Down Conductors
Natural
Components
Down Conductors
62305-3
ABB Group
September 7, 2014 | Slide 3
Class of LPS
10
II
10
III
15
IV
20
Down Conductors
62305-3
Conductors
for structural lightning protection
Min. of 2 down conductors
Flat tape conductors
25 x 3mm bare tape
25 x 3mm bare tape PVC covered tape
Stranded conductors
70mm2 bare or PVC covered stranded
Conductors
ABB Group
September 7, 2014 | Slide 4
Down Conductors
62305-3
Material,
Configuration and Min. cross sectional area of down conductors
ABB Group
September 7, 2014 | Slide 5
ABB Group
September 7, 2014 | Slide 6
kc
s = ki
l
km
Separation distance calculated from
where ki = related to class of LPS
kc = coefficient related to current flowing in d.c
km = coefficient related to separation medium
l = width of overhang (m) x height of overhang (m)
ABB Group
September 7, 2014 | Slide 7
kc
s = ki
l
km
2 down conductors (Kc = 0.66)
Class I LPS (ki = 0.08)
Medium air (km = 1)
What should be my recommended
L= w + h
ABB Group
September 7, 2014 | Slide 8
Natural Components
Steel reinforcement
within concrete (rebar)
Clamped cable to rebar
connection
Stranded copper cable
2
(70mm PVC insulated)
Bonding conductor
Vertical Conductor
Less then 20m
Vertical Conductor
more then 20m