FIXTURE SCHEDULE

NO.

DESCRIPTION

W.

PLUMBING LEGEND
C.W.

H.W.

GAS
-

15" TO RIM

17" TO RIM

MOUNTING HEIGHTS

SYMBOL
F-1

WATER CLOSET - FLOOR OUTLET, MANUAL 1.28 GPF FLUSH

4"

1"

F-2

WATER CLOSET - FLOOR OUTLET, HC ACCESSIBLE, MANUAL 1.28 GPF FLUSH

4"

1"

F-3

URINAL, MANUAL 0.125 GPF

2"

3/4"

22" TO RIM

F-4

URINAL - HC ACCESSIBLE, MANUAL 0.125 GPF

2"

3/4"

16" TO RIM

F-5

WASH FOUNTAIN, MANUAL 0.5 GPM

2"

3/4"

F-6

LAVATORY, HC ACCESSIBLE, MANUAL 0.5 GPM

1-1/2"

1/2"

1/2"

F-7

ELECTRIC WATER COOLER - STUDENT

2"

1/2"

F-8

ELECTRIC WATER COOLER - HC ACCESSIBLE - STUDENT

2"

1/2"

F-9

MOP SINK (FLOOR TYPE)

3"

1/2"

1/2"

F-10

SINK, ART ROOM - SINGLE W/ PLASTER TRAP

1-1/2"

1/2"

1/2"

SINK, ART ROOM - DOUBLE W/ PLASTER TRAP

1-1/2"

1/2"

1/2"

F-12

SINK, SCIENCE / PREP ROOM (FITTINGS ONLY)

1-1/2"

1/2"

1/2"

F-13

SINK, SCIENCE / TEACHER (FITTINGS ONLY)

1-1/2"

1/2"

1/2"

1/2"

SINK, SCIENCE / STUDENT (FITTINGS ONLY)

F-15

S.,W. OR R.W. ABOVE FL. OR GRADE

SWRW

S.,W. OR R.W. BELOW FL. OR GRADE

KD

COLD WATER PIPING

HW

HOT WATER PIPING

CLEANOUT

GV

GATE VALVE

UN

UNION

FD/KD

HUB DRAIN

DS

DOWNSPOUT

1/2"

1/2"

EMERGENCY SHOWER / EYE WASH

3"

1-1/4"

F-16

ICE MAKER CONNECTION BOX

3/8"

F-17

HOSE BIBB IN RECESSED BOX

1/2"

SA

BP
WHYD

ROOF HYDRANT

F-18

3/4"

SHOCK ABSORBER

NO.

QUAN.

RECOVERY

INPUT

STORAGE

VOLTS / PH.

LOCATION

MODEL

EWH-1

10 GPH @ 80 DEG. R

2 KW

10 GAL.

120 / 1

P12.1 - H110

A.O. SMITH DEL-10

EWH-2

1 GPM @ 61 DEG. R

9 KW

N/A

277 / 1

P12.1 - H130

EX90

EWH-3

1 GPM @ 61 DEG. R

9 KW

N/A

277 / 1

P12.1 - H129

EX90

EWH-4

10 GPH @ 80 DEG. R

2 KW

10 GAL.

120 / 1

P12.2 - J110

A.O. SMITH DEL-10

EWH-5

1 GPM @ 61 DEG. R

9 KW

N/A

277 / 1

P12.2 - J113

EX90

EWH-6

1 GPM @ 61 DEG. R

9 KW

N/A

277 / 1

P12.2 - J113

EX90

EWH-7

1 GPM @ 61 DEG. R

9 KW

N/A

277 / 1

P12.1 - J137

EX90

EWH-8

1 GPM @ 61 DEG. R

9 KW

N/A

277 / 1

P12.1 - J136

EX90

VB

VACUUM BREAKER

CI

CAST IRON

T.R.

THROUGH ROOF

ABV

ABOVE

CLG

CEILING

FL

FLOOR

DN

DOWN

INV.

INVERT ELEVATION

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303

6. ROOF PENETRATIONS FOR PIPING SHALL BE MADE WITH FLASHED IN ROOF


PIPE BOOTS, OR ROOF CURBS CAPPED WITH PIPE BOOTS, WITH STAINLESS
STEEL BANDS, BY THE PATE CO., ROOF PRODUCTS AND SYSTEMS OR EQUAL.
DO NOT USE PITCH POCKETS.

P 404.522.8888
F 404.521.6204
www.STEVENS-WILKINSON.com

8. PLUMBING CONTRACTOR SHALL VIDEO TAPE SEWER LINES WITHIN THE


BUILDING TO VERIFY THAT ALL LINES HAVE BEEN RODDED OUT AND ARE
CLEAN. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
9. MATERIALS EXPOSED WITHIN CONCEALED AIR PLENUM SYSTEMS ARE REQUIRED
TO BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAS INDEX OF NOT MORE
THAN 25 AND A SMOKE DEVELOPED INDEX OF NOT MORE THAN 50 AS DETERMINED
IN ACCORDANCE WITH ASTM E 84 EXCEPT FOR TESTED AND LABELED WIRING,
FIRE SPRINKLER PIPING, PNEUMATIC TUBING, AND ELECTRICAL EQUIPMENT
(IBC SECTIONS 716.5 AND 1017.4.1; IMC SECTION 602.2.1.)

WALL HYDRANT
SLEEVE

ELECTRIC WATER HEATER SCHEDULE

4. COORDINATE LOCATIONS OF ACCESS PANELS REQUIRED IN CEILINGS, WALLS,


ETC. SO THAT ACCESS PANELS WILL NOT INTERFERE WITH LIGHTING OR
ARCHITECTURAL ARRANGEMENTS, AND WILL AFFORD PROPER ACCESS TO
MECHANICAL EQUIPMENT WHICH REQUIRES ADJUSTMENTS OR SERVICE.

BACKFLOW PREVENTER

2. SPACE ABOVE THE CEILING IS LIMITED. COORDINATE PLUMBING & FIRE


PROTECTION WORK, ETC. WITH ALL OTHER TRADES.

7. DO NOT RUN PLUMBING PIPING BELOW ANY HVAC EQUIPMENT. SPACE TO


REMAIN CLEAR FOR EQUIPMENT REMOVAL. SEE DETAIL 4 ON M4.1 .

NON FREEZE HOSE BIBB

SHOCK ABSORBER WITH PDI SIZE

SA-"A"

1. SEE ELECTRICAL DRAWINGS FOR VOLTAGE OF ALL EQUIPMENT. DO NOT


ORDER ANY ELECTRICALLY POWERED EQUIPMENT UNTIL ELECTRICAL
CHARACTERISTICS HAVE BEEN COORDINATED WITH THE ELECTRICAL
CONTRACTOR.

5. COORDINATE LOCATION OF ALL FLOOR AND HUB DRAINS REQUIRED FOR


MECHANICAL EQUIPMENT TO ENSURE PROPER LOCATION.

FLOOR DRAIN / KITCHEN DRAIN

HD

(APPLICABLE TO ALL DRAWINGS)

3. CONTRACTOR SHALL NOT CUT ANY STRUCTURAL MEMBERS OF BUILDING


WITHOUT PRIOR APPROVAL. COORDINATE HANGING OF EQUIPMENT WITH
STRUCTURAL DRAWINGS.

HOT WATER CIRCULATING PIPING

CO

NFHB

1-1/2"

VENT PIPING

CW

HWC

F-11

F-14

SWRW

FD

DESCRIPTION

ABBREV.

GENERAL NOTES:

GAS PIPING

T.P.S.

TRAP PRIMER SUPPLY

T.P.V.

TRAP PRIMER VALVE

(SIM.)

S.I.M.

SIMILAR LAYOUT

(O.H.)

O.H.

OPPOSITE HAND LAYOUT

TMC

TMC

TEMPERATURE MAINTENANCE CABLE

BCV

BALANCE CONTROL VALVE

_______ _____________

NOTE: THERE IS NO STORAGE CAPACITY FOR WATER HEATERS EWH-2, EWH-3, EWH-5, EWH-6, EWH-7, & EWH-8

SUBMITTALS

SHOCK ABSORBER SCHEDULE


ABSORBOTRON TYPE NO.

DESCRIPTION

DATE

5005

5010

5020

5030

5040

5050

P.D.I. SYMBOLS

FIXTURE-UNIT RATING

1-11

12-32

33-60

61-113

114-154

155-330

8/15/2014
9/12/2014
9/16/2014
10/03/2014

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

NOTE: SMITH NUMBERS SHOWN, EQUAL - JOSAM, ZURN, OR LONES.

REVISIONS
DATE

DESCRIPTION

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION
THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.
UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

c STEVENS & WILKINSON GA, INC. 2012

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

10/6/2014 6:38:27 AM

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

FULTON COUNTY
BOARD OF
EDUCATION

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

PLUMBING
SCHEDULES

P01.0

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303
P 404.522.8888
F 404.521.6204
www.STEVENS-WILKINSON.com

1
P12.1

CLASSROOM
CLASSROOM
CLASSROOM
FF110

A.9

CLASSROOM

FF109

FF113

CLASSROOM

SCIENCE LAB

SCIENCE LAB

CLASSROOM

FF106

FF115

FF114

LECTURE

D.7

F658

35.7

FF112

CLASSROOM
B.9
C

D
D.2

FF111

I.R.R. SPECIAL
ED
G106
I.R.R. SPECIAL
ED
G105
S.I.I.R.
SPECIAL ED
G104

33.9

CLASSROOM

E
E.1
5

SCIENCE LAB

SCIENCE LAB

FF104

FF117

E.8
35.1

35.6

34.1

33.4

FAMILY LIVING
SUITE

CLASSROOM

CW

37.5

CLASSROOM

FF119

SUBMITTALS

KITCHEN

G102

FF120

G2

G1

EE119

EE120

EE121

FF121

FF101

4"

CW (E)

CW (E)
4"

3"

CLASSROOM
EE117

CLASSROOM
EE111

FOREIGN
E.S.O.L.
LANGUAGE RM
G7
G6

SCIENCE LAB SCIENCE LAB

CLASSROOM

EE106

EE110

CLASSROOM
T.A.G.

READING
ROOM

G8

G13

CW (E)

CW (E)

EE115

3"

FOREIGN
LANGUAGE RMFOREIGN
LANGUAGE RM
G5
G3

SCIENCE LAB SCIENCE LAB

EE112

EE104

G101

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

FAMILY &
CONSUMER
SCIENCE LAB

BUSINESS ED
G11

REVISIONS
DATE

DESCRIPTION

G9

EE114

I. S. S. ROOM

EE113

BD SPECIAL
ED

CLASSROOM

8/15/2014
9/12/2014
9/16/2014
10/03/2014

CW (E)

CLASSROOM
T.A.G.

CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM
CLASSROOM

DESCRIPTION

DATE

CAFETERIA

G12
CLASSROOM
G10

4
CW
3"
5

CLASSROOM
CLASSROOM T.A.G.
EE102
EE101

CLASSROOM
CLASSROOM
EE109

EE108

CLASSROOM
T.A.G.

CLASSROOM

STRINGS

G121

G101

G15

U.1

CW (E)

CLASSROOM
G120

35

U.5

CLASSROOM

SCIENCE LAB

SCIENCE LAB

G117

G104

V.1

G102

ENG/TECH.
LAB

CLASSROOM

G18

GYM
G14

G103

V.5
W.4
W.45
CW
W.6

CHORAL

W
5

W.5

CLASSROOM

SCIENCE LAB

SCIENCE LAB

CLASSROOM

G114

G115

G106

G108

G4

W.8
X
X.5
X.6

CLASSROOM

CLASSROOM

G113

G109

X.8

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION
THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.
UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

CLASSROOM
CLASSROOM
CLASSROOM

G112

G111

G110

Y.5

ART

BAND

G17

G16

c STEVENS & WILKINSON GA, INC. 2012

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

Z
Z.5
1
P12.2
39.2
39

37.2
38

36.1
35.9 35.5

37

34.9

34.2

33.8
33.7
34

36

32.5
33

31.5
31
32

PROJECT
NORTH

D.9
1

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

P11.0

10/3/2014 5:41:57 AM

FULTON COUNTY
BOARD OF
EDUCATION

LEVEL 1 - OVERALL PLAN


1" = 30'-0"

KEYED NOTES

(THIS SHEET 0NLY)

APPROXIMATE LOCATION OF EXISTING DOMESTIC WATER SERVICE


ENTRANCE.

APPROXIMATE LOCATION OF EXISTING 4" CW MAIN ABOVE CEILING. FIELD


VERIFY EXACT LOCATION.

APPROXIMATE LOCATION OF EXISTING 3" CW MAIN ABOVE CEILING. FIELD


VERIFY EXACT LOCATION.

CONNECT NEW 3" COLD WATER LINE TO EXISTING 3" MAIN ABOVE CEILING.
PROVIDE BALL VALVE AT CONNECTION ON NEW LINE. FIELD VERIFY EXACT
LOCATION OF MAIN.

PROVIDE NEW 3" CW TO NEW ADDITIONS. FIELD VERIFY ROUTE BEFORE


STARTING WORK. REMOVE AND REPLACE CEILING TILES AS REQUIRED.

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

PLUMBING OVERALL
FLOOR PLAN

P11.0

38

37.5

37

35.7 35.6

35.1

34.3 34.2

32.5

33.4

31

31.5

3/4" NFHB
6

17

A.9

STUDY

F-14

12

F-14

F667.1
F-14

11

F-14

F-14

3"
F-14

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303

CLASSROOM TAG
F667
A

SCIENCE LAB

F666
CW

F-14

www.STEVENS-WILKINSON.com

6
A

F-13
B.9

P 404.522.8888
F 404.521.6204

2
P30.2

CLASSROOM

FF109
7

F-14
4"

10

PREP ROOM
2"

F666.1

STOR.

24

STOR.

F664

F-15

F-12

F665.1

23
1/2"
CW
11

CLASSROOM

3/4"

F665

10

CLASSROOM SP. ED

CLASSROOM SP. ED

F654

F652

3"

CORRIDOR

CLASSROOM

F662

FF108
27

D.2

CORRIDOR
F661

F660

4"

CW

TEAM PLAN

6"

LECTURE

F658

D.8

D.7

STOR.

STOR.

F663.1

F656

26

CORRIDOR

35.2

22

19

F650

4"

2-1/2"

CORIDOR

12

15

F640
CW

25

4"V A/C

1-1/2"

F-7

F-8

SUBMITTALS

3"

DESCRIPTION

DATE

E.2

TOILET

F663

STUDY

STOR.

F663.2

F659

F-2

F657

F-6

F-1

F-1

F-2

F-2

F-1

CW

CLASSROOM TAG

F-4

3/4"
F-17

F-9

18

CW

F-5

IDF

ELEC

F643

F641

CONFERENCE
F103

F-17
F-3

F-5

1-1/2"

16

8/15/2014
9/12/2014
9/16/2014
10/03/2014

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

STOR.
F102.1

E.8

REVISIONS
DATE

JANITOR

GIRL'S RESTROOM

F655

F653

1
P30.1

DESCRIPTION

BOY'S RESTROOM
20

21

F651

6"

CLASSROOM
FF102

CW

15
6"

3"
PROJECT
NORTH

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION

14

THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.


UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

CW (E)
3"

13

3"

38

32.5

37

10/6/2014 6:10:12 AM

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

P12.1

DEMO NOTES

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

1/8" = 1'-0"

(THIS SHEET 0NLY)

REMOVE EXISTING ACID DILUTION BASIN, CONCRETE SUPPORT, AND ACCESS


COVER. FILL VOID TO RECEIVE NEW PIPING.

APPROXIMATE LOCATION OF EXISTING 4" ACID WASTE LINE BELOW FLOOR


TO REMAIN.

13

APPROXIMATE LOCATION OF EXISTING 3" CW MAIN ABOVE CEILING.


FIELD VERIFY LOCATION. SEE SHEET P11.0.

EXISTING ACCESS COVER TO BE RETURNED TO OWNER.

APPROXIMATE LOCATION OF EXISTING WASTE AND / OR SANITARY DRAIN


LINE BELOW FLOOR TO REMAIN.

14

CONNECT NEW 3" COLD WATER LINE TO EXISTING 3" MAIN ABOVE CEILING.
PROVIDE BALL VALVE AT CONNECTION ON NEW LINE.

EXISTING 3" VENT RISER TO BE REMOVED. CAP LINE ABOVE CEILING.

PROVIDE NEW PIPE SECTION WHERE EXISTING ACID DILUTION BASIN


IS REMOVED.

15

REMOVE AND REPLACE CEILING TILES AS REQUIRED FOR PIPE INSTALLATION.

16
4

CONNECT NEW 4" SANITARY LINE TO EXISTING 6" MAIN AT INVERT OF


1092.75'. FIELD VERIFY PIPE LOCATION AND EXISTING PIPE ELEVATION
BEFORE STARTING PIPE RUN.

3/4" H/CW TO EWH-1. HEATER TO BE LOCATED ABOVE JANITORS SINK.


SEE DETAIL 1 ON P40.1.

17

3/4" CW DN. TO 3/4" NFHB AT 24" ABOVE GRADE.

SEE SHEETS A1.11 AND A5.11 FOR ROOM LAYOUT.

18

1-1/2" CW & 3/4" HW DN. SEE WATER RISER W-1 ON P50.0.

2" WASTE & VENT, PROVIDE CONNECTION TO SINK.

19

2" CW DN. SEE WATER RISER W-2 ON P50.0.

3" VENT UP THROUGH ROOF.

20

3/4" CW DN. SEE WATER RISER W-2 ON P50.0.

PROVIDE 3" HUB DRAIN WITHIN SINK CABINET. SEE DETAIL 4 ON P40.2.

21

1-1/2" CW DN. SEE WATER RISER W-3 ON P50.0.

3" SHOWER DRAIN (SD-1).

22

2" CW DN. SEE WATER RISER W-3 ON P50.0.

10

2" VENT DN. & UP

23

CONDENSATE RECEIVER ABOVE CEILING. SEE DETAIL 2 ON P40.1.

11

3" FLOOR CLEANOUT WITH SQUARE TOP.

24

3" WASTE DN. AND 3" VENT UP.

12

4" FLOOR CLEANOUT WITH SQUARE TOP.

25

4" VENT UP THROUGH ROOF. SEE SHEET P12.3 FOR ROOF PLAN.

FULTON COUNTY
BOARD OF
EDUCATION

31.5 31

FLOOR PLAN - ADDITION 1

KEYED NOTES

(THIS SHEET 0NLY)

c STEVENS & WILKINSON GA, INC. 2012

26

3/4" CW UP TO ROOF HYDRANT. SEE DETAIL 5 ON P40.1 AND ROOF PLAN ON P12.3.

27

APPROXIMATE LOCATION OF EXISTING MAIN SEWER LINE TO REMAIN.

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

PLUMBING FLOOR
PLAN - ADDITION 1

P12.1

CONFERENCE
E103
2

CLASSROOM

CLASSROOM

EE109

CORIDOR

EE108

D760

17

CLASSROOM T.A.G.

STOR.

CLASSROOM

D762

EE102

CLASSROOM T.A.G.

EE101

G121
6"
100 PEACHTREE STREET NW, SUITE 2500
ATLANTA, GA 30303
P 404.522.8888
F 404.521.6204
www.STEVENS-WILKINSON.com

STOR.

STOR.

D764

E102.1

U
4"

U.2

CW (E)
F3.0A
F3.0A

CW

F6.0

F5.5

F5.5

CLASSROOM

4"

G120

U.5

STUDY

ELEC.

D763.2

D761

GIRL'S RESTROOM

BOY'S RESTROOM

D754

D752

2
2
P30.1
F6.0

JANITOR
22

D756

F6.0

24

F4.5

F5.5
18

V.1

CLASSROOM TAG

STOR.

STOR.

D763

D763.3

20

F-9

F-3 F-3 F-3

F-5
F-17

3/4"

D120.1

F-5

CONFERENCE

F-17

D119

IDF

2"

STOR.

D744
30

F5.5

F4.5

TOILET
F4.5

F6.5

V.5

F-1

F-6
F-2
F6.0

D758

F-1 F-1

29 F-2

F-2

F-1

F-1

D742
F3.0A

F-4

1-1/2"

W.4

STUDY

STOR.

CORRIDOR

D765.1

D763.1

D750

FIN. FL. 1098.33'

28

4"S
4"V A/C

34.5

21

2-1/2" A/C

F-7

F-8

23

2-1/2"

3" A/C

4"

CW
4

4"FCO
F5.5

F3.0A

27
8/15/2014
9/12/2014
9/16/2014
10/03/2014

D765

STOR.
T/FTG. = -2' - 8"

?
F5.5

F5.5

STOR.

D751.1

D741.1

3/4"

CLASSROOM

D741

T/FTG. = -1' - 0"

DATE

F6.5

F6.5
CW
26

D767.1

D767

16

TEAM PLAN
D753.1

STOR.
D767.2
4"FCO

STOR.

F4.5

1/2"

LECTURE

19

DESCRIPTION

3"

3/4" NFHB

REVISIONS

G114

CLASSROOM
CW

CW

D751

1-1/2"

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

CLASSROOM

CLASSROOM

F5.5
T/FTG. = -2' - 0"

F6.5

W.5

W.8

DESCRIPTION

DATE

F6.5
INV. 1095.79'

CLASSROOM TAG

W.6

SUBMITTALS

CW

4"

25

1/2"

CW
F5.5

F-11
1/2"

3/4"

D767.3

26

25

CLASSROOM

STOR.

2"

F5.5

11

D753

D753.2
F6.5
INV. 1096.37'

2"

ART/ LECTURE
D743.1
3"FCO

X.5
8
F-14

6
3"

PREP ROOM

X.6

F-12
2"

F6.5

14
F-15 T/FTG. = -2' - 8"
13

F-14

D769.1

F6.5

9
2"

D743

F-13

F-14

D755.1

2"

SCIENCE LAB
7

D755

STUDY

11

2"

31

CLASSROOM

F-14

12
11

ART LAB

D753.3

G113

11
2"

2"
10

9
14

F-14

T/FTG. = -2' - 8"


STUDY

CLASSROOM

15
F4.5

F-10

F-14

ART/ STUDY

D769

STOR.
9

F6.0
F-14

F5.5

D743.2

D755.2
F5.5

3"FCO

F6.5

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION

F6.0

F-14

STUDY

Y.5

THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.


UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

D757.1
F5.5

c STEVENS & WILKINSON GA, INC. 2012

1
P30.2

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

CLASSROOM

CLASSROOM

D759

D757

KEYED NOTES

F4.5

(THIS SHEET 0NLY)

APPROXIMATE LOCATION OF EXISTING 4" ACID WASTE LINE


BELOW SLAB TO REMAIN.

17

NEW 3" COLD WATER SUPPLY LINE ABOVE CEILING.


SEE P11.0 FOR CONTINUATION.

APPROXIMATE LOCATION OF EXISTING WASTE AND / OR


SANITARY DRAIN LINE. FIELD VERIFY IF REQUIRED.

18

3/4" H/CW TO EWH-4. HEATER TO BE LOCATED ABOVE


JANITORS SINK. SEE DETAIL 1 ON P40.1.

PROVIDE NEW PIPE SECTION WHERE EXISTING ACID DILUTION


BASIN IS REMOVED.

19

3/4" CW DN. TO 3/4" NFHB AT 24" ABOVE GRADE.

20

1-1/2" CW & 3/4" HW DN. SEE WATER RISER W-4 ON P50.0.

PROVIDE NEW CLEANOUT FOR INSIDE BUILDING FLOOR


CONDITION.

21

2" CW DN. SEE WATER RISER W-5 ON P50.0.

22

3/4" CW DN. SEE WATER RISER W-5 ON P50.0.

23

2" CW DN. SEE WATER RISER W-6 ON P50.0.

24

2" CW DN. SEE WATER RISER W-6 ON P50.0.

25

3" CONDENSATE RECEIVER ABOVE CEILING. SEE DETAIL 2


ON P40.1.

26

3" WASTE DN. & 3" VENT UP. SEE DETAIL 2 ON P40.1.

27

3/4" CW UP TO ROOF HYDRANT. SEE DETAIL 5 ON P40.1


AND ROOF PLAN ON P12.3.

28

4" VENT UP THROUGH ROOF. SEE ROOF PLAN ON P12.3.

29

1/2" TRAP PRIMER SUPPLY LINE TO FLOOR DRAIN. SEE


DETAIL 3 ON P40.2.

30

1/2" TRAP PRIMER SUPPLY TO FLOOR DRAIN IN JANITORS


ROOM. SEE DETAIL 1 ON P40.2.

31

SEE SHEETS A1.12 AND A5.12 FOR ROOM LAYOUT.

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

Z.5

F6.0

39.2

37.2

36.1
35.9

F6.0

35.5

34.9

10/6/2014 8:25:55 AM

T/FTG. = -2' - 0"

39

P12.2

33.8
33.7

32.5

FLOOR PLAN - ADDITION 2

31.5 31

CONNECT NEW 4" SANITARY LINE TO EXISTING 4" MAIN AT


EXISTING INVERT OF 1095.13'. FIELD VERIFY PIPE LOCATION
AND EXISTING PIPE ELEVATION BEFORE STARTING PIPE RUN.

4" WASTE AT INV. 1096.93'.

SEE SHEETS A1.12 AND A5.10 FOR ROOM LAYOUT.

3" WASTE DOWN THROUGH FLOOR. SEE DETAIL 7 ON P40.1.

2" WASTE & VENT, PROVIDE CONNECTION TO SINK.

10

RUN WASTE HEADER ABOVE FLOOR IN CHASE. SEE


DETAIL 7 ON P40.1.

11

3" VENT UP THROUGH ROOF.

12

PROVIDE 3" HUB DRAIN WITHIN SINK CABINET. SEE DETAIL 4


ON P40.2.

13

3" SHOWER DRAIN (SD-1).

14

2" VENT DN. & UP

15

1/2" CW DN. TO SINK AND WATER HEATER EWH-6. SEE


DETAIL 4 ON P40.1.

16

1/2" CW DN. TO SINK AND WATER HEATER EWH-5. SEE


DETAIL 4 ON P40.1.

1/8" = 1'-0"

DEMO NOTES

(THIS SHEET 0NLY)

REMOVE EXISTING ACID DILUTION BASIN, CONCRETE SUPPORT, AND ACCESS


COVER. FILL VOID TO RECEIVE NEW PIPING.

EXISTING ACCESS COVER TO BE RETURNED TO OWNER.

EXISTING 3" VENT RISER TO BE REMOVED. CAP LINE ABOVE CEILING.

FULTON COUNTY
BOARD OF
EDUCATION

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

PLUMBING FLOOR
PLAN - ADDITION 2

P12.2

GAS REGULATOR SCHEDULE

PROVIDE SERVICE REGULATOR TO


REDUCE PRESSURE FROM 4.5 PSI
TO 7" W.C. SEE SCHEDULE.
PROVIDE SERVICE REGULATOR TO
REDUCE PRESSURE FROM 4.5 PSI
TO 7" W.C. SEE SCHEDULE THIS
SHEET.

SEE ROOF PLAN


FOR CONT.

SEE SPECIFICATIONS
FOR PIPE SUPPORT
TYPE & MATERIAL
G

REGULATOR
NO.

ROOF

GAS FIRED EQUIP.

LOAD
CFH

WATER TIGHT
ROOF SLEEVE
SEE ROOF PLAN
FOR CONTINUATION

FULL SIZE DRIP LEG.

INLET
PRESSURE

OUTLET
PRESSURE

INLET
SIZE

OUTLET
SIZE

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303

REMARKS

P 404.522.8888
F 404.521.6204

GAS COCK

ROOF

REDUCE TO EQUIP. CONNECTION SIZE

SEE SPECIFICATIONS
FOR PIPE SUPPORT
TYPE & MATERIAL

UNION

GAS COCK

(THIS SHEET ONLY)

GAS SUPPLY TO SCIENCE LABS.


SEE FLOOR PLAN FOR
CONTINUATION.

195

4.5 PSI

7"WC

1"

1"

SEE NOTE

100

4.5 PSI

7"WC

1"

1"

SEE NOTE

100

4.5 PSI

7"WC

1"

1"

SEE NOTE

100

4.5 PSI

7"WC

1"

1"

SEE NOTE

www.STEVENS-WILKINSON.com

UNION

CEILING
4
P12.3

RTU GAS SUPPLY DETAIL

40

A.9

GAS SUPPLY DETAIL

3A

1" = 30'-0"

P12.3

38 37.5 37

39

35.7
35.6
36

35.1
35

34.3
34.2 34

33

33.4

32.5

1" = 30'-0"

3231.5

B
3"VTR
3"VTR

B.9

3
C

3"VTR
G
5
34.2

D.2

1"

10
D.8

35.2

SUBMITTALS

E.2
4"VTR

E.8
35.7
35.6

35.2
35.1

34.3

8/15/2014
9/12/2014
9/16/2014
10/03/2014

33.4
G

37.5

DESCRIPTION

DATE

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

2
1-1/4"
1

REVISIONS

DATE

3"
K

G (E)

G (E)
G

DESCRIPTION

1-1/2"

1-1/2"

G (E)

U.2

U
37.2

U.5
V
4"VTR

1-1/4"

V.5
W.4

7
34.5

W.6

V.1

W.5

W
APPROVED FOR CONSTRUCTION
NOT APPROVED FOR CONSTRUCTION

10

W.8

3"VTR

X
3"VTR

X.5
X.6

c STEVENS & WILKINSON GA, INC. 2012

Y
1"

3"VTR

3"VTR

THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.


UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

Y.5

FULTON COUNTY
BOARD OF
EDUCATION

Z.5

39.2

10/3/2014 5:43:01 AM

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

40

39

37.2
38

37

36.1
35.9 35.5
36

34.9

33.8
33.7

35

34

32.5
33

31.5
32 31

1
P12.3

ROOF - OVERALL
SCALE: 1" = 30'-0"

KEYED NOTES

GAS PIPE SUPPORT REQUIREMENTS:


1. GAS PIPING SHALL BE SUPPORTED ON ABS PLASTIC PILLOW BLOCKS EQUAL TO
MIRO INDUSTRIES AT SPACING NOTED BELOW. PROVIDE STRAP ATTACHMENTS OF
PIPE TO PILLOW BLOCKS. PROVIDE ADDITIONAL ROOFING CAP SHEET WEARING
SURFACE. ADHERED TO THE PRIMARY CAP SHEET WITH RECOMMENDED ROOFING
BITUMEN "SPOTS". DO NOT ADHERE THE PILLOW BLOCKS TO THE WEARING
SURFACE CAP SHEET MATERIAL.
2. PROVIDE PIPE SUPPORT WITHIN 1'-0" OF EACH TEE CONNECTION, 90^ HORIZONTAL
ELBOW AND AT EACH PIPE DROP OR RISE.
3. PROVIDE PIPE SUPPORTS AT THE FOLLOWING SPACING LIMITS
6 FT. ON CENTER FOR 1/2" PIPE
8 FT. ON CENTER FOR 3/4" & 1" PIPE
10 FT. ON CENTER FOR 1-1/4" & LARGER PIPE

(THIS SHEET 0NLY)

APPROXIMATE LOCATION OD EXISTING GAS MAIN SUPPLY. FIELD VERIFY


EXACT LOCATION AND PIPE SIZES.

CONNECT NEW 1-1/2" GAS TO EXISTING 3" MAIN. PROVIDE SHUTOFF VALVE
AT NEW BRANCH LINE SUPPLY.

RUN NEW GAS MAIN ON ROOF. PROVIDE PIPE SUPPORT. SEE PIPE SUPPORT
REQUIREMENTS.

PROVIDE GAS SUPPLY TO ROOFTOP HVAC UNIT. SEE DETAIL 3 THIS SHEET.

1-1/2" GAS SUPPLY DN. TO SCIENCE LABS. SEE DETAIL 3 THIS SHEET.

GAS REGULATOR R-1 FOR RTU. SEE SCHEDULE ON THIS SHEET.

GAS REGULATOR R-2 FOR RTU. SEE SCHEDULE ON THIS SHEET.

GAS REGULATOR R-3 FOR SCIENCE LABS. SEE SCHEDULE ON THIS SHEET.

GAS REGULATOR R-4 FOR SCIENCE LABS. SEE SCHEDULE ON THIS SHEET.

10

3/4" ROOF HYDRANT. SEE DETAIL 5 ON P40.1.

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

PLUMBING ROOF
PLAN

P12.3

3"
2"
100 PEACHTREE STREET NW, SUITE 2500
ATLANTA, GA 30303

2"
WF

P 404.522.8888
F 404.521.6204

www.STEVENS-WILKINSON.com

2"
3"

UR

V.1
V.1

2"

JANITOR

UR
UR

3"

UR

3"FD

4"

2"

2"

D756

WC

F-5

2"

3"
EWC

WC

2"

EWC
WC

F-6
TOILET

3"FD

2"

D752

WC

3"FD

BOY'S RESTROOM

3"
9

4"

4"VTR

F-3

D754

F-9

WC

3"

F-3

GIRL'S RESTROOM

2"
3"CO

F-3

F-5
2

WC

WF

F-2

F-2

F-1

F-2

F-1

F-1

F-1

D758

WC

F-1

F-4
6

V.5
V.5

3"

2"

SS

LAV

10

W.4
W.4
W.45

4"WCO

F-7

F-8

34.5

WC
2"
34.2

4"

33.8
33.8
33.7

34

WASTE RISER DIAGRAM

S-2
P30.1

32.5

33

TOILET PART PLAN - ADDITION 2

2
P30.1

N.T.S.

SUBMITTALS

1/4" = 1'-0"

DESCRIPTION

DATE

8/15/2014
9/12/2014
9/16/2014
10/03/2014

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

REVISIONS
DATE

34.3

32.5

33.4

M3A A S

M3A A S

F-7

F3A B

F-8

F3A B

E.2

TOILET

C4A A

C8A A

3"
F-6

2"
4"

TA-07/08
5

F-2
F-1

F3A A

M3A A

EWC

F-1

F-2

F-1

TA-6

TA-6

UR

GIRL'S RESTROOM
3"FD

3"

2"

F-9

WC
WC

4"WCO

WC

3"FD

3"

M3A A

2"

WF

F-5TA-11a

TA-10

TA-1

TA-2
2

JANITOR

F651

TA-10

C8A A

TA-1

2"

3"

BOY'S RESTROOM

F3A A

UR

F653

WF

TA-1

F-3

TA-11a
F-5

TA-1 TA-2

M3A A S

F655
E.8

WC

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION

3"CO

WC

2"

C4A B

WC

3"

F-4

3"

EWC

3"

TA-07/08

F-2

3"

4"VTR

4"

C8A A S

F657

3"

4"

C4A A

M3A A S 8

DESCRIPTION

2"

C4A B
THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.
UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

c STEVENS & WILKINSON GA, INC. 2012

LAV
2"

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

SS
3"FD
1
P30.1

S-1

10/3/2014 5:43:24 AM

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

P30.1

TOILET PART PLAN - ADDITION 1


1/4" = 1'-0"

FULTON COUNTY
BOARD OF
EDUCATION

WASTE RISER DIAGRAM


N.T.S.

KEYED NOTES

(THIS SHEET 0NLY)

3" FLOOR DRAIN (FD-1) WITH TRAP PRIMER SUPLY.

3" FLOOR DRAIN (FD-2) WITH TRAP PRIMER SUPPLY.

4" CLEANOUT WITH SQUARE TOP.

4" SANITARY LINE BELOW FLOOR. SEE FLOOR PLAN FOR CONTINUATION.

2" WASTE & VENT STACK FOR FIXTURE.

3" VENT STACK UP.

4" VENT ABOVE CEILING. SEE FLOOR PLAN FOR CONTINUATION.

4" WALL CLEANOUT.

3" CLEANOUT WITH SQUARE TOP.

10

4" WALL CLEANOUT

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

PLUMBING PART
PLANS

P30.1

39.2

37.2

SEE SHEET P12.2


FOR CONTINUATION

X.5

EWH-8

1
F-15

ICE MAKER
CONN. BOX

CW

G-2

SINK
1-1/4"

www.STEVENS-WILKINSON.com

1"

3/4"

1/2"

SINK

F-12

P 404.522.8888
F 404.521.6204

CW

X.6

1/2", TYP.

11

F-16 1/2"

F-14

F-14

CW

SINK

SINK

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303

1-1/2"

1/2"

3/4"

3/4"

G-2

CW

1-1/2"

F-14

CW

1/2"
F-14

SINK

1/2"

PREP ROOM

7
F-13

CW

SINK

EWH-7

3/4"

CW

G-2

LAB SHUTOFF
VALVE BOX

1/2"

3/4"

G-1
CW

EMER. SHWR./
EYE WASH

D769.1

G-2
F-14

10

F-14
7

SCIENCE LAB
D769
1/2"

G CW

SINK

1/2"

G-2

G-2
7

SINK
F-14

F-14

1/2", TYP.
Y.5

SUBMITTALS

SINK

DESCRIPTION

DATE

SINK

L-2
P30.2

8/15/2014
9/12/2014
9/16/2014
10/03/2014

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

LAB RISER DIAGRAM


N.T.S.

KEYED NOTES
SCIENCE CLASSROOM - ADDITION 2

1
P30.2

1/4" = 1'-0"

34.3 34.2

(THIS SHEET 0NLY)

1-1/4" CW DN. TO EMERGENCY SHOWER / EYE WASH. SEE DETAIL 5 ON P40.2.

3/8" CW TO WATER OUTLET BOX (F-16) FOR REFRIGERATOR.

1/2" CW DN. TO SINK AND HOT WATER HEATER. SEE DETAIL 4 ON P40.1.

3/4" GAS AND 1" CW DN. IN WALL TO CONTROL BOX.

RECESSED CONTROL BOX (LAB SHUTOFF VALVES). SEE DETAIL 6 ON P40.2.

3/4" GAS & 1" GAS UP. EXTEND TO GAS OUTLETS AND SINK FAUCETS AS SHOWN.

1/2" GAS AND COLD WATER DN. TO GAS OUTLETS AND SINK FACUETS. SEE
ARCH. PLANS FOR GAS OUTLET AND SINK LOCATIONS.

1/2" GAS AND 1/2" CW TO SINK AND WATER HEATER AT TEACHERS WORK STATION.

PROVIDE CONNECTIONS TO SINK, WATER HEATER AND GAS OUTLET WITHIN


SINK CABINET.

10

SEE ARCH. DRAWING FOR SCIENCE LAB AND PREP ROOM LAYOUTS.

11

3/4" GAS UP TO ROOF. SEE P12.3 FOR CONTINUATION.

REVISIONS
DATE

DESCRIPTION

A.9
A.9
B

1/2"

F-14

F-14

F-14

F-14

3/4"
F-14

CW
G
1/2"

SINK

1/2"

SINK
1/2", TYP.

F-14

SINK
CW

C
G W

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION

SCIENCE LAB
3/4"

F666

THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.


UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

SINK

10

7
c STEVENS & WILKINSON GA, INC. 2012

G
CW
G

EWH-3
B.9
B.9
C
C

CW
G

ICE MAKER
CONN. BOX

F-13
1"

CW

SINK
4

1/2"

SINK
LAB SHUTOFF
VALVE BOX

PREP ROOM

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

EMER. SHWR./
EYE WASH

11

1/2"

F-16

1/2", TYP.

EWH-2
2

1"

HOPEWELL
MIDDLE SCHOOL
ADDITION

F-15
1-1/4"

F-12

Alpharetta, Georgia
L-1
P30.2

SEE SHEET P12.1


FOR CONTINUATION

LAB RISER DIAGRAM


N.T.S.
35.7
35.6
35.6

10/6/2014 5:55:31 AM

F-14

F666.1

SINK

CW

1-1/4"

FULTON COUNTY
BOARD OF
EDUCATION

3/4"

1-1/2"

SINK

CW

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

F-14

35.2

2
P30.2

35.1
35.1
35

SCIENCE CLASSROOM - ADDITION 1


1/4" = 1'-0"

34.1 33.9

PLUMBING PART
PLANS

P30.2

STRAINER
PROVIDE PRV EQUAL TO
WATTS MODEL 26A, SET
OUTLET AT 10 PSI
PROVIDE BRACING
1/2"
UNION
COLD WATER MAIN
SEE FLOOR PLANS
PROVIDE 2' x 2'-2" AIRTIGHT
SHEETROCK BOX AROUND
P-TRAP. SEAL ALL PIPE
PENETRATIONS WITH
FIRE CAULK.

24 VOLT ELECTRONIC SOLENOID TYPE


TRAP PRIMER WITH BUILT-IN AIR GAP,
SEE SPECIFICATIONS. TRANSFORMER
AND WIRING BY OTHERS.

WATS 36A
VACUUM BREAKER

12" MIN.

3/4" SEE FLOOR PLAN


FOR CONTINUATION

FLEXCON MODEL WH-8


EXPANSION TANK

SHOCK ABSORBER - SEE


PLAN OR RISER FOR SIZE

CONDENSATE DRAIN LINE BY MECH.


CONTRACTOR. SEE MECH. DRAWINGS
FOR LOCATION

CEILING

12"

1/2"

T&P RELIEF
1/2" H/CW

2" AIR GAP

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303
P 404.522.8888
F 404.521.6204

PROVIDE ACCESS PANEL


IF NOT LAY-IN CEILING

3" VENT THROUGH ROOF


(NOTE: SOME LOCATIONS
MAY NOT GO THROUGH ROOF)

CHASE

www.STEVENS-WILKINSON.com

SIZE OF SHOCK
ABSORBER CONNECTION

HANG WATER HEATER


ABOVE JAN. SINK

8"

EXTEND RELIEF DISCHARGE AND


DRAIN LINE FROM PAN DN. TO SINK

COLD WATER LINE


(HEADER) IN CHASE
PIPE CHASE

SERVICE SINK

1-1/2" MAX.

3" WASTE - SEE FLOOR


PLANS & RISER DIAGRAM
FOR LOCATIONS
FIN. FLOOR

CEILING
FLOOR

PROVIDE 3" P-TRAP WITH HEEL TAP


FOR TRAP PRIMER SUPPLY
PROVIDE 2' x 2' EGG-CRATE GRILLE
FOR ACCESS TO P-TRAP

3
P40.1

1
P40.1

SHOCK ABSORBER DETAIL


N.T.S.

NOTE:
PROVIDE BOX AT RETURN AIR CEILING CONDITIONS, TYP.

WATER HEATER DETAIL


N.T.S.

2
P40.1

TYPICAL CONDENSATE RECEIVER DETAIL


N.T.S.

SUPPLEMENTAL ANGLE
SUPPORTS
ATTACHED TO STRUCTURE

PLUMBING & SPRINKLER


PIPING ABOVE WSHP
SUBMITTALS
DESCRIPTION

DATE

NON-FREEZE
ROOF HYDRANT

PLUMBING & SPRINKLER


PIPING ABOVE WSHP

8/15/2014
9/12/2014
9/16/2014
10/03/2014

F-18
FAUCET FLOW
CONTROL "L"

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

REVISIONS

INSTALL PER MANUFACTURERS


REQUIREMENTS
HOT OUTLET

DATE

MOUNT HP 2'-0" MAX


ABOVE CEILING
(ALLOW FOR
CLEARANCE
SHOWN HATCHED)

DESCRIPTION

COLD OUTLET

ROOF
CEILING 9'-0" A.F.F.
(UNLESS
OTHERWISE
NOTED)

INLINE FLOW CONTROL "I"


3/8" COPPER TUBING

MOUNTING FLANGES (4)

CONDENSATE DRAIN PIPING

SERVICE CLEARANCE,
DO NOT RUN PIPING
BELOW WSHP

INSTANT-FLOW HEATER
1/2" THREE WAY
ANGLE STOP VALVE

CORRIDOR

HORIZONTAL WATER SOURCE HEAT PUMP,


SEE MECH. PLANS FOR LOCATIONS

HOT

3/4"CW, SEE FLOOR PLANS


FOR CONTINUATION

COLD

JUNCTION BOX

COLD WATER INLET MAIN

FLOOR

5
COMPRESSION FITTINGS (2)

P40.1

ROOF HYDRANT

CLASSROOM

N.T.S.

INSTANT FLOW WATER HEATER

4
P40.1

N.T.S.
6
P40.1

CORRIDOR COORDINATION DETAIL


N.T.S.

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION
THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.
UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

c STEVENS & WILKINSON GA, INC. 2012

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

3" VTR

2"

SINK

2"

SINK

2"

2"

SINK

2"

FULTON COUNTY
BOARD OF
EDUCATION

SINK

2"

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

3"
3" WASTE HEADER, RUN ABOVE
FLOOR IN CHASE BEHIND CABINETS
3" WALL CLEANOUT

7
P40.1

WASTE HEADER DETAIL

3"W BELOW FLOOR

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

N.T.S.

10/6/2014 8:22:40 AM

PLUMBING DETAILS

P40.1

STRAINER
STRAINER

PROVIDE PRV EQUAL TO


WATTS MODEL 26A, SET
OUTLET AT 10 PSI

PROVIDE PRV EQUAL TO


WATTS MODEL 26A, SET
OUTLET AT 10 PSI

WALL
UNION

COLD WATER
MAIN

UNION

LAVATORY

24 VOLT ELECTRONIC SOLENOID TYPE


TRAP PRIMER WITH BUILT-IN AIR GAP,
SEE SPECIFICATIONS. TRANSFORMER
AND WIRING BY OTHERS.

COLD WATER
MAIN

TYPICAL FOR SINKS

PROVIDE DISTRIBUTION UNIT


ON WALL AT 48" AFF.

J.R. SMITH FIG. 2698


TRAP PRIMER P-TRAP
1/2" COLD WATER
TO TRAP PRIMER
FITTING

24 VOLT ELECTRONIC SOLENOID TYPE


TRAP PRIMER WITH BUILT-IN AIR GAP,
SEE SPECIFICATIONS. TRANSFORMER
AND WIRING BY OTHERS.

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303

FLOOR DRAIN
FLOOR SLAB

1/2" TRAP PRIMER


SUPPLY LINES. SEE
PLAN FOR QUANTITY

WALL ESCUTHEONS

1-1/2"
FLOOR SLAB
CAULK INTO HUB
DRAIN

FLOOR DRAIN

12"

COLD WATER
TO TRAP PRIMER
FITTING

TRAP PRIMER
CONNECTION
ON DRAIN BODY

FL/ERD

www.STEVENS-WILKINSON.com

FLOOR

HUB DRAIN
SEE FLOOR PLAN
FOR SIZE

TRAP PRIMER
CONNECTION
ON DRAIN BODY

4
P40.2

TRAP PRIMER DETAIL - SINGLE UNIT

P40.2

P 404.522.8888
F 404.521.6204

FLOOR SLAB

TRAP PRIMER
CONNECTION
ON DRAIN BODY

NOTE: WHERE WASTE TO HUB


DRAIN IS SHOWN ON DRAWING,
OMIT P-TRAP AND PROVIDE
STRAIGHT TAILPIECE EXTENSION
TO DRAIN

N.T.S.

P40.2

2
P40.2

HUB DRAIN CONNECTION


N.T.S.

TRAP PRIMER DETAIL


N.T.S.

TRAP PRIMER DETAIL


N.T.S.

SUBMITTALS
DESCRIPTION

DATE

8/15/2014
9/12/2014
9/16/2014
10/03/2014

50% CD
90% CD
DOE CHECK SET
100% CD / DOE FINAL

REVISIONS
DATE

PROVIDE PRV EQUAL TO WATTS


MODEL 26A, SET OUTLET AT 10 PSI

SA-"B"

ABOVE CEILING
TO LAB FIXTURES

ABOVE CEILING
FROM SERVICES

STRAINER
1/2" CW UP STREAM
OF MAIN SHUT-OFF
UNION

DESCRIPTION

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION

1"

1-1/4" CW A/C

THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.


UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

1"

24 VOLT ELECTRONIC SOLENOID TYPE


TRAP PRIMER WITH BUILT-IN AIR GAP,
SEE SPECIFICATIONS. TRANSFORMER
AND WIRING BY OTHERS.

c STEVENS & WILKINSON GA, INC. 2012

PIPING IN WALL
3/4"

3/4"

CEILING

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

SHR.

22-1/2"

24"

CEILING PLATE
TURN BALL VALVES SO DOOR
WILL CLOSE WHEN VALVE IS
TURNED OFF.

WATER

PROVIDE RECESSED VALVE BOX


EQUAL TO KARP MODEL KRVB
WITH 3/4" TRIM FLANGE. DOOR
TO HAVE KNOB TURN. BOX TO
BE 16 GA. WITH 14 GA. DOOR.
BOX TO BE 4" DEEP.

GAS

6'-0"

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

22-1/2"

F-15

24"

UNION, TYP.
EYEWASH
1/2" TPS IN WALL

GAS SOLENOID VALVE


EQUAL TO ASCO MODEL 8215G30. VALVE TO
BE NORMALLY CLOSED 24 VOLT AC OPERATED.
SEE ELECTRICAL DETAIL 6/EP3.3 FOR WIRING
CONNECTIONS AND LOCATION OF SWITCHES.

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

TURN DRAIN OUTLET FACING FD.


SECURE BASE TO FLOOR
3"FD-1

FIN. FLOOR

FIN. FLOOR

10/3/2014 5:44:01 AM

PROVIDE BAKELITE
PLASTIC LABELS

FULTON COUNTY
BOARD OF
EDUCATION

5
P40.2

EMERGENCY SHOWER / EYEWASH DETAIL


N.T.S.

6
P40.2

LAB SHUTOFF DETAIL


N.T.S.

PLUMBING DETAILS

P40.2

1-1/2"
3/4" CW
2-1/2"

2-1/2" CW
3" CW

1-1/2"

1-1/2"
2"

2"

SA-D

SA-D

1-1/2"

100 PEACHTREE STREET NW, SUITE 2500


ATLANTA, GA 30303

3/4"
3/4"

1-1/2"

1-1/2"

P 404.522.8888
F 404.521.6204

1-1/2"

SA-B
WC

www.STEVENS-WILKINSON.com

3/4"
EWH-1

WC

UR

2" HEADER

WC

WC

SA-B
WC

LAV

UR

WF

3/4" HB

2" HEADER

WC

WF

1-1/2"

1-1/2"
3/4"

1/2"

3/4" HB

W-3
P50.0

SS 1/2"

WATER RISER DIAGRAM

W-2
P50.0

N.T.S.

WATER RISER DIAGRAM

W-1
P50.0

N.T.S.

WATER RISER DIAGRAM


N.T.S.

SUBMITTALS
DESCRIPTION

DATE

9/12/2014
9/16/2014
10/03/2014

90% CD
DOE CHECK SET
100% CD / DOE FINAL

REVISIONS

3/4"

DATE

3/4"

DESCRIPTION

1-1/2"

3/4"
2"
EWH-4

2-1/2"
2"
3/4" HB

SA-C

1-1/2"

3/4" HB

3/4"

3/4"

WF

2-1/2"

SA-_B

1-1/2"
WF

2-1/2"
2"

UR

UR

SA-D
WC

SS

WC

UR
UR

1-1/2"

3" CW

SA-D

1-1/2"

1-1/2"

WC

WC

WC

WC

LAV

WC

1/2"
1-1/2"
WC

2" HEADER

1/2"
2" HEADER
EWC
EWC

W-6
P50.0

1/2"

WATER RISER DIAGRAM


N.T.S.

W-5
P50.0

WATER RISER DIAGRAM


N.T.S.

W-4
P50.0

WATER RISER DIAGRAM


N.T.S.

APPROVED FOR CONSTRUCTION


NOT APPROVED FOR CONSTRUCTION
THIS DRAWING IS THE PROPERTY OF STEVENS & WILKINSON GA, INC.
UNAUTHORIZED USE OF ANY KIND, INCLUDING USE ON OTHER
PROJECTS, IS PROHIBITED.

c STEVENS & WILKINSON GA, INC. 2012

PROJECT NUMBER:
13043.00
PROJECT DATE:
10/03/2014

10/3/2014 5:44:10 AM

C:\Users\charlie\Documents\13043.00
Hopewell-PLBG_V14_charlie.rvt

FULTON COUNTY
BOARD OF
EDUCATION

HOPEWELL
MIDDLE SCHOOL
ADDITION
Alpharetta, Georgia

PLUMBING RISER
DIAGRAMS

P50.0