Anda di halaman 1dari 15

ALARM

GENERATI
NG RELAY
ALARM BASIC
FUNCTION
BTS END
ALARM
GENERATI
NG RELAY
BTS END
ALAM DESTINATION
END
ALAM DESTINATION
END
ALARAM ACTIVE
ALARAM NOT ACTIVE
(SENSOR/RELAY)
(SENSOR/RELAY)
NOTE; if we define the alarm on breaking by OMT
Alarms define on Ericson BTS by
OMT
1. GEN ON
2. AC MAIN FAILURE
3. RECTIFIER DOOR
4. DC LOAD FUSE
5. BATTERY HIGH TEMP
6. LOW VOLTAGE
7. RECTIFIER MAJOR
8. RECTIFIER MINOR
9. SYSTEM ON BATTERIES


Note : when we r going to define the alarm the wording will be same like above .
All the later should be capital .

Because the filter applied on BSC end if we change the wording the alarm will report on
BTS end but not on BSC end.
ALARM DEFINATION ALARM DESTINATION
1) GEN ON

ATS
2) AC MAIN FAILURE

ATS
3)RECTIFIER DOOR

POWER CABNET
4) LOAD BREAKER TRIP

PSC3
5) BATTRY HIGH TEMP

POWER CABNET
6) DC LOW VOLT

PSC3
7) MAJOR

PSC3
8) MINOR

PSC3
9) SYSTEM ON BATTRIES

PSC3
Alarm Ericson BTS
1 2 3 4 5 6 7 8 9
Alarm relays on psc3
Relay
6
Genset
trigger
Relay
5
Dc low
volt
Relay
4
Load
breake
r trip
Relay
3
Sys on
batt
Relay
2
Minor
Relay 1
Major
BATTERY HIGH TEMP

RECTIFIER DOOR

POWER CABNET ALARMS
NOTE: we have to trace the wire coming from lower cabinet temperature sensor and
Door sensor.
Connect that with the pairs coming from BTS END
Temperature sensor
Door
sensor
Click on connect button
Click on read IDB
Right click on Alarm inlets
Define the alarm name here
Select external alarm here
Define the alarm state on breaking
Start alarm monitoring from here
ALARM
GENERATI
NG RELAY
BTS END
ALAM DESTINATION
END
ALARAM NOT ACTIVE
Alarms Trouble shooting
12 volt travels
Usually 12 volts travels on alarm wires .when the far end of the wires switch together
It sance the alarm is clear (if we define the alarm state on breaking ) .
If we are facing trouble in alarm reporting .so we have to check step by step start from
BTS end by looping .

Faisal khan
Power engineer
Relacom Pakistan