Project Name: THAI BINH - HAM RONG Prepared by: pve 04/11/2014 04:19PM
Air System Information
Air System Name Equipment Class Air System Type LFS - EQUIPMENT SPLT AHU SZCAV Number of zones Floor Area Location 1 12.9 m Thai Binh, Vietnam
Sizing Calculation Information
Zone and Space Sizing Method: Sum of space airflow rates Zone L/s Individual peak space loads Space L/s Calculation Months Sizing Data Jan to Dec Calculated
Central Cooling Coil Sizing Data
Total coil load Sensible coil load Coil L/s at Oct 1500 Max block L/s Sum of peak zone L/s Sensible heat ratio m/kW W/m Water flow @ 5.6 K rise 6.8 4.7 361 361 361 0.699 1.9 523.3 N/A kW kW L/s L/s L/s Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Oct 1500 35.8 / 35.5 25.6 / 19.6 14.7 / 14.2 13.5 0.100 53 12.8 1 of 1 0.0 C C C C % C OK K
Central Heating Coil Sizing Data
Max coil load Coil L/s at Des Htg Max coil L/s Water flow @ 11.1 K drop 0.1 kW 361 L/s 361 L/s N/A Load occurs at W/m Ent. DB / Lvg DB Des Htg 8.5 21.1 / 21.3 C
Supply Fan Sizing Data
Actual max L/s Standard L/s Actual max L/(s-m) 361 L/s 360 L/s 27.98 L/(s-m) Fan motor BHP Fan motor kW Fan static 0.01 BHP 0.01 kW 10 Pa