Note
Connect SMRT Binary Inputs (BI):
BI:1 to Relay Output(E2 & F2) for Trip 236
BI:3 to Relay Output(E4 & F4) for Healthy 205 along with isolation by making Q205 MCB to
OFF position.
BI:4 to Relay Output(F5 & F6) for Alarm 194 along with isolation by making Q190 MCB to OFF
position.
BI:5 to Relay Output(F7 & E8) for Trip 245 along with isolation by making Q245 MCB to OFF
position.
BI:6 to Relay Output(F8 & F9) for Warning OK 280 along with isolation by making Q261 MCB
to OFF position.
BI:7 to Relay Output(E11 & F10) for Trip OK 281 along with isolation by making Q261 MCB to
OFF position.