Anda di halaman 1dari 1

co2 room safeties

Exhaust fan, and suction duct:-


Provide at the bottom of the room. Any accumulated CO2 from leakage at the bottom can be
exhausted to atmosphere.
Bursting disc:-
Each bottle has a combined bursting disc, which will rupture spontaneously at a pressure of 177 bar
at 63C
co2 system safeties
Cable operated safety valve:-
Fitted on the pilot cylinder discharge line. It prevents accidental discharge of CO2 from quick release
cylinder due to action of leakage gas from pilot cylinder.
Relief valves:-
Fitted on each discharge line from cylinders so that leakage gas can safely dispose to atmosphere
Check valve:-
Fitted on connection pipe between each cylinder discharge valve and manifold, so that leakage of
one cylinder cannot effect other cylinder.
Pressure gauge and pressure alarm in the mainfold