DOK - IBA

RELAI FREKUENSI
BESARAN INPUT DARI RELAI FREKUENSI ADALAH
TEGANGAN YANG DIAMBIL DARI TRAFO TEGANGAN
[ PT ]

RELAI INI MEMONITOR BESARNYA FREKUENSI
SISTEM .

1. RELAI FREKUEN SI KURANG [ UFR ]

MEMBANDINGKAN FREKUENSI SISTEM DENGAN
FREKUENSI SETTINGNYA .
BILA FREKUENSI SISTEM LEBIH KECIL ATAU
SAMA DENGAN FREKUENSI SETTING MAKA
RELAI AKAN KERJA

2. RELAI FREKUENSI LEBIH

BILA FREKUENSI SISTEM LEBIH BEAR ATAU
SAMA DENGAN FREKUENSI SETTING MAKA
RELAI AKAN KERJA .
DOK - IBA
FUNGSI / APLIKASI UFR
1. DIPASANG PADA PENYULANG TM , UNTUK
LOAD SHEDDING SECARA OTOMATIS BILA
TERJ ADI PENURUNAN FREKUENSI SIATEM ,
AKIBAT KEHILANGAN DAYA PEMBANGKIT .
ADA 6 TAHAP PENYETELAN RELAI UFR DI
PENYULANG 20 KV PLN YAITU 48,8 48,3 Hz

2. DIPASANG DI PEMBANGKIT ,UNTUK
MEMISAHKAN PEMBANGKIT DARI SISTEM
INTERKONEKSI, BILA TERJ ADI GANGGUAN
PADA SISTEM [ ISLANDING SYSTEM ]
DILENGKAPI DENGAN UVR .
FUNGSI / APLIKASI OFR
DIPASANG DI PEMBANGKIT SEBAGAI
PENGAMAN KECPATAN LEBIH [ OVERSPEED ]
DOK - IBA
R1
R2
C
f
f
Prinsip kerja
elektrodinamik
Relai frekuensi dengan asas induksi
50
48 52
V
DOK - IBA
T1
T2
T1
T2
T T1

T T2

1
2

T1

T2
V
V
DOK - IBA
sec . 0 . 0 . 0 . 0 . 0 . 0 T
1

Hz
T
1
f
1
1

MFVU
sec . 0 . 0 . 0 . 0 . 0 . 0 T
2

Hz
2
2
T
1
f
0,05
0.1
0,2
0,2
0,5
1
2
2
5
10
0
0
0
0
0
0
0
0
0
0
0.05
0,1
0,2
0,2
0,5
1
2
2
5
10
0
0
0
0
0
0
0
0
0
0

f1

f1
f2
f2
f1 ON
OFF
ON OFF
Pu:do
1:1
f2:f1
Vx=110V=
MFVU210CA00045
f1 f2
Reset
Test
sec
) (0,1
t1

sec
) (0,1
t2

DOK - IBA
T1
T2
T1
T2

T T1

T T2

1
2

T1

T2
V
V
RESET
SET
SET
RESET
SET
RESET
RESET
PU
DO
t2
t1
&
&
V>
TEST
f2:f1
f2:f2
2
2 R
L
2
1 R
L
26
27
28
1
3
5
6
4
2
9
11
10
13
12
14 RL2-2
RL1-1
RL1-2
RL2-1
f2
f1
+
-
0V
17
18
V
V=
1
2
DIAGRAM INTERNAL
RELAI FREKUENSI
TIPE MFVU 21 GEC
DOK - IBA
V=
52TC
52TC
52a 52a
110V
+
-
27
28
17
+

18 -
PT
BUS 20 KV
1
3
9
11
MFVU 21
TRIP PMT 1
TRIP PMT 2
t1
t2
f1
f2

PT
PENGAWATAN
DOK - IBA
250V
125V
48V
OFF
V A
NORM. FREQ.
FAULT FREQ.
+
-
CONTACT
ON
OFF OUTPUT
SUPPLY
220V
FTS 300 EIL
PORTABLE TESTSET TIPE FTS 300 EIL
6
3
2
1
4
5
7
8
9
10
11
12
13
15
14
1. Power Input Connection
2. Main Power Switch
3. Function Switch
4. AC signal Output
5. Output Voltage Control
6. Output Voltage Meter
7. Frequency Range Switch
8. Frequency adjust Control
9. Frequency meter / Timer
10. Contact / DC power terninal
11. DC Power Supplay Control
12. Contact mode select switch
13. Contact status Indicator
14. Target current control /
range switch
15. DC Ammeter
Keterangan Gambar :
DOK - IBA
FUNGSI ALAT KONTROL PADA PANEL DEPAN ALAT UJI FTS 300
1. Power Input Connection
Menghubungkan power cord untuk mendapatkan power input pada
alat uji ( suplai 220V).
2. Main Power switch
Mengontrol input power dan juga sebagai pemutus dalam hal
hubung singkat atau gangguan. Untuk menunjukan bahwa alat uji
dienergis maka lampu akan menyala.
3. Function Switch
Memilih kondisi kerja dari alat uji
4. AC signal Output
Memberikan output AC signal dari alat uji
5. Output Voltage control
Mengatur besarnya AC output signal. Knob Output control terdiri
dari dua potensio konsentris, knob luar mengatur besarnya
tegangan normal, dan knob dalam mengtur besarnya tegangan
gangguan. Tombol Read Fault Voltage memungkinkan tegangan
gangguan ada dalam kondisi Set Fault sebelum diswitch ke posisi
Test
6. Output Voltage meter
Memonitor besarnya tegangan AC signal yang ada pada signal
output.
DOK - IBA
7. Frquency range switch
Untuk memilih output rentang frekuensi 40 70 Hz atau 360 440 Hz
8. Frequency Adjust control
Potensiometer dengan 15 posisi yang mana mengatur frekuensi
normal dan gangguan
9. Frequency meter / Timer
Untuk menampilkan frekuensi normal / frekuensi gangguan atau
waktu , tergantung pada kondidsi kerja / mode dari alat uji. Dibawah
meter ditunjukan 2 buah lampu Led yang ditandai dengan Hertz
dan Second.
10. Contact DC power supplay terminals
Terminal merah dan kuning digunakan untuk memonitor status dray
contact atau scr dalam kondisi Normal ,Set Fault dan Test.
Penutupan contact ditandai oleh Led dari kontak closed. Dalam
kondisi Test penutupan kontak dapat digunakan untuk menyetop
Timer.
11. Dc Power Supplay Control
Memilih tegangan output Dc yang ada pada terminal merah dan
hitam. Tiga jenis tegangan yang tersedia yaitu 48V, 125V dan 250V
sesuai kebutuhan relai. Indikator On/Reset adalah suatu Led oranye
akan menyala bila tegangan ada. Supplay diproteksi terhadap beban
lebih,dan dapat direset dengan menekan tombol tekan (Led).
DOK - IBA
12. Contact Mode Select Switch
Untuk menentukan apakah timbul atau tidak hubung pendek pada
terminal merah dan kuning, dan akan menyetop timer dalam
kondisi Test. Dengan memilih salah satu kontak normally open
atau close untuk memonitor test penundaan waktu.
13. Contact status Indicator
Led yang menyala untuk menunjukan suatu hubung pendek pada
terminal merah dan kuning.
14. Target Current Control/Range Switc
Knob luar adalah suatu saklar yang memilih range dari Ammeter
DC yang diinginkan yaitu 0,3 atau 3 A. Knob dalam adalah suatu
potensio yang mengtur besarnya arus DC dalam kondisi Target.
15. DC Ammeter
Memonitor arus dari internal DC supplay dalam kondisi Normal ,
Set Fault dan Test ,dan mengukur besarnya arus DC pada terminal
merah dan kuning dalam kondisi Target.
DOK - IBA
PENGUJIAN INDIVIDUAL
RELAI FREKUENSI KURANG
TIPE MFVU 21 GEC TEST SET FTS 300
1. TUJUAN

Setelah melaksanakan pengujian siswa diharapkan dapat mengukur:
1. pickup / drop off frequency
2. waktu kerja relai frekuensi

2. ALAT UJI / RELAI

1. Frequency Test Set model FTS 300 (EIL)
2. Relai frekuensi tipe MFVU 21 GEC

3. RANGKAIAN PENGUJIAN

1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian )
2. Hubungkan sumber tegangan 220V ke alat uji
3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300
sebagai berikut :
DOK - IBA
250V
125V
48V
OFF
V A
NORM. FREQ.
FAULT FREQ.
+
-
CONTACT
ON
OFF OUTPUT
SUPPLY
220V
FTS 300 EIL
27
26
28
18
1
3
17 +
-
RANGKAIAN PENGUJIAN RELAI FREKUENSI
TIPE MFVU 21 GEC
MFVU 21 GEC
PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI
9
11
DOK - IBA
Kontrol Posisi

Main Power switch . . . . . . . .. . . . . . Off
Function Switch . . . . . . . . . . . . . Normal
Output Voltage adjust control . . . . . . . Putar penuh kekiri
Frequency range switch . . . . . . . . . . 40 70 Hz
Frequency adjust control . . . . . . . . . Mid range
Contact mode select switch . . . . . . . . NO (open)
Target current range switch . . . . . . . . Sesuai yang diinginkan
Target current control . . . . . . . . . . . Putar penuh kekiri
DC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan
4. PENGUJIAN PICK UP / DROP OFF FREQUENCY

1. Hidupkan alat uji ( Main power switch pada posisi on )
2. Putar Output Voltage control ke kanan sampai Voltmeter
menunjuk tegangan input nominal relai (100V)
3. Atur normal frequency control sampai frekuensi meter
menunjuk harga rated dari normal frekuensi
4. Atur normal frequency control sampai relai mulai pick up
( indikator kontak menyala ) dan naikan frekuensi sampai
indikator kontak padam ( reset )
5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output
tegangan yang laian .
DOK - IBA
5. PENGUJIAN WAKTU KERJA RELAI

1. Atur nominal frequency control sehingga frekuensi meter
menunjuk harga rated dari normal frekuensi (50Hz)
2. Putar Function swicth ke posisi set fault
3. Atur Fault frequency control sehingga frekuensi meter
menunjuk frekuensi yang diinginkan
4. Tekan tombol read voltage control dan atur tegangan gangguan
dengan mengatur output voltage control
5. Putar Function switch pada posisi Test maka frekuensi meter
akan berubah menjadi Timer (akan mencatat waktu kerja relai )
6. Ulangi pengujian diatas untuk setting waktu yang lain atau
frekuensi gangguan yang lain.
7. Matikan alat uji dan lepas kabel kontrol .
DOK - IBA
A
1
6
2
3
4
5
7
8
12
9
10
11
12
11
10
9
8
7
6
5
1
2
3
Trip 2
Trip 2
Trip 1
Trip 1
PT 110V
+
+
_
+
NF92
1 1 1
3 3 3
5
13
7 7 7
9 9 9

UE--
UE+
UE+
UE--
UE+
UE--
33
45
45
45 45 45
41
37
39 39
37
41
37
39
41
29
31 31 31
29 29
33 33
FC 95 - 22
E
110V DC
AUX. SUPPLY
FCN 950 - 22
INTERNAL
DIAGRAM UFR
TIPE FCN 950
ABB
DOK - IBA
1
0
+
_
MODE f(Hz)
dF/dt
t(s)
SAVE
1
2
DC
U<
CARA SETTING UFR TIPE FCN 950 MERK ABB
1. Tekan tombol Mode + enable s/d
f(Hz) menyala, kemudian tekan
tombol Mode + enable s/d lampu 1
(Freq 1) menyala.
2. Untuk menambah / mengurangi nilai
setting freq. / waktu dengan cara
menekan tombol enable dan tombol
+ / - .
3. Untuk menyimpan data setting tekan
tombol mode + enable s/d lampu
save menyala, kemudian tekan
tombol enable dan +/- sampai
dengan display muncul angka.
Catatan : 1. Untuk merubah fungsi f(Hz)
t(sec)
Save
2. Tripping freq. 1 muncul indikasi
angka 1.
Tripping freq 2 muncul angka 2.
Tombol enable ditekan terus
dan dengan menekan tombol
mode maka fungsi akan
berubah
DOK - IBA
ENABLE
PENGUJIAN INDIVIDUAL
RELAI FREKUENSI KURANG
TIPE FCN 950 ABB TEST SET FTS 300
1. TUJUAN

Setelah melaksanakan pengujian siswa diharapkan dapat mengukur:
1. pickup / drop off frequency
2. waktu kerja relai frekuensi

2. ALAT UJI / RELAI

1. Frequency Test Set model FTS 300 (EIL)
2. Relai frekuensi tipe FCN 950 ABB

3. RANGKAIAN PENGUJIAN

1. Rangkai lah rangkaian pengujian ( lihat gambar pengujian )
2. Hubungkan sumber tegangan 220V ke alat uji
3. Posisikan kontrol ( tombol, saklar, alat ukur ) dari alat uji FTS 300
sebagai berikut :
DOK - IBA
250V
125V
48V
OFF
V A
NORM. FREQ.
FAULT FREQ.
+
-
CONTACT
ON
OFF OUTPUT
SUPPLY
220V
FTS 300 EIL
3
1
UE
7
6
UE +
-
RANGKAIAN PENGUJIAN RELAI FREKUENSI
TIPE FCN 950 ABB
FCN 950 ABB
PORTABLE TESTSET TIPE FTS 300 EIL RELAI YANG DIUJI
9
8
2
DOK - IBA
Kontrol Posisi

Main Power switch . . . . . . . .. . . . . . Off
Function Switch . . . . . . . . . . . . . Normal
Output Voltage adjust control . . . . . . . Putar penuh kekiri
Frequency range switch . . . . . . . . . . 40 70 Hz
Frequency adjust control . . . . . . . . . Mid range
Contact mode select switch . . . . . . . . NO (open)
Target current range switch . . . . . . . . Sesuai yang diinginkan
Target current control . . . . . . . . . . . Putar penuh kekiri
DC power supply . . . . . . . . . . . . . . Sesuai yang diinginkan
4. PENGUJIAN PICK UP / DROP OFF FREQUENCY

1. Hidupkan alat uji ( Main power switch pada posisi on )
2. Putar Output Voltage control ke kanan sampai Voltmeter
menunjuk tegangan input nominal relai (100V)
3. Atur normal frequency control sampai frekuensi meter
menunjuk harga rated dari normal frekuensi
4. Atur normal frequency control sampai relai mulai pick up
( indikator kontak menyala ) dan naikan frekuensi sampai
indikator kontak padam ( reset )
5. Cata kedua besaran ini , dan ulangi percobaan ini untuk output
tegangan yang laian .
DOK - IBA
5. PENGUJIAN WAKTU KERJA RELAI

1. Atur nominal frequency control sehingga frekuensi meter
menunjuk harga rated dari normal frekuensi (50Hz)
2. Putar Function swicth ke posisi set fault
3. Atur Fault frequency control sehingga frekuensi meter
menunjuk frekuensi yang diinginkan
4. Tekan tombol read voltage control dan atur tegangan gangguan
dengan mengatur output voltage control
5. Putar Function switch pada posisi Test maka frekuensi meter
akan berubah menjadi Timer (akan mencatat waktu kerja relai )
6. Ulangi pengujian diatas untuk setting waktu yang lain atau
frekuensi gangguan yang lain.
7. Matikan alat uji dan lepas kabel kontrol .
DOK - IBA
KESIMPULAN ;

BANDINGKAN HASIL UJ I DENGAN
DATA TEKNIK SEHINGGA DIPEROLEH
KESIMPULAN BAHWA KONDISI RELAI
MASIH STANDAR / NORMAL ATAU
MENGALAMI PENURUNAN KUALITAS /
CONDONG TIDAK NORMAL DAN
PERLU PENGGANTIAN .
DOK - IBA
DOK - IBA