Anda di halaman 1dari 70

SISTEM PROTEKSI

KEBAKARAN

Oleh
Drs. Pardjito, BE.

SISTEM PROTEKSI KEBAKARAN

I. DASAR HUKUM
1. UU NO.1 TH 1970 TENTANG KESELAMATAN KERJA
PASAL 3 AYAT 1 :
b. MENCEGAH MENGURANGI DAN MEMADAMKAN KEBAKARAN
c. MENCEGAH DAN MENGURANGI BAHAYA PELEDAKAN
d. MEMBERI KESEMPATAN ATAU JALAN MENYELAMATKAN DIRI
PADA WAKTU KEBAKARAN
q. MENCEGAH TERKENA ALIRAN LISTRIK YANG BERBAHAYA

2. UNDANG-UNDANG RI NO. 28 TAHUN 2002 TENTANG


BANGUNAN GEDUNG.
3. PERATURAN MENTERI TENAGA KERJA RI NO. PER.
04/MEN/1980
TENTANG
SYARAT-SYARAT PEMASANGAN DAN PEMELIHARAAN ALAT PEMADAM API
RINGAN (APAR)
4. PERATURAN MENTERI TENAGA KERJA RI NO. PER.
02/MEN/1983 TENTANG INSTALASI ALARM KEBAKARAN
AUTOMATIK.
5. PERATURAN MENTERI TENAGA KERJA RI. NO. PER.
2/MEN/1989 TENTANG
PENGAWASAN INSTALASI
PENYALUR PETIR.
6. KEPUTUSAN MENTERI TENAGA KERJA RI KEP186/MEN/1999 TENTANG UNIT PENANGGULANGAN
KEBAKARAN DI TEMPAT KERJA.

7. PERATURAN DAERAH DKI JAKARTA NO. 7 TAHUN 1991


TENTANG BANGUNAN DALAM WILAYAK DKI JAKARTA
8. PERATURAN DAERAH DKI JAKARTA NO. 3 TAHUN 1992
TENTANG PENANGGULANGAN BAHAYA KEBAKARAN
DALAM WILAYAH DKI JAKARTA
9. KEPUTUSAN MENTERI TENAGA KERJA RI NO. 75
/MEN/2002 TENTANG BERLAKUNYA SNI 04-0225-2000
MENGENAI PUIL 2000
10. PERATURAN MENTERI TENAGA KERJA RI NO.
03/MEN/1999 TENTANG SYARAT-SYARAT KESELAMATAN
DAN
KESEHATAN
KERJA
LIFT
UNTUK
PENGANGKUTAN ORANG DAN BARANG.

II. STANDARD
1. STANDAR NASIONAL INDONESIA (SNI)
CONTOH :
SNI 03 6571 2001
SISTEM PENGENDALIAN ASAP KEBAKARAN PADA
BANGUNAN GEDUNG
SNI 03 1736 2000
TATA CARA PERENCANAAN SISTEM PROTEKSI PASIF
UNTUK PENCEGAHAN BAHAYA KEBAKARAN PADA
BANGUNAN GEDUNG
SNI 04 0225 2000
PERSYARATAN UMUM INSTALASI LISTRIK 2000 (PUIL
2000)

2. NFPA
CONTOH :
NFPA 20
CENTRIFUGAL FIRE PUMPS
NFPA 25
STANDARD FOR THE INSPECTION, TESTING, AND
MAINTENANCE
OF
WATER

BASED
FIRE
PROTECTION SYSTEMS.
NFPA 13
INSTALATION OF SRINGKLER SYSTEM

III. KALISIFIKAS API KEBAKARAN


TUJUAN : MEMUDAHKAN PEMADAMAN DENGAN ALAT
PEMADAM YANG TEPAT.
KLAS A : API KEBAKARAN DARI BAHAN PADAT/SERAT ;
KAYU, KERTAS, TEXTIL DAN LAIN-LAIN.
KLAS B : API KEBAKARAN DARI BAHAN CAIR/MINYAK
/PASTA, GAS DAN LAIN-LAIN.
KLAS C : API KEBAKARAN YANG DISEBABKAN OLEH
LISTRIK.
KLAS D : API KEBAKARAN
DARI BAHAN LOGAM;
TITANIUM, SODIUM, ALUMINIUM DAN LAIN-LAIN.

IV. PRINSIP PENCEGAHAN KEBAKARAN


1. MENGENDALIKAN SETIAP BENTUK ENERGI YANG
DAPAT MENIMBULKAN KEBAKARAN.
2. MEMASANG/MENGADAKAN
SISTEM
KEBAKARAN PASIF DAN AKTIF.
3. MELAKSANAKAN
KEBAKARAN.

MANAJEMEN

PROTEKSI

PENCEGAHAN

V. PHENOMENA KEBAKARAN

INTENSITAS

Phenomena kebakaran
Flashover

GR
O

Y
CA

Initiation

STEDY
Fully development fires
(600-1000 o C)

DE

TH

3 - 10 menit

TIME

Source
Energy

10

DOMINO KEBAKARAN

11

ZAT/
ENERGI

API
MULA

KEBAKARAN
TIDAK TERKENDALI

ASAP
GAS
PANAS

KORBAN

KELEMAHAN SISTEM PROTEKSI

DETEKSI ALARM APAR

SPRINKLER

HYDRANT

KERUGIAN

MOE

PETUGAS

KELEMAHAN MANAJEMEN

12

The Potential Effect of Fire on People and Property


Smoke

Temperature
Carbon
Monoxide
Carbon
Dioxide

Pe
ril
Pa ak
ni u
k

Oxygen

13

VI. SISTEM PROTEKSI


KEBAKARAN

14

AKTIF
PASSIF

DETEKSI

ALARM

APAR

SPRINKLER

HYDRAN

MEANS OF ESCAPE
KOMPARTEMEN
SMOKE CONTROL
FIRE DAMPER
FIRE RETARDANT/TREATMENT
15

VII. ALAT PEMADAM API RINGAN

16

ALAT PEMADAM
API RINGAN
Portable Fire
Extinguisher
17

ALAT PEMADAM API RINGAN

DAPAT DIOPERASIKAN SATU


ORANG
UNTUK PEMADAMAN MULA
KEBAKARAN
SEBATAS VOLUME API KECIL

18

Perencanaa
n

Penempatan
tepat
Pengadaa
n

Petugas
kompeten
Sertifik
at

Kebijakan
Fire risk
Assessme
nt
Pemeliharaan
teratur

Jenis dan
ukuran
tepat

Efektif
Aman
Tidak Merusak

19

Designing
Listing
Selecting
Purchasing
Installing
Approving

Alat pemadam api


ringan

Inspecting
Recharging
Maintaining
Testing
Operating
20

ALAT PEMADAM API RINGAN


Ref :
Pert. Menaker No Per-04/Men/1980
HARUS SIAP PAKAI PADA WAKTUNYA

JENIS DAN UKURANNYA SESUAI


MUDAH DILIHAT DAN MUDAH
DIAMBIL
KONDISI BAIK
SETIAP ORANG DAPAT
MENGOPERASIKAN DENGAN BENAR,
TIDAK MEMBAHAYAKAN DIRINYA.

21

JENIS
JENIS MEDIA
MEDIA PEMADAM
PEMADAM

FOAM

WATER

- BUSA

POWDER

- AIR

JENIS KERING
- DRY PORDER
- CO2
- CLEANT
AGENT

HALON

JENIS BASAH

22

STORED
PRESSURE
( N2 )

CO2

Tipe konstruksi

CARTRIDGE

23

24

Ukuran tidak sesuai


Macet/tidak berfungsi
Salah penempatan

FOAM

Jenis tidak sesuai

POWDER

HALON

WATER

KEGAGALAN APAR

Tidak bertekanan
- bocor
Menggumpal
- tunda refill

belum ditunjuk
Petugas
tidak trampil

25

Klasifikasi KEBAKARAN
Ref : Permenaker -04/80

ABC

Flammable
Liquid/gas

B
A

A
D
B

Combustible
Material

Electrical
Equipment

Metals

Multi Purpose

26

FOAM

POWDER

HALON

WATER

KEGAGALAN
KEGAGALANAPAR
APAR

Jenis media tidak sesuai


Klasifikasi
api/kebakaran

Setiap jenis media pemadam masingmasing memiliki keunggulan dan


kekurangan, bahkan dapat
membahayakan bagi petugas atau
justru memperbesar api

27

TANDA PEMASANGAN

28

VIII. INSTALASI ALARM TANDA BAHAYA


KEBAKARAN

29

INSTALASI ALARM
TANDA BAHAYA KEBAKARAN

TUJUAN
TUJUAN

PEMASANGAN
PEMASANGAN INSTALASI
INSTALASI ALARM
ALARM
KEBAKARAN
KEBAKARAN OTOMATIK
OTOMATIK BERTUJUAN
BERTUJUAN
UNTUK
UNTUK MENDETEKSI
MENDETEKSI KEBAKARAN
KEBAKARAN
SEAWAL
SEAWAL MUNGKIN,
MUNGKIN, SEHINGGA
SEHINGGA TINDAKAN
TINDAKAN
PENGAMANAN
PENGAMANAN YANG
YANG DIPERLUKAN
DIPERLUKAN DAPAT
DAPAT
SEGERA
SEGERA DILAKUKAN.
DILAKUKAN.

Tindakan dalam keadaan Emergency Kebakaran


harus sudah berhasil diatasi.
sebelum 10 menit sejak penyalaan
30

PERATURAN
PERATURAN MENTERI
MENTERI TENAGA
TENAGA KERJA
KERJA RI
RI
NO.
NO. PER-02/MEN/1983
PER-02/MEN/1983
TENTANG
TENTANG
INSTALASI
INSTALASI ALARM
ALARM KEBAKARAN
KEBAKARAN OTOMATIK
OTOMATIK
Ruang lingkup
- Perencanaan
- Pemasangan,
- Pemeriksaan
- Pengujian
- Pemeliharaan
31

Sign
al
alar
m

Detektor

FIRE

FOULT
FAULT

NORMAL
Panel Indikator

32


AUDIBLE ALARM

Nyala

INPUT

DETEKTOR

Panas

VISIBLE ALARM

Asap
OUTPUT

MCFA

ANN

HYDRANT
HYDRANT

33

JENIS
JENIS DAN
DAN TIPE
TIPE DETEKTOR
DETEKTOR
Nyala

Panas

Asap
Manual

ULTRA
VIOLET
INFRA RED
FIXED
TEMPERATURE
RATE OF RISE
IONIZATIO
N
OPTIC
Push
bottom
Full down
break glass

34

ZONA
ZONADETECTION
DETECTION
Nyala 20 titik

Panas 40 titik

Asap 20 titik

ZONE 3
ZONE 2
ZONE 1

EOL

EOL

EOL

Luas tiap zone deteksi


- ruang tanpa sekat mak. 2000 m2
- terdapat sekat mak. 1000 m2
35

INTERCONECTION
INTERCONECTION

DETEKTOR
KEBAKARAN

FIRE
FIRE ALARM
ALARM SYSTEM
SYSTEM
AC
Off

SPRINKLER
(FS)

POMPA
HYDRANT
supply daya

LIFT
Off
PRESS FAN
On
MCFA

36

IX. INSTALASI PEMADAM


KEBAKARAN OTOMATIS
(TOTAL FLOODING SYSTEM)

37

SMOKE

CONTROL
CONTROL FIRE
INDIKATOR
INDIKATOR

BUZER
ALARM
DISCHART
CONTROL
CONTROL
PANEL
PANEL

VALVE

HEAT

Media pemadam Halon


(F, Cl, Br)

!!!!!!!!!!!!
Mengandung potensi bahaya
keracunan
HARUS MEMILIKI IJIN K3

INSTALASI PEMADAM KEBAKARAN


AUTOMATIC TOTAL FLOODING SYSTEM

38

X. INSTALASI HIDRAN

39

Bagian ke III
PEMELIHARAAN
SISTEM HYDRAN
DAN SPRINGLER

1 1/2 Inc

2 1/2 Inc

2 1/2 Inc

Out door

RESERVOAR

40

FIRE HYDRANT
Jaringan instalasi pipa air
untuk pemadam kebakaran
yang dipasang secara permanen
Komponen sistem Hidrant
- Sistem persediaan air (45 menit)
- Sistem Pompa
(Jockey, Utama & Cadangan)
- Jaringan pipa
- Kopling outlet / Pilar / Landing valve
- Slang dan nozle
- Sistem kontrol tekanan & aliran

1 1/2 Inc

2 1/2 Inc

2 1/2 Inc

Out door

Seamiest
Connection
RESERVOAR

41

KLASIFIKASI HUNIAN
Tingkat resiko bahaya kebakaran
Resiko Ringan Luas 1000-2000 M2
2 titik hydran, tambahan 1 titik
Tiap 1000M2
Resiko SedangLuas 800-1600 M2
2 titik hydran, tambahan 1 titik
Tiap 800M2
Resiko Berat Luas 600-1200 M2
2 titik hydran, tambahan 1
titik
Tiap 600M2
42

43

XI. INSTALASI SPINGKLER

44

Data input :
Klasifikasi hunian :

Variabel :

Ringan
Sedang I, II, III,
Berat
Khusus
Peruntukan bangunan
Jumlah dan sifat penghuni
Konstruksi bangunan
Flammability dan Quantity Material
(Fire loads)

Standard klasifikasi sistem


sprinkler

Ukuran kepala

Kepadatan pancaran

45

46
RESERVOAR
High zone
Medium Zone
Low zone

53o C

141o C

68o C
182o C
79o C

93o C

201o C
260o C

47

Q (liter/men)
A (m2)
mm/men
1/2 L

1/2 S

48

49

XII. SARANA EVAKUASI

50

EMERGENC
Y EXIT

EXIT

51

EVAKUASI
USAHA MENYELAMATKAN DIRI SENDIRI DARI TEMPA
BERBAHAYA MENUJU TEMPAT YANG AMAN

TEMPAT
BERBAHAYA

AMAN SEMENTARA

AMAN
MUTLAK

52

SARANA EVAKUASI
SARANA PADA BANGUNAN YANG
DIRANCANG
DENGAN KONSTRUKSI YANG AMAN
UNTUK DIGUNAKAN SEBAGAI JALUR/JALAN
(Horizontal/vertical) UNTUK DILALUI PADA
SAAT
TERJADI KEADAAN BAHAYA

53

KLASIFIKASI
KLASIFIKASI HUNIAN
HUNIAN
FIRE
FIRE HAZARD
HAZARD
Hunian bahaya kebakaran ringan;
Hunian bahaya kebakaran sedang;
Hunian bahaya kebakaran berat;

PARAMETER
Jenis hunian (Pabrik, Perkantoran,
Hotel, Rumah sakit, Mall dll.;
Tinggi bangunan;
Bahan konstruksi (primer-skunder)
Sifat dan Jumlah penghuni;

54

FAKTOR PERENCANAAN
MEANS OF ESCAPE
KLASIFIKASI RESIKO
BAHAYA KEBAKARAN

-RESIKO RINGAN
-RESIKO SEDANG
-RESIKO BERAT

WAKTU
EVAKUASI

3 Menit
2,5 Menit
2 Menit

PANJANG
JARAK TEMPUH

X 12
meter

BUNTU 18M

PJT : 12 M X WAKTU
55

FAKTOR PERENCANAAN MEANS OF ESCAPE

4. LEBAR UNIT EXIT


- RATE OF FLOW 40 orang/menit

- UNIT OF EXIT WIDTH 21

56

FAKTOR PERENCANAAN MEANS OF ESCAPE

4. LEBAR UNIT EXIT


JUMLAH PENGHUNI
= .. UNIT
40 X WAKTU

1 UNIT OF EXIT WIDTH = 21


2 UNIT OF EXIT WIDTH = 21 + 21

57

XIII. SISTEM PROTEKSI PETIR

58

Ref
1. Peraturan Menteri Tenaga Kerja No Per
02/Men/1989
tentang instalasi penyalur petir
Berlaku untuk sistem proteksi eksternal / proteksi
bahaya sambaran langsung
2. SNI 225 1987 (PUIL 1987)
Sebagai rujukan untuk sistem proteksi internal /
proteksi
bahaya sambaran tidak langsunglangsung

Instalasi penyalur petir yang tidak


memenuhi syarat dapat mengundang bah
59

PELEPASAN MUATAN LISTRIK


++++++
+ + + +-+
++++++

------------------

++++++
DARI AWAN KE AWAN
+++++
++++++

-----------------DARI AWAN KE BUMI

60

AWAN KE AWAN

Arus : 5.000 ~ 200.000


A
Panas: 30.000 oC

AWAN KE BUMI

Sasaran
Sasaran
KERUSAKA
KERUSAKA
OBYEK YANG
YANG TERTINGGI
TERTINGGI
OBYEK
NN
THERMIS
THERMIS
,,
61
ELEKTRI
ELEKTRI

Instalasi penyalur
petir yang tidak
memenuhi syarat
dapat mengundang
bahaya

Grounding tidak sempurna


Berbahaya

62

++++++++
++++++++
++++++++
-----------------------------------

- - - - - - - - - - - - - - - - - - - - - +++++++
+++++++
+++++

DARI AWAN
KE AWAN

+++++++
+++++++++
+++++++
- - - - - - - - - - - - - - - -

DARI AWAN
KE BUMI

MENYAMBAR
JARINGAN LISTRIK

63

BAHAYA SAMBARAN PETIR

SAMBARAN LANGSUNG

SAMBARAN TIDAK
LANGSUNG

KERUSAKAN
PADA ALAT ELEKTRONIK

64

KONSEPSI
KONSEPSI PROTEKSI
PROTEKSI BAHAYA
BAHAYA
SAMBARAN
SAMBARAN PETIR
PETIR

PERLINDUNGAN SAMBARAN LANGSUNG


Dengan memasang instalasi penyalur petir pa
bangunan
Jenis instalasi :
Sistem Franklin
Sistem Sangkar Faraday
Sistem Elektro statik

PERLINDUNGAN SAMBARAN TIDAK LANGSUNG


Dengan melengkapi peralatan penyama tegan
pada jaringan instalasi listrik (Arrester)
65

INSTALASI
INSTALASIPENYALUR
PENYALURPETIR
PETIR
PERMENAKER
PERMENAKERPER-02
PER-02MEN/1989
MEN/1989
SISTEM FRANKLIN
BAGIAN BAGIAN PENTING

PENERIMA
(AIR TERMINAL)

HANTARAN
PENURUNAN

(DOWN CONDUCTOR)
HANTARAN PEMBUMIAN
(GROUNDING)

66

Harus dipasang instalasi


PROTEKSI PETIR

SNI 225 - 2000


PUIL-2000

(Sistem internal protection)

Ruangan berpotensi
bahaya ledakan
gas/uap/debu/serat
67

PROTEKSI PETIR SYSTEM INTERNAL


Semua bagian konduktif dibonding
Semua fasa jaringan RSTNG dipasang Arrester
Bila terjadi sambaran petir pada jaringan instalasi
listrik semua kawat RSTN
RSTN tegangannya sama tidak ada beda potensial
RSTN

ARRESTER

GROUNDING

68

Pengawasan
Pengawasan K3
K3
Instalasi
Instalasi Penyalur
Penyalur
Petir
Petir
PERMENAKER
PERMENAKER

No.
No. PER
PER
02/MEN/1989
02/MEN/1989
Tentang
Tentang
Instalasi
Instalasi Penyalur
Penyalur
Petir
Petir

+++++++
+++++++++
+++++++
- - - - - - - - - - - - - - - -

Ruang
Ruang lingkup
lingkup ::
Sistem
Sistem eksternal
eksternal
Jenis
Jenis ::
konvensi
konvensi onal
onal &
&
elektrostatik
elektrostatik
69

TERIMA KASIH