Anda di halaman 1dari 1

Estimated Loads For New National Cancer Institute (500500)

Essential
Load

Norma Power Load

NO

BUILDING / FUNCTION

Area
m2

Estimated
Demand
Load
load at Dist.
(VA/m2) Trans. (kVA)

Simult.
Factor

Demand load
at Distribution
Substation
(kVA)

(kw)

Esti.
Annual
Load
Rated
Consum.
(VA/m2)
Working
Rate Million
with Div.
Hrs/Year
(kWHrs)
factor

Demand
load
(kVA)

HOSPITAL (IN &Out Patients)

211,500

170

35955

0.8

28764

23011

5621

129

90

19035

Research Center

34,000

160

5440

0.8

4352

3482

3650

13

60

2040

Conference Center

13,600

140

1904

0.8

1523

1219

1460

50

680

International Cooperation Center

28,050

140

3927

0.8

3142

2513

2920

35

982

11 Technical Institute

6,800

130

884

0.8

707

566

2190

35

238

11 Nursing Institute

5,100

130

663

0.8

530

424

2190

35

179

Housing

16,200

100

1620

0.8

1296

1037

3650

20

324

Underground Car Park

252,000

40

10080

0.8

8064

6451

4380

28

20

5040

Site Utility

1000

0.8

800

640

4380

30

0.8

24

19

2920

800

0.8

640

512

2190

800

49842

39874

189

29827

10 Mosque

500

11 Oncology Electrical Equipment

CAMPUS TOTAL

567,750

60

62303

500
20

10

30 MVA