Anda di halaman 1dari 2

DC Power Distributor 6 (DCPD6)

Product Manual (V1.0)

Product Overview
DC Power Distributor 6 (DCPD6) has the following functions:
1) Provides one channel of -48V DC power input and supports a current of not more than
100A;
2) Provides nine channels of DC power output, each of which is controlled by an independent
hydraulic breaker to support a current of not more than 20A;
3) Provides lightning protection and surge protection for the power output through a built-in
lightning protection board;
4)

Provides dry contact alarm output on the lightning protection board.


Figure 1-1 DCPD6 Ports

Specifications
The specifications of DCPD6 are described in Table 2-1.
Table 2-1 DCPD6 Specifications
Characteristics

Specifications

Model

DCPD6

Name

DC Power Distributor 6

Description

9 channels of -48V DC power output, with output lightning


protection; 19 inch cabinet installation; front cabling

Dimension (W*H*D) mm

482.6X43.6X197 (19inch / 1U)

Weight

<5kg

Surge

10KA (8//20us) for wire-wire connections; 15KA


(8//20us) for wire-earth connections

Dry contact definition

A closed circuit indicates that the lightning protection


module is normal. An open circuit indicates that the
lightning protection module fails.

Waterproof/dustproof level

IP20

Operating temperature

-20 ~55

Storage temperature

-40 ~70

Relative humidity

5%-95%

Typical Application
DCPD6 applies to distributed base station systems, in which it powers BBU and RRU. The power
cable of RRU should be shielded and the shielded layer must be connected to the outdoor
grounding bar before being connected into the cabinet or equipment room.
Figure 3-1 DCPD6 Power Distribution

DCPD6 Power Distribution

Outdoor

DC Power input
Indoor

The shielded layer


of RRUs power
cable must be
grounded.

Anda mungkin juga menyukai