5011696701-SX21
.. ..
DVP-1150070-02
ENGLISH
Thank you for choosing Delta DVP-SX2. DVP-SX2 is a 20-point (8DI + 6 DO + 4AI +
2AO) PLC MPU, offering various instructions and is with 16k steps program memory,
able to connect with all Slim series extension models, including digital input/output (max.
480 input/output extension points), analog modules (A/D, D/A transformation and
temperature units) and all kinds of new high-speed extension modules. Its 2-group
high-speed (100kHz) pulse outputs and the one new 2-axis interpolation instructions
satisfy all kinds of applications. DVP-SX2 is small in size and easy to install.
a This instruction sheet provides only information on the electrical specification,
general functions, installation and wiring. For detailed program design and applicable
instructions for DVP-SX2, please refer to DVP-SX2 Operation Manual:
Programming. For details on the optional peripheral, please refer to the instruction
sheet enclosed in the package.
a This is an OPEN TYPE PLC. The PLC should be kept in an enclosure away from
airborne dust, humidity, electric shock risk and vibration. Also, it is equipped with
protective methods such as some special tools or keys to open the enclosure, in
order to prevent hazard to users or damage on the PLC.
a DO NOT connect the AC main circuit power supply to any of the input/output
terminals, or it may damage the PLC. Check all the wiring prior to power up. To
prevent any electromagnetic noise, make sure the PLC is properly grounded
.
DO NOT touch terminals when power on.
Product Profile
1 Left-side module
connection port
3 POWER/RUN/ERROR/USB indicator
10 Direct fastening hole
4 COM1 communication
indicator (RS-232)
V0+
I0+
VI0V1+
I1+
VI1V2+
5 COM2 communication
I2+
VI2-
indicator (RS-485)
11 I/O terminal
V3+
I3+
VI3FE
6 I/O indicator
VO0
IO0
VO1
IO1
7 USB port
AG
2 Nameplate
(RS-232)
9 DIN rail clip
[ Figure 1 ]
14 COM2 port
18 I/O module
(standard component)
(RS-485)
12 RUN/STOP switch
13 COM1 port
8 VR0/VR1
positioning hole
19 I/O module
connection port
20 Mounting slot
(35mm)
15 Power input
port
[ Figure 2 ]
Electrical Specifications
Model
Item
DVP20SX211R
DVP20SX211T
DVP20SX211S
Max. 7.5A@24VDC
Fuse capacity
2.5A/30VDC, Polyswitch
-1-
Model
Item
DVP20SX211R
DVP20SX211T
DVP20SX211S
4.7W
4W
4W
Power consumption
Insulation resistance
Noise immunity
Grounding
Operation / storage
Vibration / shock
resistance
Weight (g)
243g
224g
Spec.
Items
Input No.
X0, X2
X1, X3
Input type
24VDC, 5mA
Input impedance
Response
time
X4 ~ X7
DC (SINK or SOURCE)
Action level
227g
Input Point
4.7K Ohm
OffOn
> 15VDC
OnOff
< 5VDC
OffOn
< 2.5s
< 10s
< 20us
OnOff
< 5s
< 20s
< 50us
Filter time
Spec.
Items
Relay
Output No.
Transistor
Y0 ~ Y5
Y0, Y2
Y1, Y3
Max. frequency
1Hz
100kHz
10kHz
Working voltage
Max. load
1kHz
#1
Resistive
Inductive
#2
15W (30VDC)
20WDC/100WAC
2.5W (30VDC)
Lamp
Response
time
5 ~ 30VDC
Y4, Y5
OffOn
Approx. 10 ms
OnOff
2s
20s
100s
3s
30s
100s
#1: DVP20SX211T: UP, ZP must work with external auxiliary power supply 24VDC (-15% ~
+20%), rated consumption approx. 3mA/point.
DVP20SX211S: UP, ZP must work with external auxiliary power supply 5~30VDC, rated
consumption approx. 5mA/point.
#2: Life curves
120VAC Resistive
30VDC Inductive(t= 7ms)
3000
2000
Operation(X10 3)
1000
120VAC Inductive(cos=0.4)
500
300
200
100
50
30VDC
Inductive
(t=40ms)
Contact
0.1
0.2 0.3
0.5 0.7
-2-
2 Current(A)
[ Figure 3 ]
Items
Voltage
Current
Voltage
Current
10V
20mA
4 ~ 20mA#1
10V
0 ~ 20mA 4 ~ 20mA#1
Digital conversion
range
2,000
2,000
0 ~ +2,000
2,000
0 ~ +4,000 0 ~ +4,000
Resolution #2
12-bit
Input impedance
> 1M
250
Output impedance
Tolerance carried
impedance
Overall accuracy
0.5 or lower
> 5K
< 500
Response time
Absolute input
range
15V
2ms #4
32mA
Isolation method
Protection
Voltage output has short circuit protection, but a long period of short
circuit may cause internal wire damage and open circuit of current output.
Voltage
Current
Voltage
Current
20V
40mA
20V
20mA
(5mV =
)
(10 =
)
(5mV =
)
(5 =
)
4000
4000
4000
4000
#3: When the scan period is longer than 2ms or the set value, the setting will follow the scan
period.
#4: When the scan period is longer than 2ms, the setting will follow the scan period.
#5: When the sampling range is 1, the present value will be read.
I/O Configuration
Model
Input
Point
Type
Type
20SX211R
20SX211T
Relay
DC
(Sink Or
Source)
NPN
Transistor
PNP
Transistor
20SX211S
SX2-R/T/S
Analog
Input
I/O configuration
Output
Point
Analog
output
Relay
NPN
PNP
V0+
I0+
VI0V1+
I1+
VI1V2+
I2+
VI2-
S/S
X0
X1
X2
X3
X4
X5
X6
X7
V0+
I0+
VI0V1+
I1+
VI1V2+
I2+
VI2-
S/S
X0
X1
X2
X3
X4
X5
X6
X7
V0+
I0+
VI0V1+
I1+
VI1V2+
I2+
VI2-
S/S
X0
X1
X2
X3
X4
X5
X6
X7
V3+
I3+
VI3FE
VO0
IO0
VO1
IO1
AG
C0
Y0
Y1
Y2
V3+
I3+
VI3FE
VO0
IO0
VO1
IO1
AG
UP
ZP
Y0
Y1
Y2
Y3
Y4
Y5
V3+
I3+
VI3FE
VO0
IO0
VO1
IO1
AG
UP
ZP
Y0
Y1
Y2
Y3
Y4
Y5
C1
Y3
Y4
Y5
70
53.2
Direct Mounting: Please use M4 screw according to the dimension of the product.
DIN Rail Mounting: When mounting the PLC to 35mm DIN rail, be sure to use the
retaining clip to stop any side-to-side movement of the PLC and reduce the chance of
wires being loose. The retaining clip is at the bottom of the PLC. To secure the PLC to
DIN rail, pull down the clip, place it onto the rail and gently push it up. To remove the
PLC, pull the retaining clip down with a flat screwdriver and gently remove the PLC from
DIN rail.
V0+
I0+
VI0V1+
I1+
VI1V2+
V3+
I3+
VI3-
90
109.4
101
I2+
VI2-
FE
VO0
IO0
VO1
IO1
AG
Unit: mm
[ Figure 4 ]
Wiring
1. Use 22-16AWG (1.5mm) single or multiple core wire
22-16AWG
on I/O wiring terminals. See the figure in the right hand
side for its specification. PLC terminal screws should be
tightened to 1.90 kg-cm (1.65 in-lbs) and please use only
< 1.5mm
60/75C copper conductor.
2. DO NOT wire empty terminal and place the I/O signal cable in the same wiring
circuit.
3. DO NOT drop tiny metallic conductor into the PLC while screwing and wiring. Tear
off the sticker on the heat dissipation hole for preventing alien substances from
dropping in, to ensure normal heat dissipation of the PLC.
Safety Wiring
Since DVP-SX2 is only compatible with DC power supply, Delta power supply modules
(DVPPS01/DVPPS02) are suitable power supplies for DVP-SX2. Users are suggested
to install the protection circuit at the power supply terminal to protect DVPPS01 or
DVPPS02. See the figure below.
Power indicator
Breaker
Emergency stop: This button cuts off the system power supply when accidental
emergency takes place.
5
-4-
10
DVPPS01/DVPPS02
DVP-PLC (main processing unit)
Power Supply
The power input of DVP-SX2 series is DC. When operating DVP-SX2 series, please
note the following points:
1. The power is connected to the two terminals, 24VDC and 0V, and the range of power
is 20.4 ~ 28.8VDC. If the power voltage is less than 20.4VDC, PLC will stop running,
all outputs will go Off and ERROR indicator will flash continuously.
2. The power shutdown of less than 10 ms will not affect the operation of the PLC.
However, power shutdown time that is too long or the drop of power voltage will stop
the operation of the PLC and all outputs will go OFF. When the power returns to
normal status, the PLC will automatically resume operation. (Care should be taken
on the latched auxiliary relays and registers inside the PLC when programming).
+24V
+24V
24G
24G
S/S
S/S
X0
X0
X1
X1
[ Figure 8 ]
[ Figure 7 ]
4. Isolation circuit: The optical coupler is used to isolate signals between the circuit
inside PLC and input modules.
Relay (R) output circuit wiring
-5-
DC power supply
Fuse: Uses 5~10A fuse at the shared terminal of output contacts to protect the output circuit
Transient voltage suppressor (SB360 3A 60V): To extend the life span of contact.
1. Diode suppression of DC load: Used when in smaller power (Figure 12a)
2. Diode + Zener suppression of DC load: Used when in larger power and frequent On/Off
(Figure 12b)
AC power supply
Manually exclusive output: For example, Y3 and Y4 control the forward running and reverse
running of the motor, forming an interlock for the external circuit, together with the PLC
internal program, to ensure safe protection in case of any unexpected errors.
DC power supply
Emergency stop
The output of the transistor model is open collector. If Y0/Y1 is set to pulse output, the
output current has to be bigger than 0.1A to ensure normal operation of the model.
1. Diode suppression: Used when in smaller power (Figure 15a)
2. Diode + Zener suppression: Used when in larger power and frequent On/Off (Figure 15b)
Manually exclusive output: For example, Y3 and Y4 control the forward running and reverse
running of the motor, forming an interlock for the external circuit, together with the PLC
internal program, to ensure safe protection in case of any unexpected errors.
-6-
A/D: Passive
1 Voltage input
CH1
UI N
1 Voltage input
V0+
I0+
VI0-
CH1
UIN
-
4 Shielded
4 Shielded
cable
2 Current input
CH3
UI N
4 Shielded
cable
2 Current input
V3+
I3+
VI3FE
cable
Terminal
of power module
cable
Terminal of
power module
0V
24V
5 Grounding (100
or less)
V3+
I3+
VI3FE
0V
24V
5 Grounding (100
4 Shielded
CH3
V0+
I0+
V0-
or less)
[ Figure 16 ]
[ Figure 17 ]
D/A
6 Voltage output
AC drive, recorder,
scale value...
CH1
4
Isolation wire
7 Current output
AC drive, recorder,
scale value...
VO0
IO0
Isolation wire
CH2 VO1
IO1
AG
[ Figure 18 ]
RS-485 Wiring
1 D+ D- SG
D+ D- SG
SG D+ D-
4
1
Master node
Terminal resistor
2
3
4
2
Figure 19
Slave node
Shielded cable
Note: 1. Terminal resistors are suggested to be connected to master and the last slave with
resistor value of 120.
2. To ensure communication quality, please apply double shielded twisted pair cable
(20AWG) for wiring.
3. When voltage drop occurs between the internal ground references of two systems,
connect the systems with Signal Ground point (SG) for achieving equal potential
between systems so that a stable communication can be obtained.
-7-
DVP DVP-SX2 20 8 + 6
+ 4 + 2 PLC 16k steps
I/O //
480
A/DD/A I/O
100kHz
a
DVP-SX2
a (OPEN TYPE)
/
1 [Figure 1] [Figure 2]
1
10
11
USB
12 RUNSTOP
13 COM1 (RS-232)
14 COM2 (RS-485)
COM1 (RS-232)
15
COM2 (RS-485)
16 3PIN ()
17 ()
USB
18 I/O
VR0VR1
19 I/O
DIN
20 DIN (35mm)
21 I/O
I/O
DVP20SX211R
DVP20SX211T
DVP20SX211S
Max. 7.5A@24VDC
2.5A/30VDC(Polyswitch)
4.7W
4W
4W
> 5M ( 500VDC)
PLC
0C ~ 55C50 ~ 95% 2
-25C ~ 70C5 ~ 95%
243g
224g
-8-
227g
No.
X0, X2
X1, X3
X4 ~ X7
24VDC, 5mA
(10%)
4.7K Ohm
OffOn
> 15VDC
OnOff
< 5VDC
OffOn
< 2.5s
< 10s
< 20s
OnOff
< 5s
< 20s
< 50s
D1020 0 ~ 20 ms (10ms)
No.
Y0, Y2
Y1, Y3
1Hz
100kHz
10kHz
Y4, Y5
1kHz
5 ~ 30VDC
#1
1.5A/1 (5A/COM)
#2
15W (30VDC)
20WDC/100WAC
2.5W (30VDC)
Y0 ~ Y5
OffOn
10 ms
OnOff
2s
20s
100s
3s
30s
100s
AD/DA
(A/D)
4 ~ 20mA#1
10V
0 ~ 20mA 4 ~ 20mA#1
2,000
2,000
0 ~ +2,000
2,000
0 ~ +4,000 0 ~ +4,000
12-bit
> 1M
250
0.5 or lower
> 5K
< 500
1%
1% 20mA +10V
2ms ( D1118 ) #3
15V
32mA
2ms #4
-
16 2 12 bits
20mA
10V
#2
(D/A)
( D1062 ) #5
#1 D1115
-9-
#2
(5mV =
20V
)
4000
(10 =
40mA
)
4000
(5mV =
20V
)
4000
(5 =
20mA
)
4000
#3 2ms
#4 2ms
#5 D1062 1
(Sink or Source)
20SX211R
20SX211T
20SX211S
20SX211R/T/S
(NPN)
(PNP)
I/O
3 [Figure 4]mm
PLC PLC
3 [Figure 5]
M4
DIN 35mm DIN
I/O
4 [Figure 5] I/O
1. / 22-16AWG (1.5mm) 3
PLC 1.90 kg-cm (1.65 in-lbs) 60/75C
2.
3. PLC PLC
DVP-SX2
1. 24VDC 0V 20.4 ~ 28.8VDC
20.4VDC PLC OffERROR LED
2. 10ms PLC
PLC OffPLC
PLC
DVP-SX2 DC Only
(DVPPS01/DVPPS02) DVP-SX2 DVPPS01/DVPPS02
4 [Figure 6]
1
10
2A
24VDC500mA
/
- 10 -
DVPPS01/DVPPS02
DVP PLC
DC SINK SOURCE
4~5 [Figure 7][Figure 8]
2. Y0Y1Y2 C0 Y3Y4Y5 C1
5 [Figure 9]
3. (NPN/PNP) Y0 ~Y5 UPZP 5
[Figure 10]
4. PLC
5 ~ 10A
1. DC 5 [Figure 12a]
2. DC +Zener On/Off
5 [Figure 12b]
6
Y3 Y4
PLC
5 [Figure 13]
1. DC 6 [Figure 15a]
2. DC +Zener On/Off
6 [Figure 15b]
Y3 Y4
PLC
A/D D/A
7 [Figure 16] ~ [Figure 18]
1
100
V+ I+
RS-485
7 [Figure 19]
1
1. 120
2. (20AWG)
3. SG (Signal Ground)
- 11 -
DVP DVP-SX2 20 8 + 6
+ 4 + 2 LC 16k steps
SS/SA/SX/SC/SV I/O /
480 A/DD/A
I/O 100kHz
a
DVP-SX2
a (OPEN TYPE)
1 [Figure 1] [Figure 2]
1 I/O
12 RUNSTOP
13 COM1(RS-232)
3 USB
14 COM2(RS-485)
4 COM1(RS-232)
15
5 COM2(RS-485)
16 3PIN ()
17 ()
7 USB
18 I/O
8 VR0VR1
19 I/O
9 DIN
20 DIN (35mm)
10
21 I/O
11
DVP20SX211R
DVP20SX211T
DVP20SX211S
Max. 7.5A@24VDC
2.5A/30VDC (Polyswitch)
4.7W
4W
4W
> 5M ( 500VDC)
PLC
0C ~ 55C50 ~ 95% 2
-25C ~ 70C5 ~ 95%
243g
224g
- 12 -
227g
No.
X0, X2
X1, X3
X4 ~ X7
S/S
(10%)
24VDC, 5mA
4.7K Ohm
OffOn
> 15VDC
OnOff
< 5VDC
OffOn
< 2.5s
< 10s
< 20s
OnOff
< 5s
< 20s
< 50s
D1020 0 ~ 20 ms (10ms)
No.
Y0, Y2
Y1, Y3
1Hz
100kHz
10kHz
5 ~ 30VDC
Y4, Y5
1kHz
#1
1.5A/1 (5A/COM)
#2
15W (30VDC)
20WDC/100WAC
2.5W (30VDC)
Y0 ~ Y5
OffOn
10 ms
OnOff
2s
20s
100s
3s
30s
100s
A/D D/A
(A/D)
20mA
4 ~ 20mA#1
10V
2,000
2,000
0 ~ +2,000
2,000
> 1M
0.5 or lower
> 5K
< 500
1%
1% 20mA +10V
2ms ( D1118 ) #3
15 V
32mA
2ms #4
-
16 2 12 bits
4 ~ 20mA#1
0 ~ +4,000 0 ~ +4,000
250
-
0 ~ 20mA
12-bit
10V
#2
(D/A)
( D1062 ) #5
#1 D1115
- 13 -
#2
(5mV =
20V
)
4000
(10 =
40mA
)
4000
(5mV =
20V
)
4000
(5 =
20mA
)
4000
#3 2ms ,
#4 2ms
#5 D1062 1
()
20SX211R
20SX211T
20SX211S
20SX211R/T/S
I/O
(NPN)
(PNP)
3 [Figure 4]mm
PLC PLC
3 [Figure 5]
M4
DIN 35mm DIN
I/O
4 [Figure 5] I/O
1. / 22-16AWG (1.5mm) 3
PLC 1.90 kg-cm (1.65 in-lbs) 60/75C
2.
3. PLC PLC
DVP-SX2
1. 24VDC 0V 20.4VDC ~ 28.8VDC
20.4VDC PLC OffERROR LED
2. 10ms PLC
PLC OffPLC
PLC
DVP-SX2 DC Only
(DVPPS01/DVPPS02) DVP-SX2 DVPPS01/DVPPS02
4 [Figure 6]
1
10
2A
24VDC500mA
/
- 14 -
DVPPS01/DVPPS02
DVP PLC
DC DC
4~5 [Figure 7][Figure 8]
2. Y0Y1Y2 C0 Y3Y4Y5 C1
5 [Figure 9]
3. (NPN/PNP) Y0~Y5 UPZP 5
[Figure 10]
4. PLC
5 ~ 10A
1. DC 5 [Figure 12a]
2. DC +Zener On/Off 5
[Figure 12b]
Y3 Y4
PLC
5 [Figure 13]
1. DC 6 [Figure 15a]
2. DC +Zener On/Off
6 [Figure 15b]
Y3 Y4
PLC
A/D D/A
7 [Figure 16] ~ [Figure 18]
1
100
V+ I+
RS-485
7 [Figure 19]
1
1. 120
2. (20AWG)
3. SG (Signal Ground)
- 15 -
.......
TRKE
.........
Deltann DVP-SX2 modelini setiiniz iin teekkrler. DVP-SX2 PLC 16K program
hafzas ile eitli komutlar sunar ve zerinde 20 nokta vardr (8DI + 6 DO + 4AI + 2AO).
PLCye Dijital giri/k modlleri (max. 480 giri/k nokta), analog modller (A/D, D/A
dntrc ve scaklk niteleri) ve yeni yksek hzl ilave niteler gibi ince-tip ilave
modller balanabilir. ki grup yksek-hzl (100kHz) pulse k ve yeni 2-eksen
interpolasyon komutlar ile birok uygulama iin tatmin edici zmler sunar. DVP-SX2
rn kk lsyle kurulumu ok kolaydr.
a Bu bilgi dkman sadece rnn elektriksel zellikleri, genel fonksiyonlar, kurulumu
ve balants ile ilgili bilgiler salar. Detayl programlama ve DVP-SX2 uygulama
komutlar ile ilgili ltfen DVP-SX2 Operation Manual: Programming dkmann
inceleyiniz. Opsiyonel evre birimleri ile ilgili ltfen kutunun iindeki rnle birlikte
gelen bilgi dkmann inceleyiniz.
a Bu rn AIK TP bir PLCdir. PLC rn toz, rutubet, elektrik oku riski ve
titreimden uzak yerlerde muhafaza edilmelidir. Ayrca cihaza yetkili olmayan kiilerin
mdahale etmesini engelleyecek nlemler alnmaldr. (rnein rnn kurulduu
panoya kilit konulmas gibi). Aksi halde kullanclar ve/veya PLC zarar grebilir.
a Giri/k terminallerine kesinlikle AC besleme balamaynz. Aksi halde rn zarar
grebilir. Enerji vermeden nce rnn tm balantlarn kontrol ediniz.
Elektromanyetik grlty nlemek iin topraklamann
dzgn yapldna emin
olunuz. Enerjili iken rn terminallerine mdahale etmeyiniz.
rn Grn
ngilizce (English) blmnde ekil 1 [Figure 1] ve ekil 2ye [Figure 2] baknz.
Elektriksel zellikler
Model
DVP20SX211R
Madde
DVP20SX211T
DVP20SX211S
Besleme voltaj
Sznt Akm
Maksimum 7.5A@24VDC
Sigorta Kapasitesi
2.5A/30VDC, Polyswitch
G Tketimi
4.7W
4W
4W
Izolasyon direnci
Ses Bakl
Topraklama
alma / Saklama
Titreim / ok direnci
Arlk (g)
243g
224g
zellik.
Madde
Giri No.
X0, X2
Giri Tipi
X1, X3
DC (SINK veya SOURCE)
24VDC, 5mA
Giri Empedans
impedance
Aktif seviye
227g
Giri Noktas
4.7K Ohm
OffOn
> 15VDC
OnOff
< 5VDC
- 16 -
X4 ~ X7
Giri Noktas
zellik.
Madde
Cevap
Zaman
OffOn
< 2.5s
< 10s
< 20us
OnOff
< 5s
< 20s
< 50us
Filtre zaman
zellik
Madde
Rle
k No.
Y0, Y2
Y1, Y3
1Hz
100kHz
10kHz
Maksimum frekans
alma Voltaj
Maksimum
Yk
Rezistif
5 ~ 30VDC
Y4, Y5
1kHz
#1
15W (30VDC)
20WDC/100WAC
2.5W (30VDC)
Endktif
Lamba
Cevap
Zaman
Transistor
Y0 ~ Y5
OffOn
Yaklak 10 ms
OnOff
2s
20s
100s
3s
30s
100s
#1: DVP20SX211T: UP, ZP harici 24VDC (-15% ~ +20%) g kayna ile birlikte altrlmaldr,
akm oran yaklak 3mA/noktadr.
DVP20SX211S: UP, ZP harici 5 ~ 30VDC g kayna ile birlikte altrlmaldr, akm oran
yaklak 5mA/noktadr.
#2: ngilizce (English) blmnde ekil 3e [Figure 3] baknz.
Madde
Voltaj
Analog k (D/A)
Akm
Voltaj
Akm
10V
20mA
4 ~ 20mA#1
10V
0 ~ 20mA 4 ~ 20mA#1
2,000
2,000
0 ~ +2,000
2,000
0 ~ +4,000 0 ~ +4,000
znrlk #2
12-bit
Giri empedans
> 1M
k empedans
250
Tayc empedans
tolerans
> 5K
< 500
Tam doruluk
Cevap zaman
Mutlak giri aral
Dijital data format
Ortalama fonksiyon
15V
2ms #4
32mA
Izolasyon metodu
Protection
Voltaj knda ksa devre korumas vardr, fakat uzun sureli ksa devre
durumunda dahili devreler zarar grebilir ve akm kn aabilir.
Analog k (D/A)
Voltaj
Akm
Voltaj
Akm
20V
40mA
20V
20mA
(5mV =
)
(10 =
)
(5mV =
)
(5 =
)
4000
4000
4000
4000
#3: Tarama peryodu 2 msden veya set deerinden uzun olduu zaman, ayar tarama peryodunu
takip eder.
#4: Tarama peryodu 2msden uzun olduu zaman, ayar tarama peryodunu takip eder.
#5: rnekleme aral 1olduu zaman, mevcut deer okunacak.
- 17 -
I/O Konfigurasyon
Model
Nokta
Giri
Tip
k
Nokta
20SX211R
20SX211T
20SX211S
DC
(Sink veya
Source)
SX2-R/T/S
Analog Giri
Tip
Rle
NPN Transistor
PNP Transistor
Analog k
I/O konfigurasyon
Rle
Transistor
ngilizce
(English)
blmnde
baknz
ngilizce
(English)
blmnde
baknz
Balant
1. PLCnin I/O terminal balantlarn yapmak iin 22-16 AWG
22-16AWG
(1.5mm) tek damarl veya ok damarl kablo kullannz. Kablo
zellikleri yandaki ekilde gsterildii gibi olmaldr. PLC
terminal vidalar 1.90 kg-cm (1.65 in-lbs) orannda sklmal
< 1.5mm
ve sadece bakr iletkenler kullanlmaldr.
2. Bo terminallere balant yapmaynz ve I/O sinyal kablolar ile power kablolarn ayr
kablo bloundan balaynz.
3. PLC kablo balantlarn yaparken PLCnin iine iletken paracklar drmeyiniz.
Balantlar tamamladktan sonra s dalmn salanabilmesi iin kk cisimlerin
PLCnin iine dmesini engelleyen koruyucu etiketleri kartnz.
Gvenli Balant
DVP-SX2 rnleri sadece DC voltaj ile beslenir. DELTAnn g kaynaklar (DVPPS01 /
DVPPS02), DVP-SX2 PLClerin beslemesi iin uygundur. DVPPS01 veya DVPPS02
rnlerini korumak iin power supply terminallerine koruyucu devre kurulmas nerilir.
ngilizce (English) blmnde ekil 6ya [Figure 6] baknz.
1
3
4
6
8
Devre kesici
5
7
9
AC power supply yk
DVPPS01/DVPPS02
DVP-PLC (Ana ilemci birimi)
Giri Balants
2 eit DC giri vardr, SINK veya SOURCE. ngilizce (English) blmde ekil 7ye
[Figure 7] ve ekil 8e [Figure 8] baknz.
- 18 -
k Balants
1. DVP-SX2 serisi rnlerde 2 eit k vardr. Rle ve Transistr (NPN/PNP). k
terminal balantlarn yaparken ortak terminallerin kullanmna dikkat ediniz. (COM).
2. Y0, Y1, ve Y2 k terminalleri C0 ortak ucunu, Y3, Y4 ve Y5 k terminalleri C1
ortak ucunu kullanr. ngilizce (English) blmde ekil 9a [Figure 9] baknz. k
terminallerinden biri aktif olursa o k terminaline karlk gelen indicator ON olur.
3. Y0 ~Y5 transistr k terminalli (NPN/PNP) modeller UP, ZP ortak ularn kullanr.
ngilizce (English) blmde ekil 9a [Figure 9] baknz.
4. zolasyon devresi: PLC i devreleri ve giri modlleri arasn izole etmek iin
optokuplr kullanlr.
Rle (R) k devre balants
Balant detay iin ngilizce (English) blmde ekil 11 - ekil 13e [Figure 11] ~
[Figure 13] baknz.
1
3
4
5
7
DC power supply
2 Acil stop: Harici switch kullanr.
Sigorta: k devrelerini korumak iin klarn ortak terminallerinde 5~10A sigorta kullanr.
Yksek gerilim darbe koruyucu (SB360 3A 60V): Kontak mrn uzatmak iin kullanlr.
1. DC yk diyot koruma: Dk power olduu zaman kullanlr. (ngilizce (English) blmde
ekil 12aya [Figure 12a] baknz).
2. DC yk Diyot + Zener koruma: Yksek power veya ok sk On/Off durumlarda kullanlr.
(ngilizce (English) blmde ekil 12bye [Figure 12b] baknz See [Figure 12b])
Akkor Lamba (resistif yk)
6 AC power supply
Manual tek k: rnein, Y3 ve Y4 klar motorun ileri ve geri almasn kontrol etsin.
klarn ayn anda almasn ve beklenmeyen hatalar nlemek iin PLC programnda
ve harici devre balantsnda gerekli nlemler alnarak ayn anda sadece tek kn
almas salanabilir.
Dalga Emici (Absorber): AC ykteki grlty nlemek iin kullanlr. (ngilizce (English)
blmde ekil 13e [Figure 13] baknz)
1
4
DC power supply
2 Acil stop
3 Devre koruma sigortas
Transistor kl modeler ak kolektr(open collector) dr. Eer Y0/Y1 pulse k olarak
ayarlandysa, normal alma iin k akm 0.1Aden byk olmaldr.
1. Diyot koruma: Dk power olduu zaman kullanlr. (ngilizce (English) blmde
ekil 15aya [Figure 15a] baknz)
2. Diyot + Zener koruma: Yksek power veya ok sk On/Off durumlarda kullanlr
(ngilizce (English) blmde ekil 15bye [Figure 15b] baknz)
Manual tek k: rnein, Y3 ve Y4 klar motorun ileri ve geri almasn kontrol etsin.
klarn ayn anda almasn ve beklenmeyen hatalar nlemek iin PLC programnda
ve harici devre balantsnda gerekli nlemler alnarak ayn anda sadece tek kn
almas salanabilir.
RS-485 Wiring
ngilizce (English) blmde ekil 19a (Figure 19) baknz.
1
3
Master istasyon
2 Slave istasyon
Terminal resistor
4 Ekranl kablo
Not : 1. Terminal resistorun master ve son slave arasnda 120W olacak ekilde balanlmas
nerilir.
2. Haberleme kalitesini arttrmak iin, ltfen balantda double shield (ift ekranl) twisted
pair (sarmal iftli) kablo (20AWG) kullannz.
3. ki sistemde dahili ground referanslar arasnda voltage dmesi meydana gelirse,
sistemler e potansiyel salanabilmesi iin SG Sinyal Ground noktasna ortak
balanarak dzgn haberleme salanr.
- 19 -