SISTEM OTOMASI GARDU INDUK

(SOGI)
Jakarta, 1 Juni 2011 PT PLN (Persero) P3B Jawa Bali

Fungsi Yang Terpasang Di P3B JB


No 1 2 Perangkat RTU C264 SAS Pacis Fungsi % 100 80 Time Tag di HMI, Lokal HMI,
IED beda Keterangan
3 4
PLC T390 PLC 5000
40 0 Belum berfungsi

Uji Fungsi SCADA Di P3B JB


SOGI
NARI RCS 9698 L ABB SYS 600 L Siemens SICAM PAS L ALSTOM PACIS BL
RTU
L = Lulus BL = Belum Lulus
SELTA STCE L
ABB 560 L
Siemens AK 1703 L
ALSTOM C264 L

SOGI

Standard SPLN
Teleinformasi Data untuk Pemeliharaan Instalasi Sistem Tenaga Listrik SPLN S5.00
2:2008 dengan SK Dir No.169.K/DIR/2009 Protokol IEC 61850 : IED proteksi dan IED
BCU Protokol IEC 60870-5-101

Syarat Teknis

Relay Proteksi lulus Real Time Digital Simulator (RTDS) dari PLN PUSLITBANG Lulu
s uji protokol IEC 60870-5-101 dan IEC 61850 Lulus komunikasi partyline dan seri
al port RS232 Lulus uji digital input, digital output ,analog input, analog outp
ut Time tag di IED, Lokal HMI, Dispatcher

Syarat Non Teknis


Surat keterangan kepuasan pengguna dari P3B JB Sudah diimplementasikan di negara
maju diluar negara pembuat Original Engineering Manufacture

Proses Lelang
Dua sampul satu tahap :
Sampul pertama : Syarat administrasi dan teknik dan Uji fungsi Sampul ke dua : P
enawaran harga

Perencanaan PLN
Membangun secara terpadu untuk : Gardu Induk SOGI yang memenuhi Teleinformasi Da
ta untuk Pemeliharaan Instalasi Sistem Tenaga Listrik SPLN S5.002:2008 dengan SK
Dir No.169.K/DIR/2009

Konfigurasi Master Station


01 02 03 04 05 06
SD
PROLIANT
8000
ESC
SD
DLT
A
B
C
D
E
F
G
H
SELECTED ON-LINE
A
B
C
D
E
F
G
H
SELECTED ON-LINE
SD
CONSOLE LOOP BRI S/T CONSOLE WIC 0 OK FDX 100 LNK AUX LOOP DSU CPU S3 WIC 1 OK S
D DSU CPU S3
Cisco 1720
WIC 0 OK
BRI S/T
FDX 100 LNK

AUX
WIC 1 OK
08
LCD 1 bh
12 13
Cisco 1720
14
OK
OK
Inter Center Link ( IEC 870-6 (ICCP) )
LP
B1
B2
LP
B1
B2
07
09
A
B
C
D
E
F
G
H
SELECTED ON-LINE
11
A B C D E F G H
SELECTED ON-LINE
RTU IEC 870-5-101, DNP 3.0 Serial RTU IEC 870-5-104 Ethernet
SD

PROLIANT
8000
ESC
15
SD
16
DLT
10

Arsitektur SOGI

Kinerja SOGI
Kapasitas station unit minimal 10.000 I/O. Kapasitas Otomasi GI minimal 96 IED K
apasitas switch 48 bh, fault recovery time max 150 ms. Pertukaran data peer to p
eer melalui protocol IEC 61850 maksimal 30 milidetik. Keakuratan telemetering da
ri IED BCU:
Arus dan tegangan kelas 0,5
Daya aktif dan reaktif (MW dan MVAr) kelas 0,5 Energ
i meter (MWh dan MVArh) kelas 1,0

Switchover otomatis (failover) station unit maksimal 30 detik. Penyimpanan uruta


n kejadian minimal 120.000 event dan 60 recording pengukuran selama 100 hari.

Kapan SOGI Di Bangun


Gardu Induk Baru Penambahan Bay baru Rehabilitasi Gardu Induk Tersedia media kom
unikasi 64 kbps

Opsi Pembangunan SOGI


Bay Level Opsi 1 Opsi 2 Opsi 3 : : : RTU IED I/O Proteksi Existing Existing Pane
l Kontrol Existing BCU per CB BCU & IED Proteksi Bay Baru BCU & IED Prot BCU & I
ED Prot

Yang Tidak Dibahas Pada Spesifikasi SOGI


Peralatan tegangan tinggi Power supply Telekomunikasi Disturbance fault recorde
Fault locator Energy meter

Standard Teleinformasi SCADA Fungsi Operasi Dan Pemeliharaan


Mnemo
VDCF
Designation
VDC FAILURE..
220RF 220VDC RECTIFIER FAILURE
110RF 10VDC RECTIFIER FAILURE

Jumlah Input/Output IBT


Operasi
Telemetering 4
Pemeliharaan
37
Remote Control
Telesignal Double Telesignal Single
3
6 17
18
17 129

Station Level Opsi 1


Control Center
Gateway Station Unit 1 Station Unit 2
Switch
Switch
Switch

Station Level Opsi 2


Control Center
Gateway Station Unit 1 Station Unit 2
Switch
Switch
Switch

Bay Transformer
Bus A
Q0A
Q0AB
Q0B
Bus B
1 IED untuk bay TRAFO

Bay Level Double Busbar


Bus 1
Bus 2 Q1 Q2 Q1 Q2 Q1 Q2 Q0
Single Line Diagram
Q0 Q9 Q8 OHL
Q0
Transfor mer
Bus Coupler
Station LAN IEC 61850: Ethernet 100 Mbps Fiber Optic single ring
switch
switch
switch
switch
switch
OHL
Trafo
Trafo
Busbar & Coupler
Common
BCU MPU BPU
BCU AVR
MPU BPU1 BPU2
BCU MPU BPU
IED I/O

Level 150 kV One Half Breaker


Bus A
Station LAN IEC 61850: Ethernet 100 Mbps Fiber Optic single ring
Q0A
switch
Q0AB
OHL
switch
switch
switch
switch
switch
Diameter
Trafo
Trafo
Busbar
Common
MPU
Q0B
BCU A BCU AB BCU B
AVR
MPU BPU 1 BPU 2 CCP
BUS PRO BUS A BUS PRO BUS B CBF AB
(N Diemeter)
IED I/O
BPU
Bus B
CCP

Level 500 kV One Half Breaker


Bus A
Station LAN IEC 61850: Ethernet 100 Mbps Fiber Optic single ring
Q0A
switch Bay switch switch
switch
switch
switch
switch
switch
switch
Q0AB
OHL
OHL
MPU 2 CCP 2
Diameter
BCU A BCU AB BCU B
Trafo
BCU 150 kV AVR RST
Trafo
MPU1 BPU1 CCP1
Trafo
MPU2 BPU2
BUSBAR
BUSPRO Bus A Main 1 BUSPRO Bus B Main 1 CBF AB1
(n diameter)
BUSBAR
BUSPRO Bus A Main 2 BUSPRO Bus B Main 2 CBF AB2
(n diameter)
COMMON
IED I/O
Q0B Bus B
MPU 1
CCP 1
CCP2

Penambahan Bay Baru dan Up Grade RTU


Gateway Station Unit 1 Station Unit 2
Switch
Switch
Switch
Switch
Switch
IED I/O
MPU BPU-1 BPU-2
BCU AVR
Bay Trafo Baru

Penambahan Diameter, Unit Pembangkit dan IBT

Station Level
HMI Station Unit :
Server redundant Fungsi SCADA, historikal data dan statistik Server berfungsi un
tuk manajemen dari IED dan workstation.

Gateway Dapat menampung IED sesuai kapasitas I/O Dapat meneruskan perintah kontr
ol dari Master station atau lokal kontrol. Inverter 110 VDC ke 220 VAC.

Peralatan Yang Diakusisi SOGI


1. Pemutus (CB): a. Status & perintah open-close b. Counter of circuit Breaker c
. Pressure (SF6) d. Alarm gangguan (misal: SF6 alarm)
CB untuk transmisi
Kontrol box CB
Indicator alarm tekanan SF6 (berupa kontak saja)
Transducer: tekanan SF6 ke 4-20 mA untuk monitor SF6 Pressure

Peralatan Yang Diakusisi SOGI


2. Pemisah (DS/isolator) a. Status & perintah open-close b. Alarm gangguan

Peralatan Yang Diakusisi SOGI


3. Sakelar pentanahan (Earthing Switch) a. Status & perintah open-close b. Alarm
gangguan

Peralatan Yang Diakusisi SOGI


4. Lightning Arrester
Lightning Arrester dengan counter
Lightning Arrester tanpa signal untuk SOGI

Peralatan Yang Diakusisi SOGI


5. Transformator (Daya & Inter Bus Transformator)
a. Tap position indication dari OLTC b. Counter pengoperasian OLTC c. Temperatur
e winding & oil d. Transformer electromechanical protection (level alarm maupun
trip) e. Sistim pendinginan f. Early Warning System g. Alarm gangguan

Peralatan Yang Diakusisi SOGI


6. Counter operasi OLTC
Counter operasi OLTC
OLTC Motor Drive Unit

Peralatan Yang Diakusisi SOGI


7. Automatic Voltage Regulator
Automatic Voltage Regulator
Kontrol panel

Peralatan Yang Diakusisi SOGI


8. Panel distribusi tegangan menengah 20kV a. Status dari Circuit Breaker, Earth
ing Switch, posisi CB rack in-rack out. b. Kontrol CB c. Alarm gangguan d. Pengu
kuran besaran-besaran listrik
Penyulang 20kV dengan IED
IED Kontrol & proteksi

Peralatan Yang Diakusisi SOGI


9. Ruang kendali GITET/GI Temperatur & Kelembaban
Ruang kendali GI
IED sensor kelembaban dan suhu

Peralatan Yang Diakusisi SOGI


10. Sistim SOGI
Control centre
IEC 60870 101 -5Time synchr (optional)
Log.IN1 1100
ICCP/TASE 2
Control centre Lokal HMI
F1 F2
1530 1530
1503 Log.IN2 Log.IN3 1530 2173
>1
2173
8888
Log.Out1
Ethernet IEC 60870-5-104 (eksisting) IEC 60870-5-103 (eksisting) IEC 60870-5-101
LFC Modbus (temperatur & kelembaban)
IEC 61850

Kesimpulan
Sertifikasi uji fungsi dari PUSLITBANG Kepuasan pengguna Pembangunan terpadu per
alatan Gardu Induk dengan SOGI Audit spesifikasi teknik, proses lelang dan pengu
jian Performance terbaik yang terpasang di PLN ALSTOM agar mengganti/memperbaiki
PLC T390, PLC 5000 dan PACIS