Anda di halaman 1dari 6

Sr. No.

Ibase (%)

Tbase (deg C)

Tau

Ttrip(degC)

Iinj

Talarm(deg c)

Tdreset

90

90

110

2A

90

10

80

90

110

2A

90

10

90

80

110

2A

90

10

80

80

110

2A

90

10

I
p2
Ibase
t = . ln .
2
T T amb
I
trip
Ibase
T base

Where:
P = is Ip/Ibase (ie 0/0.9)=0
Ip = Continuous load current before the current is increased to I (assumed "0")
Tamb = is ambient temperature (fixed to 20 deg)
I = Injected current (ie 2A)
Ibase = Base current (ie 0.9)
Tbase = Temperature rise at base current (ie 90 deg)
Tau = Thermal time constant (ie 2)
t = Time to trip
Ttrip = Trip level (ie 110 deg)

2
0.9

0.9

(
)
(
)
t = . ln .
2
11020

( 0 . 9 ) 90
2

t= . ln (1 . 2539)

t =2 x 0 . 2262

t =2 x 0 . 2262
t=0. 4525min x60
t =27 . 15 sec

T trip (sec)
result
26.7

Time to trip
(t) sec
27.15

20.6

20.92

30.49

31,025

23.39

23.81

Enter the settings and current used during the test in the BLUE fields.
Sr. No.

Ibase (%) Tbase (deg C)

Tau

Ttrip(degC)

Iinj

Ip

Talarm(deg c)

100

70

62

85

83

80

90

110

90

90

80

110

90

80

80

110

90

Tdreset
10

T trip (sec) Trip time expected


result
0
222.41

10

20.92

10

31.02

10

23.81

Anda mungkin juga menyukai