Anda di halaman 1dari 1

Recommended Generator Report

Pgina 1 de 1

Recommended Generator Report - 50DGCA


for Project proyecto HRC
Project Parameters
Generator Sets Running in Parallel:
Max Allowable Starting Voltage Dip:
Max Allowable Peak Voltage Dip:
Max Allowable Frequency Dip:
Site Altitude, Ft. (M):
Site Ambient Temperature, oF (oC):

499
77

1
35 %
35 %
10 %
(152)
(25)

Fuel:
Phase:
Frequency, Hz:
Voltage:
Quiet Site:
Duty:

Diesel
3
60
277/480, Series Wye
No
Prime

Calculated Individual Generator Set Load Running and Peak Requirements


Running kW:
Running kVA:
Running PF:
Alternator kW:

33.9
38.1
0.89
33.9

Max Step kW:


Max Step kVA:
Peak kW:
Peak kVA:

54.3 In Step 1
118 In Step 1
None
None

Cumulative Step kW:


Cumulative Step kVA:
Cumulative Peak kW:
Cumulative Peak kVA:

71.2
137
None
None

Generator Set Configuration


Engine Model:
Fuel:
Engine Displacement, cu in (liters):
Engine Cylinders:
Excitation:
Temp. Rise at Full Rated Load, oC:

4BTA3.9-G5
Diesel
239
(4)
4
Shunt
1252

Alternator:
Feature Code:
Reconnectable

Set Performance
75.3% Rated Capacity
Running at:
Starting Voltage Dip:
22 %
Peak Voltage Dip:
None %
Frequency Dip:
3%
Site Rated kW:
45
Site Rated Alternator Max kW at 125oC and 480 volts:
60
Site Rated Alternator Max kVA at 125oC and 480 volts:
75
Site Rated Max SkW:
66.00
Max SkVA:
188

Load Requirements

Voltage Range:
Number Leads:

Max Starting Voltage Dip:


Max Peak Voltage Dip:
Max Frequency Dip:
Running kW:
Alternator kW:
Running kVA:
Effective Step kW:
Effective Step kVA:

UCD2E
B414

UBR 208-240/416-480
12

35 %
35 %
10 %
33.9
33.9
38.1
57.7
122.1

2Note: Higher temperature rise at


3Note: Step

full rated load.


requirement has been reduced.

file:///C:/Program%20Files%20(x86)/Cummins%20Power%20Suite/Recommended.ht... 21/11/2013