the 3095FB Transmitter and the Omni Flow Computer ...........................................................................................................14
Polling Intervals for Process Variables and Critical Alarms......................................... 15 Critical 3095FB Alarms Monitored By The Flow Computer ......................................... 15
Technical Bulletin
Viewing the 3095FB Data at the Flow Computer Front Panel.......................16 Installing, Replacing and Calibrating 3095FB Transmitters .........................17
Wiring Issues ...............................................................................................................17 Using the Omni Flow Computer to Set the Modbus Address of the 3095FB...............18 Using a Laptop PC to Trim the 3095FB Calibration.....................................................19
Scope
Firmware Revisions 21.72+/25.72+ and 23.72+/27.72+ of Omni 6000/Omni 3000 Flow Computers are affected by the issues contained in this technical bulletin. This Bulletin applies to Orifice/Differential Pressure Liquid Flow Metering Systems and to Orifice Gas Flow Metering Systems.
Abstract
The Rosemount 3095FB Multivariable sensor assembly is used to measure differential pressure (DP), static pressure (SP) and line temperature (T). Application of the 3095FB is limited to flow computer revisions 21, 23, 25 and 27 which work with differential head devices such as orifice meters, nozzles and venturi meters. Because the flow computer is limited to a maximum of four meter runs it is also limited to a maximum of four 3095FB multivariable transmitters. Data is accessed from the 3095FB transmitter via a 2 wire RS-485 data link at 9600 baud using Modbus protocol. Technically, it would have been possible to use one of the flow computers standard serial ports to communicate with the 3095FB but this would have caused several problems: u Reduced the number of serial ports available for use with SCADA, PLCs and OmniCom etc. u Extra 'A type combo modules would have to be purchased simply to provide analog outputs in a minimum system requiring just the multivariables. Omni chose to design a special SV combo module which includes two 2 wire RS-485 ports and six 4-20 mA analog outputs. With this module it becomes possible to provide a powerful Omni 3000 system with the following specs: u Four meter runs with Differential Pressure, Static Pressure and Temperature inputs. u Four communication ports for SCADA, PLC, Printer, OmniCom etc. u Twelve Digital I/O for logic control u Six digital to analog outputs. This SV module is capable of connecting to one to four 3095FBs in various multi-drop configurations. A second SV combo module can be utilized in applications where point to point operation of more than two multivariable transmitters is desirable.
TB-980501
Important Omni Flow Computer Compatibility Issues When Using SV Combo Modules
The SV combo modules are effectively serial I/O modules which have been specially designed to communicate with various multivariable transmitters. Changes have been made to the IRQ priorities to accommodate these SV combo modules. These IRQ changes also involve the Serial I/O Combo Modules that are used to connect to printers, OmniCom, PLCs and SCADA devices.
Technical Bulletin
Connectivity Issues When Connecting to the 3095FB Multivariable Transmitters: Multi-drop versus Point-to-Point
The 3095 FB multivariable transmitter is a four wire device, two power wires and two wires for the RS-485 serial communication link. It can be connected in a point-to-point or multi-drop wiring configuration.
TB-980501
SV RS-485 Termination Jumpers Both Jmpers In = Port Terminated Both Jmpers Out = Port Un-Terminated Always RTS SV Address Jumper Jmp Out = 1st SV Combo nd Jmp In = 2 SV Combo Always IRQ 2
2 BRD SEL 4 IRQ
SV Port 1 ( 3 )
RTS T E R M
GND T E R M
SV Port 2 ( 4 )
Technical Bulletin
Setting the Termination Jumpers for the Each of the SV RS-485 Ports
Multivariable RS-485 communication circuits must have two ends only, a star configuration with more than two ends or a loop configuration with no ends is not allowed. The devices at both ends of the circuit must be jumpered to provide termination.
3095 FB MV ID #2
3095 FB MV ID #3
3095 FB MV ID #4
Both jumpers marked TERM must be installed to terminate a flow computer SV port (see Fig. 1 previous page). Termination settings for the 3095FB are shown later in this document.
3095 FB MV ID #4
3095 FB MV ID #2
3095 FB MV ID #3
TB-980501
3095 FB MV ID #1
3095 FB MV ID #2
3095 FB MV ID #3
3095 FB MV ID #4
Fig. 4.
3095 FB MV ID #1
3095 FB MV ID #1
3095 FB MV ID #1
3095 FB MV ID #1
Modbus IDs of 3095FBs Can Be The Same In This Point to Point Configuration
Fig. 5.
In the point-to-point configuration each 3095FB transmitter is connected to an independent SV port of the flow computer. Because each SV port is now connected to only one 3095FB, each 3095FB can now use the default Modbus address 1, greatly simplifying transmitter replacement issues discussed later in this document.
Technical Bulletin
All ON = Terminated All OFF = Un-Terminated AC TERMINATION PULL DOWN (B) PULL UP (A)
o OFF o ON o SECURITY o o
o o o o o
ON 1 2 3 S1 S2 ON 1 2
Place the security jumper in the OFF position, this allows the Omni flow computer to write to the 3095FB registers ensuring that the internal configuration matches the flow computer. Both baud rate switches S1 and S2 must be set to 9600; i.e., in the ON position. The termination switches should be all ON or all OFF depending upon whether device termination is required.
TB-980501
Fig. 7. Module
A RS-485 B + PWR -
Fig. 8.
Technical Bulletin
A RS-485 B + PWR -
A RS-485 B + PWR -
A RS-485 B + PWR -
Termination OFF
Termination OFF
Termination ON
10
TB-980501
11
Technical Bulletin
Configuring the Omni Flow Computer to use the 3095FB Multi Variable Transmitter
Configuring the Meter Run I/O
Selecting the Device Type
The existing Select Turbine Y/N entry in the Config Meter Run menu has been changed to Select Device Type. Valid selections at this point are: 0 1 2 3 = = = = DP Sensor Turbine Meter 3095FB Multivariable SMV 3000 Multivariable
12
TB-980501
EXAMPLE 1 CONFIGURATION A1 Combo Module I/O Points A2 Combo Module I/O Points B1 Combo Module I/O Points 1
st nd rd th
6000 - 2A - 1B 2SV 1-4 5-8 9 - 12 DP=13, T=14, P=15 DP=16, T=17, P=18 DP=19, T=20, P=21 DP=22, T=23, P=24
Fig. 10.
EXAMPLE 2 CONFIGURATION A1 Combo Module I/O Points E/D1 Combo Module I/O Points 1
st nd
6000 - 1A - 1E/D 1SV 1-4 5-8 DP=9, T=10, P=11 DP=12, T=13, P=14 DP=15, T=16, P=17 DP=18, T=19, P=20
3095FB Configured Uses 3095FB Configured Uses 3095FB Configured Uses 3095FB Configured Uses
2 3
rd th
Fig. 11.
13
Technical Bulletin
u 4mA Value (read only) u 20mA Value (read only) u Damping Code
0 1 2 3 4 = 0.108 Seconds5 = 3.456 Seconds = 0.216 Seconds6 = 6.912 Seconds = 0.432 Seconds7 = 13.824 Seconds = 0.864 Seconds (Default) 8 = 27.648 Seconds = 1.728 Seconds
All of these data entries are changeable when using analog transmitters but when using the 3095FB multi variable transmitter the 4mA and 20mA scaling values cannot be changed. The upper and lower range of the 3095FB sensors are fixed by design. The Omni flow computer simply reads these values and displays them in the 4mA and 20mA fields for information only. While the 3095FB transmitter has internal alarm setpoints and alarm status points, Omni has chosen to ignore the 3095FB integral alarming functions and use the existing flow computer alarm setpoints and alarm status points. The Low and High Alarm Setpoints of the flow computer therefore behave exactly as they would with an analog transmitter. The 3095FB Critical Alarm states are monitored continuously.
Data Transferred between the 3095FB Transmitter and the Omni Flow Computer
In operation the Omni flow computer automatically sets up the 3095FB transmitter to use the correct floating point format and units of measure needed to match the flow computers configuration. The Omni continuously reads the following data: u u u u u u Process Variables DP, Pressure and Temperature Individual Transmitter Sensor Ranges Critical Transmitter Alarms (Sensor failures etc) Transmitter Information (Body and Fill material etc) Manufacturers Code Transmitter Tags
TB-980501 21/25.72+ & 23/27.72+
14
TB-980501
ALARM POINT DESCRIPTION DP signal 10% above upper range limit DP signal 10% below lower range limit Pressure signal 10% above upper range limit Pressure signal 10% below lower range limit Pressure sensor is shorted Pressure sensor bridge is open circuit Temperature signal 10% above upper range limit Temperature signal 10% below lower range limit Temperature RTD is disconnected Sensor internal temperature above upper range limit Sensor internal temperature below upper range limit Critical 3095FB sensor electronics failure Security jumper of 3095FB is set to Write Protect No Communications between the Omni and 3095FB unit
DP transmitter failure flagged DP transmitter failure flagged Pressure transmitter failure flagged Pressure transmitter failure flagged Pressure transmitter failure flagged Pressure transmitter failure flagged Temperature transmitter failure flagged Temperature transmitter failure flagged Temperature transmitter failure flagged DP, P and T, transmitter failures flagged DP, P and T, transmitter failures flagged DP, P and T, transmitter failures flagged DP, P and T transmitter failures flagged if write to 3095FB is attempted and fails. DP, P and T, transmitter failures flagged
^ 1n96
15
Technical Bulletin
Critical 3095FB configuration data which is checked every 10 seconds are: u u u u u u u Floating Point Number Format ** (0132) Measurement Engineering Units of Measure ** (0060 - 0062) Minimum and Maximum Ranges of each Signal * (7407 - 7416) Transmitter Identification (Information Only) (0001 - 0011) Damping Factors ** (7421, 7424, 7427) Transmitter ASCII Tags (3x8 characters) ** (0032 - 0047) Transmitter Information (Materials of Construction) (0017 - 0029)
**
The flow computer will attempt to correct the database of the 3095FB transmitter if miss matches are detected for these variables.
The flow computer will adjust its database to agree with the 3095FB database if miss matches are detected for these variables.
1 digit is the SV port nd number, 2 digit is the Modbus Address of the 3095FB
st
16
TB-980501
!" # $ %!! &'
()* + , - " " - *# ( - ! ". /
0 % .# .
# ## .-
0 % .- ()* 1* ,# % #- (.23(4 ()* 5 .# 5 / 5 5
5
17
Technical Bulletin
Using the Omni Flow Computer to Set the Modbus Address of the 3095FB
The 3095FB transmitter will normally be shipped with a default Modbus address of 1. While this is fine for a point to point installation, it will cause a problem if two or more devices have the same Modbus ID in a multi-drop scheme. The Modbus ID of a transmitter can be set using the Configurator User Interface PC Software available from Rosemount. It is anticipated though that some situations may arise where a 3095FB transmitter must be installed or replaced without this software being available. In this case the Omni flow computer can be connected to a 3095FB in the point to point mode using any available SV port and the Modbus ID changed to what is required in the flow computer configuration.
CAUTION!
Proceed as follows: 1. Setup the 3095FB as described previously in the section titled Initial Setup of the Rosemount 3095FB Multi Variable Transmitter. 2. Setup the 3095FB to be RS-485 terminated. 3. Connect the transmitter to any open SV port (terminal A to A, B to B). The SV port should be jumpered for RS-485 termination. If this SV channel is not an open channel, all 3095FB transmitters except the one needing the address change must be disconnected. 4. Apply power to the 3095FB transmitter. 5. At the flow computer front panel press the following keys:
[Alpha Shift] [Diag] [Setup] [n] [Enter]
This procedure involves broadcast transmitting a Modbus address out of a SV port. All devices connected to this SV port will have their Modbus address set to the ID broadcast. This would cause data collisions and a complete loss of communication when more than one 3095FB transmitter is connected. Be sure to temporarily disconnect any 3095FB transmitters which addresses you do not want to change.
The computer will enter the Diagnostic mode. Where n is the SV port number that the 3095FB is connected to.
6. The following warning screen may display ( SV port 1 is used as an example) or the screen in (7) below will display.
6 (7# 1
) 1#-
. 89 1#
3:54;
This means that the flow computer has detected that this SV port is currently configured to communicate with one or more transmitters. You may or may not have selected the wrong SV port (see the cautions in sidebar).
7. If you wish to continue with the address broadcast operation enter Y and
the following screen will display.
18
TB-980501
#- 5= <
9. The flow computer will wait a short time and then attempt to communicate with the 3095FB using the new address. If communications are established the following message will be displayed for a few seconds.
< 17-
The following message will display for a second or two should the transmission fail.
.# 17-
Should this message appear check your wiring, switch and jumper settings and repeat the procedure. 10. Disconnect and reinstall 3095FB to the appropriate SV port for normal operation making sure to observe the termination requirements of only two devices at the end of a loop being terminated.
19
Date: 05
13
98
TB # 980503
Scope....................................................................................................................1 Abstract ................................................................................................................1 Features and Specifications...............................................................................2 Dual Channel RS-232-C Serial I/O Module Model #68-6005 ............................3 RS-232-C / RS-485 Serial I/O Module Model #68-6205-A .................................4 RS-232-C / RS-485 Serial I/O Module Model #68-6205-B .................................6 RS-232-C / RS-485 Serial Port Jumper Options................................................8
Scope
All Omni 6000/3000 Flow Computers have serial communications capabilities via proprietary serial I/O modules.
Abstract
Omni flow computers can come equipped with serial I/O modules that communicate with RS-232-Compatible or RS-485 devices. Omni manufactures three models of serial modules: u Dual Channel RS-232-C Serial I/O Module Model # 68-6005 u RS-232-C/RS-485 Serial I/O Module Model # 68-6205-A u RS-232-C/RS-485 Serial I/O Module Model # 68-6205-B Each serial module has 2 ports. Omni 6000 flow computers can have up to two serial modules installed for a maximum of 4 ports. Omni 3000 flow computers typically use one serial module providing 2 ports. Each serial communication port is individually optically isolated for maximum common-mode and noise rejection. Jumpers are provided for selection of module address and serial port communication standards. Communication parameters such as protocol type, baud rate, stop bits and parity settings are software selectable.
Technical Bulletin
68-6005
68-6205-A
68-6205-B
1.2, 2.4, 4.8, 9.6, 19.2, & 38.4 k bps (software selectable) 250 Volts to chassis ground channel inputs/outputs & handshaking signals
TB-980503
Dual channel serial communication modules can be installed providing two RS232-Compatible ports. Although providing RS-232-C signal levels, the tristate output design allows multiple flow computers to share one RS-232 device. This serial module is the oldest model manufactured by Omni.
Jumper Settings - For information on setting the jumpers of serial I/O modules refer to 1.6.3. Serial Communication Modules in Volume 1, Chapter 1 of the User Manual.
LED Indicators
RX In RDY In RX In RDY In Chan. B Chan. A
Fig. 1. Dual RS-232 Serial I/O Module Model Showing Selection Jumper and Indicator LEDs
Technical Bulletin
Serial I/O Module # 68-6205-A (manufactured 1997) has two communication ports. The first serial port (Ports #1 and #3 if two 68-6205 modules are installed) is factory set in the RS-232-C mode (jumpers are soldered into place and cannot be moved). The second serial port (Ports #2 and #4) is configurable for RS-485 communications only. Although the first serial port provides RS-232-C signal levels, the tristate output design allows multiple flow computers to share one serial link.
Jumper Settings - For information on setting the jumpers of serial I/O modules refer to 1.6.3. Serial Communication Modules in Volume 1, Chapter 1 of the User Manual. For serial port jumper settings see also Fig. 6 in this bulletin.
LED Indicators
68-6205
REV: A
Fig. 2. RS-232/485 Module #68-6205-A Showing Selection Jumpers and Indicator LEDs
TB-980503
The first serial port jumpers are factory hard-wired for RS-232-C mode. This port is non-selectable and cannot be changed by the user. The second serial port jumpers are factory preset in the RS-485 two-wire, terminated positions. This port is user-selectable for RS-485 two-wire/four-wire terminated/non-terminated jumper positions (see Fig. 6). Back panel wiring is shown below.
Micro Motion RFT 9739 Devices - Users of Micro Motion RFT 9739 devices connected to the peer-topeer port (Port #2) of the Omni, please note that the resistor networks should be positioned for 2-wire RS485 and that Terminal A from the RFT 9739 should be wired to Omni Terminal B (7), and B from the RFT must be wired to Omni Terminal A (11). Refer to technical bulletin TB980401 Peer-to-Peer Basics for more information.
RS-485 2-Wire
RS-485 4-Wire
3 4 5 6 7 8
RS-232-C Hard-wired
9 10 11 12
N/A
GND A
Technical Bulletin
Serial I/O Module # 68-6205-B is the latest serial module manufactured by Omni (1998). It is capable of handling two communication ports. Each serial port is jumper-selectable for either RS-232-Compatible or RS-485 communications. Although providing RS-232-C signal levels when in this mode, the tristate output design allows multiple flow computers to share one serial link. In addition to the RS-232 mode, jumper selections have been provided on each port to allow selection of RS-485 format. With this option, a total of two RS-485 ports are available on this model.
Jumper Settings - For information on setting the jumpers of serial I/O modules refer to 1.6.3. Serial Communication Modules in Volume 1, Chapter 1 of the User Manual. For serial port jumper settings see also Fig. 6 in this bulletin.
LED Indicators
68-6205
REV: B
Port #2 (#4)Jumpers
Fig. 4. RS-232-C/RS-485 Module #68-6205-B Showing Selection Jumpers and Indicator LEDs
TB-980503
Jumpers for both serial ports are user-selectable to RS-232-C or RS-485 formats (see Fig. 6). The RS-485 options are either 2-wire or 4-wire mode; each mode can be set as terminated or non-terminated connections. Back panel wiring is shown below.
Micro Motion RFT 9739 Devices - Users of Micro Motion RFT 9739 devices connected to the peer-topeer port (Port #2) of the Omni, please note that the resistor networks should be positioned for 2-wire RS485 and that Terminal A from the RFT 9739 should be wired to Omni Terminal B (7), and B from the RFT must be wired to Omni Terminal A (11). Refer to technical bulletin TB980401 Peer-to-Peer Basics for more information.
RS-485 4-Wire TX-B RX-A GND TX-A RX-B TX-B RX-A GND TX-A RX-B
3 4 5 6 7 8
9 10 11 12
Technical Bulletin
The RS-232-C/RS-485 serial port has been designed so that RS-232 or RS-485 communications standards can be selected by placement of 16-pin resistor networks into the correct blocks. The following diagrams show the locations of blocks JB1, JB2, JB3 for the first serial port (Model #68-6205-B only), and JB4, JB5, JB6 for the second serial port (Models #68-6205-A and #68-6205-B) for each format. Serial I/O Module #68-6205-A only has the RS-485 options available for the second serial port, and the first port is hard-wired to the RS-232C position and cannot be changed by the user.
RS-232
JB1 or JB4 JB2 or JB5 JB3 or JB6
RS-485
RS-232
RS-232/485 4-WIRE
RS-485 TERMINATED
Terminated/Nonterminated RS-485 - The RS-485 devices located at each extreme end of an RS485 run should be terminated. Note that the device located at an extreme end may or may not be an Omni Flow Computer.
LIMITED WARRANTY. Omni Flow Computers, Inc. (Omni Flow) warrants all equipment manufactured by it to be free from defects in workmanship and materials, provided that such equipment was properly selected for the service intended, properly installed, and not misused. Equipment which is returned, transportation prepaid, to Omnis assembly plant within three (3) years after date of shipment, and is found after inspection by Omni Flow Computers, Inc. to be defective in workmanship or materials, will be repaired or replaced, at the sole option of Omni Flow Computers, Inc., free-of-charge, and return-shipped at lowest cost transportation, prepay and add. Warranties on third-party manufactured devices supplied by Omni Flow or incorporated by Omni Flow in the manufacture of equipment bearing an Omni label shall be extended by the original device manufacturer. This Limited Warranty is void if failure of the equipment has resulted from accident, abuse or misapplication. NO OTHER WARRANTIES. Omni Flow disclaims any and all warranties, either expressed or implied, including but not limited to implied warranties of merchantibility, fitness for a particular purpose, and any other warranties which extend beyond the terms herein. No agreement varying or extending the foregoing warranties or limitations will be binding upon Omni Flow unless in writing, signed by a duly authorized officer. LOSS OR DAMAGE. Omni Flow shall by liable only for loss or damage caused directly by its sole negligence. Liability of Omni Flow for any claim of any kind for any loss or damage arising out of, or connected with this warranty; or from the performance or breach hereof shall in no case exceed the price allocated to the equipment or unit thereof which gives rise to the claim. The liability of Omni Flow shall terminate three (3) years after the shipment of the equipment from Omni Flow. NO LIABILITY FOR CONSEQUENTIAL DAMAGES. Omni Flow shall not be liable in any circumstance for any incidental or consequential damages whatsoever (including, without limitation, loss of business profits or revenue, business interruption, loss of business information, or other pecuniary loss, or claims of customers of the purchaser for any and such damages) arising out of the use or inability to use Omni Flow equipment or devices manufactured by third party manufacturers.
(SINGLE-USER PRODUCTS)
This is a legal agreement between you, the end user, and Omni Flow Computers, Inc. By the installation and use of accompanying equipment manufactured by Omni Flow Computers, Inc., you are agreeing to be bound by the terms of this Agreement.
LIMITED WARRANTY
LIMITED WARRANTY. Omni Flow warrants that the SOFTWARE will perform substantially in accordance with the accompanying written materials provided with the purchase of an Omni manufactured product for a period of three (3) years from the date of shipment from Omnis production facility. Omni Flows entire liability shall be, at Omni Flows sole option, (a) remedy any defect and provide you, at no charge, with replacement magnetic media or (b) download an upgrade via a dial-up modem connection between Omni Flow and the end user, provided that equipment specified by Omni Flow for that purpose is used. This Limited Warranty is void if failure of the SOFTWARE has resulted from accident, abuse or misapplication. NO OTHER WARRANTIES. Omni Flow disclaims any and all warranties, either expressed or implied, including but not limited to implied warranties of merchantibility, fitness for a particular purpose, and any other warranties which extend beyond the terms herein, with respect to the SOFTWARE and accompanying hardware. No agreement varying or extending the foregoing warranties or limitations will be binding upon Omni Flow unless in writing, signed by a duly authorized officer. NO LIABILITY FOR CONSEQUENTIAL DAMAGES. Omni Flow shall not be liable in any circumstance for any damages whatsoever (including, without limitation, loss of business profits or revenue, business interruption, loss of business information, or other pecuniary loss, or claims of customers of the purchaser for any and such damages) arising out of the use or inability to use the SOFTWARE.
(SINGLE-USER PRODUCTS)
This is a legal agreement between you, the end user, and Omni Flow Computers, Inc. By the installation and use of this product you are agreeing to be bound by the terms of this Agreement.
LIMITED WARRANTY
LIMITED WARRANTY. Omni Flow warrants that the SOFTWARE will perform substantially in accordance with the accompanying written materials provided with the purchase of an Omni manufactured product for a period of three (3) years from the date of shipment from Omnis production facility. Omni Flows entire liability shall be, at Omni Flows sole option, (a) remedy any defect and provide you, at no charge, with replacement magnetic media or (b) download an upgrade via a dial-up modem connection between Omni Flow and the end user, provided that equipment specified by Omni Flow for that purpose is used. This Limited Warranty is void if failure of the SOFTWARE has resulted from accident, abuse or misapplication. NO OTHER WARRANTIES. Omni Flow disclaims any and all warranties, either expressed or implied, including but not limited to implied warranties of merchantibility, fitness for a particular purpose, and any other warranties which extend beyond the terms herein, with respect to the SOFTWARE, the accompanying written materials and hardware. NO LIABILITY FOR CONSEQUENTIAL DAMAGES. Omni Flow or its suppliers shall not be liable in any circumstance for any damages whatsoever (including, without limitation, loss of business profits or revenue, business interruption, loss of business information, or other pecuniary loss, or claims of customers of the purchaser for any and such damages) arising out of the use or inability to use the SOFTWARE.