ANSI Standard
Short-Circuit Analysis
Types of SC Faults
Three-Phase Ungrounded Fault
Three-Phase Grounded Fault
Phase to Phase Ungrounded Fault
Phase to Phase Grounded Fault
Phase to Ground Fault
Fault Current
IL-G can range in utility systems from a few percent to
possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all
faults).
In industrial systems the situation IL-G > I3-phase is rare.
Typically IL-G
.87 * I3-phase
Slide 2
Purpose of Short-Circuit
Studies
A Short-Circuit Study can be used to determine
any or all of the following:
Verify protective device close and latch capability
Verify protective device Interrupting capability
Slide 3
System Components
Involved in SC Calculations
Power Company Supply
In-Plant Generators
Transformers (using negative tolerance)
Slide 4
System Components
Involved in SC Calculations
Overhead Lines (at lower temperature limit)
Synchronous Motors
Induction Motors
Protective Devices
Slide 5
Synchronous Motors
Induction Machines
Lumped Loads
(with some % motor load)
Inverters
I0 from Yg-Delta Connected Transformer
1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI
Slide 6
Slide 7
Short-Circuit Phenomenon
i(t)
v(t)
v(t) Vm Sin( t
Slide 8
v(t)
i(t)
di
v(t) Ri L
Vm Sin( t
) (1)
dt
Solving equation 1 yields the following expression
i(t)
R
- t
Vm
Vm
sin( t
- )
sin( - ) e L
Z
Z
Steady State
Transient
(DC Offset)
Slide 9
DC Current
Slide 10
Slide 11
Machine Reactance ( = L I )
AC Decay Current
Slide 12
Slide 13
ANSI
Slide 14
Models
All sources are modeled by an internal
voltage behind its impedance.
E = Prefault Voltage
R = Machine Armature Resistance
X = Machine Reactance (Xd, Xd, Xd)
1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI
Slide 15
Synchronous Generators
Synchronous Generators are modeled
in three stages.
Induction Machines
Transient Reactance
Subtransient Reactance
Synchronous Reactance
Slide 16
Cycle Network
1 to 4 Cycle Network
This network is used to calculate the interrupting short-circuit current
and protective device duties 1.5-4 cycles after the fault.
30-Cycle Network
This is the network used to calculate the steady-state short-circuit
current and settings for over current relays after 30 cycles.
Slide 17
1 to 4 Cycle
30 Cycle
Xd
Xd
Xd
Xd
Xd
Xd
Hydro-Gen with
Amortisseur
winding
Xd
Xd
Xd
Hydro-Gen without
Amortisseur
winding
0.75*Xd
0.75*Xd
Xd
Xd
Xd
Xd
1.5*Xd
Utility
Turbo Generator
Condenser
Synchronous
Motor
Slide 18
1 to 4
Cycle
Xd
1.5*Xd
Xd
1.5*Xd
1.2*Xd
3.0*Xd
< 50 hp
1.67*Xd
Note: Xd = 1 / LRCpu
Slide 19
1 to 4 Cycle
Currents
(Transient Network)
HV Circuit Breaker
Interrupting
Capability
LV Circuit Breaker
Interrupting Capability
---
Fuse
Interrupting
Capability
SWGR / MCC
Bus Bracing
---
Relay
Instantaneous
Settings
---
---
Slide 20
Momentary Multiplying
Factor
Device Rating
HV CB
Asymmetrical RMS
Crest
C&L RMS
C&L RMS
HV Bus
Asymmetrical RMS
Crest
Asymmetrical RMS
Symmetrical RMS
Asymmetrical RMS
Symmetrical RMS
Asymmetrical RMS
LV Bus
Crest
Slide 21
Interrupting Multiplying
Factor
MFi is calculated based on:
Device Rating
Symmetrical RMS
HV CB
LV CB & Fuse
1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit ANSI
Slide 22
HV CB Closing and
Latching Duty
Calculate Cycle Current (Imom, rms, sym) using Cycle Network.
Slide 23
HV CB Interrupting Duty
Calculate 1 to 4 Cycle Current (Imom, rms, sym) using Cycle Network.
Determine Local and Remote contributions (A local contribution is
fed predominantly from generators through no more than one
transformation or with external reactances in series that is less than
1.5 times generator subtransient reactance. Otherwise the
contribution is defined as remote).
Calculate no AC Decay ratio (NACD) and multiplying factor MFi
NACD = IRemote / ITotal
ITotal = ILocal + IRemote
Slide 24
HV CB Interrupting
Capability
CB Interrupting kA varies between Max kA and Rated kA
as applied kV changes MVAsc capability.
ETAPs comparison between CB Duty of Adj.
Symmetrical kA and CB capability of Adjusted Int. kA
verifies both symmetrical and asymmetrical rating.
Slide 25
LV CB Interrupting Duty
Slide 26
Slide 27
L-G Faults
Slide 28
L-G Faults
Symmetrical Components
Slide 29
Sequence Networks
Slide 30
If
3 Ia 0
If
3 VPrefault
Z1 Z 2 Z0
if Zg
Slide 31
Ia 2
I a1
If
3 VPrefault
Z1 Z 2
Slide 32
I a1 I a 0
VPrefault
Z0 Z 2
Z1
Z0 Z 2
if Zg
0 Ia
Slide 33
Slide 34
Z2 & Z0
Z1
I f1
Slide 35
Slide 36
Slide 37
Slide 38
Slide 39
Slide 40
Length
Adjustments
Cable Length
Transmission
Line Length
Temperature
Corrections
Adjust Fault
Impedance
Transmission
Line Resistance
L-G fault
Impedance
Cable Resistance
Slide 41
Tolerance Adjustments
Z 'Transformer
Z Transformer * (1 Tolerance)
Length'Cable
LengthCable * (1 Tolerance)
Length'TransmissionLine
LengthTransmissionLine * (1 Tolerance)
Slide 42
Temperature Correction
(234 .5 Tc )
R'Copper ' RBASE *
(234 .5 Tb )
(228 .1 Tc )
R' Alumi RBASE *
(228 .1 Tb )
RBASE
R'
Tb
Tc
Slide 43
Transformers
T1 X/R
PS =12
PT =12
ST =12
T2 X/R = 12
Gen1
Voltage Control
Design Setting:
%Pf = 85
MW = 4
Max Q = 9
Min Q = -3
Lump1
Y open grounded
Slide 44
Slide 45
Slide 46
Short-Circuit Alerts
Bus Alert
Protective Device Alert
Marginal Device Limit
Slide 47
Bus SC Rating
Type of Device
Monitored Parameter
Condition Reported
Bracing Asymmetrical
Bracing Crest
Bracing Symmetrical
Bracing Asymmetrical
LV Bus (<1000Volts)
LVCB
Breaking
Momentary C&L
Making
N/A
Breaking
Fuse
Breaking
SPDT
Making
SPST Switches
Making
HV CB
Slide 48
Slide 49
Slide 50