Anda di halaman 1dari 2

DO NOT SCALE - DO NOT MODIFY

GENERAL NOTES & REFERENCE DRAWINGS


1.

FOR GENERAL NOTES FOR CONCRETE WORKS SEE DWG


BMPS-Q-50701.

h ef
(H-K)

h ef
(H-D)

h ef
(H-K)

GROUT
25 min.

eh( > 3D)

TABLE 1. BOLT SIZE


BOLT

BOLT TYPE

TYPE L

TYPE I

TYPE IX

D
(mm)

DIMENSIONS (mm)

DIAMETER

FOR FABRICATION

Tensile
Thread
Wrench Stress
Area
Pitch (mm) Size (mm)
(mm)

FOR DESIGN

TK

H
min.

DB

M10

X 1.5

17

58,0

50

220

20

120

80

140

190

M12

X 1.75

19

84,3

55

285

25

180

80

160

250

M16

X 2

24

156,7

60

350

35

240

100

200

300

M20

X 2.5

30

244,8

65

425

40

310

100

230

370

M24

X 3

36

352,5

80

540

50

410

150

280

470

M30

X 3.5

46

560,6

105

685

65

525

150

340

600

M36

X 4

55

816,8

115

785

75

615

150

390

690

M16

X 2

24

156,7

60

350

35

55

50

240

M20

X 2.5

30

244,8

65

425

45

60

60

12

310

AAA TIGHTENING METHOD FOR DOUBLE NUTS

M24

X 3

36

352,5

80

540

55

80

75

16

410

M30

X 3.5

46

560,6

105

685

65

100

90

16

525

M36

X 4

55

816,8

115

785

75

115

110

19

615

1) FIRSTLY, PUT A NUT (CALLED AS A LOWER NUT) TURN


DOWN TO TOUCHING WITH A BASE PLATE. IT IS NOT
NECESSARY TO GIVE TORQUE SO STRONGLY.

M42

X 4.5

65

1121,0

135

925

85

130

130

22

745

M48

X 5

75

1473,2

150

1045

100

150

145

25

855

M56

X 5.5

85

2030,1

170

1115

115

175

170

30

910

M64

X 6

95

2676,1

200

1250

135

200

195

35

1030

M16

X 2

24

156,7

120

555

35

55

50

240

M20

X 2.5

30

244,8

130

635

45

60

60

12

310

M24

X 3

36

352,5

145

750

55

80

75

16

410

M30

X 3.5

46

560,6

180

910

65

100

90

16

525

M36

X 4

55

816,8

190

1010

75

115

110

19

615

M42

X 4.5

65

1121,0

200

1150

85

130

130

22

M48

X 5

75

1473,2

220

1270

100

150

145

M56

X 5.5

85

2030,1

235

1340

115

175

M64

X 6

95

2676,1

255

1475

135

200

CONSTRUCTION NOTE

DETAIL FOR PLASTIC SLEEVE

2) SECONDARY, PUT ANOTHER NUT (CALLED AS AN UPPER


NUT) TURN DOWN TO TOUCHING WITH THE TOP SURFACE
OF THE LOWER NUT.

NOTES :
1. MATERIALS
BOLTS

: F1554 Gr. 36 Anchor Bolts

DIMENSION: ANSI B 18.2.3.6M HEAVY HEX BOLT

UPPER NUT

: ASTM A563 GRADE A

DIMENSION: ANSI B 18.2.4.6 M HEAVY HEX NUT

LOWER NUT
WASHER

: ASTM A563 GRADE A


: ASTM F436

DIMENSION: ANSI B 18.2.4.6 M HEAVY HEX NUT

ANCHOR PLATE

: ASTM A36

745

25

855

170

30

910

195

35

1030

3) THIRDLY, GIVE TORQUE TO THE UPPER NUT TO GO DOWN.


SIMULTANEOUSLY, GIVE THE SAME VALUE OF TORQUE
IN REVERSE DIRECTION TO THE LOWER NUT AND
MAINTAIN IT NOT TO BE TURNED.

2. THREADING OF BOLTS AND NUTS


THREADS SHALL BE THE UNIFIED COARSE THREADS IN ACCORDANCE WITH ANSI B1.1.
THE TOLERANCE CLASSES OF THREADS SHALL BE CLASS 2A FOR BOLTS AND CLASS 2B FOR NUTS.
3. ANCHOR PLATE HOLE
ANCHOR PLATE HOLE DIAMETERS SHALL BE MIN.4mm LARGER THAN THE NOMINAL BOLT DIAMETERS.
(REFER TABLE 2)

TABLE 2. PROJECTION LENGTH "P"

UPPER NUT*

BOLT
DIAMETER
D
(mm)

H1

H2

WT

M10

(EQ-1)

10

10

VAR

M12

(EQ-1)

12

12

VAR

M16

(EQ-1)

16

16

VAR

M20

(EQ-1)

20

20

VAR

M24

(EQ-1)

24

24

VAR

M30

(EQ-1)

11

30

30

VAR

M36

(EQ-1)

12

36

36

VAR

M42

(EQ-1)

14

42

42

VAR

M48

(EQ-1)

15

48

48

VAR

M56

(EQ-1)

17

56

56

VAR

M64

(EQ-1)

18

64

64

VAR

DIMENSIONS (mm)

: RECOMMENDING ANCHOR HOLE DIAMETER ON BASE PLATE.

PJ

LOWER NUT*

D+4

PJ=Thk. GROUT+ Thk. BASE


PLATE+3D >150mm U.O.N.
TOP OF
GROUT

BASE PLATE

D+6
D
D+10

* IS RACCOMENDED FOR ALL ANCHOR BOLT TYPES.

D+14

BMPS-M1

Basic Civil and Structural Design Data

Drawing No

12 - M20 - LX (- 2 - L650 )
NUMBERS OF BOLT IN A GROUP
DIAMETER
TYPE OF BOLT

Grouting

DESCRIPTION

REFERENCE DRAWINGS
EX

TOTAL LENGTH
NUMBER OF NUTS

NOTE - DOUBLE NUTS SHALL BE USED FOR ALL MAJOR EQUIPMENTS, VESSELS , EXCHANGERS & TALL COLUMNS
AND WHEREVER.

P.N.

REVISION

4. ANCHOR BOLTS SHALL BE INDICATED ON CIVIL DETAIL DRAWINGS AS FOLLOWS


(EXAMPLE) : SYMBOLS IN BLANKET ( ) ARE OPTIONAL.

BMPS-Q2

Date
EX
P.N.
Date

5. GALVANIZING
ALL MATERIALS SHALL BE HOT-DIP GALVANIZED IN ACCORDANCE WITH ASTM A153 CLASS C.
6. BOX OUT
a) MORTAR IN BOX-OUT SHALL BE NON SHRINK, TYPE G2 TO 00L 3PS-DB02-00001 SEC. 20.2,
OTHERWISE NOTED.
b) USE BOX-OUT DETAILS FOR "TYPE L" ONLY.
c) EDGE OF BOX-OUT SHALL BE MIN.100mm FROM CONCRETE EDGE.

UNIT ..AREA

UNLESS

7. "PJ (mm)" LENGTH SHALL BE INDICATED IN CIVIL DETAIL DRAWING.


8. FOR SELECTION OF ANCHOR BOLT SEE DESIGN GUIDELINE RP003211.
SCALE:

62756
E.X. ............
EN0815
P.N. ............

DATE:

BMPS-Q-141752

Sht. 1
1
of

REV.

Anda mungkin juga menyukai