FASE =
I 30
=
V. LINEA =
SECCION
50
70
95
120
150
185
240
300
400
500
POT.
RES2
REACT.
=
=
=
34,5
1.73
34,5
RES1
0.370
0.270
0.196
0.150
0.122
0.097
0.074
0.060
0.047
0.037
Vatios
Ohm/Km.
Ohm/Km.
KVoltios
KVoltios
RES2
0.448
0.327
0.237
0.182
0.148
0.118
0.090
0.073
0.057
0.044
COS
=
ACOS
=
SEN
=
diam. cond.
9.06
10.75
12.60
14.10
15.70
17.60
20.10
22.70
25.70
28.80
INTEN.
=
Ra. REQUI =
LONGITUD =
Amp.
mm.
m
0.9
0.45
0.44
R-S
3455
3455
3455
3455
3455
3455
3455
3455
3455
3455
SECCION =
DMG
=
Pot.
F.S. sp. =
F.S ce.
=
S-T
2744
2744
2744
2744
2744
2744
2744
2744
2744
2744
1
1
1
R-T
2100
2100
2100
2100
2100
2100
2100
2100
2100
2100
KVA
Coef. Cu. =
Temp. 2 =
Frecuen. =
RMG
3.528
4.186
4.906
5.491
6.114
6.853
7.827
8.839
10.008
11.215
DMG
2710.299
2710.299
2710.299
2710.299
2710.299
2710.299
2710.299
2710.299
2710.299
2710.299
0.00382
75
60
REACT.
0.5010
0.4881
0.4761
0.4676
0.4595
0.4509
0.4409
0.4317
0.4223
0.4138
1/C
C
Hz.(Ciclos/Seg.)
IMPEDAN.
0.6213
0.5068
0.4210
0.3672
0.3332
0.3024
0.2728
0.2536
0.2353
0.2202
mm.
mm.
ANEXO 1.2
Caida de tensin
CUADRO DE CAIDA DE TENSION EN 34,5 KV., 3
PUNTOS
POTENCIA
KVA
INTENSIDAD
(AMP.)
SUM. INTEN.
(AMP.)
SECCION
mm2
FCT
LONGITUD
mts.
CAIDA.TEN.
VOLTIOS
SUM. CAID.
VOLTIOS
% CAIDA
DE TENSION
A
B
C
D
D.2
4000
6000
3000
3000
10000.00
67.02
100.53
50.26
50.26
167.55
435.62
368.60
268.07
217.81
167.55
240
240
240
240
240
0.4724
0.4724
0.4724
0.4724
0.4724
2370
6800
2375
400
440
487.76
1184.17
300.79
41.16
34.83
487.76
1671.93
1972.72
2013.88
2048.71
1.41
4.85
5.72
5.84
5.94
6000 KVA
B.1
4000 kVA
3000 KVA
C.1
A.1
6800 m
2375
3000 KVA
D1
400
440
D2
2370 m
A
AMP SE MINA
Longitud equivalente
258820
9,954.62
10000 KVA
F.C.T. (K)
1.0762
0.8778
0.7292
0.6360
0.5771
0.5238
0.4724
0.4393
0.4075
0.3814
SECCION
50
75
95
120
150
185
240
300
400
500
=
=
=
22.9
1.73
22.9
RES1
3.130
1.860
1.170
0.730
0.530
0.370
0.270
0.196
0.150
0.122
0.097
0.074
0.060
0.047
0.037
Vatios
Ohm/km
Ohm/km
kVoltios
kVoltios
RES2
3.788
2.251
1.416
0.883
0.641
0.448
0.327
0.237
0.182
0.148
0.118
0.090
0.073
0.057
0.044
INTEN.
=
Ra. REQUI =
LONGITUD =
COS
ACOS
SEN
=
=
=
0.9
0.45
0.44
diam. cond.
3.12
4.05
5.10
6.45
7.56
9.06
10.75
12.60
14.10
15.70
17.60
20.10
22.70
25.70
28.80
Amp
mm
m
Pot.
F.S. sp.
F.S ce.
R-S
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
SECCION =
DMG
=
=
=
S-T
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1200
1
1
1
R-T
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
2400
KVA
Coef. Cu. =
Temp. 2 =
Frecuen. =
DMG
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
1511.905
0.00382
75
60
RMG
1.133
1.470
1.851
2.341
2.744
3.528
4.186
4.906
5.491
6.114
6.853
7.827
8.839
10.008
11.215
REACT.
0.5426
0.5229
0.5056
0.4879
0.4759
0.4569
0.4440
0.4321
0.4236
0.4155
0.4069
0.3969
0.3877
0.3783
0.3697
1/C
C
Hz (Ciclos/Seg)
IMPEDAN.
3.6454
2.2537
1.4946
1.0077
0.7847
0.6021
0.4876
0.4018
0.3480
0.3140
0.2832
0.2536
0.2344
0.2161
0.2010
F.C.T. (K)
6.3140
3.9034
2.5887
1.7454
1.3591
1.0429
0.8446
0.6959
0.6028
0.5438
0.4905
0.4392
0.4061
0.3743
0.3482
SECCION
6
10
16
25
35
50
75
95
120
150
185
240
300
400
500
mm
mm
SUBESTACIN
PUNTOS
SUBESTACIN
TOTAL
POTENCIA
INTENSIDAD
SUM. INTEN.
SECCIN
kVA
(AMP.)
(AMP.)
mm2
3,240
81.69
81.69
120
3,240
FCT
1.0429
LONGITUD
CAIDA.TEN.
SUM. CAID.
% CAIDA
VOLTIOS
VOLTIOS
DE TENSIN
900
76.67
76.67
0.33
900
0.33 %
SUBESTACIN
OBSERVACIONES