Calculating Equivalent Utility Impedance

Base MVA selected for calculations


Base kV for power supply
Present Three Phase Short Circuit Current
Present Phase to Ground Short Circuit Curr
X/R Ratio for present conditions

Enter Data
100
MVA
34.5
kV
3200
3200
5

Amperes
Amperes
Ratio

Calculated OUTPUT Data


Base Current
Base ohms
Positive and Negative Sequence Data
Actual ohms impedance
Per Unit impedance
X/R angle
R1 or R2
X1 or X2
Short Circuit MVA
Zero Sequence Data
Actual ohms impedance
Per Unit impedance
X/R angle
R0
X0
Short Circuit MVA

Answers
1673.48 Amperes
11.90 Ohms

6.2246
0.5230
78.69
0.1026
0.5128
191

ohms
ohms p.u.
degrees
ohms p.u.
ohms p.u.
MVA

6.2251
0.5230
78.69
0.1026
0.5129
64

ohms
ohms p.u.
degrees
ohms p.u.
ohms p.u.
MVA

Chuck Forster
Forster Electrical Engineering, Inc.