Q = 0.

839 x A x (P)
1/2
Q = Volumetric Flow Rate in M
3
/Sec.
A = Flow Area in Sq. Mtr.
P =
Pressure Difference Maintained Across the Lift Door in Pascal
( 50 Pascal to be maintained as per NBC-2005)
0.83 = Coefficient
Leakage Area Per Lift Door = 0.065 Sq. Mtr. (As per ASHRAE Handbook of Application)
No. of Floors = Level- Ground Floor to 17th Floor = 17
Total Leakage Area = 0.065x18
= 1.17 Sq.Mtr.
Total Leakage Air Flow (Q) = 0.839 x 1.17 x (50)
1/2
= 6.95 M
3
/Sec.
= 14609 CFM
Say = 15000 CFM / Lift Well
2NOS. Selected Fan Capacity for two Lift Well = 30000 CFM
Fan Static Pressure = 40 MMWG
Calculated Power Consumption (BHP) = 10.53
Calculated Power Consumption (IHP) = 12.11
Selected Motor = 15 HP
Selected Fan Capacity for one Lift Well = 15000 CFM
Fan Static Pressure = 40 MMWG
Calculated Power Consumption (BHP) = 10.53
Calculated Power Consumption (IHP) = 12.11
Selected Motor = 15 HP
LIFT WELL PRESSURIZATION CALCULATION FOR ,48 ACRE NORTH TOWN CHENNAI EKANTA TOWER
TOWER C - (G+17)
Q = 0.839 x A x (P)
1/2
Q = Volumetric Flow Rate in M
3
/Sec.
A = Flow Area in Sq. Mtr.
P =
Pressure Difference Maintained Across the Lift Door in Pascal (
50 Pascal to be maintained as per NBC-2005)
0.83 = Coefficient
Leakage Area Per Lift Door = 0.051 Sq. Mtr. (As per ASHRAE Handbook of Application)
No. of Floors = Level- Ground Floor to 15th Floor = 16
Total Leakage Area = 0.051x16
= 0.816 Sq.Mtr.
Total Leakage Air Fow (Q) = 0.839 x 0.816 x (50)
1/2
= 4.84 M3/Sec.
= 10248 CFM
Say = 10500 CFM / Lift Well
Selected Fan Capacity for Two Lift Well = 21000 CFM
Fan Static Pressure = 40 MMWG
Calculated Power Consumption (BHP) = 11.05
Selected Motor = 12.5 HP
LIFT WELL PRESSURIZATION CALCULATION FOR ONE LIT WELL
TOWER-1 to 9 IN ANANDA- (G+15)