Anda di halaman 1dari 1

Penstock Sizing

Existing Penstock :
Flow
MGD

m3/Sec

Say

Size (SQ)

Area

Velocity V
= Q/A

30

1.578

1.6

900

0.81

2.0

15

0.789

0.8

900

0.81

1.0

Remarks

* It seems it has been designed for two penstocks to be kept open for 30 mgd flow, to get less
velocity 1 m/sec

Penstock Sizing For The New P/S


By Single Penstock :
Flow
MGD

m3/Sec

Say

Size (SQ)

Area

40
40
40
40
40
40
40

2.104
2.104
2.104
2.104
2.104
2.104
2.104

2.1
2.1
2.1
2.1
2.1
2.1
2.1

900
1000
1100
1200
1300
1400
1500

0.81
1.0
1.21
1.44
1.69
1.96
2.25

Velocity V
= Q/A
2.6
2.1
1.7
1.5
1.2
1.1
0.9

Remarks

**

** We have to select 1500 Sq penstock if we use one penstock closed condition for 40 mgd
By Sharing Two Penstocks :
Flow
MGD

m3/Sec

Say

Size (SQ)

Area

20
20
20
20

1.052
1.052
1.052
1.052

1.1
1.1
1.1
1.1

900
1000
1100
1200

0.81
1.0
1.21
1.44

Velocity V
= Q/A
1.4
1.1
0.9
0.8

Remarks

***

*** It is suggested to select 1100 Sq penstock at two penstocks opened condition, for 40 mgd.
(still it is fully submerged condition)