01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37
Table of contents Overall view Overall dimensions Pre-plumbing jig and Wall Spacing Frame Installation recommendations Start-up Checklist (I) Start-up Checklist (II) Pressures of gas Electronic PCB Electrical wiring Laura 2020 F Electrical wiring Main components (I) Main components (II) Control panel Sleeve Demand for Heating Demand for DHW (Winter) Demand for DHW (Summer) Stop and fault Set Time Hydraulic circuit Mains Water Inlet Demand for Heating Mini-accumulator Safety valve and By-Pass 3-way valve Gauge and Lack-of-water pressure switch Central Heating mode operation DHW mode operation Overheat thermostat Flame safeguard rectification system (I) Flame safeguard rectification system (II) Chimney pull safety 20/20 Process of code 22 Burner Combustion chamber Kit valve G20 and G25
38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56
Cross-section of gas valve Gas changeover Kit Components of the boilers F and T Flue duct kit (I) Flue duct kit (II) Flue duct kit (III) Flue duct kit (V) Flue duct kit (VII) Central Heating programming (I) Central Heating programming (II) Central Heating programming (III) Central Heating programming (IV) Central Heating programming (V) Set-Up (I) - TECHNICIAN ONLY Set-Up (II) - TECHNICIAN ONLY Mantenance Fault codes Outlines hydraulic (I) Outlines hydraulic (II)
Table of Contents
Laura wall-hung waterheaters
1
Laura 20/20F
CSA
CERTIFIED FOR NORTH AMERICA
USA CANADA
Low NOx emission level (Class 3) Laura 20/20F Electrical protection level: IP44D CE market. These waterheaters comply with the requirements of the Electromagnetic Compatibility Directive 89/336/EEC, the Gas Appliance Directive 90/396/EEC,the Low Voltage Directive 73/23/EEC, and the Efficiency Directive 92/42/EEC .
Overall View
Laura 20/20Fwall-hung waterheaters
2
247mm 9 3/4"
33 1/2" 850mm
33 1/2" 850mm
15 7/16" 392mm
17 23/32" 450mm
15 7/16" 392mm
17 23/32" 450mm
Laura 20/20F
Laura 20/20F
Overall Dimensions
Laura 20/20F wall-hung waterheaters
3
PMI
Please refer to the Instructions which are delivered with the appliance
Installation Recommendations
Laura 20/20F wall-hung waterheaters
5
Connect power supply 220v 15 amp service Connect room thermostat. Unlock the pump motor shaft (turn center screw to bleed). Make sure flue vent is properly installed. Fill the primary loop (if no DHW storage tank has been installed) slowly until the pressure reaches 1-2 bar. (If a DHW storage tank has been installed, then fill the secondary loop first). Open the DHW circuit for it to fill up and vent. With the gas inlet cock closed, start up the Central Heating/DHW mode (p15 #2). The boiler will per form a lighting cycle and will then lock out under code 12. Leave it like that for five minutes so that the pump , which is still running, can help vent the circuit. Next chec k the pressure level (p14 #1) and top up if it has dropped below 1 .5 bar. Open the gas inlet cock, reset the system ( p14 #5) and the boiler will start operating. Allow the boiler to operate in the Heating mode for ten minutes , in which period it should be checked that all radiators warm up. Should one radiator fail to warm up, bleed the air out of it. But if it still does not warm up, ays optimizing the pump performance curve then the flow rates in all radiators should be balanced, alw (flow rate/pressure) through its speed selector control (to left of pump - select one of three settings). Open the DHW tap with highest flow rate in the house. The boiler will operate for ten minutes continuously at full output. If the flue spillage detection thermostat (p40) does not trip, that means that the removal of flue gases is correct. The DHW flow can be adjusted if necessary. To do that, open the tap fully and turn the main water inlet flow adjustment screw (p22) until the leaving water temperature is 120F/49C (on screen, upper right), at full output. If a gas meter is available , check the gas supply pressure (p8 & p37 gas supply pressure test point).
Connect tester to the operating gas pressure test point and check the working pressure with the boiler operating at full output. Remove the tester, replace the plug and washer, restart the system, and using soapy water check the whole circuit for gas tightness. For a higher level of comfort, particularly where substantial pressure variations in the water supply occur, set the program close to the draw-off temperature.
Instruct the user on the following points: Recommend user to read the Users Instructions. Instruct user on how to program the Central Heating and DHW temperature and the room thermostat (if any). Instruct user on how to top up the Heating system (1.5 mbar). Demonstrate how the fault codes work for insufficient gas (12 and 17). This is the most common fault code due to user error. Demonstrate to user how to reset after opening the gas inlet cock. Recommend that user press reset button (p14 #5) whenever a red fault lamp lights up. If the red light appears two or three consecutive times, tell the user to write down the fault codes and notify the nearest Service Center or Installer. Train user on the various safety devices, recommendations and maintenance operations specified in the waterheater instructions.
Gas Inlet Pressure: G20(NG - Natural Gas): 8 water column inches (20 mbar) G31(LP - Liquid Propane): 11.0 water column inches (27.4 mbar) Operating gas pressure test point Gas Input Rate (m3/h) (*) Pressure (mmwg) (**) G20 G31 Heat Output G20 G31 341 1.06 83 2.38 79,347 Btu 332 1.04 71 2.26 71,412 Btu 241 55 0.89 1.96 59,510 Btu 179 38 0.77 1.64 47,608 Btu 52 14 0.38 0.87 27,771 Btu Gas input rates and pressures with Natural gas (G20) are for a 3 L.H.O.= 36,500Btu/m, density= 0,62, 59F and 14.7 PSI (*) measured under standard conditions (59F and 14.7 PSI) (**) burner setting pressure Gas supply pressure test point (On the gas governor)
Pressures of Gas
Laura 20/20F wall-hung waterheaters
8
T 160 MA
SAFETY RELAYS C.T. FUSE SAFETY FUSE IGNITION TRANSFORMER
2A
C.T. 12/230
RELAYS
RELAYS
RELAYS
RELAYS
CHIMNEY SWEEP
Sw10
3.15 A
RSEAU
MAIN FUSE
WATER PRESION
EXHAUST FAN AND PUMP DHW DEMAND SOLENOID VAL VE AND BOILER MODEL SENSORS AND LIMIT STA TS HOME AUTO.
THERMOSTA T COMMUNICATIONS
Electronic PCB
Laura 20/20F wall-hung waterheaters
9
DHW SENSOR
GAS VALVE
HEATING SENSOR
Sanitarium sensor Sanitarium sensor Heating sensor Heating sensor Bridge Bridge Exchanger safety device Exchanger safety device Earth Pressure switch (Vcc) Pressure switch (Signal) Pressure switch (GND)
Valves common Safety valve Valve 18Th Valve 12Th Valve 7Th
Bridge Bridge
A.T. BRIDGE
TWO SPEED FAN POWER SOCKET 230v
TELEPHONE REMOTE CONTROL CONNECTOR
ELECTRONIC BOX
Electrical Wiring
Laura 20/20F wall-hung waterheaters
10
Electrical Wiring
Laura 20/20F wall-hung waterheaters
11
Compact casing Top fixing: Locating pins Bottom fixing: Screws Removable decorative Color of casing: White RAL 9016 Stages of Output: 27,772 Btu 47,608 Btu 59,511 Btu 71,413 Btu 79,347 Btu Adjustable for Heating Net efficiency: 85%
Draught Diverter
flue socket collar: 127 Flue duct 4.9" / 125 mm
Expansion Vessel
Fill pressure: 10.88 psi / 0.75 bar. Butyl diaphragm and nitrogen charge Total/Useful capacity: 2.11 gal/1.19 gal (8 litres/4.5 litres)
Heat Exchanger
Bithermal. 6 steps in DHW andHeating. Made of copper and high-temperature aluminium paint.
Gas Valve
5 stages of output. Nat Gas governor: 6.8:8 wc" (17:25 mbar). No internal diaphragms. Coil voltage: 12Vdc.
Burner
Stainless steel. 13 becks Clover-like flame on the ends for interlighting.
Mini-accumulator
Capacity: 1.6 qt/1.5 litres. Made of copper
Combustion chamber
Compact. Side fixing rods
Flow Meter
Control Panel for Laura 20/20F 1. Pressure gauge 2. Heating+DHW service 3. DHW service 4. Stop 5. Fault Warning and Reset Button 6. Set Central Heating Temperature 7. Set DHW Temperature 8. Operating Temperature Control Knob 9. Digital LCD Display 10. Set Time 11. Validate Program 12. Mode Selection: Manual/Program 13. Set Day 14. Set Day/Time/Programmer Knob
Circulator
Air Purge
11 9 7 6 2 3 1
12
13
14
10
Control Panel
Laura 20/20F wall-hung waterheaters
14
12
11
10
13
14
1. 2. 3. 4. 5. 6. 7.
8
Pressure gauge Heating+DHW service DHW service Stop
8. 9. 10. 11.
Operating Temperature Control Knob Digital LCD Display Set Time Validate Program Mode Selection: Manual/Program Set Day Set Day/Time/Programmer Knob
Fault Warning and Reset Button 12. Set Central Heating Temperature 13. Set DHW Temperature
14.
Sleeve
Laura 20/20F wall-hung waterheaters
15
Winter Mode
(2)
(1)
1 2 3 4 5 6 7
(3)
1. 2. 3.
Press button for Central Heating + DHW service. The green indicator lamp will light up. Press the Set Central Heating Temperature button. The green lamp will light up and the temperature digits on the display will flash. Turn the temperature control knob as required. To exit the mode, press any button or wait 10 seconds.
Winter Mode
(1)
(2)
(3)
1. 2. 3.
Press button for Central Heating + DHW service. The green indicator lamp will light up. Press the Set DHW Temperature button. The green lamp will light up and the temperature digits on the display will flash. Turn the temperature control knob as required. To exit the mode, press any button or wait 10 seconds.
Summer Mode
(2)
(1)
(3)
1. 2.
Press button for DHW service. The green indicator lamp will light up. Press the Set DHW Temperature button. The green lamp will light up and the temperature digits on the display will flash. 3. Turn the temperature control knob as required. To exit the mode, press any button or wait 10 seconds.
(1)
1. Press the Stop button. The boiler will switch to permanent monitoring mode.
(1)
(2)
1. The fault code will be displayed on the screen. See list on last page. 2. The reset button will also light up. If necessary, press it once the fault has cleared.
(1) (2)
Setting the Time 1. Press the Set Time button. The clock hands will flash on the LCD display. 2. Using the Set Day/Time Knob, set the desired time. Setting the Day 1. Press the Set Time button. The day will flash. 2. Using the Set Day/Time Knob, set the desired day (1 for Monday, 2 for Tuesday, etc.) 3. To exit this mode, press the Set Time button again.
Set Time
Laura 20/20F wall-hung waterheaters
20
Expansion Vessel
Fill pressure:10.88 psi/0,75 bar. Butyl diaphragm and nitrogen charge Useful capacity:1.19 gal (/4.5 litres)
Heat Exchanger
6 steps in Heating: 3 for flow and 3 for return Primary capacity: 0.08 gal/300 cm3 3 Secondary capacity: 0.07 gal/270 cm
Mini-accumulator
0.4 gal/1.5 litres
Circulator
3 speed
Hydraulic Circuit
Laura 20/20F wall-hung waterheaters
21
Inlet filter
132(500)
41(5)
46(8)
57(14)
63(17)
Inlet
Outlet
Mini-Accumulator
Laura 20/20F wall-hung waterheaters
24
Flow to radiators
Safety valve
Set at 43.5 psi / 3 bar
Bypass connection
Opens at 5.8 psi / 0.4 bar
3-way valve
Turns in 10 seconds
Bypass connection
Opens at 5.8 psi / 0.4 bar
Anti-backdraught valve
3-way Valve
Laura 20/20F wall-hung waterheaters
26
If pressure drops below 7.25 psi / 0.5 bar, an intermittent beep will be sounded and code 03 will be displayed.The beep will sound every 5 seconds for 3 minutes, will stop for 2 hours, then will continue beeping for another 3 minutes, after which it will stop for good.
Connection to pump
Expansion Vessel
Fill pressure:10.88 psi / 0.75 bar. Butyl diaphragm and nitrogen charge
Useful capacity: 1.19 gal (4,5 litres)
Heating sensor
Temp. Res. kW 14F/10 C 55.2 32F/ 0 C 32.6 50F/10 C 19.9 68F/20 C 12.4 77F/25 C 10.0 86F/30 C 8.06 104F/40 C 5.33 122F/50 C 3.60 140F/60 C 2.49 158F/70 C 1.75 176F/80 C 1.25 194F/90 C 0.91 212F/100 C 0.67 230F/110 C 0.51
Heat Exchanger
6 steps in Heating: 3 for flow and 3 for return 3 Primary capacity: 0.08 gal/ 300 cm Secondary capacity: 0.07 gal/ 270 cm3
To radiators
Maximum operating pressure: 43.5 psi / 3 bar Temperature selectable between 86F/30C and 194F/90C
Exchanger
6 steps DHW Primary capacity : 0.08 gal/300 cm 3 Secondary capacity : 0.07 gal/270 cm 3
Mini-accumulator
DHW sensor
Temperature selectable between 86F/30C and 194F/60C Temp. Res. kW
86F/30 C 104F/40 C 122F/50 C 140F/60 C 8.060 5.330 3.605 2.490
Overheat thermostat
automatic reset 221F(105C)
Lockout
No No
Service restored
Overheat Thermostat
Laura 20/20F wall-hung waterheaters
30
Attempt to light up
End of spark ignition Safety solenoid No valve closes Display of fault code 12 and red LED
Fault corrected
No
Interruption of service
Attempt to relight
1st solenoid valve opens (27,769 Btu/7 Th) Boiler reset Press reset button
Light-up process
No
Yes
End of sparks ignition Safety solenoid No valve closes Display of fault code 17 and red LED
Fault corrected
No
No
SPOTT safety detects backflow of flue gases Three-minute pause before operating
Lockout
Fault corrected
No
No
Pull restored
Yes Light-up
No
Lockout (SPOTT triggered)
Yes
No
Boiler reset
Yes
Locked out again (Spott triggered) Stop
No
Fault corrected
No
Yes
Light-up
Yes Yes
Calling for service
Yes
No
Stop
No
Yes
No DHWT>131F(64 C)
Legend CHSPT=Central Heating Setpoint Temperature CHT= Central Heating Temperature DHWSPT=DHW Setpoint Temperature DHWT= DHW Temperature
Yes
Algorithm conditions - Thermostat ON - CH mode enabled - DHW demand OFF Automatic RESET conditions of algorithm (while code 22 is not displayed) - If there is demand for DHW - Thermostat OFF - CH mode OFF
No
Yes
Display: Code 22 Red LED flashing and beep-beep CHSPT=140F (60C) and the user cannot change it
Reset
Process of Code 22
Laura 20/20F wall-hung waterheaters
34
Ignition Sequence
2 seconds at 27,769 Btu 3 seconds at 47,604 Btu
13 becks
Material: Stainless Steel
Ignition Electrodes
Centered on the middle burner 5 mm higher and a 4 mm electrode gap
Baffle plate
Burner
Laura 20/20F wall-hung waterheaters
35
Do not start the boiler until the insulation panels have been properly assembled. For optimum boiler operation it is essential that these insulation panels be in good condition.
Side insulation panels
Material: Ceramic Fibre
Side tabs
Fold them after fitting side insulation panels
Combustion Chamber
Laura 20/20F wall-hung waterheaters
36
Chassis fixing bracket Allen 4mm Operating gas pressure test point 71,412 Btu Solenoid valve. Grey Cable 47,608 Btu Solenoid valve. Orange cable 27,771 Btu Solenoid valve. Blue cable
Allen key 4mm
Red cable
Burner fixing
Self-tapping tri-lobed Allen M5x12
71,412 Btu Solenoid valve. Grey cable 47,608 Btu Solenoid valve. Orange cable 27,771 Btu Solenoid valve. Blue cable Safety Solenoid valve. Red cable
Valve gasket
Material: Cork + Nitrile
Hood extractor
Laura 20/20 F
Configuratin C12: Horizontal concentric flue pipe. Flue gases discharged directly into the atmosphere.
Laura 20/20 F
L 4"(100)
L 10' (3m)
Configuratin C42: Horizontal concentric flue pipe connected to twin common shunt or stack.
43
Laura 20/20 F
427/32"(125) L 35/16"(100)
441/64"(118) L 35/16"(100)
With no diaphragm : 7'10"(2.4m) < L 36'(11 m) 45/8"(1.4m)< L 23'(7m) With diaphragm 17/8"(46mm): 4 5/8"(1.4m) < L 7'10"(2.4m)
Configuratin C32: Room-sealed waterheater. Vertical concentric flue pipe. Flue gases discharged directly into the atmosphere. Exhaust fan located above the combustion chamber. 140040034-03 Configuration C32. Directional, concentric vertical flue pipe kit with 60/100 damper. Quick coupling. 1 m vertical flue length. 140040059-00 Optional vertical concentric accessory in the C32 configuration for vetical outlet to the roof.
100/ 125 P M P
Each 90concentric elbow 100/60 o 125/80 reduces 0.7 m Each single 90 elbow 80 reduces 0.5 m. The first boiler outlet elbow should not be taken into account. No reduction is necessary when using 45elbows.
M
100/ 125
(4) (1)
1 2 3 4 5 6 7
(3)
(2)
1. Press the Set Day button. The clock disappears from the LCD display and the 24-hour time clock is then displayed. 2. With the Set Day/Time Knob, set the desired day. 3. The arrow beside the number should indicate the desired day. 4. Press the Validate Program button to store the day.
(3)
1 2 3 4 5 6 7
(2)
(1)
1. Using the Set Day/Time/Programmer Knob, move the flashing schedule sector. 2. Set this sector at the time you wish the first operating event of the day to start. 3. When that is correctly positioned, press the Validate Program button.
(3)
1 2 3 4 5 6 7
(2)
(1)
1. Using the Set Day/Time/Programmer Knob, move the sectors to the time you wish the boiler to switch off. 2. You will notice that as you progress the sectors will remain lit. 3. Press the Validate Program button to store the first event.
(3)
1 2 3 4 5 6 7
(2)
(1)
1. Using the Set Day/Time/Programmer Knob, move the sector to the time you wish the second operating event to start. 2. You will notice that as you progress the sectors do not remain lit. 3. Press the Validate Program button to store the start of the second event and move again the sectors using the Set Day/Time/Programmer Knob until the time you wish the boiler to switch off for the second time. Press the Validate Program button. 4. Once the first day of the week has been scheduled, press the Set Day button; and the rest of the days can now be programmed. 5. To exit this mode, press any button.
(1)
(2)
1. To set the boiler under the programming mode, press the Mode Selection: Manual/Program key. 2. Should the clock symbol appear on the LCD display, it means that the waterheater is under the Central Heating mode.
13
Press the Validate Program button (11) to store the change. Press the Validate Program button (11) for 10 seconds. After this 10-sec time-delay you will access the Set-up mode. This screen displays the DHW flow rate (litres/h) provided there is The following screen will be consumption. Open a tap to view. displayed. The flame output can be Example on display: 527 l/h adjusted with button (13) and the t1 liter = 0.26 gallons (US liquid) pump time-delay with button (10). Press the Validate Program button (11) to store the change.
tt1 = six minute delay tto = immediate flame
The next screen will display 1 m3 = 264.17 gallons (US liquid) the delta T (hysteresis) between cutoff and restart of flame. Press the Validate Program button (11) to store the change. Change delta T with button (13). The pump program will be displayed This screen displays the total as well on the same screen and operating hours of the safety can be changed with button (10). solenoid on the gas valve. Press the Validate Program button (11) to store the change
PO = Thermostat activated P1 = continuous operation in CH mode
This screen shows the total volume (m3) of DHW usage. Example on display: 1 m3
Set-up (I)
Laura 20/20F wall-hung waterheaters
51
10
13
This screen allows the year to be set. To do that, press button(13). Example on display: 2001
Press the Validate Program button (11) for 10 seconds, or any other button on the right-hand of the panel. After that time-delay you will exit the Set-up mode.
Press the Validate Program button (11) to store the change. This screen displays the value on the flue gas pressure switch (in mbar x 10). Example on display: 2 mm w.g. Press the Validate Program button (11) to store the change.
Set-up (II)
Laura 20/20F wall-hung waterheaters
52
Carry out the following maintenance operations at least once a year, and preferably at the beginning of the Heating season: DHW Clean the cold water filter Check the DHW temperature Heating Check the system pressure Check the waterheater water temperature Check the pump operation Bleed the air in the radiators and waterheater Check the room thermostat Check the safety valve Gas Clean filter Check the burner setting pressure Check the input rate Check the circuit for gas tightness Clean the burner Venturis Combustion and Ventilation Check the flue duct tightness Check the effectiveness of ventilations and air renewal system. Ensure there are no obstuctions Conduct a flue gas analysis
Maintenance
Laura 20/20F wall-hung waterheaters
53
Designation
N Fault Code
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 17 19 20 21 22 23 24
DHW sensor interrupted Heating sensor interrupted Lack of pressure in CH circuit Faulty flame relay: stuck Faulty safety circuit (*) Overheat thermostat open during ignition Flue spillage limit thermostat open before ignition Faulty safety fuse open Faulty safety relay (energized) Faulty safety relay (will not close following demand) (*) Burner off. Ignition time-delay too short Burner off for lack of gas at lighting up (*) Safety relay. Ignition time-delay too long Overheat thermostat open during operation (*) Flue gas spillage during operation (*) Faulty safety relay. Lack of gas or electrical fault (*) Pressure switch opening time-delay Pressure switch close time-delay Safety relay open during temperature control Some hot water tap is dripping (*) Faulty communication between micro-panels (electronic noise)(*) Faulty internal wiring or bad contact of panel pins
(*) Whenever these fault codes appear, reset the waterheater by turning the selector knob to the reset buttom. For the other codes, the waterheater will reset automayically once the fault is cleared.
Fault Codes
Laura 20/20F wall-hung waterheaters
54
Error Code s
Code 01 & 02: Interruption of the DHW (01) and Heating (02) circuit sensors 1. The sensors (DHW or Heating) are out of order Verify the Ohm-value of the sensors with an Ampmeter, and change the sensor if broken. 2. Verify the correct sensor plug connection 3. Verify that the sensor-cable is correct (not broken or worn out) Code 03 (40-50-90): Pressure of the heating circuit < 0.5 bar This happens only in LAURA and SARA boilers, not in VICTORIA. There is a lack of water in the circuit 1. There is a bad air purge after the first start up and the purged air has dropped the pressure. 2. Manometer failure Remove the broken manometer. 3. Expansion vessel without pressure Empty the heating circuit above the boiler, leave the circuit open and fill up the expansion vessel with an air pump (10.88 psi). Code 06 (50-60-90): Overheating after flame The water inside the heat-exchanger exceeds of 221 F flame has estinguished.
1. Due to a bad purge, the air inside the heat exchanger does not allows the water temperature to cooldown. 2. The pump is blocked and the water does not circulates through the heat exchanger. 3. The DHW- flow meter is broken and gives the order to heat up DHW without any real demand. Due to this, the pump does not turns and the water inside the heat exchanger gets too hot.
55
Code 14 (50-60-70-90): Overheating during flame The water inside the heat-exchanger exceeds of 221 F flame is burning.
The causes are the same as in the Code 06, with the difference that the overheating sensor has a bad contact and does not reads properly the temperature. Code 09 (40-70-90): Solenoid valve circuit open (gas valves) connector.
Broken control panel Change the control panel. Code 12 (60-70-90): Error in the flame detection at start-up The control panel does not recieves flame detection during the safety ignition time before the burner has lighted up (there was no flame before). 1. There is no sparkle between the electrodes in the burner Check if there is a brocken electrode. Check if the control panel is broken (you can hardly hear the sparkle inside the control panel) Change the control panel.
2. No flame detection There is flame but electrodes continue giving sparkles until the safety flameup time is exceeded. Check if the flame-sensor (ionisation-sensor) is broken and replace it. Check the cable from control panel to the flame-sensor. If the flame-sensor & cable are ok, replace the control panel. 3. Wrong Gas supply to the burner-becks. Lack of gas supply Check the gas pressure at inlet regulator (20 mbar) with the boiler working If no pressure at all, check the gas valve if closed or the main gas supply. The solenoid valves are not opening
DC.
Code 17 (40-80-90): Error in the flame detection during boiler function The control panel does not recieves flame detection while the burner is burning (the boiler already flamed up and is working) All causes are the same than in Code 12, except the problems related to the sparkle (because the boiler already lighted up successfully). Code 19 (40-80-90): Problems at the Pressure-Switch (presostat) a. The pressure switch is broken Change the pressure switch b. The pressure switch is not properly connected into the right pin-holes
Code 20: Problems related to the Exhaust System If when removing the burner seal panel the boiler works properly, and when replacing it an error occurs, this means there is a problem in the exhaust pipe. a. Too long exhaust pipe. b. Verify the connection between the 1 meter vent pipes is correct. It might be ok on the outer pipe, but the inner pipe could be loose. This would make the in and out air mix, causing the flame to extin guish due to the lack of oxygen (Code 17) or that the exhaust gases couldnt escape due th the high loss of the charge produced by this open connector (Code 20). If the error code 20 comes up continuously, verify that the presostat plastic pipes arent connected wrong (in the correct position they should be crossed, where the pipe from the presostat is connected to the Venturi). Blocking of the pipes can also occur, which can be cleared by gently sucking on the pipes.
57
Laura 20/20F
Stopped Way
Heating Way
NOTE: OPEN THE BUILT-IN REGULATOR COMPLETELY TO ACCOMMODATE STANDARD GAS PRESSURES
waterheater heating loop side of the unit Outlines Hydraulic (II) Domestic Hot Water; Fill & Backflow Change; 30 psi ASME Relief Valve
59