Anda di halaman 1dari 1

S

W
N

103062

220KV SIDE OF400KV ASOJ SUBSTATION

1950
700

36000

36000

36000

36000

36000

36000

36000

CG

1000

36000

2CPA2

CG

2CPA4

18000

2BB2

2BB1
MAIN BUS-I

STR.

TANDEM ISO/PI

TANDEM ISO/PI

TANDEM ISO/PI

CE

CA
2CB1

4500

2BB2

4500

2BB1
MAIN BUS-II

2CB1

4500

CA

STR./PI

TANDEM ISO/PI

TANDEM ISO/PI

4500

TANDEM ISO/PI

STR./PI

Yard Kiosk

3500

Yard Kiosk
3500

2750

ACDB

BMK

HDB ISO

2CB1

CF

STR./PI

LA

220/66KV
TRANS.2
100MVA

TRANSFORMER

HBPI

HBPI

LA

LA

4500 M M

WIDE

ROAD

CE
PI
CT
CB

1BC2
06CPB3

1CPC2
06CPB3

1CPC2

1BC2

CB
1CPC2

06CPB3

36000

4600

ISO

06BA3

1000

PI

06BA3

36000

2BB1

220/66KV
TRANS NO.1
100MVA

4600

4600 4600

36000

2CPA4

06CPB3

CE

25000

3500
220/132KV
TRANSFORMER

ROAD

TANDEM ISO/PI

06BA3

WIDE

2BA1

2CPA3

PTJB

4000 M M

ROAD

2CPA2

06BA3

WIDE

TANDEM ISO/PI

HBPI

4000 4000

4000 M M

2BA1

15000

220/132KV
TRANSFORMER

TANDEM ISO/PI

STR./CT

2CPA3

CF

7500

CE

TRANSFER BUS

CF

2CB1

2BB2

CE

2750

CB

BMK

18000

CF

3000

8000

CB

1300

2CB1

5000

CD

5000

7700

CD

2CB1

66KV MAIN
BUS-I

ISO
06CPB3

CB
06CPA2

CT

06BA3

06BA3

06BA3

06BA3

06BA3

06BA3
06CPB3

PI

ISO

06CPB3

06BA3

06BA3

06BA3

06BA3

06BA3

06BA3

06BA3

06BA3

06CPB3

06BA3

CTJB

06CPA2

66KV MAIN
BUS-II

06CPB3

PTJB

CTJB

3400

06BA3

06BA3

06BA3

Yard Kiosk

06CPA2

06BA3

06BA3

06BA3

06BA3

06BA3

66/11KV
5 MVA
Stn.TR.
500KVA

5000

06BA3

6000

3400

3500

06CPA2

CHAINLINK FENCING

6000

ACDB

PT

SYSTEM PARAMETERS
120020

NOTES:1. ALL DIMENSIONS ARE IN M.M. UNLESS OTHERWISE SPECIFIED.


2. CONDUCTOR DETAILS (APPLICABLE ONLY FOR PROPOSED SCOPE) :(A) FOR 220KV :QUAD MOOSE ACSR FOR MAIN BUS ; TWIN MOOSE ACSR FOR TRANSFER BUS & FLY OVER BUS.
EQUIPMENT CONNECTION :- TWIN MOOSE ACSR
JUMPERS: QUAD MOOSE ACSR FOR MAIN BUS ; TWIN MOOSE ACSR FOR TRANSFER BUS & FLY OVER BUS.
DROPPERS :TWIN MOOSE ACSR
INSULATOR STRING:- TENSION -TWIN 120KN AF (16NOS. EACH STRING)
- SUSPENSION -SINGLE 120KN AF (15NOS. EACH STRING)
(B) FOR 66KV :TWIN ZEBRA ACSR FOR MAIN BUS AND FLYOVER BUS.
EQUIPMENT CONNECTION :- SINGLE MOOSE ACSR FOR FEEDER BAY , 66/11KV TR BAY AND PT BAY
TWIN ZEBRA ACSR FOR BUS COUPLER & 220/66KV TR BAY(66KV SIDE)
JUMPERS ; :- TWIN ZEBRA ACSR FOR MAIN BUS ,
DROPPERS: TWIN ZEBRA ACSR FOR BUS COUPLER & 220/66KV TR BAY(66KV SIDE);
SINGLE MOOSE FOR LA , FEEDER AND 66/11KV TR BAY
INSULATOR STRING:- TENSION -TWIN 90KN AF (6NOS. EACH STRING)
- SUSPENSION -SINGLE 90KN AF (5NOS. EACH STRING)
3. INTER EQUIPMENT SPACING IS PLANNED TO ENSURE STATUTORY CLEARANCES.
4. TOWERS WITH PEAK SHALL BE EARTHED WITH UNTREATED ELECTRODE

LEGEND:-

SCOPE OF PROJECT

220 KV CIRCUIT BREAKER


66 KV CIRCUIT BREAKER
220 KV CT
66 KV CT
LA
PT
CVT
WT
PI

EXISTING

HDB ISOLATOR W/O ES.

PROPOSED

HDB ISOLATOR WITH ES.


TANDOM DB ISOLATOR

5 AS THE STRUCTURE DETAILS OF EXISTING 220KV SWITCHYARD IS NOT SHOWN, PLEASE VERIFY THAT
STRUCTURES ARE SUITABLE FOR EXTENSION WORK OR NOT AT FIELD LEVEL.

TRANSFORMER
TENDER PURPOSE
G
E
T
C
O

YARD KIOSK WITH DCDB

(12) THIS DRAWING MAY PLEASE BE REFFERED ONLY FOR SCOPE SHOWN IN THE DRAWING.

E-MAIL FROM CE(TR) ON DTD. 24.10.2011.

CE(PROJECT)/SE/V/1426,DTD.28.12.2010.

CE(PROJECT)/SE/V/383,DTD.01.10.2010.

SR NO.

REFERENCE

R3

YARD ACDB SHOWN ON 220KV SIDE., BMK POSITION CHANGED. THIS


DRAWING SUPERSEDES EARLIER RELEASED DRAWING R2.

R2

220 / 66 KV SYSTEM ADDED CONSIDERING SCADA OPERATION, 1 NO. OF


66/11KV STN. TRANFORMER BAY ADDED DTD. 09.11.11.

DRAWN:

R1

220 / 66 KV SYSTEM ADDED AND METERING SCHEME IS PROVIDE FOR


132KV RAILWAY FEEDER. DT.19.03.11.
DRAWING SUBMITTED BY FIELD OFFICE.

SCALE:

RO
REV:

DESCRIPTION

GUJARAT ENERGY TRANSMISSION CORPN.LTD.


S.P.VIDYUT BHAVAN, RACE COURSE,
VADODARA - 390 007

LAYOUT PLAN OF 400 KV ASOJ SUB-STATION


(220/132/66KV YARD)

JE (ENGG.)

N.T.S

CHECKED:
DE (ENGG.)

APPD:
DE (CIVIL)

DATE:

EE (ENGG.)

CE (ENGG.)

DRG. NO:
13.01.12

GETCO / E /
4S - 118 / P-004

SIZE:
A0

SHEET: REV:
1 OF 1