Boiler Parameters
Main Steam BMCR 500 MW CL 250 MW Steam flow at SHO t/hr 1625 1495.2 772.7 Pressure at SHO Kg/cm 2 (g) 178 176.7 171.1 Temp at SHO o C 540 540 540 Reheat Steam Steam flow at RHO t/hr 1392.4 1334.9 670.2 Pressure at RHI Kg/cm 2 (g) 45.03 43.21 21.39 Pressure at RHO Kg/cm 2 (g) 42.39 40.69 20.13 Temperature at RHI o C 337 336.7 311.4 Temp at RHO o C 540 540 540 Feed Water Temp o C 254.6 253.4 219.3 Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
Proximate Analysis of Unwashed Coal
Group I Group II Group III Design Coal Range Design Coal Range Design Coal Range Fixed Carbon % 34.5 32 37 28 24 32 22 20 24 Volatile Matter % 23 22 24 23 22 24 20.5 19 22 Total Moisture % 10 9 11 12.5 11 14 13.5 12 15 Ash % 32.5 32 33 36.5 33 40 44 42 46 Total % 100 - 100 100 HHV K.cal/kg 4250 4000 - 4500 3700 3400 - 4000 3100 2800 - 3400 HGI 50 45 - 55 50 45 - 55 50 45 - 55 Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
Proximate Analysis of Unwashed Coal
Group I Group II Group III Best Coal Design Coal Worst Coal Best Coal Design Coal Worst Coal Best Coal Design Coal Worst Coal Fixed Carbon % 37 34.5 32 32 28 24 24 22 20 Volatile Matter % 22 23 24 24 23 22 22 20.5 19 Total Moisture % 9 10 11 11 12.5 14 12 13.5 15 Ash % 32 32.5 33 33 36.5 40 42 44 46 Total % 100 100 100 100 100 100 100 100 100 HHV K.cal/kg 4500 4250 4000 4000 3700 3400 3400 3100 2800 HGI 55 50 45 55 50 45 55 50 45 Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
Expected Proximate Analysis (Range) of Washed Coal
Two-pass design Controlled circulation Pressure part materials selection as per code. Radiant reheat Balanced draft Side mill layout cold PA system
Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
Salient Features contd.
Axial reaction FD fans Axial reaction PA fans Radial ID fans with VFD Regenerative Tri-sector air preheaters Vertical spindle bowl mills Gravimetric feeders ESP to suit outlet dust emission Micro-processor based BMS, SADC and SB controls.
Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
BOILER ARRANGEMENT
Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
Design Details Unwashed Coal Group I Group II Group III Furnace Depth - mm D ~ 1.05 D 1.14 D Furnace With - mm W W W Furnace height - mm H ~ 1.04 H ~ 1.08 H Furnace Plan Area - m 2 PA ~ 1.05 PA ~ 1.14 PA Furnace Volume - m 3 V 1.09 V 1.24 V Furnace Heat Loadings- BMCR DC Plan Area M K.cal/h-m 2 4.28 4.15 3.86 EPRS 10 5 K.cal/h-m 2 1.77 1.74 1.68 Volumetric 10 3 K.cal/h-m 3 82.2 75.9 67.4 Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
Design Details Unwashed Coal
Group I Group II Group III Heat Input per burner M K.cal / hr 74.8 60.3 50.7 Max Gas Velocity in horz pass / second pass m/s 12 / 10 Cold air / hot air duct velocity m/s 12.7 / 16 Gas duct velocity m/s 16 Excess Air at Eco. out let % 20 Boiler Exit Gas Temp o C
125 at TMCR with Design coal (DC) Boiler Efficiency at TMCR DC % Base - 0.7 - 1.4 Coal Fired BMCR DC - T/hr 285 330 400 Coal Fired BMCR WC - T/hr 305 365 450 Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
Major Boiler Auxiliaries Unwashed Coal
Group I Group II Group III Bowl Mills 6 Nos BHEL 280 (XRP 1063) 7 Nos BHEL 280 (XRP 1063) 8 Nos BHEL 280 (XRP 1103) No. of Spare mills 1 mill spare with Worst coal at BMCR Regenerative AH 2 Nos Tri Sector - 31.5 VI 80 (T) FD Fans - 2 Nos Axial AP1-26/16 PA Fans - 2 Nos Axial AP2-20/12 AP2-21/12 ID Fans 2 Nos Radial with VFD - NDZV 47 ESP Out let Dust concentration 100 mg/Nm 3 with n -1 fields in service
Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
FD Fan Performance (per fan) Group I Group II Group III BMCR DC Fan DP BMCR DC Fan DP BMCR DC Fan DP Volume m 3 /s 155.3 215 145.9 210 126.8 200 Head mmwc 255 385 238 395 208 360 Fan Shaft Power KW 505 943 453 945 364 823 Fan Efficiency % 78.7 86 77.2 86 73.5 85.9 Motor Rating KW 1050 KW at 980 rpm
1050 KW at 980 rpm
Bharat Heavy Electricals Limited, Tiruchy
CEA Workshop, May - 2005
PA Fan Performance (per fan) Group I Group II Group III BMCR DC Fan DP BMCR DC Fan DP BMCR DC Fan DP Volume m 3 /s 90 164 92.7 196 112.5 225 Head mmwc 822 1230 927 1270 940 1375 Fan Shaft Power KW 872 2339 979 3032 1206 3631 Fan Efficiency % 82 81.5 84.4 77.4 84.1 80 Motor Rating KW 2575 KW 1480 rpm
ID Fan Performance (per fan) Group I Group II Group III BMCR DC Fan DP BMCR DC Fan DP BMCR DC Fan DP Volume m 3 /s 376 500 386.2 515 387 535 Head mmwc 312 440 331 470 335 470 Fan Shaft Power KW 1419 2682 1544 2949 1565 3044 Fan Efficiency % 81 79.6 81 79.5 81 80 Motor Rating KW 3000 KW at 580 rpm 3250 KW at 580 rpm