Anda di halaman 1dari 4

259978257.

xls

Calculations for Recommended Flue Gas temperature to avoid S-dew point corrosion.
INPUTS
SO2 in flue gas ppm v/v
FD Fan outlet air temperture
Flue gas pressure-Air preheater outlet
H2O in flue gas
CALCULATION(Please do not change the formulae)
SO2 in flue gas vol %
H2O in flue gas vol %
Flue gas pressure

80
30
15
5

ppm v/v
deg.c.
mm WC
% vol

as given by EMS Lab/Online analyser


Site Reading
Site Reading
Lab analysis

0.008
5
15
mm WC
0.59055118 inch WG
1.0015 ata

Dew Point of Acid Vapors


Sulfurous acid
1000/Tdp=2.276-0.0294 ln(PH2O)-.0858 ln(PSO3)+0.0062 ln(PH2O)ln(PSO3)
The dew points are in deg K and partial pressures in mm Hg.

tw=tg-(tg-ti)xhi/(hi+ho)
tw=average tube wall temperature
tg,ti= flue gas and air inlet temperatures
hi,ho= tube side and gas side heat transfer coefficients
In an air preheater ,hi and ho=10 & 15 Btu/ft2hF respectively.

PH20
Ln(PH2O)
SO2 to SO3
PSO3
Ln(PSO3)
1000/Tdp
Tdp

2.6073920502
383.52498618
110.52498618

tw recomm.

110.52498618

hi/(hi+ho) =

0.4

tI =
tw=
tg =

RESULTS
S-Dew Point Temperature
Recommended Flue gas Temp

110.52499 Deg.c.
164.20831 Deg.c.
PAGE 1

38.1103549
3.64048603
2%
0.00097421
-6.9338821

30
110.52498618
164.2083103

259978257.xls

Issued by

Technical Services
TCL Mithapur
18/04/2003

PAGE 2

259978257.xls

mm Hg
wt. basis
mm Hg

deg K
Deg C

PAGE 3

259978257.xls

PAGE 4