STC = Standard Test Condition


=
1.irradiance 1000 W/m2 atau
1kW/m2
2.module temperature 25C
3.1.5 AM

SOLAR PV ENERGY

Irradiance
= Sun radiation
= Solar Power
Intensity in an area
Unit : kW/m2

Irradiation
= Insolation
= Energy in an area
mmmmmm
Unit : kWh/m2

INSOLATION MAP

Cara Design Sistem Solar PV


Offgrid
(sederhana)
1. Menentukan konsumsi energi harian oleh beban
2. Menghitung energi yang harus disediakan oleh
batere dengan memasukkan autonomy day
3. Menentukan ukuran batere, solar PV, dan BCR
(battery charge controller)

BCR
Beban

PV
Batere

Contoh : Rumah Sederhana di


Kupang
(Asumsi PSH = 4.5)

No
.

Alat

Jumla
h
(unit)

Teganga
n (V)

Day
a
(W)

Operasi
Harian
(h)

Konsumsi
Energi (Wh)

Lampu

12

10

120

Kipas
Angin

12

25

12

300

Konsumsi Energi Harian Total

420

Menentukan Ukuran Batere


(Asumsi autonomy day = 3)

Batere untuk aplikasi solar PV adalah


batere tipe khusus, biasa tipe OPzV
atau OPzS, atau minimal tipe gel
Disarankan Depth of Discharge
70% supaya batere bisa awet
Kapasitas batere untuk 1 hari
= 420Wh / 70% = 600Wh
Kapasitas batere untuk 3 hari
= 3 x 600Wh = 1800Wh = 12V 150Ah

Menentukan PV Modul
Dari konsumsi harian 420Wh, dan
asumsi losses di PV modul 10% karena
debu dan proses degradasi, ukuran PV
Modul menjadi
= (420 / 4.5) x (100% + 10%) =
102.67Wp
100 Wp

Menentukan ukuran BCR


Tegangan kerja BCR = 12V
Arus yg harus bisa dihandle oleh BCR
= 1.25 x 6.53A = 8.16A 10A (tipe umum)
Spec PV modul :

http://www.victronenergy.com/upload/documents/Datasheet-BlueSolar-Monocrystalline-Panels-EN.pdf

Dimensi Lengkap Sistem PV

BCR
10A 12V
PV
100Wp
12V

Beban
Lampu 12V, 10W x 2@6jam
Batere Kipas angin 12V, 20W x 1@12jam
12V 150Ah