Anda di halaman 1dari 11

Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.

Data Compilato Foglio - di


Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
1 11 F.V. SETT.94
QUADRO BASSA TENSIONE
COMPLESSO ARRIVI DA ALIM. PRINCIPALE ED EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Main and emergency feeder
Automatic change over
Operable from board
COM7
IN73 GE72
(T)
D
G
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
2 11 F.V. SETT.94
QUADRO BASSA TENSIONE
COMPLESSO ARRIVI DA ALIM. PRINCIPALE ED EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Main and emergency feeder
Automatic change over
Operable from board
LEGENDA CODICI APPARECCHIATURE AUSILIARIE ARRIVO
Legend and codes of incoming auxiliary equipment
Cubicle auxiliary circuits-breaker
Signalling of flag relay - aux. circuits C.B. operating
- Legend and codes of ECD auxiliary equipment
Control and signallings auxiliary circuits protection circuit-breakers
Change over automatic mode selector - inserted/excluded
PREDISPOSITORE COMMUTAZIONE AUTOMATICA - INSERITA / DISINSERITA
PULSANTE DI APERTURA
PULSANTE DI CHIUSURA
COMMUTATORE VOLTMETRICO
RELE' CARTELLINO - MANCANZA Vcc
PULSANTE DI RIPRISTINO BLOCCO COMMUTAZIONE
LAMPADA ROSSA - COMMUTAZIONE DISINSERITA
LAMPADA BIANCA - INTERRUTTORE CHIUSO
LAMPADA VERDE - INTERRUTTORE APERTO
LAMPADA BIANCA - COMMUTAZIONE INSERITA
RELE' CARTELLINO - APERTURA INTERRUTTORI CIRC. AUX.
LAMPADA VERDE - INTERRUTTORE APERTO
LAMPADA BIANCA - INTERRUTTORE CHIUSO
LEGENDA CODICI APPARECCHIATURE AUSILIARIE ECD
LAMPADA ROSSA - COMMUTAZIONE IN BLOCCO
NOTE
HG
HW
K2H
K1H
- Notes
HG
HR
HR
HW
HW
S5
S4.O
S3.C
S2
White light - circuit breaker closed
Green light - circuit-breaker opened
Undervoltage release auxiliary relay
Change over lock-out reset P.B.
Red light - excluded change over
Red light - lock-out change over
White light - circuit breaker closed
White light - inserted change over
Green light - circuit-breaker opened
Circuit-breaker opening push button
Circuit-breaker closure push button
Voltmeter selector switch
INTERRUTTORE CIRCUITI AUSILIARI DI SCOMPARTO
INTERRUTTORI PROTEZIONI CIRC. AUX., COMANDI E SEGNALAZIONI
INTERRUTTORI ALIMENTAZIONE CIR. AUX. c.c
INTERRUTTORI ALIMENTAZIONE CIR. AUX. c.a.
CODICE
Q2-Q4
Q5-Q9
S1
Q10
Q1
- Codes DESCRIZIONE
D.C. auxiliary circuits isolating switch
A.C. auxiliary circuits isolating switch
- Description
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
3 11 F.V. SETT.94
QUADRO BASSA TENSIONE
COMPLESSO ARRIVI DA ALIM. PRINCIPALE ED EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Main and emergency feeder
Automatic change over
Operable from board
SCHEMA UNIFILARE
One line diagram
K1H
CARICA MOLLE - SEGNAL.
STACCO PER MIN. TENSIONE
CHIUSURA E APERTURA
Q6 Q5
3
3
CT1
QM-A
.V
.V
Q10
K2H
E1
Q1
PEN
+2-
3N
/
n
2-
2-
3
.Hz
.Hz
A
VT1
3
Q3 Q2 Q4
S1
S4.O
HG
HR
HW
S3.C S2
HW HR
D.C. voltage failure
Aux. circuits C.B. operating
Lock-out automatic change over
Automatic change over excluded
380 A.C. minimum voltage
- Alarms legend
COMM.AUT. IN BLOCCO
NOTES
MANCANZA Vcc
APERTURA INTER.CIRC.AUX.
- Notes
COMM.AUT. DISINSERITA
MINIMA TENSIONE
LEGENDA ALLARMI
U
F27A
S5
V
Q9
V
Q8
Q7
F64AUX
VT2
220
380
VV
1CS
1CA
Summarized alarms
Spring loading & indic.
Undervoltage release
Closing & shunt trip
Auxiliary services
RIASSUNTO ALLARMI
SERVIZI AUSILIARI
220V 50Hz
(VEDI LEGENDA)
(See legend)
HW HG
ALLARMI
Alarms
ECD
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
4 11 F.V. SETT.94
QUADRO BASSA TENSIONE
COMPLESSO ARRIVI DA ALIMENTAZIONE PRINCIPALE ED EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Main and emergency feeder
Automatic change over
Operable from board
SCHEMA LOGICO COMANDI
Controls logic diagram
K94
- Closed
- Closed
- Self energ. closed
- In "CLOSED" position
- Operated
- Opened
- Pushed
- Opened
- Operated
- Operated
- Operated
- Operated
- Operated
-K86-GE
PMCC/K86-QM
-K94
-S2
CHIUSO PER AUTORIT.
IN POS. "CHIUSO"
INTERVENTO
INTERVENTO
-F27A
-QM-GE
PMCC-QM
-QM-GE
PMCC-QM
-K94
-F27A
-S4.O
-K94
CHIUSO
APERTO
PREMUTO
INTERVENTO
INTERVENTO
APERTO
CHIUSO
INTERVENTO
INTERVENTO
1
&
1
1
- In "INSERTED" position
- In "EXCLUDED" position
-QM-A
-F27A
-S1
-S3.C
-S1
- Opened
IN POS. "INSERITA"
INTERVENTO
APERTO
- Operated
- Pushed
IN POS. "DISINSERITA"
PREMUTO
&
&
1
lock-out
Aut. change over
AUTOMATICA
BLOCCO COMM.
&
APERTO
Opened
CHIUSO
Closed
QM-A
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
5 11 F.V. SETT.94
QUADRO BASSA TENSIONE
COMPLESSO ARRIVI DA ALIMENTAZIONE PRINCIPALE ED EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Main and emergency feeder
Automatic change over
Operable from board
SCHEMA LOGICO SEGNALAZIONI E ALLARMI
Alarm indications - Logic diagram
- Unavailable
- Operated
- Operated
- Operated
-K2H
-Q4
-Q3
-Q2
-K2H
INTERVENTO
APERTO
INTERVENTO
APERTO
APERTO
- Opened
- Opened
- Opened
-Q9
-Q8
-Q7
-Q6
-Q5
-Q4
-Q3
-Q2
-Q1
-K94
APERTO
APERTO
APERTO
APERTO
APERTO
APERTO
- Opened
- Opened
- Opened
- Opened
- Opened
- Opened
APERTO
APERTO
APERTO
INTERVENTO
- Opened
- Opened
- Opened
1
INDISPONIBILITA'
1
K1H
- Lock-out automatic change over
- Excluded automatic change over
- Inserted automatic change over
- Operated
-QM-A
-QM-A
COMM. AUTOMATICA IN BLOCCO
COMM. AUTOMATICA DISINSERITA
COMM. AUTOMATICA INSERITA
-S1
-F27A
IN POS. "DISINSERITA"
INTERVENTO
CHIUSO
APERTO
- Closed
- Opened
- In "EXCLUDED" position
QM-A
STRU
A
ECD
A
ECD
A
ECD
ECD
A
HR
HR
HW
HW
HG
ECD
A
A
ECD-HW
ECD-HG
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
6 11 F.V. SETT.94
QUADRO BASSA TENSIONE
COMPLESSO ARRIVI DA ALIMENTAZIONE PRINCIPALE ED EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Main and emergency feeder
Automatic change over
Operable from board
MORSETTIERA
Terminal strip
1CA
ECD
ECD
Alarms
alarms
ALLARMI
A QUADRO
From
DCP board
110 Vcc
DA QUADRO
DCP
110Vcc
PMCC board
DA QUADRO
1CP
From
PMCC
1CC
Controls
COMANDI
2 + - 1 4 3 5
Permissions
CONSENSI
feeder
ALIM.
indications
A QUADRO
ECD
ECD
1CS
SEGNALAZIONI
9 6 7 8 10 11 12
Indications
16 14 13 15 17 18 19 33
To stru
A STRU
2CA
26
Unavailable
INDISPONIBILITA'
23 21 20 22 24 25 28 27 29 30 31 32 35 34
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
7 11 F.V. SETT.94
QUADRO BASSA TENSIONE
COMPLESSO ARRIVI DA ALIM. PRINCIPALE ED EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Main and emergency feeder
Automatic change over
Operable from board
LEGENDA CODICI APPARECCHIATURE AUSILIARIE ARRIVO GENERATORE
Legend and codes of incoming generator auxiliary equipment
Signalling of flag relay - aux. circuits C.B. operating
- Legend and codes of ECD auxiliary equipment
White light - circuit breaker closed
Green light - circuit-breaker opened
White light - generator ready to load
Red light - circuit breaker lock-out
White light - circuit breaker closed
Generator set automatic emergency stop push button
Green light - circuit-breaker opened
Red light - generator in failure
White light - power generator running
Red light - generator in shutdown
INTERRUTTORI PROTEZIONI CIRC. AUX., COMANDI E SEGNALAZIONI
Generator set automatic stop push button
Generator set automatic start push button
LAMPADA BIANCA - INTERRUTTORE CHIUSO
LAMPADA VERDE - INTERRUTTORE APERTO
LAMPADA ROSSA - GRUPPO IN AVARIA
LAMPADA BIANCA - GRUPPO PRONTO AD EROGARE
LAMPADA ROSSA - INTERRUTTORE IN BLOCCO
LAMPADA BIANCA - INTERRUTTORE CHIUSO
LAMPADA BIANCA - GRUPPO IN MARCIA
LAMPADA ROSSA - GRUPPO IN BLOCCO
RELE' CARTELLINO - APERTURA INTERRUTTORI CIRC. AUX.
LEGENDA CODICI APPARECCHIATURE AUSILIARIE ECD
NOTE
HW
HG
- Notes
HR
K1H
HR
HW
HW
HR
HW
PULSANTE DI CHIUSURA
PULSANTE DI START GENERATORE
PULSANTE DI APERTURA
PULSANTE DI STOP GENERATORE
COMMUTATORE VOLTMETRICO
PULSANTE ARRESTO EMERGENZA GENERATORE
LAMPADA VERDE - INTERRUTTORE APERTO
CODICE
S8
HG
S7
S6
S5
S4.O
S3.C
Q1-Q7
Voltmeter selector switch
Circuit-breaker opening push button
Circuit-breaker closure push button
Control and signallings auxiliary circuits protection circuit-breakers
- Codes DESCRIZIONE - Description
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
8 11 F.V. SETT.94
QUADRO BASSA TENSIONE
ARRIVO ALIMENTAZIONE DA GENERATORE EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Feeder from emergency generator
Change over automatic
Operable from board
SCHEMA UNIFILARE ARRIVO GENERATORE
Incoming geenrator - One line diagram
SCOMP.ARRIVO GENERATORE
* Supplied by P.C. board manufacturer
3
* DI FORNITURA DEL COSTRUTTORE DEL QUADRO P.C.
CTR
CT2
3
NOTE - Note
*
%%126
G
Q5
VT1
3
Q7
Q6
CT1
GE-QM
CTR
PEN
+2-
2-
n
/
2-
3N
3 ....Hz
....Hz
K86
HW
S3.C S4.O
HR
HG HW
S7
S5
HR
S6
HW HR
A W
S8 S8
VV Hz
Q1
....V
....V
Q2 Q3 Q4
- Power generator running
- Emergency stop
- Over current
- Generator in manual mode
- Generator in failure
- Generator in shutdown
- Alarms legend
MIN.TENSIONE/MIN.FREQUENZA
INTERVENTO RELE' DI BLOCCO
GRUPPO PRONTO AD EROGARE
APERTURA EMERGENZA
GUASTO A TERRA
TERRA CAVO
MASSIMA CORRENTE
APERTURA INTER. CIRC. AUX.
GRUPPO IN MANUALE
- Earth fault
- Cable earth
GRUPPO IN MARCIA
GRUPPO IN AVARIA
GRUPPO IN BLOCCO
LEGENDA ALLARMI
1CM
F81
F64
F27
d
U
f
F50t
- Low voltage/low frequency
- Lock-out relay operated
- Aux. circuits C.B. operating
- Generator ready to load
F51V
F51N
>
K1H
1CS
SERVIZI AUSILIARI
CHIUSURA E APERTURA
STACCO PER MIN. TENSIONE
CARICA MOLLE - SEGNAL.
RIASSUNTO ALLARMI
Gen. incoming cubicle
Closing & shunt trip
Undervoltage release
Spring loading & indic.
Summarized alarms
Auxiliary services
1CA
HW HG
(See legend)
(VEDI LEGENDA)
ALLARMI
Alarms
ECD
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
9 11 F.V. SETT.94
QUADRO BASSA TENSIONE
ARRIVO ALIMENTAZIONE DA GENERATORE EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Feeder from emergency generator
Change over automatic
Operable from board
SCHEMA LOGICO COMANDI
Controls logic diagram
- Operated INTERVENTO -F27A
- Operated
- Operated
- Operated
- Operated
- In "INSERTED" position
- Permission
- Operated
- Operated
- Operated
- Operated
-F64
-S5
-F51V
-F51N
-F50
INTERVENTO
INTERVENTO
INTERVENTO
INTERVENTO
PREMUTO- Pushed
-F27/B
-QM-A
CP-EDG
-QM-A
CP-EDG
-S1
-F27A
-S4.O
-F27B
-K86
INTERVENTO
PREMUTO
IN POS. "INSERITA"
CHIUSO
INTERVENTO
COMANDO
- Closed
- Pushed
- Control
APERTO
CONSENSO
INTERVENTO
INTERVENTO
- Opened
1
K86
&
- in "INSERTED" position
IN POS. "DISINSERITA"
-QM-GE
-S1
-S1
-S3.C
APERTO
IN POS. "INSERITA"
PREMUTO
- Opened
- Pushed
- In "EXCLUDED" position
&
&
1
1
&
QM-GE
Opened
Closed
APERTO
CHIUSO
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
10 11 F.V. SETT.94
QUADRO BASSA TENSIONE
ARRIVO ALIMENTAZIONE DA GENERATORE EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Feeder from emergency generator
Change over automatic
Operable from board
SCHEMA LOGICO SEGNALAZIONI ALLARMI
Alarm indications - Logic diagram
- Unavailable
- Operated
- Operated
- Operated
- Pushed
-K2H
-Q1
-Q3
-Q4
-Q2
INTERVENTO
APERTO
APERTO
APERTO
APERTO- Opened
- Opened
- Opened
- Opened
-Q6
-Q7
-Q5
-Q3
-Q4
-Q1
-Q2
-S5
-K86
-F64
APERTO
APERTO
APERTO
APERTO
APERTO
APERTO
APERTO
- Opened
- Opened
- Opened
- Opened
- Opened
- Opened
- Opened
INTERVENTO
INTERVENTO
PREMUTO
1
INDISPONIBILITA'
1
K1H
- Operated
- Operated
GRUPPO IN MARCIA
GRUPPO PRONTO AD EROGARE
GRUPPO IN AVARIA
GRUPPO IN BLOCCO
- Opened
- Operated
- Operated
-F27/F81
-F50/F51V
-F51N
CP-EDG
CP-EDG
CP-EDG
CP-EDG
-K86
INTERVENTO
INTERVENTO
INTERVENTO
INTERVENTO
-QM-GE
-QM-GE
APERTO
CHIUSO - Closed
- Generator ready to load
- Generator in shutdown
- Power generator running
- Generator in failure
QM-GE
STRU
A
ECD
A
ECD
A
ECD
A
ECD
A
ECD
A
HW
HR
HR
HW
HW
HR
HG
ECD-HW
ECD
A
ECD
A
ECD-HG
Documento di propriet aziendale. La Societ tuteler i propri diritti a termini di legge.
Data Compilato Foglio - di
Rev.
Agip
Sheet - of Compiled Date
This document is Company Property. The Company lawfully reserves all rights.
0
NORMALIZZAZIONE INTERNA
STANDARDIZATION
CODICE Code -
- Symbol SIMBOLO
20128.EQP.ELE.STD
11 11 F.V. SETT.94
QUADRO BASSA TENSIONE
ARRIVO ALIMENTAZIONE DA GENERATORE EMERGENZA
COMMUTAZIONE AUTOMATICA
COMANDO DA QUADRO
LVS907
Low voltage switchboard
Feeder from emergency generator
Change over automatic
Operable from board
MORSETTIERA
Terminal strip
2CA
CP-EDG
DA QUADRO
CP-EDG
A QUADRO
INDISPONIBILITA'
E ALLARMI
SEGNALAZIONI CONSENSI
CP-EDG
DA QUADRO
COMANDI SEGNALAZIONI
ECD
A QUADRO
ECD
A QUADRO A STRU
ALLARMI
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
board
To CP-EDG
2CC 1CC
board
To CP-EDG
Unavaiable
indications
Alarms and
Permissions
board
To CP-EDG
1CS
Controls Indications
indications
ECD
2CS
31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60
Alarms
ECD
1CA
To stru
Alarms

Anda mungkin juga menyukai