Anda di halaman 1dari 12

PROJECT

CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT
LTD.
401_ _LDT001_

TITLE

INSTRUMENT LIST

DOCUMENT NO.

401_ _LDT002_

DGT-000-L-LI-IN-001

REV-A

DATE - 19-10-2012

402_ _LIT001_

SR.
NO.

INSTRUMENT DESCRIPTION

TAG NO.

(A)

FLUID

RANGE

UNIT

SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

PID REFERENCE NO. -- DGT-401-L-DS-PR-001 (INLET/SLIT CHAMBER & CATCH PIT)

DIFFERENTIAL LEVEL TRANSMITTER

SEWAGE

0-1

Mtr

25MM MEDIUM BAR SCREEN CHANNEL

TO START/STOP THE SCREEN AT DIFFERENTIAL LEVELS

0-1m

DIFFERENTIAL LEVEL TRANSMITTER

SEWAGE

0-1

Mtr

25MM MEDIUM BAR SCREEN CHANNEL

TO START/STOP THE SCREEN AT DIFFERENTIAL LEVELS

0-1m

ULTRASONIC LEVEL TRANSMITTER

RAW SEWAGE SUMP


DISCHARGE OF SAMPLING PUMP

TO START/STOP THE PUMPS AT DIFFERENT LEVELS OF SEWAGE IN TANK

TOTAL SUSPENDED SOLID ANALYSER (TSS)

5
6

BIOLOGICAL OXYGEN DEMAND ANALYSER (BOD)


pH ANALYSER

402_ _AI001A
402_ _AI001B
402_ _AI001C

SEWAGE

0-10

Mtr

SEWAGE

0-1000

Mg/l

SEWAGE
SEWAGE

0-500
2 to 14

DISCHARGE OF SAMPLING PUMP


SEWAGE SAMPLING LINE

RAW

DISCHARGE OF SAMPLING PUMP


SEWAGE SAMPLING LINE

RAW

DISCHARGE OF SAMPLING PUMP


SEWAGE SAMPLING LINE

RAW

DISCHARGE OF SAMPLING PUMP


SEWAGE SAMPLING LINE

RAW

Mg/l
pH

CHEMICAL OXYGEN DEMAND (COD) ANALYSER

402_ _AI001D

SEWAGE

0-1000

ppm

TOTAL ORGANIC CARBON (TOC) ANALYSER

402_ _AI001E

SEWAGE

0-1000

ppm

SD-8.45m LWL-7.4m, HWL-4.75m

TO MEASURE THE TSS VALUE AT INLET RAW SEWAGE

0 - 1000 ppm

TO MEASURE THE BOD VALVE AT INLET RAW SEWAGE

0 - 500 ppm

TO MEASURE THE pH VALUE AT INLET RAW SEWAGE

2 - 14 pH

TO MEASURE THE COD VALUE AT INLET RAW SEWAGE

0 - 1000 ppm

TO MEASURE THE TOC VALUE AT INLET RAW SEWAGE

0 - 1000 ppm

TO INDICATE THE DISCHARGE PRESSURE OF RAW SEWAGE PUMP-A

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

402_ _PG001A

SEWAGE

0-6

kg/cm2

RAW
SEWAGE SAMPLING LINE
DISCHARGE OF RAW SEWAGE PUMP-A

10

PRESSURE GAUGE (WITH CHEMICAL SEAL)

402_ _PG001B

SEWAGE

0-6

kg/cm2

DISCHARGE OF RAW SEWAGE PUMP-B

TO INDICATE THE DISCHARGE PRESSURE OF RAW SEWAGE PUMP-B

0 - 6 kg/cm2

11

PRESSURE GAUGE (WITH CHEMICAL SEAL)

402_ _PG001C

SEWAGE

0-6

kg/cm

DISCHARGE OF RAW SEWAGE PUMP-C

TO INDICATE THE DISCHARGE PRESSURE OF RAW SEWAGE PUMP-C

0 - 6 kg/cm2

12

PRESSURE GAUGE (WITH CHEMICAL SEAL)

402_ _PG001D

SEWAGE

0-6

kg/cm

DISCHARGE OF RAW SEWAGE PUMP-D

TO INDICATE THE DISCHARGE PRESSURE OF RAW SEWAGE PUMP-D

0 - 6 kg/cm2

13

PRESSURE GAUGE (WITH CHEMICAL SEAL)

402_ _PG001E

SEWAGE

0-6

kg/cm2

DISCHARGE OF RAW SEWAGE PUMP-E

TO INDICATE THE DISCHARGE PRESSURE OF RAW SEWAGE PUMP-E

0 - 6 kg/cm2

14

PRESSURE GAUGE (WITH CHEMICAL SEAL)

402_ _PG001F

SEWAGE

0-6

kg/cm2

DISCHARGE OF RAW SEWAGE PUMP-F

TO INDICATE THE DISCHARGE PRESSURE OF RAW SEWAGE PUMP-F

0 - 6 kg/cm2

DIFFERENTIAL LEVEL TRANSMITTER

411B_LDT002_

SEWAGE

0-1

mtr

12MM MEDIUM FINE BAR SCREEN

TO START/STOP THE SCREEN AT DIFFERENTIAL LEVELS

0-1m

DIFFERENTIAL LEVEL TRANSMITTER

411C_LDT002_

SEWAGE

0-1

mtr

12MM MEDIUM FINE BAR SCREEN

TO START/STOP THE SCREEN AT DIFFERENTIAL LEVELS

0-1m

DIFFERENTIAL LEVEL TRANSMITTER

411B_LDT001_

SEWAGE

0-1

mtr

3MM MEDIUM FINE BAR SCREEN

TO START/STOP THE SCREEN AT DIFFERENTIAL LEVELS

0-1m

DIFFERENTIAL LEVEL TRANSMITTER

411C_LDT001_

SEWAGE

0-1

mtr

3MM MEDIUM FINE BAR SCREEN

TO START/STOP THE SCREEN AT DIFFERENTIAL LEVELS

ELECTROMAGNETIC FLOWMETER

411_ _FITx005_

SEWAGE

0-6000

m3/hr

RAW SEWAGE TO INLET DISTRIBUTION


CHAMBER INLET LINE

TO MEASURE THE FLOW GOING TOWARDS THE INLET DISTRIBUTION CHAMBER &
CONTROL THE SPEED OF RAW SEWAGE PUMPS

CONDUCTIVITY LEVEL SWITCH

411_ _LS001_

SEWAGE

0-2

mtr

INLET DISTRIBUTION CHAMBER

TO INDICATE THE HIGH ALARM & TO TRIP RAW SEWAGE PUMPS IN OVERFLOW
CONDITION

mtr

TO MEASURE LEVEL & CALCULATE THE FLOW AND TO ADJUST EQUAL DISTRIBUTION
INLET SCREEN OUTLET DISTRIBUTION CHAMBER
OF RAW SEWAGE

SD-2.55
SD-2.55

TO MEASURE LEVEL & CALCULATE THE FLOW AND TO ADJUST EQUAL DISTRIBUTION
OF RAW SEWAGE

SD-2.55

(B)

PID REFERENCE NO. -- DGT-411-L-DS-PR-001 SCREENS

WIER LEVEL/FLOW TRANSMITTER (ULTRASONIC TYPE)

411_ _LITx002_

SEWAGE

0-5

WIER LEVEL/FLOW TRANSMITTER (ULTRASONIC TYPE)

411_ _LITx003_

SEWAGE

0-5

mtr

TO MEASURE LEVEL & CALCULATE THE FLOW AND TO ADJUST EQUAL DISTRIBUTION
INLET SCREEN OUTLET DISTRIBUTION CHAMBER
OF RAW SEWAGE

WIER LEVEL/FLOW TRANSMITTER (ULTRASONIC TYPE)

411_ _LITx004_

SEWAGE

0-5

mtr

INLET SCREEN OUTLET DISTRIBUTION CHAMBER

0-1m
0 - 6000 m3/hr
2 PROBE (SD-2.65m, HWL-0.71m)

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

REV-A

DATE - 19-10-2012

TAG NO.

FLUID

RANGE

UNIT

SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

WIER LEVEL/FLOW TRANSMITTER (ULTRASONIC TYPE)

411_ _LITx006_

SEWAGE

0-5

mtr

INLET SCREEN OUTLET DISTRIBUTION CHAMBER

TO MEASURE LEVEL & CALCULATE THE FLOW AND TO ADJUST EQUAL DISTRIBUTION
OF RAW SEWAGE

SD-2.55

ULTRASONIC LEVEL TRANSMITTER

413_ _LIT001_

DIRTY WATER

0-5

mtr

DIRTY WATER DRAINAGE TRANSFER SUMP

TO MEASURE THE LEVEL AT DIRTY WATER & DRAINAGE SUMP & TO CONTROL THE
OPERATION OF DIRTY WATER PUMPS

CONDUCTIVITY LEVEL SWITCH

413A_LS001_

SEWAGE

0-2 m

mtr

ORGANIC RETURN SUMP

TO START/STOP THE ORGANIC RETURN PUMP AT HIGH/LOW LEVELS

CONDUCTIVITY LEVEL SWITCH

413B_LS001_

SEWAGE

0-2 m

mtr

ORGANIC RETURN SUMP

TO START/STOP THE ORGANIC RETURN PUMP AT HIGH/LOW LEVELS

PRESSURE GAUGE (WITH CHEMICAL SEAL)

413_ _PG001A

DIRTY WATER

0-6

kg/cm2

DISCHARGE OF DIRTY WATER & DRAINAGE


PUMP-A

TO INDICATE THE DISCHARGE PRESSURE OF FIRTY WATER & DRAINAGE PUMPS

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

413_ _PG001B

DIRTY WATER

0-6

kg/cm2

DISCHARGE OF DIRTY WATER & DRAINAGE


PUMP-A

TO INDICATE THE DISCHARGE PRESSURE OF FIRTY WATER & DRAINAGE PUMPS

0 - 6 kg/cm2

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

(C)

PID REFERENCE NO. -- DGT-413-L-DS-PR-001 GRIT CLASSIFIER & DIRTY WATER SUMP

(D)

SD-2.75m LWL-2.0m, HWL-1.05m


3 PROBE
3 PROBE

PID REFERENCE NO. -- DGT-445-L-DS-PR-001 DENSADEG 4D30

SLUDGE BLANKET MONITOR

445A_LIT001_

SLUDGE

DENSADEG 4D30 -445A

TO MEASURE THE SLUDGE BLANKET FORMATION AT DENSADEG

SD-6.4m

SLUDGE BLANKET MONITOR

445B_LIT001_

SLUDGE

DENSADEG 4D30 -445B

TO MEASURE THE SLUDGE BLANKET FORMATION AT DENSADEG

SD-6.4m

SLUDGE

m3/h

COMMON DISCHARGE HEADER OF SLUDGE


RECIRCULATION/EXTRACTION PUMP FOR
DENSADEG-445A

TO MEASURE THE FLOW RATE FROM DISCHARGE OF RECIRCULATION PUMPS TO


SLUDGE BUFFERING TANK

0-40 m3/h

COMMON DISCHARGE HEADER OF SLUDGE


RECIRCULATION/EXTRACTION PUMP FOR
DENSADEG-445B

TO MEASURE THE FLOW RATE FROM DISCHARGE OF RECIRCULATION PUMPS TO


SLUDGE BUFFERING TANK

0-40 m3/h

ELECTROMAGNETIC FLOWMETER

445A_FITx001_

0-40

ELECTROMAGNETIC FLOWMETER

445B_FITx001_

SLUDGE

0-40

m3/h

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445A_PG001A

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445A

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445A_PG001B

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-B DENSADEG -445A

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445A_PG001C

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-C DENSADEG -445A

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445B_PG001A

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445B

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445B_PG001B

SLUDGE

0-6

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-B DENSADEG -445B

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

10

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445B_PG001C

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-C DENSADEG -445B

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

11

PRESSURE SWITCH (PSH)

445_ _PSH001A

SLUDGE

0-1

kg/cm2

GRIT TRANSFER PUMPS

TO TRIP GRIT TRANSFER PUMPS

0 - 1 kg/cm2

12

PRESSURE SWITCH (PSH)

445_ _PSH001B

SLUDGE

0-1

kg/cm2

GRIT TRANSFER PUMPS

TO TRIP GRIT TRANSFER PUMPS

0 - 1 kg/cm2

13

PRESSURE SWITCH (PSH)

445_ _PSH001B

SLUDGE

0-5

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445A

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

14

PRESSURE SWITCH (PSH)

445_ _PSH001B

SLUDGE

0-5

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-B DENSADEG -445A

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

15

PRESSURE SWITCH (PSH)

445_ _PSH001B

SLUDGE

0-5

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-C DENSADEG -445A

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

16

PRESSURE SWITCH (PSH)

445_ _PSH001B

SLUDGE

0-5

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445B

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

17

PRESSURE SWITCH (PSH)

445_ _PSH001B

SLUDGE

0-5

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-B DENSADEG -445B

18

PRESSURE SWITCH (PSH)

445_ _PSH001B

SLUDGE

0-5

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-C DENSADEG -445B

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

REV-A

TAG NO.

FLUID

(E)

RANGE

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

PID REFERENCE NO. -- DGT-445-L-DS-PR-002 DENSADEG 4D30

SLUDGE BLANKET MONITOR

445C_LIT001_

SLUDGE

DENSADEG 4D30 -445A

TO MEASURE THE SLUDGE BLANKET FORMATION AT DENSADEG

SD-6.4m

SLUDGE BLANKET MONITOR

445D_LIT001_

SLUDGE

DENSADEG 4D30 -445B

TO MEASURE THE SLUDGE BLANKET FORMATION AT DENSADEG

SD-6.4m

TO MEASURE THE FLOW RATE FROM DISCHARGE OF RECIRCULATION PUMPS TO


SLUDGE BUFFERING TANK

0-40 m3/h

ELECTROMAGNETIC FLOWMETER

445C_FITx001_

SLUDGE

0-40

m3/h

COMMON DISCHARGE HEADER OF SLUDGE


RECIRCULATION/EXTRACTION PUMP FOR
DENSADEG-445C

ELECTROMAGNETIC FLOWMETER

445D_FITx001_

SLUDGE

0-40

m3/h

COMMON DISCHARGE HEADER OF SLUDGE


RECIRCULATION/EXTRACTION PUMP FOR
DENSADEG-445D

TO MEASURE THE FLOW RATE FROM DISCHARGE OF RECIRCULATION PUMPS TO


SLUDGE BUFFERING TANK

0-40 m3/h

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445C_PG001A

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445C

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445C_PG001B

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-B DENSADEG -445C

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445C_PG001C

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-C DENSADEG -445C

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445D_PG001A

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445D

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445D_PG001B

SLUDGE

0-6

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-B DENSADEG -445D

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

10

PRESSURE GAUGE (WITH CHEMICAL SEAL)

445D_PG001C

SLUDGE

0-6

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-C DENSADEG -445D

TO INDICATE THE DISCHARGE PRESSURE OF SLUDGE RECIR/EXTRACTION PUMP

0 - 6 kg/cm2

11

PRESSURE SWITCH (PSH)

445_ _PSH001D

SLUDGE

0-1

kg/cm2

GRIT TRANSFER PUMPS

TO TRIP GRIT TRANSFER PUMPS

0 - 1 kg/cm2

12

PRESSURE SWITCH (PSH)

445_ _PSH001C

SLUDGE

0-1

kg/cm2

GRIT TRANSFER PUMPS

TO TRIP GRIT TRANSFER PUMPS

0 - 1 kg/cm2

13

PRESSURE SWITCH (PSH)

445C _PSH001A

SLUDGE

0-5

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445C

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

14

PRESSURE SWITCH (PSH)

445C _PSH001B

SLUDGE

0-5

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445C

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

15

PRESSURE SWITCH (PSH)

445C _PSH001C

SLUDGE

0-5

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445C

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445D

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

TO TRIP SLUDGE RECIRCULATION EXTRACTION PUMP

0 - 5 kg/cm2

16

PRESSURE SWITCH (PSH)

445D _PSH001A

SLUDGE

0-5

17

PRESSURE SWITCH (PSH)

445D _PSH001B

SLUDGE

0-5

kg/cm2

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445D

18

PRESSURE SWITCH (PSH)

445D _PSH001C

SLUDGE

0-5

kg/cm

DISCHARGE OF SLUDGE RECIRCULATION


EXTRACTION PUMP-A DENSADEG -445D

(F)
1
2
3

PID REFERENCE NO. -- DGT-492-L-DS-PR-001 BIOFOR STAGE-I


CONDUCTIVITY LEVEL SWITCH
CONDUCTIVITY LEVEL SWITCH
CONDUCTIVITY LEVEL SWITCH

492A1LS001_
492A2LS001_
492B1LS001_

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A1 STAG-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-A1 STAGE-I & TO START THE SEQUENCE
TO BAKWASH AT HIGH LEVEL

2 PROBE

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A2 STAG-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-A2 STAGE-II & TO START THE SEQUENCE
TO BAKWASH AT HIGH LEVEL

3 PROBE

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B1 STAG-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-B1 STAGE-I & TO START THE SEQUENCE
TO BAKWASH AT HIGH LEVEL

3 PROBE

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B2 STAG-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-B2 STAGE-II & TO START THE SEQUENCE
TO BAKWASH AT HIGH LEVEL

3 PROBE

CONDUCTIVITY LEVEL SWITCH

492B2LS001_

DIRTY WATER

DISSOLVED OXYGEN ANALYSER (DO)

492A1AITx001_

DIRTY WATER

0-10

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A1 STAG-I

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-A1


STAGE-I

DISSOLVED OXYGEN ANALYSER (DO)

492A2AITx001_

DIRTY WATER

0-10

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A2 STAG-I

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-A2


STAGE-I
TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-B1
STAGE-I
TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-B2
STAGE-I

DISSOLVED OXYGEN ANALYSER (DO)

492B1AITx001_

DIRTY WATER

0-10

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B1 STAG-I

DISSOLVED OXYGEN ANALYSER (DO)

492B2AITx001_

DIRTY WATER

0-10

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B2 STAG-I

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

REV-A

TAG NO.

FLUID

RANGE

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

THERMAL MASS AIR FLOW METER

492A1FITx001_

AIR

0-1000

Nm3/h

PROCESS AIR BLOWER TO BIOFOR FILTER -A1


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERA1 STAGE-I

0 - 1000 Nm3/hr

10

THERMAL MASS AIR FLOW METER

492A2FITx001_

AIR

0-1000

Nm /h

PROCESS AIR BLOWER TO BIOFOR FILTER -A2


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERA2 STAGE-I

0 - 1000 Nm3/hr

11

THERMAL MASS AIR FLOW METER

492B1FITx001_

AIR

0-1000

Nm3/h

PROCESS AIR BLOWER TO BIOFOR FILTER -B1


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERB1 STAGE-I

0 - 1000 Nm3/hr

12

THERMAL MASS AIR FLOW METER

492B2FITx001_

AIR

0-1000

Nm3/h

PROCESS AIR BLOWER TO BIOFOR FILTER -B2


STAGE-I LINE
INLET WATER CHANNEL FOR BIOFOR

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERB2 STAGE-I

0 - 1000 Nm3/hr

13

pH ANALYSER

492_ _AIT001_

SEWAGE

2 to 14

pH

TO MEASURE THE VALUE OF pH AT THE INLET CHANNEL OF BIOFOR FILTER STAGE-I


INLET WATER CHANNEL FOR BIOFOR
STAGE-1

492_ _AIT002_

SEWAGE

0-10

mg/l

2 - 14 pH

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT THE INLET CHANNEL OF


BIOFOR FILTER STAGE-I

14

DISSOLVED OXYGEN ANALYSER (DO)

15

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

16

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

17

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

18

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

STAGE-1

Not to be submitted to the Client

(G)
1
2

PID REFERENCE NO. -- DGT-492-L-DS-PR-002 BIOFOR STAGE-I


CONDUCTIVITY LEVEL SWITCH
CONDUCTIVITY LEVEL SWITCH

492A3LS001_
492A4LS001_

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A3 STAGE-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-A3 & TO START THE SEQUENCE TO


BAKWASH AT HIGH LEVEL

3 PROBE

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A4 STAGE-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-A4 & TO START THE SEQUENCE TO


BAKWASH AT HIGH LEVEL

3 PROBE

TO MEASURE THE LEVEL AT BIOFOR FILTER-B3 & TO START THE SEQUENCE TO


BAKWASH AT HIGH LEVEL

3 PROBE
3 PROBE

CONDUCTIVITY LEVEL SWITCH

492B3LS001_

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B3 STAGEE-I

CONDUCTIVITY LEVEL SWITCH

492B4LS001_

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B4 STAGE-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-B4 & TO START THE SEQUENCE TO


BAKWASH AT HIGH LEVEL

DISSOLVED OXYGEN ANALYSER (DO)

492A3AITx001_

DIRTY WATER

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A3 STAGE-I

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-A3


STAGE-I
TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-A4
STAGE-I

0-10

DISSOLVED OXYGEN ANALYSER (DO)

492A2A4Tx001_

DIRTY WATER

0-10

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A4 STAGE-I

DISSOLVED OXYGEN ANALYSER (DO)

492B3AITx001_

DIRTY WATER

0-10

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B3 STAGE-I

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-B3


STAGE-I

DISSOLVED OXYGEN ANALYSER (DO)

492B4AITx001_

DIRTY WATER

0-10

mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B4 STAGE-I

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-B4


STAGE-I

11

THERMAL MASS AIR FLOW METER

492A3FITx001_

AIR

0-1000

Nm3/hr

PROCESS AIR BLOWER TO BIOFOR FILTER -A3


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERA3 STAGE-I

0 - 1000 Nm3/hr

12

THERMAL MASS AIR FLOW METER

492A4FITx001_

AIR

0-1000

Nm3/hr

PROCESS AIR BLOWER TO BIOFOR FILTER -A4


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERA4 STAGE-I

0 - 1000 Nm3/hr

0-1000

Nm3/hr

PROCESS AIR BLOWER TO BIOFOR FILTER -B3


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERB3 STAGE-I

0 - 1000 Nm3/hr

0-1000

Nm /hr

PROCESS AIR BLOWER TO BIOFOR FILTER -B4


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERB4 STAGE-I

0 - 1000 Nm3/hr

13

THERMAL MASS AIR FLOW METER

492B3FITx001_
492B4FITx001_

AIR
AIR

14

THERMAL MASS AIR FLOW METER

15

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

16

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

17

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

18

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

Not to be submitted to the Client

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001
TAG NO.

REV-A
FLUID

RANGE

(H)

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

PID REFERENCE NO. -- DGT-492-L-DS-PR-003 BIOFOR STAGE-I

CONDUCTIVITY LEVEL SWITCH

492A5LS001_

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A5 STAGE-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-A5 & TO START THE SEQUENCE TO


BAKWASH AT HIGH LEVEL

3 PROBE

CONDUCTIVITY LEVEL SWITCH

492B5LS001_

DIRTY WATER

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B5 STAGE-I

TO MEASURE THE LEVEL AT BIOFOR FILTER-B5 & TO START THE SEQUENCE TO


BAKWASH AT HIGH LEVEL

3 PROBE

DISSOLVED OXYGEN ANALYSER (DO)

492A5AITx001_

DIRTY WATER

0-10 mg/l

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-A5 STAGE-I

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-A5


STAGE-I

TREATED WATER OUTLET CHAMBER BIOFOR


FILTER-B5 STAGE-I

TO MEASURE THE VALUE OF DISSOLVED OXYZEN AT OUTLET OF BIOFOR FILTER-B5


STAGE-I

DISSOLVED OXYGEN ANALYSER (DO)

492B5AITx001_

DIRTY WATER

0-10 mg/l

THERMAL MASS AIR FLOW METER

492A5FITx001_

AIR

0 - 1000

Nm3/hr

PROCESS AIR BLOWER TO BIOFOR FILTER -A5


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERA5 STAGE-I

0 - 1000 Nm3/hr

THERMAL MASS AIR FLOW METER

492B5FITx001_

AIR

0 - 1000

Nm /hr

PROCESS AIR BLOWER TO BIOFOR FILTER -B5


STAGE-I LINE

TO MEASURE THE AIR FLOW RATE FROM PROCESS AIR BLOWER TO BIOFOR FILTERB5 STAGE-I

0 - 1000 Nm3/hr

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

PRESSURE TRANSMITTER

TO MEASURE THE HEAD LOSS IN THE OUTLET OF BIOFOR

Not to be submitted to the Client

(I)

PID REFERENCE NO. -- DGT-495-L-DS-PR-001 BIOFOR STAGE-II

DIFFERENTIAL PRESSURE TRANSMITTER

495A1LDT001_

DIRTY WATER

0 - 0.5

kg/cm2

BIOFOR FILTER-A1 STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-A1 STAGE-II

0 - 0.5 kg/cm2

DIFFERENTIAL PRESSURE TRANSMITTER

495A2LDT001_

DIRTY WATER

0 - 0.5

kg/cm2

BIOFOR FILTER-A2 STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-A2 STAGE-II

0 - 0.5 kg/cm2

DIFFERENTIAL PRESSURE TRANSMITTER

495B1LDT001_

DIRTY WATER

0 - 0.5

kg/cm2

BIOFOR FILTER-B1 STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-B1 STAGE-II

0 - 0.5 kg/cm2

DIFFERENTIAL PRESSURE TRANSMITTER

495B2LDT001_

DIRTY WATER

0 - 0.5

kg/cm

BIOFOR FILTER-B2 STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-B2 STAGE-II

0 - 0.5 kg/cm2

(J)

PID REFERENCE NO. -- DGT-495-L-DS-PR-002 BIOFOR STAGE-II

DIFFERENTIAL PRESSURE TRANSMITTER

495A3LDT001_

DIRTY WATER

0 - 0.5

kg/cm2

BIOFOR FILTER STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-A3 STAGE-II

0 - 0.5 kg/cm2

DIFFERENTIAL PRESSURE TRANSMITTER

495A4LDT001_

DIRTY WATER

0 - 0.5

kg/cm

BIOFOR FILTER STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-A4 STAGE-II

0 - 0.5 kg/cm2

DIFFERENTIAL PRESSURE TRANSMITTER

495B3LDT001_

DIRTY WATER

0 - 0.5

kg/cm

BIOFOR FILTER STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-B3 STAGE-II

0 - 0.5 kg/cm2

DIFFERENTIAL PRESSURE TRANSMITTER

495B4LDT001_

DIRTY WATER

0 - 0.5

kg/cm2

BIOFOR FILTER STAGE-II

TO MEASURE THE LOSS OF HEAD AT BIOFOR FILTER-B4 STAGE-II

0 - 0.5 kg/cm2

0 - 6000 m3/hr

(K)

PID REFERENCE NO. -- DGT-523-L-DS-PR-001 CHLORINE CONTACT TANK

FLOW INDICATOR TRANSMITTER (OPEN CHANNEL)

523_ _FIT001_

TREATED EFFLUENT

0 - 6000

m3/hr

TREATED EFFLUENT CHANNEL

TO MEASURE THE FLOW AT TREATED EFFLUENT CHANNEL FROM CCT

BIOLOGICAL OXYGEN DEMAND ANALYSER (BOD)

523_ _AI001A

TREATED EFFLUENT

0 - 100

ppm

TREATED EFFLUENT CHANNEL SAMPLING LINE

TO MEASURE THE VALUE OF BOD AT TREATED EFFLUENT CHANNEL FROM CCT

0 - 100 ppm

TOTAL SUSPENDED SOLID ANALYSER (TSS)

523_ _AI001B

TREATED EFFLUENT

0 - 100

ppm

TREATED EFFLUENT CHANNEL SAMPLING LINE

TO MEASURE THE VALUE OF TSS AT TREATED EFFLUENT CHANNEL FROM CCT

0 - 100 ppm

DISSOLVED OXYGEN ANALYSER (DO)

523_ _AI001C

TREATED EFFLUENT

0 - 100

ppm

TREATED EFFLUENT CHANNEL SAMPLING LINE

TO MEASURE THE VALUE OF DO AT TREATED EFFLUENT CHANNEL FROM CCT

0 - 100 ppm

CHLORINE ANALYSER (Cl2)

523_ _AI001D

TREATED EFFLUENT

0-2

ppm

TREATED EFFLUENT CHANNEL SAMPLING LINE

TO MEASURE THE VALUE OF CHLORINE AT TREATED EFFLUENT CHANNEL FROM CCT

0 - 2 ppm

ELECTROMAGNETIC FLOWMETER

495_ _FITx001_

TREATED EFFLUENT

0 - 6000

m /hr

BIOFOR STAGE-II TO FILTERED WATER OUTLET


SUMP LINE

TO MEASURE THE OUTLET FLOW OF BIOFOR FILTERS STAGE-II TOWARDS FILTERED


WATER OUTLET SUMP

0 - 6000 m3/hr

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

REV-A

TAG NO.

FLUID

RANGE

UNIT

495_ _LITx001_

TREATED EFFLUENT

0 - 10

mtr

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

FILTERED WATER OUTLET SUMP

TO MEASURE THE LEVEL AT FILTERED WATER SUMP & TO CONTROL THE OPERATION
OF BACKWASH & FILTERED WATER PUMPS

SD-5.63m LWL-4.58m, HWL-0.64m

ULTRASONIC LEVEL TRANSMITTER

DISSOLVED OXYGEN ANALYSER (DO)

495_ _AI001A

TREATED EFFLUENT

0 - 10

ppm

FILTERED WATER OUTLET SUMP SAMPLING LINE

TO MEASURE THE VALUE OF DO AT FILTERED WATER SUMP

TURBIDITY ANALYSER (TU)

495_ _AI001B

TREATED EFFLUENT

0 - 100

NTU

FILTERED WATER OUTLET SUMP SAMPLING LINE

TO MEASURE THE VALUE OF TURBIDITY AT FILTERED WATER SUMP

10

ELECTROMAGNETIC FLOWMETER

495A_FITx001_

TREATED EFFLUENT

0 - 2000

m3/hr

FILTER BACKWASH WATER INLET STAGE-I LINE

TO MEASURE THE FLOW AT COMMON DISCHARGE OF FILTERED WATER PUMPS FOR


BIOFOR STAGE-I

0 - 2000 m3/hr
0 - 1000 m3/hr

0 - 10 ppm
0 - 100 NTU

11

ELECTROMAGNETIC FLOWMETER

495A_FITx002_

TREATED EFFLUENT

0 - 1000

m3/hr

FILTER BACKWASH WATER INLET STAGE-I I LINE

TO MEASURE THE FLOW AT COMMON DISCHARGE OF FILTERED WATER PUMPS FOR


BIOFOR STAGE-II

12

PRESSURE GAUGE BOURDON

495A_PG001A

TREATED EFFLUENT

0-6

kg/cm

DISCHARGE OF BACKWASH WATER TRANSFER


PUMP-A FOR STAGE-I

TO INDICATE THE DISCHARGE OF BACKWASH WATER PUMP-A FOR STAGE-I

13

PRESSURE GAUGE BOURDON

495A_PG001B

TREATED EFFLUENT

0-6

kg/cm

DISCHARGE OF BACKWASH WATER TRANSFER


PUMP-B FOR STAGE-I

TO INDICATE THE DISCHARGE OF BACKWASH WATER PUMP-B FOR STAGE-I

14

PRESSURE GAUGE BOURDON

495A_PG002A

TREATED EFFLUENT

0-6

kg/cm2

DISCHARGE OF BACKWASH WATER TRANSFER


PUMP-A FOR STAGE-II

TO INDICATE THE DISCHARGE OF BACKWASH WATER PUMP-A FOR


II
TO INDICATE THE DISCHARGE OF BACKWASH WATER PUMP-B FOR STAGE-II

0 - 6 kg/cm2

0 - 6 kg/cm2
0 - 6 kg/cm2
STAGE-

0 - 6 kg/cm2

15

PRESSURE GAUGE BOURDON

495A_PG002B

TREATED EFFLUENT

0-6

kg/cm2

DISCHARGE OF BACKWASH WATER TRANSFER


PUMP-B FOR STAGE-II

16

PRESSURE GAUGE BOURDON

495B_PG001A

TREATED EFFLUENT

0-6

kg/cm2

DISCHARGE OF OXAZUR WASH WATER PUMP-A

TO INDICATE THE DISCHARGE OF OXAZUR WASH WATER PUMP-A

0 - 6 kg/cm2

17

PRESSURE GAUGE BOURDON

495B_PG001A

TREATED EFFLUENT

0-6

kg/cm

DISCHARGE OF OXAZUR WASH WATER PUMP-B

TO INDICATE THE DISCHARGE OF OXAZUR WASH WATER PUMP-B

0 - 6 kg/cm2

(L)

PID REFERENCE NO. -- DGT-623-L-DS-PR-001 MECHANICAL SLUDGE THICKNER

ULTRASONIC LEVEL TRANSMITTER

603_ _LIT001_

SLUDGE

0 - 10

mtr

SLUDGE BUFFERING TANK

TO MEASURE THE LEVEL AT SLUDGE BUFFERING TANK & TO CONTROL THE


START/STOP OPERATION OF THICKNER FEED PUMPS & SLUDGE BUFFERING TANK
MIXER

Sump GA not finalized

TO MEASURE THE PRESSURE AT DISCHARGE OF THICKNER


2

PRESSURE SWITCH (PSH)

621A_PSH001A

SLUDGE

0-3

kg/cm2

PRESSURE SWITCH (PSH)

621A_PSH001B

SLUDGE

0-3

PRESSURE GAUGE (WITH CHEMICAL SEAL)

621A_PG001A

SLUDGE

0-6

DISCHARGE OF THICKNER FEED PUMP-A

0 - 3 kg/cm2
FEED PUMP-A
TO MEASURE THE PRESSURE AT DISCHARGE OF THICKNER

kg/cm

DISCHARGE OF THICKNER FEED PUMPB

kg/cm

DISCHARGE OF THICKNER FEED PUMP-A

0 - 3 kg/cm2
FEED PUMP-B
TO INDICATE THE PRESSURE AT DISCHARGE OF THICKNER
0 - 6 kg/cm2
FEED PUMP-A

PRESSURE GAUGE (WITH CHEMICAL SEAL)

621A_PG001B

SLUDGE

0-6

kg/cm2

DISCHARGE OF THICKNER FEED PUMP-B

TO INDICATE THE PRESSURE AT DISCHARGE OF THICKNER


FEED PUMP-B

0 - 6 kg/cm2

PRESSURE SWITCH (LOW)

623A_PS001_

SERVICE WATER

0-3

kg/cm2

SERVICE WATER LINE TO THICKNER

TO MEASURE THE PRESSURE AT SERVICE WATER LINE TO THICKNER

0 - 3 kg/cm2

PRESSURE SWITCH (LOW)

623B_PS001_

SERVICE WATER

0-3

kg/cm

SERVICE WATER LINE TO THICKNER

TO MEASURE THE PRESSURE AT SERVICE WATER LINE TO THICKNER

0 - 3 kg/cm2

ELECTROMAGNETIC FLOWMETER

621B_FITx001A

SLUDGE

0-100

m /hr

COMMON DISCHARGE OF DIGESTER FEED


PUMPS

TO MEASURE THE FLOW TO DIGESTER FROM DIGESTER FEED PUMPS

PRESSURE SWITCH (HIGH)

621B_PSH001A

SLUDGE

0-5

kg/cm2

DISCHARGE OF DIGESTER FEED PUMP-A

TO MEASURE THE PRESSURE AT DISCHARGE OF DIGESTER


PUMP-A

10

PRESSURE SWITCH (HIGH)

621B_PSH001B

SLUDGE

0-5

kg/cm2

DISCHARGE OF DIGESTER FEED PUMP-B

TO MEASURE THE PRESSURE AT DISCHARGE OF DIGESTER


PUMP-B

FEED

DISCHARGE OF DIGESTER FEED PUMP-A

TO INDICATE THE PRESSURE AT DISCHARGE OF DIGESTER


PUMP-A

FEED

DISCHARGE OF DIGESTER FEED PUMP-B

TO INDICATE THE PRESSURE AT DISCHARGE OF DIGESTER


PUMP-B

FEED

Sump GA not finalized

Sump GA not finalized

11

PRESSURE GAUGE (WITH CHEMICAL SEAL)

621B_PG001A

SLUDGE

0-5

kg/cm2

12

PRESSURE GAUGE (WITH CHEMICAL SEAL)

621B_PG001B

SLUDGE

0-5

kg/cm

13

ULTRASONIC LEVEL TRANSMITTER

628_ _LIT002_

SLUDGE

0 - 10

mtr

THIKENED SLUDGE SUMP

TO MEASURE THE LEVEL AT THICKENED SLUDGE TANK & TO CONTROL THE


START/STOP OF DIGESTER FEED PUMPS & THICKENED SLUDGE MIXER

14

SLUDGE CONSISTENCY INDICATOR

628_ _LITx001_

SLUDGE

0 - 10

mtr

THIKENED SLUDGE SUMP

TO MEASURE THE SLUDGE CONSISTENCY AT THICKENED SLUDGE SUMP

0 - 100 m3/hr
FEED

0 - 5 kg/cm2
0 - 5 kg/cm2
0 - 6 kg/cm2
0 - 6 kg/cm2

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001
TAG NO.

REV-A
FLUID

(M)

RANGE

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

PID REFERENCE NO. -- DGT-632-L-DS-PR-001 ANAEROBIC SLUDGE DIGESTER

PRESSURE INDICATOR TRANSMITTER

632_ _PIT001_

SLUDGE

Package

SLUDGE DIGESTER

TO MEASURE THE PRESSUER AT SLUDGE DIGESTER

TEMPERATURE INDICATOR TRANSMITTER

632_ _TIT001A

SLUDGE

Package

SLUDGE DIGESTER

TO MEASURE & INDICATE THE TEMPERATURE AT SLUDGE DIGESTIER

CONDUCTIVITY LEVEL SWITCH

632_ _LSHH001_

SLUDGE

Package

SLUDGE DIGESTER

TO MEASURE THE HIGH LEVEL AT SLUDGE DIGESTER

2 PROBE

CONDUCTIVITY LEVEL SWITCH

632_ _LSH001_

SLUDGE

Package

SLUDGE DIGESTER

TO MEASURE THE HIGH HIGH LEVEL AT SL;UDGE DIGESTER

2 PROBE

PRESSURE GAUGE BOURDON

632_ _PG001_

SLUDGE

Package

SLUDGE DIGESTER

TO INDICATE THE PRESSURE AT SLUDGE DIGESTER

pH ANALYSER

632_ _AIT002A

SLUDGE

Package

SLUDGE DIGESTER

TO MEASURE THE VALUE OF pH AT SLUDGE DIGESTER

CONDUCTIVITY LEVEL SWITCH

632_ _LSH002_

SLUDGE

Package

SLUDGE DIGESTER

TO MEASURE THE HIGH LEVEL AT SLUDGE DIGESTER

TEMPERATURE GAUGE

632_ _TG002_

SLUDGE

Package

INLET OF HEAT EXCHANGER

TO INDICATE THE TEMPERATURE AT INLET OF HEAT EXCHANGER

10

TEMPERATURE GAUGE

632_ _TG001_

SLUDGE

Package

OUTLET OF HEAT EXCHANGER

TO INDICATE THE TEMPERATURE AT OUTLET OF HEAT EXCHANGER

2 PROBE

11

TEMPERATURE INDICATOR TRANSMITTER

637_ _TIT002_

SLUDGE

Package

OUTLET OF HEAT EXCHANGER

TO INDICATE & MONITOR THE TEMPERATURE AT OUTLET OF HEAT EXCHANGER

12

PRESSURE GAUGE BOURDON

637_ _PI001_

HOT WATER

Package

INLET OF HEAT EXCHANGER

TO INDICATE THE PRESSURE AT HOT WATER LINE OUTLET FROM HEAT EXHANGER

Package

13

PRESSURE GAUGE BOURDON

751_ _PG001A

HOT WATER

Package

DISCHARGE OF HOT WATER PUMP-A

TO INDICATE THE PRESSURE AT DISCHARGE OF HOT WATER PUMP-A

Package

14

PRESSURE GAUGE BOURDON

751_ _PG001B

HOT WATER

Package

DISCHARGE OF HOT WATER PUMP-B

TO INDICATE THE PRESSURE AT DISCHARGE OF HOT WATER PUMP-B

Package

15

TEMPERATURE GAUGE

632_ _TG003_

HOT WATER

Package

OUTLET OF GAS ENGINE HEAT EXCHANGER

TO INDICATE THE TEMPERATURE AT HOTWATER INLET LINE TO HEAT EXHANGER

16

THERMAL MASS GAS FLOW METER

742_ _FITx001_

BIOGAS

Package

BIOGAS DESULPHURIZATION LINE

TO MEASURE THE FLOW OF GAS TO BIOGAS DESULPHURISATION UNIT

17

PRESSURE GAUGE BOURDON

742_ _PG001_

BIOGAS

Package

INLET OF DRIP TRAP

TO INDICATE THE PRESSURE AT DRIP TRAP LINE FROM DIGESTER


TO INDICATE & MONITOR THE PRESSURE AT COMMON SUCTION HEADER OF BIOGAS
COMPRESSOR

18

PRESSURE INDICATOR TRANSMITTER

742_ _PIT001A

BIOGAS

Package

COMMON SUCTION HEADER OF GAS


COMPRESSORS

19

PRESSURE SWITCH HIGH

742_ _PSH002A

BIOGAS

Package

SUCTION OF BIOGAS COMPRESSOR -A

TO MONITOR THE PRESSURE AT SUCTION OF BIOGAS COMPRESSOR-A

20

PRESSURE GAUGE BOURDON

742_ _PG002B

BIOGAS

Package

SUCTION OF BIOGAS COMPRESSOR -A

TO INDICATE THE PRESSURE AT SUCTION OF BIOGAS COMPRESSOR-A

21

TEMPERATURE SWITCH

742_ _TSH001A

BIOGAS

Package

SUCTION OF BIOGAS COMPRESSOR -A

TO INDICATE THE TEMPERATURE AT SUCTION OF BIOGAS COMPRESSOR-A

22

PRESSURE SWITCH LOW

742_ _PSL001A

BIOGAS

Package

DISCHARGE OF BIOGAS COMPRESSOR-A

23

PRESSURE GAUGE BOURDON

742_ _PG002A

BIOGAS

Package

DISCHARGE OF BIOGAS COMPRESSOR-A

24

PRESSURE SWITCH HIGH

742_ _PSH003A

BIOGAS

Package

SUCTION OF BIOGAS COMPRESSOR -B

TO MONITOR THE PRESSURE AT SUCTION OF BIOGAS COMPRESSOR-B

25

PRESSURE GAUGE BOURDON

742_ _PG002C

BIOGAS

Package

SUCTION OF BIOGAS COMPRESSOR -B

TO INDICATE THE PRESSURE AT SUCTION OF BIOGAS COMPRESSOR-B

26

TEMPERATURE SWITCH

742_ _TSH002A

BIOGAS

Package

SUCTION OF BIOGAS COMPRESSOR -B

TO INDICATE THE TEMPERATURE AT SUCTION OF BIOGAS COMPRESSOR-B

27

PRESSURE SWITCH LOW

742_ _PSL002A

BIOGAS

Package

DISCHARGE OF BIOGAS COMPRESSOR-B

28

PRESSURE GAUGE BOURDON

742_ _PG002D

BIOGAS

Package

DISCHARGE OF BIOGAS COMPRESSOR-B

29

CH4 GAS DETECTOR

742_ _AIT001_

CH4

Package

COMPRESSOR ROOM

TO MONITOR THE PRESSURE AT DISCHARGE OF BIOGAS


COMPRESSOR-A
TO INDICATE THE PRESSURE AT DISCHARGE OF BIOGAS
COMPRESSOR-A

TO MONITOR THE PRESSURE AT DISCHARGE OF BIOGAS


COMPRESSOR-B
TO INDICATE THE PRESSURE AT DISCHARGE OF BIOGAS
COMPRESSOR-B
TO MONITOR THE PRESENCE OF CH4 AT BIOGAS COMPRESSOR ROOM

Package
0 - 600 Nm3/hr
(-)2 to (+)3 kg/cm2

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001
TAG NO.

REV-A
FLUID

(N)

RANGE

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

DIGESTED SLUDGE SUMP

TO MEASURE THE LEVEL AT DIGESTED SLUDGE SUMP & TO CONTROL THE


START/STOP OPERATION OF CENTRIFUGE FEED PUMPS & DIGESTED SLUDGE MIXER

Sump GA not finalized

Sump GA not finalized

PID REFERENCE NO. -- DGT-642-L-DS-PR-001 SLUDGE HANDLING SYSTEM

ULTRASONIC LEVEL TRANSMITTER

638_ _LIT002_

SLUDGE

0-10

mtr

2
3

SLUDGE CONSISTENCY INDICATOR

638_ _AITx001_

SLUDGE

PRESSURE SWITCH (HIGH)

638_ _PSH001A

DIGESTED SLUDGE SUMP

TO INDICATE & MONITOR THE SLUDGE CONSISTANCY AT DIGESTED SLUDGE SUMP

SLUDGE

0-3

kg/cm2

DISCHARGE OF CENTRIFUGE FEED PUMP-A

TO MONITOR THE PRESSURE AT DISCHARGE OF CENTRIFUGE PUMP-A

0 - 3 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

638_ _PG001A

SLUDGE

0-6

kg/cm2

DISCHARGE OF CENTRIFUGE FEED PUMP-A

TO MONITOR THE PRESSURE AT DISCHARGE OF CENTRIFUGE PUMP-A

0 - 6 kg/cm2

ELECTROMAGNETIC FLOWMETER

638_ _FITx001A

SLUDGE

0 - 20

m3/hr

PRESSURE SWITCH (HIGH)

638_ _PSH001B

SLUDGE

PRESSURE GAUGE (WITH CHEMICAL SEAL)

638_ _PG001B

SLUDGE

ELECTROMAGNETIC FLOWMETER

638_ _FITx001B

PRESSURE SWITCH (HIGH)

10
11
14

H2S GAS DETECTOR

DISCHARGE OF CENTRIFUGE FEED PUMP-A

TO MEASURE THE FLOW TO CENTRIFUGE FROM CENTRIFUGE FEED PUMP-A

0 - 20 m3/hr

0-3

kg/cm

DISCHARGE OF CENTRIFUGE FEED PUMP-B

TO MONITOR THE PRESSURE AT DISCHARGE OF CENTRIFUGE PUMP-B

0 - 3 kg/cm2

0-6

kg/cm2

DISCHARGE OF CENTRIFUGE FEED PUMP-B

TO MONITOR THE PRESSURE AT DISCHARGE OF CENTRIFUGE PUMP-B

0 - 6 kg/cm2

SLUDGE

0 - 20

m3/hr

DISCHARGE OF CENTRIFUGE FEED PUMP-B

TO MEASURE THE FLOW TO CENTRIFUGE FROM CENTRIFUGE FEED PUMP-B

0 - 20 m3/hr

638_ _PSH001C

SLUDGE

0-3

kg/cm 2

DISCHARGE OF CENTRIFUGE FEED PUMP-C

TO MONITOR THE PRESSURE AT DISCHARGE OF CENTRIFUGE PUMP-C

0 - 3 kg/cm2

PRESSURE GAUGE (WITH CHEMICAL SEAL)

638_ _PG001C

SLUDGE

0-6

kg/cm

DISCHARGE OF CENTRIFUGE FEED PUMP-C

TO MONITOR THE PRESSURE AT DISCHARGE OF CENTRIFUGE PUMP-C

0 - 6 kg/cm2

ELECTROMAGNETIC FLOWMETER

638_ _FITx001C

SLUDGE

0 - 20

m3/hr

DISCHARGE OF CENTRIFUGE FEED PUMP-C

TO MEASURE THE FLOW TO CENTRIFUGE FROM CENTRIFUGE FEED PUMP-C

0 - 20 m3/hr

642_ _AIT001_

H2S

0 - 1000

ppm

CENTRIFUGE ROOM

TO MONITOR THE PRESENCE OF H2S AT CENTRIFUGE AREA

0 - 1000 ppm

(O)
1

PID REFERENCE NO. -- DGT-712-L-DS-PR-001 PROCESS/SCOUR AIR BLOWERS


PRESSURE GAUGE BOURDON

712_ _PG001A

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-A

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-A

Package

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

REV-A

TAG NO.

FLUID

RANGE

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

PRESSURE GAUGE BOURDON

712_ _PG001B

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-B

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-B

Package

PRESSURE GAUGE BOURDON

712_ _PG001C

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-C

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-C

Package

PRESSURE GAUGE BOURDON

712_ _PG002A

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-D

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-D

Package

PRESSURE GAUGE BOURDON

712_ _PG002B

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-E

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-E

Package

PRESSURE GAUGE BOURDON

712_ _PG002C

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-F

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-F

Package

PRESSURE GAUGE BOURDON

712_ _PG003A

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-G

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-G

Package

PRESSURE GAUGE BOURDON

712_ _PG003B

AIR

0-7.5 mWC

DISCHARGE OF PROCESS AIR BLOWER-H

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-H

PRESSURE SWITCH (HIGH)

712_ _PSH001_

AIR

0-2

kg/cm 2

DISCHARGE OF COMMON DISCHARGE OF


BLOWER-A/B/C

TO MONITOR THE PRESSURE AT COMMON DISCHARGE OF BLOWER-A/B/C

0 - 2 kg/cm2

10

PRESSURE SWITCH (HIGH)

712_ _PSH002_

AIR

0-2

kg/cm 2

DISCHARGE OF COMMON DISCHARGE OF


BLOWER-A/B/C

TO MONITOR THE PRESSURE AT COMMON DISCHARGE OF BLOWER-A/B/C

0 - 2 kg/cm2

Package

11

PRESSURE SWITCH (HIGH)

712_ _PSH003_

AIR

0-2

kg/cm 2

DISCHARGE OF COMMON DISCHARGE OF


BLOWER-D/E/F

TO MONITOR THE PRESSURE AT COMMON DISCHARGE OF BLOWER-D/E/F

0 - 2 kg/cm2

12

PRESSURE SWITCH (HIGH)

712_ _PSH004_

AIR

0-2

kg/cm

DISCHARGE OF COMMON DISCHARGE OF


BLOWER-D/E/F

TO MONITOR THE PRESSURE AT COMMON DISCHARGE OF BLOWER-D/E/F

0 - 2 kg/cm2

13

PRESSURE SWITCH (HIGH)

712_ _PSH005_

AIR

0-2

kg/cm 2

DISCHARGE OF COMMON DISCHARGE OF


BLOWER-G/H

TO MONITOR THE PRESSURE AT COMMON DISCHARGE OF BLOWER-G/H

0 - 2 kg/cm2

14

PRESSURE GAUGE BOURDON

713A_PG001A

AIR

0-2

kg/cm 2

DISCHARGE OF SCOUR AIR BLOWER -A FOR


STAGE-I

TO INDICATE THE PRESSURE AT DISCHARGE OF SCOUR AIR BLOWER-A FOR STAGE-I

0 - 2 kg/cm2

15

PRESSURE GAUGE BOURDON

713A_PG001B

AIR

0-2

kg/cm 2

DISCHARGE OF SCOUR AIR BLOWER -B FOR


STAGE-I

TO INDICATE THE PRESSURE AT DISCHARGE OF SCOUR AIR BLOWER-B FOR STAGE-I

0 - 2 kg/cm2

16

PRESSURE GAUGE BOURDON

713A_PG001C

AIR

0-2

kg/cm

DISCHARGE OF SCOUR AIR BLOWER -C FOR


STAGE-I

TO INDICATE THE PRESSURE AT DISCHARGE OF SCOUR AIR BLOWER-C FOR STAGE-I

0 - 2 kg/cm2

17

PRESSURE SWITCH (HIGH)

713A_PSH001_

AIR

0-2

kg/cm

COMMON DISCHARGE OF SCOUR AIR BLOWER


FOR STAGE-I

TO MONITOR THE PRESSURE AT COMMON DISCHARGE OF SCOUR AIR BLOWER FOR


STAGE-I

0 - 2 kg/cm2

18

PRESSURE GAUGE BOURDON

713B_ _PG002A

AIR

0-7.1 mWC

DISCHARGE OF SCOUR AIR BLOWER-A FOR


STAGE-II

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-A FOR STAGE-II

Package

DISCHARGE OF SCOUR AIR BLOWER-B FOR


STAGE-II

TO INDICATE THE PRESSURE AT DISCHARGE OF AIR BLOWER-B FOR STAGE-II

Package

COMMON DISCHARGE OF SCOUR AIR BLOWER


FOR STAGE-II

TO MONITOR PRESSURE AT COMMON DISCHARGE OF SCOUR AIR BLOWER FOR


STAGE-II

19

PRESSURE GAUGE BOURDON

713B_ _PG002B

AIR

0-7.1 mWC

20

PRESSURE SWITCH (HIGH)

713B_PSH001_

AIR

0-2

(P)

kg/cm

0 - 2 kg/cm2

PID REFERENCE NO. -- DGT-741-L-DS-PR-001 GAS HOLDER

PRESSURE SWITCH (HIGH,LOW)

744_ _PS001_

BIOGAS

Package

COMMON DISCHARGE OF COMPRESSOR OF GAS TO MONITOR THE PRESSURE AT COMMON DISCHARGE OF COMPRESSOR FOR GAS
HOLDER
HOLDER

ULTRASONIC LEVEL TRANSMITTER

741_ _LIT001_

BIOGAS

Package

GAS HOLDER

TO MEASURE & INDICATE THE LEVEL OF GAS AT GAS HOLDER

CH4 GAS DETECTOR

741_ _AIT001_

BIOGAS

Package

GAS HOLDER

TO MONITOR THE PRESENCE OF H2S AT GAS HOLDER

CALORIFIC VALUE INDICATOR

741_ _AIT002A

BIOGAS

Package

GAS LINE TO GENSET

TO MEASURE & INDICATE THE CALORIFIC VALUE

(Q)

0 - 3 kg/cm2

PID REFERENCE NO. -- DGT-811-L-DS-PR-001 POLY DOSING SYSTEM FOR DENSADEG 4D30

CONDUCTIVITY LEVEL SWITCH

811A1LS001_

POLYMER

Package

POLYMER DOSING TANK -A1

TO MONITOR THE LEVEL AT POLY DOSING TANK-A1 & TO CONTROL THE START/STOP
OPERATION OF POLY DOSING PUMPS & POLY TANK AGITATOR

LEVEL GAUGE

811A1LG001_

POLYMER

Package

POLYMER DOSING TANK -A1

TO INDICATE THE LEVEL AT POLY TANK-A1

4 PROBE (Not in package) TH-4.2m


LWL-3.6m, LLWL-3.95, HWL-0.9
TH - 3.6m (Not in package)

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

REV-A

TAG NO.

FLUID

RANGE

811A2LS001_

POLYMER

Package

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

POLYMER DOSING TANK -A2

TO MONITOR THE LEVEL AT POLY DOSING TANK-A2 & TO CONTROL THE START/STOP
OPERATION OF POLY DOSING PUMPS & POLY TANK AGITATOR

POLYMER DOSING TANK -A2

TO INDICATE THE LEVEL AT POLY TANK-A2

POLMER DOSING PUMP-A

TO INDICATE THE PRESSURE AT DISCHARGE OF POLY DOSING PUMP-A

0 - 10 kg/cm2

kg/cm2

POLMER DOSING PUMP-B

TO INDICATE THE PRESSURE AT DISCHARGE OF POLY DOSING PUMP-B

0 - 10 kg/cm2

0 - 10

kg/cm2

POLMER DOSING PUMP-C

TO INDICATE THE PRESSURE AT DISCHARGE OF POLY DOSING PUMP-C

0 - 10 kg/cm2

POLYMER

0 - 10

kg/cm

POLMER DOSING PUMP-D

TO INDICATE THE PRESSURE AT DISCHARGE OF POLY DOSING PUMP-D

0 - 10 kg/cm2

POLYMER

0 - 10

kg/cm2

POLMER DOSING PUMP-E

TO INDICATE THE PRESSURE AT DISCHARGE OF POLY DOSING PUMP-E

0 - 10 kg/cm2

811A_PG001B

POLYMER

0 - 10

kg/cm2

POLMER DOSING PUMP-F

TO INDICATE THE PRESSURE AT DISCHARGE OF POLY DOSING PUMP-F

0 - 10 kg/cm2

FLOW SWITCH / ROTAMETER

811A_FSL001A

POLYMER

0-5

m3/hr

DISCHARGE OF POLMER DOSING PUMP-A

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

12

FLOW SWITCH / ROTAMETER

811A_FSL001B

POLYMER

0-5

m /hr

DISCHARGE OF POLMER DOSING PUMP-C

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

13

FLOW SWITCH / ROTAMETER

811A_FSL001C

POLYMER

0-5

m /hr

DISCHARGE OF POLMER DOSING PUMP-D

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

14

FLOW SWITCH / ROTAMETER

811A_FSL001D

POLYMER

0-5

m3/hr

DISCHARGE OF POLMER DOSING PUMP-F

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

CONDUCTIVITY LEVEL SWITCH

LEVEL GAUGE

811A2LG001_

POLYMER

Package

PRESSURE GAUGE BOURDON

811A_PG001A

POLYMER

0 - 10

kg/cm2

PRESSURE GAUGE BOURDON

811A_PG001B

POLYMER

0 - 10

PRESSURE GAUGE BOURDON

811A_PG001B

POLYMER

PRESSURE GAUGE BOURDON

811A_PG001B

PRESSURE GAUGE BOURDON

811A_PG001B

10

PRESSURE GAUGE BOURDON

11

(R)

4 PROBE (Not in package) TH-4.2m


LWL-3.6m, LLWL-3.95, HWL-0.9
TH - 3.6m (Not in package)

PID REFERENCE NO. -- DGT-811-L-DS-PR-002 POLY DOSING SYSTEM FOR CENTRIFUGE & THICKNER

CONDUCTIVITY LEVEL SWITCH

811B1LS001_

POLYMER

Package

POLYMER DOSING TANK -B1

TO MONITOR THE LEVEL AT POLY DOSING TANK-B1 & TO CONTROL THE START/STOP
OPERATION OF POLY TANK AGITATOR

4 PROBE (Package)

CONDUCTIVITY LEVEL SWITCH

811B2LS001_

POLYMER

Package

POLYMER DOSING TANK -B2

TO MONITOR THE LEVEL AT POLY DOSING TANK-B2 & TO CONTROL THE START/STOP
OPERATION OF POLY TANK AGITATOR

4 PROBE (Package)

PRESSURE GAUGE BOURDON

811B_PG001A

POLYMER

0 - 10

kg/cm2

DISCHARGE OF POLY DOSING PUMP-A FOR


THICKNER

TO INDICATE THE PRESSURE AT DISCHARGE OF POLYDOSING PUMP-A FOR


THICKNER

0 - 10 kg/cm2

TO INDICATE THE PRESSURE AT DISCHARGE OF POLYDOSING PUMP-B FOR


THICKNER

0 - 10 kg/cm2

PRESSURE GAUGE BOURDON

811B_PG001B

POLYMER

0 - 10

kg/cm2

DISCHARGE OF POLY DOSING PUMP-B FOR


THICKNER

PRESSURE GAUGE BOURDON

811B_PG003A

POLYMER

0 - 10

kg/cm

DISCHARGE OF POLY DOSING PUMP-A FOR


CENTRIFUGE

TO INDICATE THE PRESSURE AT DISCHARGE OF POLYDOSING PUMP-C FOR


THICKNER

0 - 10 kg/cm2

PRESSURE GAUGE BOURDON

811B_PG003B

POLYMER

0 - 10

kg/cm2

DISCHARGE OF POLY DOSING PUMP-B FOR


CENTRIFUGE

TO INDICATE THE PRESSURE AT DISCHARGE OF POLYDOSING PUMP-D FOR


THICKNER

0 - 10 kg/cm2

PRESSURE GAUGE BOURDON

811B_PG003C

POLYMER

0 - 10

kg/cm2

DISCHARGE OF POLY DOSING PUMP-C FOR


CENTRIFUGE

TO INDICATE THE PRESSURE AT DISCHARGE OF POLYDOSING PUMP-E FOR


THICKNER

0 - 10 kg/cm2

FLOW SWITCH / ROTAMETER

811B_FSL001A

POLYMER

0-5

m3/hr

DISCHARGE OF POLYDOSING PUMP A

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

FLOW SWITCH / ROTAMETER

811B_FSL001B

POLYMER

0-5

m /hr

DISCHARGE OF POLYDOSING PUMP B

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

10

FLOW SWITCH / ROTAMETER

811B_FSL001C

POLYMER

0-5

m /hr

DISCHARGE OF POLYDOSING PUMP C

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

(S)

PID REFERENCE NO. -- DGT-825-L-DS-PR-001 ALUM DOSING SYSTEM

CONDUCTIVITY LEVEL SWITCH

825A_LS001_

ALUM

ALUM DOSING TANK-A

TO MONITOR THE LEVEL AT ALUM DOSING TANK-A & TO CONTROL THE START/STOP
OPERATION OF ALUM DOSING PUMPS & ALUM TANK AGITATOR

4 PROBE (Not in package) TH-3.5m


LWL-2.3m, LLWL-3.2 HWL-0.6

CONDUCTIVITY LEVEL SWITCH

825B_LS001_

ALUM

ALUM DOSING TANK-B

TO MONITOR THE LEVEL AT ALUM DOSING TANK-B & TO CONTROL THE START/STOP
OPERATION OF ALUM DOSING PUMPS & ALUM TANK AGITATOR

4 PROBE (Not in package) TH-3.5m


LWL-2.3m, LLWL-3.2 HWL-0.6

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

REV-A

TAG NO.

FLUID

RANGE

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

CONDUCTIVITY LEVEL SWITCH

825C_LS001_

ALUM

ALUM DOSING TANK-C

TO MONITOR THE LEVEL AT ALUM DOSING TANK-C & TO CONTROL THE START/STOP
OPERATION OF ALUM DOSING PUMPS & ALUM TANK AGITATOR

4 PROBE (Not in package) TH-3.5m


LWL-2.3m, LLWL-3.2 HWL-0.6

LEVEL GAUGE

825A_LG001_

ALUM

ALUM DOSING TANK-A

TO INDICATE THE LEVEL AT ALUM TANK-A

TH - 3.5m (Not in package)

LEVEL GAUGE

825B_LG001_

ALUM

ALUM DOSING TANK-B

TO INDICATE THE LEVEL AT ALUM TANK-B

TH - 3.5m (Not in package)

LEVEL GAUGE

825C_LG001_

ALUM

TH - 3.5m (Not in package)

PRESSURE GAUGE BOURDON

825_ _PG001A

ALUM

PRESSURE GAUGE BOURDON

825_ _PG001B

ALUM

PRESSURE GAUGE BOURDON

825_ _PG001C

10

PRESSURE GAUGE BOURDON

ALUM DOSING TANK-C

TO INDICATE THE LEVEL AT ALUM TANK-C

0 - 10

kg/cm

DISCHARGE OF ALUM DOSING PUMP-A

TO INDICATE THE PRESSURE AT DISCHARGE OF ALUM DOSING PUMP-A

0 - 10 kg/cm2

0 - 10

kg/cm2

DISCHARGE OF ALUM DOSING PUMP-B

TO INDICATE THE PRESSURE AT DISCHARGE OF ALUM DOSING PUMP-B

0 - 10 kg/cm2

ALUM

0 - 10

kg/cm2

DISCHARGE OF ALUM DOSING PUMP-C

TO INDICATE THE PRESSURE AT DISCHARGE OF ALUM DOSING PUMP-C

0 - 10 kg/cm2

825_ _PG001D

ALUM

0 - 10

kg/cm2

DISCHARGE OF ALUM DOSING PUMP-D

TO INDICATE THE PRESSURE AT DISCHARGE OF ALUM DOSING PUMP-D

0 - 10 kg/cm2

11

PRESSURE GAUGE BOURDON

825_ _PG001E

ALUM

0 - 10

kg/cm

DISCHARGE OF ALUM DOSING PUMP-E

TO INDICATE THE PRESSURE AT DISCHARGE OF ALUM DOSING PUMP-E

0 - 10 kg/cm2

12

PRESSURE GAUGE BOURDON

825_ _PG001F

ALUM

0 - 10

kg/cm2

DISCHARGE OF ALUM DOSING PUMP-F

TO INDICATE THE PRESSURE AT DISCHARGE OF ALUM DOSING PUMP-F

0 - 10 kg/cm2

12

PRESSURE GAUGE BOURDON

825_ _PG001F

ALUM

0 - 10

kg/cm2

DISCHARGE OF ALUM DOSING PUMP-F

TO INDICATE THE PRESSURE AT DISCHARGE OF ALUM DOSING PUMP-F

0 - 10 kg/cm2

PROJECT
CLIENT

15MGD STP AT DELHI GATE (PHASE-II)


DELHI JAL BOARD

CONSULTANT
CONTRACTOR

DEGRMONT LTD.

TITLE

INSTRUMENT LIST

DOCUMENT NO.
SR.
NO.

INSTRUMENT DESCRIPTION

DGT-000-L-LI-IN-001

REV-A

TAG NO.

FLUID

RANGE

UNIT

DATE - 19-10-2012
SERVICE

INSTRUMENT FUNCTIONAL DESCRIPTION

REMARKS

13

FLOW SWITCH / ROTAMETER

825_ _FSL001A

ALUM

0-5

m3/hr

DISCHARGE OF ALUM DOSING PUMP-A

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

14

FLOW SWITCH / ROTAMETER

825_ _FSL001B

ALUM

0-5

m /hr

DISCHARGE OFALUM DOSING PUMP-C

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

15

FLOW SWITCH / ROTAMETER

825_ _FSL001C

ALUM

0-5

m3/hr

DISCHARGE OF ALUM DOSING PUMP-D

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)

16

FLOW SWITCH / ROTAMETER

825_ _FSL001D

ALUM

0-5

m3/hr

DISCHARGE OF ALUM DOSING PUMP-F

TO INDICATE THE FLOW IN THE DILUTION

0 - 5 m3/hr (25NS Line Size)