Flow compensated block

The purpose of this block is to compensate a gas flow by pressure and temparture.
The measured values of flow, pressure and temperature are those used as variable inputs in
the formula.




RV1= Measured uncompensated flow (NCMH)


RV2= Measured pressure (Kg/cm2 Abs)
RV3= Measured temperature (C)

The reference values of pressure and temperature are those used for design and are defined
as internal parameters.



P02= Reference pressure (Kg/cm2 Abs)


P03= Reference temperature (C)

The formula is represented as:


Compensated flow (NCMH)= RV1*SQRT[(RV2/P02)*((P03+273.15)/(RV3+273.15))]