FUNGSI

SEBAGAI PENGAMAN UTAMA ATAU CADANGAN


UNTUK GANGGUAN HUBUNG SINGKAT
FASA FASA
FASA TANAH

APLIKASI
PENGAMAN UTAMA
JTM ( DISTRIBUSI )
GENERATOR ( Kapasitas kecil )
TRAFO DAYA ( Kapasitas kecil )
MOTOR
SEBAGAI PENGAMAN CADANGAN

PENGERTIAN

RELAI ARUS LEBIH


SUATU RELAI YANG BEKERJANYA
BERDASARKAN ADANYA KENAIKAN
ARUS YANG MELAMPAUI NILAI
SETTINGNYA .

JENIS RELAI ARUS LEBIH

NON DIRECTIONAL
DIRECTIONAL
KONTROL TEGANGAN
PENAHAN TEGANGAN

KARAKTERISTIK
@ ARAH
1. TIDAK BERARAH ( NON DIRECTIONAL )
2. BERARAH ( DIRECTIONAL )

@ ARUS WAKTU
1. TANPA TUNDA ( MOMENT = INSTANT )
2. TUNDA WAKTU ( TIME DELAY )
# DEFINITE ( TERTENTU ) = INDEPENDEN
# INVERSE ( I t BERBANDING TERBALIK )
= DEPENDEN

SI / NI = Standard / Normal Iverse


VI
= Very Inverse
EI
= Exteremely Inverse
LTI
= Long Time Invers

KARAKTERISTIK INSTANT = MOMENT


t

t SET
I SET MOMENT

KARAKTERISTIK TUNDA WAKTU


TERTENTU ( DEFINITE TIME )
t

t SET

I SET

KARAKTERISTIK TUNDA WAKTU


INVERSE
t

t SET

I SET

KARAKTERISTIK KOMBINASI INSTANT


DENGAN TUNDA WAKTU TERTENTU
(DEFINITE TIME )
t

t SET

I SET

I SET MOMENT

KARAKTERISTIK KOMBINASI INSTANT


DENGAN TUNDA WAKTU INVERSE
t

I SET

I SET MOMENT

TIPE PLUNGER
KONTAK
PLUNGER

PEGAS
0.6

BELITAN

0.8
1.0
1.2
INTI LUAR

SETTING

Fe = GAYA ELEKTROMEKANIK
Fp = GAYA PEGAS

Fe < Fp
Fe > Fp

DROP OFF
PICK UP

TIPE KWH
L U
2

L
2
KUMPARAN LAGGING

PIRINGAN

Is
KUMPARAN UTAMA

SETTING ARUS DAN WAKTU

TAP SETTING

TAP / PLUG SETING


KUMPARAN
UTAMA

ARUS DARI
CT

KONTAK DIAM

TIME DIAL SETTING


DENGAN MENGATUR
JARAK KONTAK

KONTAK GERAK

TIPE RELAI STATIK

A CT

SUPLAI DC

RECTIFIER

R
SETTING

Vin

LEVEL
DETECTOR

Vo
RELAI
BANTU

V REF V IN V O 0 ( Pickup )
V REF V IN V O 0 (Re set )

BLOK DIAGRAM RELAI ARUS LEBIH STATIK


CURVE
SHAPER

FILTER

CS
Ia
Ib
Ic

MAX
I
GATE
&
RECT.

LD
1

Is
INSTANT
LD = LEVEL DETECTOR
T = TIMER
R = REGULATOR
SETTING
INSTANT
IBA DOC

Is
LD
2

LD
3

RL
3

RL
1

HS OUTPUT
RELAY

STATIC OVER CURRENT RELAY


MCGG

OUTPUT
DRIVER
HS

TIME / CURRENT
OUTPUT RELAY
TIME
0.4/0

INTERPOSSING
CT

FULLWAVE
RECTIFIER

MICRO
COMPUTER

INPUT

A/D

0.2/0
0.2/0
0.1/0
0.05/0
0.05/0.025
TMS SWITCH SETTING

16/0
8//0
4//0
2/0
1/0

0.2/0.1
0.4/0
0.8/0
0.2/0
0.4/0
CURRENT SETTING

HIGH SET SWITCH


SETTING

CURVE SELECT SWITCH


IBA DOC

RELAI
OCR / GFR
TIPE
MCGG 82

E
INST

t
I > Is

IS IN

xt
I INST

Is

INST

t
I > Is

IS IN

xt

NAME
PLATE

RESET

KARAK
TERISTIK

I INST

Is

IBA DOC

PRINSIP SETTING OCR

Iset Tunda waktu


* Is = k In

* Plug Setting

IBA DOC

In = Arus Nominal
k = Faktor pabrik ( 1 s/d 2 )
atau 0,05 s/d 2,4 dengan
step 0.05

# Waktu kerja
* Definite ( Langsung atau dengan Tms )
* Inverse ( Td atau Tms dan Mps = I / Is )
t

tk

Tms ( td )

Mps = 4 x Is

IBA DOC

Td = Time dial setting


Tms = Time multiple seting
Mps = Multiple plug setting
. X Is

x Is

# Is instant ( moment )
* Is instant = k In atau
k Is
In = Arus Nominal
Is = Arus setting tunda waktu
k = Faktor pabrik
* Plug setting

IBA DOC

@ SETTING ARUS OCR /GFR DENGAN TUNDA WAKTU

IBA DOC

ARUS SETTING

ARUS NOMINAL RELAI

FAKTOR PABRIK

0.1
0.1
0.2
0.4
0.4
0.4
0.8

0.05
0
0
0
0
0
0

# MISAL ARUS SETTING Is = 6 A.


Is = 1.2 In
POSISI SAKLAR :

0.1
0.1
0.2
0.4
0.4
0.4
0.8

IBA DOC

0.05
0
0
0
0
0
0

Is = ( 0.1 + 0.1 + 0.2 + 0 + 0 + 0 + 0.8 ) x 5A


= 1,2 x 5A
= 6A

PEMILIHAN KARAKTERISTIK

SI

VI

EI

LTI

D2

D4

D8

0
0
0

1
0
0

0
1
0

1
1
0

0
0
1

1
0
1

0
1
1

TRIP TEST :

0
0
0

IBA DOC

CURVA SI :

1
1
1

0
0
0

1
1
1

KURVA / KARAKTERISTIK

@ STANDARD / NORMAL INVERSE ( SI )

0 ,14
t 0 , 02
tms
I
1
@ VERY INVERSE ( VI )

13 , 5
t
tms
I 1
@ EXTREMELY INVERSE ( EI )

80
t 2 tms
I 1
@ LONG TIME INVERSE ( LTI )

120
t
tms
I 1
IBA DOC

SETTING WAKTU

MISAL :

KARAKTERISTIK EI
ARUS GANGGUAN 3 x Is ( I = 3 )
WAKTU KERJA = 1 DETIK

PEMILIHAN TMS :

I 2 1
32 1
tms
tk
1 0,1 det ik
80
80

POSISI SAKLAR

0,025
0
0
0
0
0

0,05
0,05
0,1
0,2
0,2
0,4

IBA DOC

SETTING INSTANT

I S inst 18 A
IS 6 A
18
6 3
I S inst I S

POSISI SAKLAR
0
0
0
0
0
0

1
2
4
8
16

IBA DOC

SAMBUNGAN ( WIRING )

OCR

PMT

R
P1

OCR
S

S1

GFR
E

T
OCR

CT
S2

P2

3 Buah OCR
1 Buah GFR

IBA DOC

SAMBUNGAN ( WIRING )

PMT

OCR
R

P1

GFR
E

S1

T
OCR

CT
S2

P2

2 Buah OCR
1 Buah GFR

IBA DOC

PENGUJIAN RELAI ARUS LEBIH


1.

PENGUJIAN INDIVIDUAL
MENGUJI INDIVIDU RELAI ITU SENDIRI , UNTUK
MENGETAHUI
APAKAH MASIH DALAM KEADAAN STANDAR ATAU TIDAK

2.

PENGUJIAN FUNGSI
MENGUJI FUNGSI DARI SISTEM PROTEKSI
SECARAKESELURUHANAPAKAH MASIH BERFUNGSI ATAU
TIDAK

PENGUJIAN INDIVIDUAL

HAL HAL YANG PERLU DIPERHATIKAN :


1.
2.
3.
4.
5.
6.

CARA SETTING
INTERNAL DIAGRAM RELAI
ALAT UJI / RANGKAIAN PENGUJIAN
ITEM PENGUJIAN
PROSEDUR PENGUJIAN
HASIL UJI DAN KESIMPULAN

JENIS / ITEM PENGUJIAN

1.

ARUS PICK UP DAN ARUS DROP OFF


SERTA
RASIO ARUS PICK UP DENGAN DROP OFF

2.

KARAKTERISTIK ARUS WAKTU

3.

KARAKTERISTIK INSTANTANEOUS

1.

ARUS PICK UP [ ARUS AWAL / MULA ]


ARUS MINIMUM YANG MENYEBABKAN RELAI BEKERJA

2.

ARUS DROP OFF [RESET/ KEMBALI ]


ARUS MAKSIMUM YANG MENYEBABKAN RELAI TIDAK BEKERJA.

3.

RASIO ARUS PICK UP DENGAN DROP OFF

KD

ID
100%
IP

I pick up
I reset
I beban
t
t gangguan

PENGUJIAN INDIVIDUAL
RELAI ARUS LEBIH

21
22
23
24
25
26
27
28

TIMER
START

STOP
220 Vac
R
A

220 Vac

SLIDE

TRAFO ISOLASI

RANGKAIAN PENGUJIAN

29
30

13
14

Vdc

(+)
KONTAK
OCR/GFR

DIAGRAM
KONTROL DC

(+)

RELAI
BANTU
RE 1
(-)

TRIP PMT

(+)

RE 2

RELAI
BANTU
RE 3

(-)

ALARM

RANGKAIAN SIGNALISASI

(+)

KONTAK
RELAI
RESET

TEST LAMP

RELAI BANTU
RE

LAMPU
SIGNAL

SETTING OCR
GANGGUAN FASA FASA [ TUNDA WAKTU

I SEI min

k S I max
.....[ 1]
kD

I SET max 0 ,8 I HS 2 min ....[ 2 ]


I SET min I SET max I SET I SET min
I SET max I SET min I SET I SET max
k S 1,1 1, 2
k D 80 %
I max arusbeban max .

KOORDINASI OCR
# DEFINITE TIME

I SC I SB I SA I HS
tC t B t A
t 0 , 4 0 , 5 det

1,3 det
0,8 det
0,3 det
I

KOORDINASI OCR
# INVERSE TIME
SETING WAKTU DENGAN PEMILIHAN TD / TMS
TD = TIME DIAL
TMA = TIME MULTIPLE SETTING

TMS A

TMS B

TMS C

SETTING ELEMEN INSTANTANEOUS

DIMAKSUDKAN UNTUK GANGGUAN 3 FASA ,TETAPI HARUS


MEMPERHATIKAN ARUS KETAHANAN KABEL .

I HS 2 min I SET 1 I HS 3 min


I SET 2 I kemampuank abel
SETTING INSTANT

I SET1 I SET2 I SET I SET1


I SET2 I SET1 I SET I SET2

KOORDINASI OCR
# INSTANTANEOUS

I SET inst . A 1, 2 I HS 3 B
I SET inst . B 1, 2 I HS 3 C

KOORDINASI DARI RELAI KOMBINASI TUNDA WAKTU


DENGAN INSTANT /
A

tA
tB
t INST

t INST

tC
I

TMS B

TMS A

t INST

TMS C

t INST

SETTING GFR
[RELAI GANGGUAN TANAH ]

PERLU DIPERHATIKAN ;
1.
2.
3.
4.

SISTEM PENTANAHAN TITIK NETRAL


BESARNYA ARUS HUBUNG SINGKAT SATU FASA
KE TANAH .
ARUS KETIDAKSEIMBANGAN BEBAN
ARUS KAPASITANSI JARINGAN .

SISTEM PENTANAHAN DENGAN TAHANAN RENDAH


3

PADA SKTM SPINDEL


BATAS MINIMUM ADALAH RELAI PADA SALURAN
YANG SEHAT TIDAK BOLEH BEKERJA OLEH ARUS
KAPASITANSI 3 I OR

I SET GFR 1, 3 3 I OR
#

PADA SUTM
SAMA SEPERTI DI SKTM

@ SISTEM PENTANAHAN LANGSUNG [ SOLID ]

KARENA ARUS GANGGUAN BESAR , KRITERIA SETTINGNYA


SEPERTI PADA RELAI PENGAMAN ANTAR FASA .
TETAPI BATAS MINIMUMNYA LEBIH KECIL DARI ARUS
BEBAN , TETAPI LEBIH BESAR DARI ARUS KETIDAKSEIMBANGAN
BEBAN .

@ SISTEM MENGAMBANG
1.

RELAI TEGANGAN NOL


RELAI INI TIDAK BOLEH BEKERJA BILA TERJADI
PERGESERAN TEGANGAN NOMINAL

3VO 0,3V Nom


2.

RELAI GANGGUAN TANAH BERARAH


[ DIRECTONAL GFR ]

@ SISTEM PENTANAHAN DENGAN TAHANAN TINGGI


RELAI YANG DIGUNAKAN ADALAH DGFR .
RELAI OCR SEBAGAI GFR TIDAK DAPAT DIPAKAI .
KARENA ARUS GANGGUAN SATU FASA KETANAH
LEBIH KECIL DARI ARUS KAPASITANSI .