Atmospheric Tank Normal Venting Calculation (Inbreathing)

Tank Inputs Tank Volume Pump Out Rate Latitude Average Storage Temp Vapor pressure Insulation Inputs Insulation Thickness Thermal Cond. of Insulation Inside heat transfer coefficient Tank total surface area Insulated surface area

m3 11095 m3/h 2107 25 C 40 equal or less than Hexane

m W/mK W/m2K m2 m2

0 0.05 4 2260.8 2260.8 2260 8

Calculation Results Liquid movement inbreathing Rate C-Factor Reduction factor Thermal inbreathing Rate Total Inbreathing Rate

Nm3/h ------Nm3/h Nm3/h

2107 6.5 1.00 4410.6 6517.6

Note

www.chemwork.org

PROJECT : CLIENT: PROJ. NO. : UNIT :

DATE : BY : REV : DOC NO.:

5-Mar-11

Atmospheric Tank Normal Venting Calculation (Outbreathing)

Tank Inputs Tank Volume Pump-in Rate Latitude Evaporation Rate Flashing Rate

m3 m3/h Nm3/hr Nm3/hr

11095 2107 25 0 971

Insulation Inputs Insulation Thickness Thermal Conduction of Insulation Inside heat transfer coefficient Tank total surface area Insulated surface area

m W/mK W/m2K m2 m2

0 0.05 4 2260.8 2260.8

Calculation Results Liquid movement out breathing Y-Factor Reduction factor Thermal Outbreathing Rate Total Outbreathing Rate

Nm3/h ------Nm3/h Nm3/h

2107 0.32 1.00 1398.8 4476.8

Note